COMPRESSOR DATA SHEET
In Accordance with Federal Uniform Test Method for Certain Lubricated Air Compressors
Rotary Compressor: Fixed Speed
MODEL DATA - FOR COMPRESSED AIR
1 Manufacturer: FS-Curtis
Model Number: NxB04-150 Date: 07/20/2021
2 X Air-cooled Water-cooled Type: Screw
# of Stages: 1
a, e a,e
3* Rated Capacity at Full Load Operating Pressure 15.4 acfm
b b
4* Full Load Operating Pressure 150 psig
c c
5 Maximum Full Flow Operating Pressure 150 psig
6 Drive Motor Nominal Rating 5.5 hp
7 Drive Motor Nominal Efficiency 89.5 percent
8 Fan Motor Nominal Rating (if applicable) N/A hp
9 Fan Motor Nominal Efficiency N/A percent
e e
10* Total Package Input Power at Zero Flow 1.3 kW
Total Package Input Power at Rated Capacity and Full Load d
11
Operating Pressure
d 5.4 kW
Package Specific Power at Rated Capacity and Full Load Operating
e
12* e 35.06 kW/100 cfm
Pressure
13 Isentropic Efficiency 47.17 Percent
*For models that are tested in the CAGI Performance Verification Program, these items are verified by the third party administrator.
Consult CAGI website for a list of participants in the third party verification program: www.cagi.org
NOTES: a. Measured at the discharge terminal point of the compressor package in accordance with
ISO 1217, Annex C; ACFM is actual cubic feet per minute at inlet conditions.
b. The operating pressure at which the Capacity (Item 3) and Electrical Consumption (Item 11) were measured
for this data sheet.
c. Maximum pressure attainable at full flow, usually the unload pressure setting for load/no load control or the
maximum pressure attainable before capacity control begins. May require additional power.
d. Total package input power at other than reported operating points will vary with control strategy.
e. Tolerance is specified in ISO 1217, Annex C, as shown in table below:
NOTE: The terms "power" and "energy" are synonymous for purposes of this document. No Load /
Volume Flow Rate Specific Energy Zero Flow
at specified conditions Volume Flow Rate Consumption Power
3 3
Member m / min ft / min % % %
Below 0.5 Below 17.6 +/- 7 +/- 8
0.5 to 1.5 17.6 to 53 +/- 6 +/- 7
+/- 10%
1.5 to 15 53 to 529.7 +/- 5 +/- 6
ROT 030.1 Above 15 Above 529.7 +/- 4 +/- 5
12/19 Rev 3 This form was developed by the Compressed Air and Gas Institute for the use of its members participating in the PVP. CAGI has not independently verified the reported data.