0% found this document useful (0 votes)
11 views22 pages

3axd50000645015 Reva

This technical note provides guidelines for acceptable alternative fuses for various ABB drives, including ACS380, ACx580, and ACS880 models. It emphasizes the importance of using fuses that meet specific characteristics outlined in the drive's hardware manual to ensure proper protection and compliance with UL standards. The document includes tables detailing recommended fuses from major manufacturers for different drive configurations.

Uploaded by

asolelpancho
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
11 views22 pages

3axd50000645015 Reva

This technical note provides guidelines for acceptable alternative fuses for various ABB drives, including ACS380, ACx580, and ACS880 models. It emphasizes the importance of using fuses that meet specific characteristics outlined in the drive's hardware manual to ensure proper protection and compliance with UL standards. The document includes tables detailing recommended fuses from major manufacturers for different drive configurations.

Uploaded by

asolelpancho
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 22

Technical Note 019

Fuses for ABB drives


Acceptable fuses

Purpose
This document outlines which alternative fuses may be used various ABB drives.

How to use this information


The specific drive’s hardware manual includes fuse recommendations for the drive. In addition to the fuses
identified in the manuals, alternative fuses can be used if they meet certain characteristics. The guidelines in
this document describe which fuses are an acceptable alternative.

3AXD50000645015 1
REV A Effective: 12/6/2019

Contents

ACS380 drives ............................................................................................................................................................. 3


Table 1: ACS380-04, 200...240 V, 1-phase ........................................................................................................................ 5
Table 2: ACS380-04, 200...240 V ......................................................................................................................................... 6
Table 3: ACS380-04, 380...480 V ........................................................................................................................................ 7
Table 4: [Table reserved for future use] ........................................................................................................................... 8
Table 5: [Table reserved for future use] ........................................................................................................................... 8
Table 6: [Table reserved for future use] ........................................................................................................................... 8

ACx580 drives ................................................................................................................................................................... 9


Table 7: ACH/ACQ/ACS580-01, 208/230 V ...................................................................................................................... 11
Table 8: ACH580-01, 480 V .................................................................................................................................................. 12
Table 9: ACQ/ACS580-01, 480 V ........................................................................................................................................ 13
Table 10: ACH/ACQ/ACS580-01, 600 V ............................................................................................................................ 14
Table 11: ACH/ACQ580-31, 480 V ....................................................................................................................................... 15

ACS880 drives ................................................................................................................................................................... 16


Table 12: ACS880-01, 230 V ................................................................................................................................................. 18
Table 13: ACS880-01, 480 V ................................................................................................................................................. 19
Table 14: ACS880-01, 575 V ................................................................................................................................................. 20
Table 15: ACS880-31, 480 V ................................................................................................................................................. 21
Table 16: ACS880-11, 480 V ................................................................................................................................................. 22

3AXD50000645015 2
REV A Effective: 12/6/2019

ACS380 drives

Purpose
This section outlines which alternative fuses may be used with ACS380-04 base drives R0 through R4 frame size.

How to use this information


The drive hardware manual includes fuse recommendations for the drive. In addition to the fuses identified in
the manual, alternative fuses can be used if they meet certain characteristics. The guidelines in this document
describe which fuses are an acceptable alternative. This document is a supplement to the following drive
hardware manuals:

• 3AXD50000029274 ACS380-04 drives

Information
ACS380-04 drives are suitable for use on a circuit capable of delivering not more than 100 kA symmetrical
amperes (RMS) at 240 and 480 V maximum, when protected by appropriate fuses.

The drives are tested to UL 61800-5-1 standard on a circuit having available system fault of 100 kA.
Hardware manuals for ACS380-04 drives recommend:

• Listed Class T (UL 248-15) fast acting fuses up to 100A.

ABB performed the fault testing with “umbrella fuses.” These fuses are calibrated to create worst case peak let-
through current (Ipeak) and let-through energy (I2t) limits. The umbrella fuse testing allows other listed fuses,
which have let-through characteristics equal to or below these limits, to be used. Therefore, listed
Class CC (UL 248-4) fuses (up to 30A) and listed (UL 248-8) Class J fast acting and high-speed fuses can also be
used, since they provide equal or better protection. Likewise, listed (UL 248-17) fast acting cubed body (CF)
fuses can be used as well.

3AXD50000645015 3
REV A Effective: 12/6/2019
In addition to the above guidelines, the following are additional rules that should be followed:

1. The UL listed fuses in the hardware manual tables, or the tables in this document, are the required
branch circuit protection per NEC.
2. Fuses are required as part of the installation. Fuses are not included in the base drive configuration
and must be provided by others.
3. Fuses with a higher current rating than specified must not be used.
4. Fuses with a lower current rating than specified may be used if they are of the same voltage and are
UL 248 listed fast acting or high-speed fuses.
5. A fuse of a different class can be used at the high fault rating where the Ipeak and I2t of the new fuse is
not greater than that of the specified fuse.
6. Recommended drive fuses must be used to maintain drive UL listing. Additional protection can be
used. Refer to local codes and regulations.
7. When installing a drive always follow installation instructions and NEC requirements.
8. UL 248 listed, fast acting or high-speed fuses from other manufacturers can be used if they meet the
rating requirements specified in the rules above.

Alternate recommended fuses for some of the major fuse manufacturers can be found in tables on the
following pages. Other manufacturers not found on the tables below may be used if they meet the fuse
requirements stated above.

3AXD50000645015 4
REV A Effective: 12/6/2019
Table 1: ACS380-04, 200...240 V, 1-phase

Frame 1-Phase Input UL Fuse Size (A) UL 248-15 Class T Fast Acting Fuses UL 248-8 Fast Acting Class J Fuses
Size 200….240 V Current and Voltage (V) 300 V or 600 V 600 V
ACS380-04 Max Mersen/ Mersen/
Voltage Rating
Current Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison
A A V Shawmut Shawmut
R0 02A4-1 5.0 10 300 or 600 JJN-10 or JLLN010 or A3T10 or TJN10 or JKS-10 JLS10 A4J10 JFL10
JJS-10 JLLS010 A6T10 TJS10
R0 03A7-1 7.8 10 300 or 600 JJN-10 or JLLN010 or A3T10 or TJN10 or JKS-10 JLS10 A4J10 JFL10
JJS-10 JLLS010 A6T10 TJS10
R1 04A8-1 10.1 20 300 or 600 JJN-20 or JLLN020 or A3T20 or TJN20 or JKS-20 JLS20 A4J20 JFL20
JJS-20 JLLS020 A6T20 TJS20
R1 06A9-1 14.5 20 300 or 600 JJN-20 or JLLN020 or A3T20 or TJN20 or JKS-20 JLS20 A4J20 JFL20
JJS-20 JLLS020 A6T20 TJS20
R1 07A8-1 16.4 25 300 or 600 JJN-25 or JLLN025 or A3T25 or TJN25 or JKS-25 JLS25 A4J25 JFL25
JJS-25 JLLS025 A6T25 TJS25
R2 09A8-1 20.6 25 300 or 600 JJN-25 or JLLN025 or A3T25 or TJN25 or JKS-25 JLS25 A4J25 JFL25
JJS-25 JLLS025 A6T25 TJS25
R2 12A2-1 25.6 35 300 or 600 JJN-35 or JLLN035 or A3T35 or TJN35 or JKS-35 JLS35 A4J35 JFL35
JJS-35 JLLS035 A6T35 TJS35

Frame 1-Phase Input UL Fuse Size (A) UL 248-8 High Speed Class J Fuses UL 248-4 Class CC Fast Acting Fuses UL 248-17
Size 200….240 V Current and Voltage (V) 600 V 600 V Class CF
ACS380-04 Fast Acting
Cube Fuse
600 V
Max Mersen/ Mersen/
Voltage Rating
Current Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison Bussmann
A A V Shawmut Shawmut
R0 02A4-1 5.0 10 300 or 600 DFJ-10 LDFJ010 HSJ10 JHL10 KTK-R-10 KLKR10 ATMR10 HCLR10 FCF10RN
R0 03A7-1 7.8 10 300 or 600 DFJ-10 LDFJ010 HSJ10 JHL10 KTK-R-10 KLKR10 ATMR10 HCLR10 FCF10RN
R1 04A8-1 10.1 20 300 or 600 DFJ-20 LDFJ020 HSJ20 JHL20 KTK-R-20 KLKR20 ATMR20 HCLR20 FCF20RN
R1 06A9-1 14.5 20 300 or 600 DFJ-20 LDFJ020 HSJ20 JHL20 KTK-R-20 KLKR20 ATMR20 HCLR20 FCF20RN
R1 07A8-1 16.4 25 300 or 600 DFJ-25 LDFJ025 HSJ25 JHL25 KTK-R-25 KLKR25 ATMR25 HCLR25 FCF25RN
R2 09A8-1 20.6 25 300 or 600 DFJ-25 LDFJ025 HSJ25 JHL25 KTK-R-25 KLKR25 ATMR25 HCLR25 FCF25RN
R2 12A2-1 25.6 35 300 or 600 DFJ-35 LDFJ035 HSJ35 JHL35 - - - - FCF35RN
3AXD10001032874.xls Rev B

3AXD50000645015 5
REV A Effective: 12/6/2019
Table 2: ACS380-04, 200...240 V

Frame 3-Phase Input UL Fuse Size (A) UL 248-15 Class T Fast Acting Fuses UL 248-8 Fast Acting Class J Fuses
Size 200….240 V Current and Voltage (V)
ACS380-04 Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison
A A V Shawmut Shawmut
R1 02A4-2 3.6 6 600 JJS-6 JLLS006 A6T6 TJS6 JKS-6 JLS6 A4J6 JFL6
R1 03A7-2 5.6 10 600 JJS-10 JLLS010 A6T10 TJS10 JKS-10 JLS10 A4J10 JFL10
R1 04A8-2 7.2 10 600 JJS-10 JLLS010 A6T10 TJS10 JKS-10 JLS10 A4J10 JFL10
R1 06A9-2 10.4 20 600 JJS-20 JLLS020 A6T20 TJS20 JKS-20 JLS20 A4J20 JFL20
R1 07A8-2 11.7 20 600 JJS-20 JLLS020 A6T20 TJS20 JKS-20 JLS20 A4J20 JFL20
R1 09A8-2 14.7 20 600 JJS-20 JLLS020 A6T20 TJS20 JKS-20 JLS20 A4J20 JFL20
R2 12A2-2 18.3 25 600 JJS-25 JLLS025 A6T25 TJS25 JKS-25 JLS25 A4J25 JFL25
R3 17A5-2 24.6 35 600 JJS-35 JLLS035 A6T35 TJS35 JKS-35 JLS35 A4J35 JFL35
R3 25A0-2 35.1 40 600 JJS-40 JLLS040 A6T40 TJS40 JKS-40 JLS40 A4J40 JFL40
R4 032A-2 45.0 60 600 JJS-60 JLLS060 A6T60 TJS60 JKS-60 JLS60 A4J60 JFL60
R4 048A-2 57.6 100 600 JJS-100 JLLS100 A6T100 TJS100 JKS-100 JLS100 A4J100 JFL100
R4 055A-2 60.0 100 600 JJS-100 JLLS100 A6T100 TJS100 JKS-100 JLS100 A4J100 JFL100

Frame 3-Phase Input UL Fuse Size (A) UL 248-8 High Speed Class J Fuses UL 248-4 Class CC Fast Acting Fuses UL 248-17
Size 200….240 V Current and Voltage (V) Class CF
ACS380-04 Fast Acting
Cube Fuse
Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison Bussmann
A A V Shawmut Shawmut
R1 02A4-2 3.6 6 600 DFJ-6 LDFJ006 HSJ6 JHL6 KTK-R-6 KLKR6 ATMR6 HCLR6 FCF6RN
R1 03A7-2 5.6 10 600 DFJ-10 LDFJ010 HSJ10 JHL10 KTK-R-10 KLKR10 ATMR10 HCLR10 FCF10RN
R1 04A8-2 7.2 10 600 DFJ-10 LDFJ010 HSJ10 JHL10 KTK-R-10 KLKR10 ATMR10 HCLR10 FCF10RN
R1 06A9-2 10.4 20 600 DFJ-20 LDFJ020 HSJ20 JHL20 KTK-R-20 KLKR20 ATMR20 HCLR20 FCF20RN
R1 07A8-2 11.7 20 600 DFJ-20 LDFJ020 HSJ20 JHL20 KTK-R-20 KLKR20 ATMR20 HCLR20 FCF20RN
R1 09A8-2 14.7 20 600 DFJ-20 LDFJ020 HSJ20 JHL20 KTK-R-20 KLKR20 ATMR20 HCLR20 FCF20RN
R2 12A2-2 18.3 25 600 DFJ-25 LDFJ025 HSJ25 JHL25 KTK-R-25 KLKR25 ATMR25 HCLR25 FCF25RN
R3 17A5-2 24.6 35 600 DFJ-35 LDFJ035 HSJ35 JHL35 - - - - FCF35RN
R3 25A0-2 35.1 40 600 DFJ-40 LDFJ040 HSJ40 JHL40 - - - - FCF40RN
R4 032A-2 45.0 60 600 DFJ-60 LDFJ060 HSJ60 JHL60 - - - - FCF60RN
R4 048A-2 57.6 100 600 DFJ-100 LDFJ100 HSJ100 JHL100 - - - - FCF100RN
R4 055A-2 60.0 100 600 DFJ-100 LDFJ100 HSJ100 JHL100 - - - - FCF100RN
3AXD10001032874.xls Rev B

3AXD50000645015 6
REV A Effective: 12/6/2019
Table 3: ACS380-04, 380...480 V

Frame 3-Phase Input UL Fuse Size (A) UL 248-15 Class T Fast Acting Fuses UL 248-8 Fast Acting Class J Fuses
Size 380….480 V Current and Voltage (V)
ACS380-04
Max Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison
Shawmut Shawmut
A A V
R0 01A8-4 2.9 / 2.6 6 600 JJS-6 JLLS006 A6T6 TJS6 JKS-6 JLS6 A4J6 JFL6
R1 02A6-4 4.2 / 3.4 6 600 JJS-6 JLLS006 A6T6 TJS6 JKS-6 JLS6 A4J6 JFL6
R1 03A3-4 5.3 / 4.8 6 600 JJS-6 JLLS006 A6T6 TJS6 JKS-6 JLS6 A4J6 JFL6
R1 04A0-4 6.4 / 5.4 10 600 JJS-10 JLLS010 A6T10 TJS10 JKS-10 JLS10 A4J10 JFL10
R1 05A6-4 9.0 / 7.7 10 600 JJS-10 JLLS010 A6T10 TJS10 JKS-10 JLS10 A4J10 JFL10
R1 07A2-4 11.5 / 9.6 20 600 JJS-20 JLLS020 A6T20 TJS20 JKS-20 JLS20 A4J20 JFL20
R1 09A4-4 15.0 / 12.2 20 600 JJS-20 JLLS020 A6T20 TJS20 JKS-20 JLS20 A4J20 JFL20
R2 12A6-4 20.2 / 17.6 25 600 JJS-25 JLLS025 A6T25 TJS25 JKS-25 JLS25 A4J25 JFL25
R3 17A0-4 27.2 / 22.4 35 600 JJS-35 JLLS035 A6T35 TJS35 JKS-35 JLS35 A4J35 JFL35
R3 25A0-4 40.0 / 33.6 40 600 JJS-40 JLLS040 A6T40 TJS40 JKS-40 JLS40 A4J40 JFL40
R4 032A-4 45.0 / 37.9 60 600 JJS-60 JLLS060 A6T60 TJS60 JKS-60 JLS60 A4J60 JFL60
R4 038A-4 50.0 / 44.7 80 600 JJS-80 JLLS080 A6T80 TJS80 JKS-80 JLS80 A4J80 JFL80
R4 045A-4 56.0 / 49.8 100 600 JJS-100 JLLS100 A6T100 TJS100 JKS-100 JLS100 A4J100 JFL100
R4 050A-4 60.0 / 50.4 100 600 JJS-100 JLLS100 A6T100 TJS100 JKS-100 JLS100 A4J100 JFL100

Frame 3-Phase Input UL Fuse Size (A) UL 248-8 High Speed Class J Fuses UL 248-4 Class CC Fast Acting Fuses UL 248-17
Size 380….480 V Current and Voltage (V) Class CF
ACS380-04 Fast Acting
Cube Fuse
Max Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison Bussmann
A A V Shawmut Shawmut
R0 01A8-4 2.9 / 2.6 6 600 DFJ-6 LDFJ006 HSJ6 JHL6 KTK-R-6 KLKR6 ATMR6 HCLR6 FCF6RN
R1 02A6-4 4.2 / 3.4 6 600 DFJ-6 LDFJ006 HSJ6 JHL6 KTK-R-6 KLKR6 ATMR6 HCLR6 FCF6RN
R1 03A3-4 5.3 / 4.8 6 600 DFJ-6 LDFJ006 HSJ6 JHL6 KTK-R-6 KLKR6 ATMR6 HCLR6 FCF6RN
R1 04A0-4 6.4 / 5.4 10 600 DFJ-10 LDFJ010 HSJ10 JHL10 KTK-R-10 KLKR10 ATMR10 HCLR10 FCF10RN
R1 05A6-4 9.0 / 7.7 10 600 DFJ-10 LDFJ010 HSJ10 JHL10 KTK-R-10 KLKR10 ATMR10 HCLR10 FCF10RN
R1 07A2-4 11.5 / 9.6 20 600 DFJ-20 LDFJ020 HSJ20 JHL20 KTK-R-20 KLKR20 ATMR20 HCLR20 FCF20RN
R1 09A4-4 15.0 / 12.2 20 600 DFJ-20 LDFJ020 HSJ20 JHL20 KTK-R-20 KLKR20 ATMR20 HCLR20 FCF20RN
R2 12A6-4 20.2 / 17.6 25 600 DFJ-25 LDFJ025 HSJ25 JHL25 KTK-R-25 KLKR25 ATMR25 HCLR25 FCF25RN
R3 17A0-4 27.2 / 22.4 35 600 DFJ-35 LDFJ035 HSJ35 JHL35 - - - - FCF35RN
R3 25A0-4 40.0 / 33.6 40 600 DFJ-40 LDFJ040 HSJ40 JHL40 - - - - FCF40RN
R4 032A-4 45.0 / 37.9 60 600 DFJ-60 LDFJ060 HSJ60 JHL60 - - - - FCF60RN
R4 038A-4 50.0 / 44.7 80 600 DFJ-80 LDFJ080 HSJ80 JHL80 - - - - FCF80RN
R4 045A-4 56.0 / 49.8 100 600 DFJ-100 LDFJ100 HSJ100 JHL100 - - - - FCF100RN
R4 050A-4 60.0 / 50.4 100 600 DFJ-100 LDFJ100 HSJ100 JHL100 - - - - FCF100RN
3AXD10001032874.xls Rev B

3AXD50000645015 7
REV A Effective: 12/6/2019
Table 4: [Table reserved for future use]

Table 5: [Table reserved for future use]

Table 6: [Table reserved for future use]

3AXD50000645015 8
REV A Effective: 12/6/2019

ACx580 drives
Purpose
This section outlines which alternative fuses may be used with ACH580-01/31, ACQ580-01/31, and ACS580-01
base drives through the R8 frame size.

How to use this information


The drive hardware manual includes fuse recommendations for the drive. In addition to the fuses identified in
the manual, alternative fuses can be used if they meet certain characteristics. The guidelines in this document
describe which fuses are an acceptable alternative. This document is a supplement to the following drive
hardware manuals:

• 3AXD50000044839 ACH580-01 drives


• 3AXD50000044862 ACQ580-01 drives
• 3AXD50000018826 ACS580-01 drives
• 3AXD50000037066 ACH580-31 drives
• 3AXD50000045935 ACQ580-31 drives

Information
ACH580-01, ACQ580-01 and ACS580-01 drives are suitable for use on a circuit capable of delivering not more
than 100 kA symmetrical amperes (RMS) at 240, 480 and 600 V maximum, when protected by appropriate fuses.

ACH580-31 and ACQ580-31 drives are suitable for use on a circuit capable of delivering not more than 100 kA
symmetrical amperes (RMS) at 480 V maximum, when protected by appropriate fuses.

The drives are tested to UL 61800-5-1 standard on a circuit having available system fault of 100 kA.
Hardware manuals for ACH580-01/31, ACQ580-01/31 and ACS580-01 drives recommend:

• Listed Class CC (UL 248-4) fuses (up to 30A)


• Listed Class T (UL 248-15) fast acting fuses up to 400A.

ABB performed the fault testing with “umbrella fuses.” These fuses are calibrated to create worst case peak let-
through current (Ipeak) and let-through energy (I2t) limits. The umbrella fuse testing allows other listed fuses,
which have let-through characteristics equal to or below these limits, to be used. Therefore, listed (UL 248-8)
Class J fast acting and high-speed fuses can also be used, since they provide equal or better protection.
Likewise, listed (UL 248-17) fast acting cubed body (CF) fuses can be used as well.

3AXD50000645015 9
REV A Effective: 12/6/2019
In addition to the above guidelines, the following are additional rules that should be followed:

1. The UL listed fuses in the hardware manual tables, or the tables in this document, are the required
branch circuit protection per NEC.
2. Fuses are required as part of the installation. Fuses are not included in the base drive configuration and
must be provided by others.
3. Fuses with a higher current rating than specified must not be used.
4. Fuses with a lower current rating than specified may be used if they are of the same voltage and are
UL 248 listed fast acting or high-speed fuses.
5. A fuse of a different class can be used at the high fault rating where the Ipeak and I2t of the new fuse is not
greater than that of the specified fuse.
6. Recommended drive fuses must be used to maintain drive UL listing. Additional protection can be used.
Refer to local codes and regulations.
7. When installing a drive always follow installation instructions and NEC requirements.
8. UL 248 listed, fast acting or high-speed fuses from other manufacturers can be used if they meet the
rating requirements specified in the rules above.

Alternate recommended fuses for some of the major fuse manufacturers can be found in tables on the following
pages. Other manufacturers not found on the tables below may be used if they meet the fuse requirements
stated above.

3AXD50000645015 10
REV A Effective: 12/6/2019
Table 7: ACH/ACQ/ACS580-01, 208/230 V

Frame 208/230 V Input UL Fuse Size (A) UL 248-15 Class T Fast Acting Fuses UL 248-8 Fast Acting Class J Fuses
Size ACH580-01 Current and Voltage (V)
ACQ580-01 Maximum Voltage Mersen/ Mersen/
ACS580-01 Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison
A A V Shawmut Shawmut
R1 04A6-2 4.6 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R1 06A6-2 6.6 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R1 07A5-2 7.5 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R1 10A6-2 10.6 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R1 017A-2 16.7 30 600 JJS-30 JLLS030 A6T30 TJS30 JKS-30 JLS30 A4J30 JFL30
R2 024A-2 24.2 40 600 JJS-40 JLLS040 A6T40 TJS40 JKS-40 JLS40 A4J40 JFL40
R2 031A-2 30.8 40 600 JJS-40 JLLS040 A6T40 TJS40 JKS-40 JLS40 A4J40 JFL40
R3 046A-2 46.2 80 600 JJS-80 JLLS080 A6T80 TJS80 JKS-80 JLS80 A4J80 JFL80
R3 059A-2 59.4 80 600 JJS-80 JLLS080 A6T80 TJS80 JKS-80 JLS80 A4J80 JFL80
R4 075A-2 74.8 100 600 JJS-100 JLLS100 A6T100 TJS100 JKS-100 JLS100 A4J100 JFL100
R5 088A-2 88.0 150 600 JJS-150 JLLS150 A6T150 TJS150 JKS-150 JLS150 A4J150 JFL150
R5 114A-2 114 150 600 JJS-150 JLLS150 A6T150 TJS150 JKS-150 JLS150 A4J150 JFL150
R6 143A-2 143 200 600 JJS-200 JLLS200 A6T200 TJS200 JKS-200 JLS200 A4J200 JFL200
R7 169A-2 169 250 600 JJS-250 JLLS250 A6T250 TJS250 JKS-250 JLS250 A4T250 JFL250
R7 211A-2 211 300 600 JJS-300 JLLS300 A6T300 TJS300 JKS-300 JLS300 A4J300 JFL300
R8 273A-2 273 400 600 JJS-400 JLLS400 A6T400 TJS400 JKS-400 JLS400 A4J400 JFL400

Frame 208/230 V Input UL Fuse Size (A) UL 248-8 High Speed Class J Fuses UL 248-4 Class CC Fast Acting Fuses UL 248-17
Size ACH580-01 Current and Voltage (V) Class CF
ACQ580-01 Fast Acting
ACS580-01 Cube Fuse
Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison Bussmann
A A V Shawmut Shawmut
R1 04A6-2 4.6 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R1 06A6-2 6.6 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R1 07A5-2 7.5 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R1 10A6-2 10.6 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R1 017A-2 16.7 30 600 DFJ-30 LDFJ030 HSJ30 JHL30 KTK-R-30 KLKR30 ATMR30 HCLR30 FCF30RN
R2 024A-2 24.2 40 600 DFJ-40 LDFJ040 HSJ40 JHL40 - - - - FCF40RN
R2 031A-2 30.8 40 600 DFJ-40 LDFJ040 HSJ40 JHL40 - - - - FCF40RN
R3 046A-2 46.2 80 600 DFJ-80 LDFJ080 HSJ80 JHL80 - - - - FCF80RN
R3 059A-2 59.4 80 600 DFJ-80 LDFJ080 HSJ80 JHL80 - - - - FCF80RN
R4 075A-2 74.8 100 600 DFJ-100 LDFJ100 HSJ100 JHL100 - - - - FCF100RN
R5 088A-2 88.0 150 600 DFJ-150 LDFJ150 HSJ150 JHL150 - - - - -
R5 114A-2 114 150 600 DFJ-150 LDFJ150 HSJ150 JHL150 - - - - -
R6 143A-2 143 200 600 DFJ-200 LDFJ200 HSJ200 JHL200 - - - - -
R7 169A-2 169 250 600 DFJ-250 LDFJ250 HSJ250 JHL250 - - - - -
R7 211A-2 211 300 600 DFJ-300 LDFJ300 HSJ300 JHL300 - - - - -
R8 273A-2 273 400 600 DFJ-400 LDFJ400 HSJ400 JHL400 - - - - -
3AXD10001032874.xls Rev B

3AXD50000645015 11
REV A Effective: 12/6/2019
Table 8: ACH580-01, 480 V

Frame 480 V Input UL Fuse Size (A) UL 248-15 Class T Fast Acting Fuses UL 248-8 Fast Acting Class J Fuses
Size ACH580-01 Current and Voltage (V)
Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison
A A V Shawmut Shawmut
R1 02A1-4 2.1 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R1 03A0-4 3.0 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R1 03A5-4 3.5 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R1 04A8-4 4.8 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R1 07A6-4 7.6 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R1 012A-4 12.0 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R2 014A-4 14.0 30 600 JJS-30 JLLS030 A6T30 TJS30 JKS-30 JLS30 A4J30 JFL30
R2 023A-4 23.0 30 600 JJS-30 JLLS030 A6T30 TJS30 JKS-30 JLS30 A4J30 JFL30
R3 027A-4 27.0 40 600 JJS-40 JLLS040 A6T40 TJS40 JKS-40 JLS40 A4J40 JFL40
R3 034A-4 34.0 60 600 JJS-60 JLLS060 A6T60 TJS60 JKS-60 JLS60 A4J60 JFL60
R3 044A-4 44.0 60 600 JJS-60 JLLS060 A6T60 TJS60 JKS-60 JLS60 A4J60 JFL60
R4 052A-4 52 80 600 JJS-80 JLLS080 A6T80 TJS80 JKS-80 JLS80 A4J80 JFL80
R4 065A-4 65 100 600 JJS-100 JLLS100 A6T100 TJS100 JKS-100 JLS100 A4J100 JFL100
R4 077A-4 77 100 600 JJS-100 JLLS100 A6T100 TJS100 JKS-100 JLS100 A4T100 JFL100
R5 096A-4 96 150 600 JJS-150 JLLS150 A6T150 TJS150 JKS-150 JLS150 A4J150 JFL150
R6 124A-4 124 200 600 JJS-200 JLLS200 A6T200 TJS200 JKS-200 JLS200 A4J200 JFL200
R7 156A-4 156 225 600 JJS-225 JLLS225 A6T225 TJS225 JKS-225 JLS225 A4J225 JFL225
R7 180A-4 180 300 600 JJS-300 JLLS300 A6T300 TJS300 JKS-300 JLS300 A4J300 JFL300
R8 240A-4 240 350 600 JJS-350 JLLS350 A6T350 TJS350 JKS-350 JLS350 A4J350 JFL350

Frame 480 V Input UL Fuse Size (A) UL 248-8 High Speed Class J Fuses UL 248-4 Class CC Fast Acting Fuses UL 248-17
Size ACH580-01 Current and Voltage (V) Class CF
Fast Acting
Cube Fuse
Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison Bussmann
A A V Shawmut Shawmut
R1 02A1-4 2.1 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R1 03A0-4 3.0 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R1 03A5-4 3.5 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R1 04A8-4 4.8 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R1 07A6-4 7.6 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R1 012A-4 12.0 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R2 014A-4 14.0 30 600 DFJ-30 LDFJ030 HSJ30 JHL30 KTK-R-30 KLKR30 ATMR30 HCLR30 FCF30RN
R2 023A-4 23.0 30 600 DFJ-30 LDFJ030 HSJ30 JHL30 KTK-R-30 KLKR30 ATMR30 HCLR30 FCF30RN
R3 027A-4 27.0 40 600 DFJ-40 LDFJ040 HSJ40 JHL40 - - - - FCF40RN
R3 034A-4 34.0 60 600 DFJ-60 LDFJ060 HSJ60 JHL60 - - - - FCF60RN
R3 044A-4 44.0 60 600 DFJ-60 LDFJ060 HSJ60 JHL60 - - - - FCF60RN
R4 052A-4 52 80 600 DFJ-80 LDFJ080 HSJ80 JHL80 - - - - FCF80RN
R4 065A-4 65 100 600 DFJ-100 LDFJ100 HSJ100 JHL100 - - - - FCF100RN
R4 077A-4 77 100 600 DFJ-100 LDFJ100 HSJ100 JHL100 - - - - -
R5 096A-4 96 150 600 DFJ-150 LDFJ150 HSJ150 JHL150 - - - - -
R6 124A-4 124 200 600 DFJ-200 LDFJ200 HSJ200 JHL200 - - - - -
R7 156A-4 156 225 600 DFJ-225 LDFJ225 HSJ225 JHL225 - - - - -
R7 180A-4 180 300 600 DFJ-300 LDFJ300 HSJ300 JHL300 - - - - -
R8 240A-4 240 350 600 DFJ-350 LDFJ350 HSJ350 JHL350 - - - - -
3AXD10001032874.xls Rev B

3AXD50000645015 12
REV A Effective: 12/6/2019
Table 9: ACQ/ACS580-01, 480 V

Frame 480 V Input UL Fuse Size (A) UL 248-15 Class T Fast Acting Fuses UL 248-8 Fast Acting Class J Fuses
Size ACQ580-01 Current and Voltage (V)
ACS580-01 Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison
A A V Shawmut Shawmut
R1 02A1-4 2.1 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R1 03A0-4 3.0 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R1 03A5-4 3.5 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R1 04A8-4 4.8 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R1 07A6-4 7.6 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R1 012A-4 12.0 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R2 014A-4 14.0 30 600 JJS-30 JLLS030 A6T30 TJS30 JKS-30 JLS30 A4J30 JFL30
R2 023A-4 23.0 30 600 JJS-30 JLLS030 A6T30 TJS30 JKS-30 JLS30 A4J30 JFL30
R3 027A-4 27.0 40 600 JJS-40 JLLS040 A6T40 TJS40 JKS-40 JLS40 A4J40 JFL40
R3 034A-4 34.0 60 600 JJS-60 JLLS060 A6T60 TJS60 JKS-60 JLS60 A4J60 JFL60
R3 044A-4 44.0 60 600 JJS-60 JLLS060 A6T60 TJS60 JKS-60 JLS60 A4J60 JFL60
R4 052A-4 52 80 600 JJS-80 JLLS080 A6T80 TJS80 JKS-80 JLS80 A4J80 JFL80
R4 065A-4 65 100 600 JJS-100 JLLS100 A6T100 TJS100 JKS-100 JLS100 A4J100 JFL100
R4 077A-4 77 100 600 JJS-100 JLLS100 A6T100 TJS100 JKS-100 JLS100 A4T100 JFL100
R5 096A-4 96 150 600 JJS-150 JLLS150 A6T150 TJS150 JKS-150 JLS150 A4J150 JFL150
R6 124A-4 124 200 600 JJS-200 JLLS200 A6T200 TJS200 JKS-200 JLS200 A4J200 JFL200
R7 156A-4 156 225 600 JJS-225 JLLS225 A6T225 TJS225 JKS-225 JLS225 A4J225 JFL225
R7 180A-4 180 300 600 JJS-300 JLLS300 A6T300 TJS300 JKS-300 JLS300 A4J300 JFL300
R8 240A-4 240 350 600 JJS-350 JLLS350 A6T350 TJS350 JKS-350 JLS350 A4J350 JFL350
R8 260A-4 240 400 600 JJS-400 JLLS400 A6T400 TJS400 JKS-400 JLS400 A4J400 JFL400

Frame 480 V Input UL Fuse Size (A) UL 248-8 High Speed Class J Fuses UL 248-4 Class CC Fast Acting Fuses UL 248-17
Size ACQ580-01 Current and Voltage (V) Class CF
ACS580-01 Fast Acting
Cube Fuse
Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison Bussmann
A A V Shawmut Shawmut
R1 02A1-4 2.1 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R1 03A0-4 3.0 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R1 03A5-4 3.5 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R1 04A8-4 4.8 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R1 07A6-4 7.6 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R1 012A-4 12.0 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R2 014A-4 14.0 30 600 DFJ-30 LDFJ030 HSJ30 JHL30 KTK-R-30 KLKR30 ATMR30 HCLR30 FCF30RN
R2 023A-4 23.0 30 600 DFJ-30 LDFJ030 HSJ30 JHL30 KTK-R-30 KLKR30 ATMR30 HCLR30 FCF30RN
R3 027A-4 27.0 40 600 DFJ-40 LDFJ040 HSJ40 JHL40 - - - - FCF40RN
R3 034A-4 34.0 60 600 DFJ-60 LDFJ060 HSJ60 JHL60 - - - - FCF60RN
R3 044A-4 44.0 60 600 DFJ-60 LDFJ060 HSJ60 JHL60 - - - - FCF60RN
R4 052A-4 52 80 600 DFJ-80 LDFJ080 HSJ80 JHL80 - - - - FCF80RN
R4 065A-4 65 100 600 DFJ-100 LDFJ100 HSJ100 JHL100 - - - - FCF100RN
R4 077A-4 77 100 600 DFJ-100 LDFJ100 HSJ100 JHL100 - - - - -
R5 096A-4 96 150 600 DFJ-150 LDFJ150 HSJ150 JHL150 - - - - -
R6 124A-4 124 200 600 DFJ-200 LDFJ200 HSJ200 JHL200 - - - - -
R7 156A-4 156 225 600 DFJ-225 LDFJ225 HSJ225 JHL225 - - - - -
R7 180A-4 180 300 600 DFJ-300 LDFJ300 HSJ300 JHL300 - - - - -
R8 240A-4 240 350 600 DFJ-350 LDFJ350 HSJ350 JHL350 - - - - -
R8 260A-4 240 400 600 DFJ-400 LDFJ400 HSJ400 JHL400 - - - - -
3AXD10001032874.xls Rev B

3AXD50000645015 13
REV A Effective: 12/6/2019
Table 10: ACH/ACQ/ACS580-01, 575 V

Frame 575 V Input UL Fuse Size (A) UL 248-15 Class T Fast Acting Fuses UL 248-8 Fast Acting Class J Fuses
Size ACH580-01 Current and Voltage (V)
ACQ580-01 Maximum Voltage Mersen/ Mersen/
ACS580-01 Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison
A A V Shawmut Shawmut
R2 02A7-6 2.7 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R2 03A9-6 3.9 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R2 06A1-6 6.1 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R2 09A0-6 9 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R2 011A-6 11 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R2 017A-6 17 30 600 JJS-30 JLLS030 A6T30 TJS30 JKS-30 JLS30 A4J30 JFL30
R3 022A-6 22 40 600 JJS-40 JLLS040 A6T40 TJS40 JKS-40 JLS40 A4J40 JFL40
R3 027A-6 27 40 600 JJS-40 JLLS040 A6T40 TJS40 JKS-40 JLS40 A4J40 JFL40
R3 032A-6 32 40 600 JJS-40 JLLS040 A6T40 TJS40 JKS-40 JLS40 A4J40 JFL40
R5 041A-6 41 100 600 JJS-100 JLLS100 A6T100 TJS100 JKS-100 JLS100 A4T100 JFL100
R5 052A-6 52 100 600 JJS-100 JLLS100 A6T100 TJS100 JKS-100 JLS100 A4T100 JFL100
R5 062A-6 62 100 600 JJS-100 JLLS100 A6T100 TJS100 JKS-100 JLS100 A4T100 JFL100
R5 077A-6 77 100 600 JJS-100 JLLS100 A6T100 TJS100 JKS-100 JLS100 A4T100 JFL100
R7 099A-6 99 150 600 JJS-150 JLLS150 A6T150 TJS150 JKS-150 JLS150 A4J150 JFL150
R7 125A-6 125 200 600 JJS-200 JLLS200 A6T200 TJS200 JKS-200 JLS200 A4J200 JFL200
R8 144A-6 144 250 600 JJS-250 JLLS250 A6T250 TJS250 JKS-250 JLS250 A4J250 JFL250

Frame 575 V Input UL Fuse Size (A) UL 248-8 High Speed Class J Fuses UL 248-4 Class CC Fast Acting Fuses UL 248-17
Size ACH580-01 Current and Voltage (V) Class CF
ACQ580-01 Fast Acting
ACS580-01 Cube Fuse
Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison Bussmann
A A V Shawmut Shawmut
R2 02A7-6 2.7 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R2 03A9-6 3.9 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R2 06A1-6 6.1 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R2 09A0-6 9 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R2 011A-6 11 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R2 017A-6 17 30 600 DFJ-30 LDFJ030 HSJ30 JHL30 KTK-R-30 KLKR30 ATMR30 HCLR30 FCF30RN
R3 022A-6 22 40 600 DFJ-40 LDFJ040 HSJ40 JHL40 - - - - FCF40RN
R3 027A-6 27 40 600 DFJ-40 LDFJ040 HSJ40 JHL40 - - - - FCF40RN
R3 032A-6 32 40 600 DFJ-40 LDFJ040 HSJ40 JHL40 - - - - FCF40RN
R5 041A-6 41 100 600 DFJ-100 LDFJ100 HSJ100 JHL100 - - - - FCF100RN
R5 052A-6 52 100 600 DFJ-100 LDFJ100 HSJ100 JHL100 - - - - FCF100RN
R5 062A-6 62 100 600 DFJ-100 LDFJ100 HSJ100 JHL100 - - - - FCF100RN
R5 077A-6 77 100 600 DFJ-100 LDFJ100 HSJ100 JHL100 - - - - FCF100RN
R7 099A-6 99 150 600 DFJ-150 LDFJ150 HSJ150 JHL150 - - - - -
R7 125A-6 125 200 600 DFJ-200 LDFJ200 HSJ200 JHL200 - - - - -
R8 144A-6 144 250 600 DFJ-250 LDFJ250 HSJ250 JHL250 - - - - -
3AXD10001032874.xls Rev B

3AXD50000645015 14
REV A Effective: 12/6/2019
Table 11: ACH/ACQ580-31, 480 V

Frame 480 V Input UL Fuse Size (A) UL 248-15 Class T Fast Acting Fuses UL 248-8 Fast Acting Class J Fuses
Size ACH580-31 Current and Voltage (V)
ACQ580-31 Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison
A A V Shawmut Shawmut
R3 07A6-4 7 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R3 012A-4 9 20 600 JJS-20 JLLS020 A6T20 TJS20 JKS-20 JLS20 A4J20 JFL20
R3 014A-4 12 25 600 JJS-25 JLLS025 A6T25 TJS25 JKS-25 JLS25 A4J25 JFL25
R3 023A-4 17 35 600 JJS-35 JLLS035 A6T35 TJS35 JKS-35 JLS35 A4J35 JFL35
R6 027A-4 24 40 600 JJS-40 JLLS040 A6T40 TJS40 JKS-40 JLS40 A4J40 JFL40
R6 034A-4 29 50 600 JJS-50 JLLS050 A6T50 TJS50 JKS-50 JLS50 A4J50 JFL50
R6 044A-4 34 60 600 JJS-60 JLLS060 A6T60 TJS60 JKS-60 JLS60 A4J60 JFL60
R6 052A-4 44 80 600 JJS-80 JLLS080 A6T80 TJS80 JKS-80 JLS80 A4J80 JFL80
R6 065A-4 54 90 600 JJS-90 JLLS090 A6T90 TJS90 JKS-90 JLS90 A4J90 JFL90
R6 077A-4 66 110 600 JJS-110 JLLS110 A6T110 TJS110 JKS-110 JLS110 A4J110 JFL110
R8 096A-4 82 150 600 JJS-150 JLLS150 A6T150 TJS150 JKS-150 JLS150 A4J150 JFL150
R8 124A-4 111 200 600 JJS-200 JLLS200 A6T200 TJS200 JKS-200 JLS200 A4J200 JFL200
R8 156A-4 134 225 600 JJS-225 JLLS225 A6T225 TJS225 JKS-225 JLS225 A4J225 JFL225
R8 180A-4 163 300 600 JJS-300 JLLS300 A6T300 TJS300 JKS-300 JLS300 A4T300 JFL300

Frame 480 V Input UL Fuse Size (A) UL 248-8 High Speed Class J Fuses UL 248-4 Class CC Fast Acting Fuses UL 248-17
Size ACH580-31 Current and Voltage (V) Class CF
ACQ580-31 Fast Acting
Cube Fuse
Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison Bussmann
A A V Shawmut Shawmut
R3 07A6-4 7 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R3 012A-4 9 20 600 DFJ-20 LDFJ020 HSJ20 JHL20 KTK-R-20 KLKR20 ATMR20 HCLR20 FCF20RN
R3 014A-4 12 25 600 DFJ-25 LDFJ025 HSJ25 JHL25 KTK-R-25 KLKR25 ATMR25 HCLR25 FCF25RN
R3 023A-4 17 35 600 DFJ-35 LDFJ035 HSJ35 JHL35 - - - - FCF35RN
R6 027A-4 24 40 600 DFJ-40 LDFJ040 HSJ40 JHL40 - - - - FCF40RN
R6 034A-4 29 50 600 DFJ-50 LDFJ050 HSJ50 JHL50 - - - - FCF50RN
R6 044A-4 34 60 600 DFJ-60 LDFJ060 HSJ60 JHL60 - - - - FCF60RN
R6 052A-4 44 80 600 DFJ-80 LDFJ080 HSJ80 JHL80 - - - - FCF80RN
R6 065A-4 54 90 600 DFJ-90 LDFJ090 HSJ90 JHL90 - - - - FCF90RN
R6 077A-4 66 110 600 DFJ-110 LDFJ110 HSJ110 JHL110 - - - - -
R8 096A-4 82 150 600 DFJ-150 LDFJ150 HSJ150 JHL150 - - - - -
R8 124A-4 111 200 600 DFJ-200 LDFJ200 HSJ200 JHL200 - - - - -
R8 156A-4 134 225 600 DFJ-225 LDFJ225 HSJ225 JHL225 - - - - -
R8 180A-4 163 300 600 DFJ-300 LDFJ300 HSJ300 JHL300 - - - - -
3AXD10001032874.xls Rev B

3AXD50000645015 15
REV A Effective: 12/6/2019

ACS880 drives

Purpose
This section outlines which fuses alternatively may be used with ACS880-01 R1 through R8 frame
sizes and ACS880-11 and ACS880-31 R3, R6 and R8 frame sizes.

How to use this information


The drive hardware manual includes fuse recommendations for the drive. In addition to the fuses identified in
the manual, alternative fuses can be used if they meet certain characteristics. The guidelines in this document
describe which fuses are an acceptable alternative. This document is a supplement to the following drive
hardware manuals:

• 3AUA0000078093 ACS880-01 drives


• 3AXD50000045932 ACS880-11 drives
• 3AXD50000045933 ACS880-31 drives

Information
ACS880-01 drives are suitable for use on a circuit capable of delivering not more than 100 kA symmetrical
amperes (RMS) at 240, 480 and 600 V maximum, when protected by appropriate fuses.

ACS880-11 and ACS880-31 drives are suitable for use on a circuit capable of delivering not more than 100 kA
symmetrical amperes (RMS) at 480 V maximum when protected by appropriate fuses.

The drives are tested to UL 61800-5-1 standard on a circuit having available system fault of 100 kA.
Hardware manuals for ACS880-01, ACS880-11 and ACS880-31 drives recommend listed Class T (UL 248-15) fast
acting fuses up to 400A.

ABB performed the fault testing with “umbrella fuses.” These fuses are calibrated to create worst case peak
let-through current (Ipeak) and let-through energy (I2t) limits. The umbrella fuse testing allows other Listed fuses,
which have let-through characteristics equal to or below these limits, to be used. Therefore, listed (UL 248-8)
Class J fast acting and high-speed fuses can also be used, since they provide equal or better protection.
Likewise, listed (UL 248-17) fast acting cubed body (CF) fuses can be used as well.

3AXD50000645015 16
REV A Effective: 12/6/2019
In addition to the above guidelines, the following are additional rules that should be followed:

1. The UL listed fuses in the hardware manual tables, or the tables in this document, are the required
branch circuit protection per NEC.
2. Fuses are required as part of the installation. Fuses are not included in the base drive configuration and
must be provided by others.
3. Fuses with a higher current rating than specified must not be used.
4. Fuses with a lower current rating than specified may be used if they are of the same voltage and are
UL 248 listed fast acting or high-speed fuses.
5. A fuse of a different class can be used at the high fault rating where the Ipeak and I2t of the new fuse is
not greater than that of the specified fuse.
6. Recommended drive fuses must be used to maintain drive UL listing. Additional protection can be
used. Refer to local codes and regulations.
7. When installing a drive always follow installation instructions and NEC requirements.
8. UL 248 listed, fast acting or high-speed fuses from other manufacturers can be used if they meet the
rating requirements specified in the rules above.

Alternate recommended fuses for some of the major fuse manufacturers can be found in tables on the
following pages. Other manufacturers not found on the tables below may be used if they meet the fuse
requirements stated above.

3AXD50000645015 17
REV A Effective: 12/6/2019
Table 12: ACS880-01, 230 V

Frame 230 V Input UL Fuse Size (A) UL 248-15 Class T Fast Acting Fuses UL 248-8 Fast Acting Class J Fuses
Size ACS880-01 Current and Voltage (V)
Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison
A A V Shawmut Shawmut
R1 04A6-2 4.4 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R1 06A6-2 6.3 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R1 07A5-2 7.1 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R1 10A6-2 10.1 20 600 JJS-20 JLLS020 A6T20 TJS20 JKS-20 JLS20 A4J20 JFL20
R2 16A8-2 16.0 25 600 JJS-25 JLLS025 A6T25 TJS25 JKS-25 JLS25 A4J25 JFL25
R2 24A3-2 23.1 40 600 JJS-40 JLLS040 A6T40 TJS40 JKS-40 JLS40 A4J40 JFL40
R3 031A-2 29.3 50 600 JJS-50 JLLS050 A6T50 TJS50 JKS-50 JLS50 A4J50 JFL50
R4 046A-2 44.0 80 600 JJS-80 JLLS080 A6T80 TJS80 JKS-80 JLS80 A4J80 JFL80
R4 061A-2 58.0 100 600 JJS-100 JLLS100 A6T100 TJS100 JKS-100 JLS100 A4J100 JFL100
R5 075A-2 71.0 125 600 JJS-125 JLLS125 A6T125 TJS125 JKS-125 JLS125 A4J125 JFL125
R5 087A-2 83.0 125 600 JJS-125 JLLS125 A6T125 TJS125 JKS-125 JLS125 A4J125 JFL125
R6 115A-2 109 150 600 JJS-150 JLLS150 A6T150 TJS150 JKS-150 JLS150 A4J150 JFL150
R6 145A-2 138 200 600 JJS-200 JLLS200 A6T200 TJS200 JKS-200 JLS200 A4J200 JFL200
R7 170A-2 162 250 600 JJS-250 JLLS250 A6T250 TJS250 JKS-250 JLS250 A4T250 JFL250
R7 206A-2 196 300 600 JJS-300 JLLS300 A6T300 TJS300 JKS-300 JLS300 A4J300 JFL300
R8 274A-2 260 400 600 JJS-400 JLLS400 A6T400 TJS400 JKS-400 JLS400 A4J400 JFL400

Frame 230 V Input UL Fuse Size (A) UL 248-8 High Speed Class J Fuses UL 248-4 Class CC Fast Acting Fuses UL 248-17
Size ACS880-01 Current and Voltage (V) Class CF
Fast Acting
Cube Fuse
Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison Bussmann
A A V Shawmut Shawmut
R1 04A6-2 4.4 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R1 06A6-2 6.3 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R1 07A5-2 7.1 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R1 10A6-2 10.1 20 600 DFJ-20 LDFJ020 HSJ20 JHL20 KTK-R-20 KLKR20 ATMR20 HCLR20 FCF20RN
R2 16A8-2 16.0 25 600 DFJ-25 LDFJ025 HSJ25 JHL25 KTK-R-25 KLKR25 ATMR25 HCLR25 FCF25RN
R2 24A3-2 23.1 40 600 DFJ-40 LDFJ040 HSJ40 JHL40 - - - - FCF40RN
R3 031A-2 29.3 50 600 DFJ-50 LDFJ050 HSJ50 JHL50 - - - - FCF50RN
R4 046A-2 44.0 80 600 DFJ-80 LDFJ080 HSJ80 JHL80 - - - - FCF80RN
R4 061A-2 58.0 100 600 DFJ-100 LDFJ100 HSJ100 JHL100 - - - - FCF100RN
R5 075A-2 71.0 125 600 DFJ-125 LDFJ125 HSJ125 JHL125 - - - - -
R5 087A-2 83.0 125 600 DFJ-125 LDFJ125 HSJ125 JHL125 - - - - -
R6 115A-2 109 150 600 DFJ-150 LDFJ150 HSJ150 JHL150 - - - - -
R6 145A-2 138 200 600 DFJ-200 LDFJ200 HSJ200 JHL200 - - - - -
R7 170A-2 162 250 600 DFJ-250 LDFJ250 HSJ250 JHL250 - - - - -
R7 206A-2 196 300 600 DFJ-300 LDFJ300 HSJ300 JHL300 - - - - -
R8 274A-2 260 400 600 DFJ-400 LDFJ400 HSJ400 JHL400 - - - - -
3AXD10001032874.xls Rev B

3AXD50000645015 18
REV A Effective: 12/6/2019
Table 13: ACS880-01, 480 V

Frame 480 V Input UL Fuse Size (A) UL 248-15 Class T Fast Acting Fuses UL 248-8 Fast Acting Class J Fuses
Size ACS880-01 Current and Voltage (V)
Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison
A A V Shawmut Shawmut
R1 02A1-5 2.1 3 600 JJS-3 JLLS003 A6T3 TJS3 JKS-3 JLS3 A4J3 JFL3
R1 03A0-5 3.0 6 600 JJS-6 JLLS006 A6T6 TJS6 JKS-6 JLS6 A4J6 JFL6
R1 03A4-5 3.4 6 600 JJS-6 JLLS006 A6T6 TJS6 JKS-6 JLS6 A4J6 JFL6
R1 04A8-5 4.8 10 600 JJS-10 JLLS010 A6T10 TJS10 JKS-10 JLS10 A4J10 JFL10
R1 05A2-5 5.2 10 600 JJS-10 JLLS010 A6T10 TJS10 JKS-10 JLS10 A4J10 JFL10
R1 07A6-5 7.6 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R1 11A0-5 11 20 600 JJS-20 JLLS020 A6T20 TJS20 JKS-20 JLS20 A4J20 JFL20
R2 014A-5 14 25 600 JJS-25 JLLS025 A6T25 TJS25 JKS-25 JLS25 A4J25 JFL25
R2 021A-5 21 35 600 JJS-35 JLLS035 A6T35 TJS35 JKS-35 JLS35 A4J35 JFL35
R3 027A-5 27 40 600 JJS-40 JLLS040 A6T40 TJS40 JKS-40 JLS40 A4J40 JFL40
R3 034A-5 34 50 600 JJS-50 JLLS050 A6T50 TJS50 JKS-50 JLS50 A4J50 JFL50
R4 040A-5 40 60 600 JJS-60 JLLS060 A6T60 TJS60 JKS-60 JLS60 A4J60 JFL60
R4 052A-5 52 80 600 JJS-80 JLLS080 A6T80 TJS80 JKS-80 JLS80 A4J80 JFL80
R5 065A-5 65 90 600 JJS-90 JLLS090 A6T90 TJS90 JKS-90 JLS90 A4T90 JFL90
R5 077A-5 77 110 600 JJS-110 JLLS110 A6T110 TJS110 JKS-110 JLS110 A4J110 JFL110
R6 096A-5 96 150 600 JJS-150 JLLS150 A6T150 TJS150 JKS-150 JLS150 A4J150 JFL150
R6 124A-5 124 200 600 JJS-200 JLLS200 A6T200 TJS200 JKS-200 JLS200 A4J200 JFL200
R7 156A-5 156 225 600 JJS-225 JLLS225 A6T225 TJS225 JKS-225 JLS225 A4J225 JFL225
R7 180A-5 180 300 600 JJS-300 JLLS300 A6T300 TJS300 JKS-300 JLS300 A4J300 JFL300
R8 240A-5 240 350 600 JJS-350 JLLS350 A6T350 TJS350 JKS-350 JLS350 A4J350 JFL350
R8 260A-5 260 400 600 JJS-400 JLLS400 A6T400 TJS400 JKS-400 JLS400 A4J400 JFL400

Frame 480 V Input UL Fuse Size (A) UL 248-8 High Speed Class J Fuses UL 248-4 Class CC Fast Acting Fuses UL 248-17
Size ACS880-01 Current and Voltage (V) Class CF
Fast Acting
Cube Fuse
Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison Bussmann
A A V Shawmut Shawmut
R1 02A1-5 2.1 3 600 DFJ-3 LDFJ003 HSJ3 JHL3 KTK-R-3 KLKR3 ATMR3 HCLR3 FCF3RN
R1 03A0-5 3.0 6 600 DFJ-6 LDFJ006 HSJ6 JHL6 KTK-R-6 KLKR6 ATMR6 HCLR6 FCF6RN
R1 03A4-5 3.4 6 600 DFJ-6 LDFJ006 HSJ6 JHL6 KTK-R-6 KLKR6 ATMR6 HCLR6 FCF6RN
R1 04A8-5 4.8 10 600 DFJ-10 LDFJ010 HSJ10 JHL10 KTK-R-10 KLKR10 ATMR10 HCLR10 FCF10RN
R1 05A2-5 5.2 10 600 DFJ-10 LDFJ010 HSJ10 JHL10 KTK-R-10 KLKR10 ATMR10 HCLR10 FCF10RN
R1 07A6-5 7.6 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R1 11A0-5 11 20 600 DFJ-20 LDFJ020 HSJ20 JHL20 KTK-R-20 KLKR20 ATMR20 HCLR20 FCF20RN
R2 014A-5 14 25 600 DFJ-25 LDFJ025 HSJ25 JHL25 KTK-R-25 KLKR25 ATMR25 HCLR25 FCF25RN
R2 021A-5 21 35 600 DFJ-35 LDFJ035 HSJ35 JHL35 - - - - FCF35RN
R3 027A-5 27 40 600 DFJ-40 LDFJ040 HSJ40 JHL40 - - - - FCF40RN
R3 034A-5 34 50 600 DFJ-50 LDFJ050 HSJ50 JHL50 - - - - FCF50RN
R4 040A-5 40 60 600 DFJ-60 LDFJ060 HSJ60 JHL60 - - - - FCF60RN
R4 052A-5 52 80 600 DFJ-80 LDFJ080 HSJ80 JHL80 - - - - FCF80RN
R5 065A-5 65 90 600 DFJ-90 LDFJ090 HSJ90 JHL90 - - - - FCF90RN
R5 077A-5 77 110 600 DFJ-110 LDFJ110 HSJ110 JHL110 - - - - -
R6 096A-5 96 150 600 DFJ-150 LDFJ150 HSJ150 JHL150 - - - - -
R6 124A-5 124 200 600 DFJ-200 LDFJ200 HSJ200 JHL200 - - - - -
R7 156A-5 156 225 600 DFJ-225 LDFJ225 HSJ225 JHL225 - - - - -
R7 180A-5 180 300 600 DFJ-300 LDFJ300 HSJ300 JHL300 - - - - -
R8 240A-5 240 350 600 DFJ-350 LDFJ350 HSJ350 JHL350 - - - - -
R8 260A-5 260 400 600 DFJ-400 LDFJ400 HSJ400 JHL400 - - - - -
3AXD10001032874.xls Rev B

3AXD50000645015 19
REV A Effective: 12/6/2019
Table 14: ACS880-01, 575 V

Frame 575 V Input UL Fuse Size (A) UL 248-15 Class T Fast Acting Fuses UL 248-8 Fast Acting Class J Fuses
Size ACS880-01 Current and Voltage (V)
Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison
A A V Shawmut Shawmut
R3 07A4-7 7 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R3 09A9-7 9.4 20 600 JJS-20 JLLS020 A6T20 TJS20 JKS-20 JLS20 A4J20 JFL20
R3 14A3-7 13.6 30 600 JJS-30 JLLS030 A6T30 TJS30 JKS-30 JLS30 A4J30 JFL30
R3 019A-7 18 40 600 JJS-40 JLLS040 A6T40 TJS40 JKS-40 JLS40 A4J40 JFL40
R3 023A-7 22 50 600 JJS-50 JLLS050 A6T50 TJS50 JKS-50 JLS50 A4J50 JFL50
R3 027A-7 27 50 600 JJS-50 JLLS050 A6T50 TJS50 JKS-50 JLS50 A4J50 JFL50
R5 07A3-7 9 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R5 09A8-7 11 20 600 JJS-20 JLLS020 A6T20 TJS20 JKS-20 JLS20 A4J20 JFL20
R5 14A2-7 17 30 600 JJS-30 JLLS030 A6T30 TJS30 JKS-30 JLS30 A4J30 JFL30
R5 018A-7 22 40 600 JJS-40 JLLS040 A6T40 TJS40 JKS-40 JLS40 A4J40 JFL40
R5 022A-7 27 50 600 JJS-50 JLLS050 A6T50 TJS50 JKS-50 JLS50 A4J50 JFL50
R5 026A-7 32 50 600 JJS-50 JLLS050 A6T50 TJS50 JKS-50 JLS50 A4J50 JFL50
R5 035A-7 41 60 600 JJS-60 JLLS060 A6T60 TJS60 JKS-60 JLS60 A4T60 JFL60
R5 042A-7 52 80 600 JJS-80 JLLS080 A6T80 TJS80 JKS-80 JLS80 A4T80 JFL80
R5 049A-7 52 80 600 JJS-80 JLLS080 A6T80 TJS80 JKS-80 JLS80 A4T80 JFL80
R6 061A-7 62 110 600 JJS-110 JLLS110 A6T110 TJS110 JKS-110 JLS110 A4J110 JFL110
R6 084A-7 77 150 600 JJS-150 JLLS150 A6T150 TJS150 JKS-150 JLS150 A4J150 JFL150
R7 098A-7 99 150 600 JJS-150 JLLS150 A6T150 TJS150 JKS-150 JLS150 A4J150 JFL150
R7 119A-7 125 200 600 JJS-200 JLLS200 A6T200 TJS200 JKS-200 JLS200 A4J200 JFL200
R8 142A-7 144 250 600 JJS-250 JLLS250 A6T250 TJS250 JKS-250 JLS250 A4J250 JFL250
R8 174A-7 180 300 600 JJS-300 JLLS300 A6T300 TJS300 JKS-300 JLS300 A4J300 JFL300

Frame 575 V Input UL Fuse Size (A) UL 248-8 High Speed Class J Fuses UL 248-4 Class CC Fast Acting Fuses UL 248-17
Size ACS880-01 Current and Voltage (V) Class CF
Fast Acting
Cube Fuse
Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison Bussmann
A A V Shawmut Shawmut
R3 07A4-7 7 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R3 09A9-7 9.4 20 600 DFJ-20 LDFJ020 HSJ20 JHL20 KTK-R-20 KLKR20 ATMR20 HCLR20 FCF20RN
R3 14A3-7 13.6 30 600 DFJ-30 LDFJ030 HSJ30 JHL30 KTK-R-30 KLKR30 ATMR30 HCLR30 FCF30RN
R3 019A-7 18 40 600 DFJ-40 LDFJ040 HSJ40 JHL40 - - - - FCF40RN
R3 023A-7 22 50 600 DFJ-50 LDFJ050 HSJ50 JHL50 - - - - FCF50RN
R3 027A-7 27 50 600 DFJ-50 LDFJ050 HSJ50 JHL50 - - - - FCF50RN
R5 07A3-7 9 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R5 09A8-7 11 20 600 DFJ-20 LDFJ020 HSJ20 JHL20 KTK-R-20 KLKR20 ATMR20 HCLR20 FCF20RN
R5 14A2-7 17 30 600 DFJ-30 LDFJ030 HSJ30 JHL30 KTK-R-30 KLKR30 ATMR30 HCLR30 FCF30RN
R5 018A-7 22 40 600 DFJ-40 LDFJ040 HSJ40 JHL40 - - - - FCF40RN
R5 022A-7 27 50 600 DFJ-50 LDFJ050 HSJ50 JHL50 - - - - FCF50RN
R5 026A-7 32 50 600 DFJ-50 LDFJ050 HSJ50 JHL50 - - - - FCF50RN
R5 035A-7 41 60 600 DFJ-60 LDFJ060 HSJ60 JHL60 - - - - FCF60RN
R5 042A-7 52 80 600 DFJ-80 LDFJ080 HSJ80 JHL80 - - - - FCF80RN
R5 049A-7 52 80 600 DFJ-80 LDFJ080 HSJ80 JHL80 - - - - FCF80RN
R6 061A-7 62 110 600 DFJ-110 LDFJ110 HSJ110 JHL110 - - - - -
R6 084A-7 77 150 600 DFJ-150 LDFJ150 HSJ150 JHL150 - - - - -
R7 098A-7 99 150 600 DFJ-150 LDFJ150 HSJ150 JHL150 - - - - -
R7 119A-7 125 200 600 DFJ-200 LDFJ200 HSJ200 JHL200 - - - - -
R8 142A-7 144 250 600 DFJ-250 LDFJ250 HSJ250 JHL250 - - - - -
R8 174A-7 180 300 600 DFJ-300 LDFJ300 HSJ300 JHL300 - - - - -
3AXD10001032874.xls Rev B

3AXD50000645015 20
REV A Effective: 12/6/2019
Table 15: ACS880-31, 480 V

Frame 480 V Input UL Fuse Size (A) UL 248-15 Class T Fast Acting Fuses UL 248-8 Fast Acting Class J Fuses
Size ACS880-31 Current and Voltage (V)
Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison
A A V Shawmut Shawmut
R3 07A6-5 5.8 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R3 11A0-5 7.8 20 600 JJS-20 JLLS020 A6T20 TJS20 JKS-20 JLS20 A4J20 JFL20
R3 014A-5 10.6 25 600 JJS-25 JLLS025 A6T25 TJS25 JKS-25 JLS25 A4J25 JFL25
R3 021A-5 15.6 35 600 JJS-35 JLLS035 A6T35 TJS35 JKS-35 JLS35 A4J35 JFL35
R6 027A-5 21.3 40 600 JJS-40 JLLS040 A6T40 TJS40 JKS-40 JLS40 A4J40 JFL40
R6 034A-5 26.2 50 600 JJS-50 JLLS050 A6T50 TJS50 JKS-50 JLS50 A4J50 JFL50
R6 040A-5 31.2 60 600 JJS-60 JLLS060 A6T60 TJS60 JKS-60 JLS60 A4J60 JFL60
R6 052A-5 40.1 80 600 JJS-80 JLLS080 A6T80 TJS80 JKS-80 JLS80 A4J80 JFL80
R6 065A-5 49.5 90 600 JJS-90 JLLS090 A6T90 TJS90 JKS-90 JLS90 A4J90 JFL90
R6 077A-5 60.2 110 600 JJS-110 JLLS110 A6T110 TJS110 JKS-110 JLS110 A4J110 JFL110
R8 101A-5 74 150 600 JJS-150 JLLS150 A6T150 TJS150 JKS-150 JLS150 A4J150 JFL150
R8 124A-5 100 200 600 JJS-200 JLLS200 A6T200 TJS200 JKS-200 JLS200 A4J200 JFL200
R8 156A-5 120 225 600 JJS-225 JLLS225 A6T225 TJS225 JKS-225 JLS225 A4J225 JFL225
R8 180A-5 147 300 600 JJS-300 JLLS300 A6T300 TJS300 JKS-300 JLS300 A4T300 JFL300

Frame 480 V Input UL Fuse Size (A) UL 248-8 High Speed Class J Fuses UL 248-4 Class CC Fast Acting Fuses UL 248-17
Size ACS880-31 Current and Voltage (V) Class CF
Fast Acting
Cube Fuse
Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison Bussmann
A A V Shawmut Shawmut
R3 07A6-5 5.8 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R3 11A0-5 7.8 20 600 DFJ-20 LDFJ020 HSJ20 JHL20 KTK-R-20 KLKR20 ATMR20 HCLR20 FCF20RN
R3 014A-5 10.6 25 600 DFJ-25 LDFJ025 HSJ25 JHL25 KTK-R-25 KLKR25 ATMR25 HCLR25 FCF25RN
R3 021A-5 15.6 35 600 DFJ-35 LDFJ035 HSJ35 JHL35 - - - - FCF35RN
R6 027A-5 21.3 40 600 DFJ-40 LDFJ040 HSJ40 JHL40 - - - - FCF40RN
R6 034A-5 26.2 50 600 DFJ-50 LDFJ050 HSJ50 JHL50 - - - - FCF50RN
R6 040A-5 31.2 60 600 DFJ-60 LDFJ060 HSJ60 JHL60 - - - - FCF60RN
R6 052A-5 40.1 80 600 DFJ-80 LDFJ080 HSJ80 JHL80 - - - - FCF80RN
R6 065A-5 49.5 90 600 DFJ-90 LDFJ090 HSJ90 JHL90 - - - - FCF90RN
R6 077A-5 60.2 110 600 DFJ-110 LDFJ110 HSJ110 JHL110 - - - - -
R8 101A-5 74 150 600 DFJ-150 LDFJ150 HSJ150 JHL150 - - - - -
R8 124A-5 100 200 600 DFJ-200 LDFJ200 HSJ200 JHL200 - - - - -
R8 156A-5 120 225 600 DFJ-225 LDFJ225 HSJ225 JHL225 - - - - -
R8 180A-5 147 300 600 DFJ-300 LDFJ300 HSJ300 JHL300 - - - - -
3AXD10001032874.xls Rev B

3AXD50000645015 21
REV A Effective: 12/6/2019
Table 16: ACS880-11, 480 V

Frame 480 V Input UL Fuse Size (A) UL 248-15 Class T Fast Acting Fuses UL 248-8 Fast Acting Class J Fuses
Size ACS880-11 Current and Voltage (V)
Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison
A A V Shawmut Shawmut
R3 07A6-5 5.8 15 600 JJS-15 JLLS015 A6T15 TJS15 JKS-15 JLS15 A4J15 JFL15
R3 11A0-5 7.8 20 600 JJS-20 JLLS020 A6T20 TJS20 JKS-20 JLS20 A4J20 JFL20
R3 014A-5 10.6 25 600 JJS-25 JLLS025 A6T25 TJS25 JKS-25 JLS25 A4J25 JFL25
R3 021A-5 15.6 35 600 JJS-35 JLLS035 A6T35 TJS35 JKS-35 JLS35 A4J35 JFL35
R6 027A-5 21.3 40 600 JJS-40 JLLS040 A6T40 TJS40 JKS-40 JLS40 A4J40 JFL40
R6 034A-5 26.2 50 600 JJS-50 JLLS050 A6T50 TJS50 JKS-50 JLS50 A4J50 JFL50
R6 040A-5 31.2 60 600 JJS-60 JLLS060 A6T60 TJS60 JKS-60 JLS60 A4J60 JFL60
R6 052A-5 40.1 80 600 JJS-80 JLLS080 A6T80 TJS80 JKS-80 JLS80 A4J80 JFL80
R6 065A-5 49.5 90 600 JJS-90 JLLS090 A6T90 TJS90 JKS-90 JLS90 A4J90 JFL90
R6 077A-5 60.2 110 600 JJS-110 JLLS110 A6T110 TJS110 JKS-110 JLS110 A4J110 JFL110
R8 101A-5 74 150 600 JJS-150 JLLS150 A6T150 TJS150 JKS-150 JLS150 A4J150 JFL150
R8 124A-5 100 200 600 JJS-200 JLLS200 A6T200 TJS200 JKS-200 JLS200 A4J200 JFL200
R8 156A-5 120 225 600 JJS-225 JLLS225 A6T225 TJS225 JKS-225 JLS225 A4J225 JFL225
R8 180A-5 147 300 600 JJS-300 JLLS300 A6T300 TJS300 JKS-300 JLS300 A4T300 JFL300

Frame 480 V Input UL Fuse Size (A) UL 248-8 High Speed Class J Fuses UL 248-4 Class CC Fast Acting Fuses UL 248-17
Size ACS880-11 Current and Voltage (V) Class CF
Fast Acting
Cube Fuse
Maximum Voltage Mersen/ Mersen/
Current Rating Bussmann Littelfuse Ferraz Edison Bussmann Littelfuse Ferraz Edison Bussmann
A A V Shawmut Shawmut
R3 07A6-5 5.8 15 600 DFJ-15 LDFJ015 HSJ15 JHL15 KTK-R-15 KLKR15 ATMR15 HCLR15 FCF15RN
R3 11A0-5 7.8 20 600 DFJ-20 LDFJ020 HSJ20 JHL20 KTK-R-20 KLKR20 ATMR20 HCLR20 FCF20RN
R3 014A-5 10.6 25 600 DFJ-25 LDFJ025 HSJ25 JHL25 KTK-R-25 KLKR25 ATMR25 HCLR25 FCF25RN
R3 021A-5 15.6 35 600 DFJ-35 LDFJ035 HSJ35 JHL35 - - - - FCF35RN
R6 027A-5 21.3 40 600 DFJ-40 LDFJ040 HSJ40 JHL40 - - - - FCF40RN
R6 034A-5 26.2 50 600 DFJ-50 LDFJ050 HSJ50 JHL50 - - - - FCF50RN
R6 040A-5 31.2 60 600 DFJ-60 LDFJ060 HSJ60 JHL60 - - - - FCF60RN
R6 052A-5 40.1 80 600 DFJ-80 LDFJ080 HSJ80 JHL80 - - - - FCF80RN
R6 065A-5 49.5 90 600 DFJ-90 LDFJ090 HSJ90 JHL90 - - - - FCF90RN
R6 077A-5 60.2 110 600 DFJ-110 LDFJ110 HSJ110 JHL110 - - - - -
R8 101A-5 74 150 600 DFJ-150 LDFJ150 HSJ150 JHL150 - - - - -
R8 124A-5 100 200 600 DFJ-200 LDFJ200 HSJ200 JHL200 - - - - -
R8 156A-5 120 225 600 DFJ-225 LDFJ225 HSJ225 JHL225 - - - - -
R8 180A-5 147 300 600 DFJ-300 LDFJ300 HSJ300 JHL300 - - - - -
3AXD10001032874.xls Rev B

3AXD50000645015 22
REV A Effective: 12/6/2019