0% found this document useful (0 votes)
17 views11 pages

Schneider Electric - TeSys-Deca-frame-4 - GV4P07N

The document provides a detailed datasheet for the TeSys GV4 motor circuit breaker, model GV4P07N, which features a 3-pole design with a rated current of 7A and a breaking capacity of 50kA. It includes specifications such as operational voltage, thermal and electrical durability, dimensions, and environmental standards, along with information on its sustainability and compliance with various regulations. The product is suitable for motor protection and can operate in various positions with specific terminal connections.

Uploaded by

iqbal hussein
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
17 views11 pages

Schneider Electric - TeSys-Deca-frame-4 - GV4P07N

The document provides a detailed datasheet for the TeSys GV4 motor circuit breaker, model GV4P07N, which features a 3-pole design with a rated current of 7A and a breaking capacity of 50kA. It includes specifications such as operational voltage, thermal and electrical durability, dimensions, and environmental standards, along with information on its sustainability and compliance with various regulations. The product is suitable for motor protection and can operate in various positions with specific terminal connections.

Uploaded by

iqbal hussein
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

Product datasheet

Specifications

Motor circuit breaker, TeSys GV4,


3P, 7A, Icu 50kA, thermal
magnetic, Everlink terminals
GV4P07N

Main
Range Of Product TeSys GV4

Range TeSys Deca


TeSys Deca

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Device Short Name GV4P

Product Name TeSys GV4


TeSys Deca

Product Or Component Type Motor circuit breaker

Device Application Motor protection

Trip Unit Technology Electronic


Thermal-magnetic

Complementary
Poles Description 3P

Utilisation Category Category A conforming to IEC 60947-2


AC-3 conforming to IEC 60947-4-1

Operating Position Any position

Motor Power Kw 1.5 kW at 400...415 V AC 50/60 Hz


2.2 kW at 400...415 V AC 50/60 Hz
2.5 kW at 400...415 V AC 50/60 Hz
3 kW at 400...415 V AC 50/60 Hz
2.2 kW at 500 V AC 50/60 Hz
2.5 kW at 500 V AC 50/60 Hz
3 kW at 500 V AC 50/60 Hz
4 kW at 500 V AC 50/60 Hz
3 kW at 660...690 V AC 50/60 Hz
4 kW at 660...690 V AC 50/60 Hz
5.5 kW at 660...690 V AC 50/60 Hz
7.5 kW at 660...690 V AC 50/60 Hz

Breaking Capacity 100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2


50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 208Y/120 V AC 50/60 Hz conforming to UL 60947
65 kA at 240 V AC 50/60 Hz conforming to UL 60947
35 kA at 480Y/277 V AC 50/60 Hz conforming to UL 60947
8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
18 kA at 600Y/347 V AC 50/60 Hz conforming to UL 60947

Control Type Rotary handle

[In] Rated Current 7A

Magnetic Tripping Current 119 A

[Ue] Rated Operational Voltage 690 V AC 50/60 Hz conforming to IEC 60947-2

[Ui] Rated Insulation Voltage 800 V AC 50/60 Hz conforming to IEC 60947-2

15-Apr-2024 1
[Ith] Conventional Free Air 115 A conforming to IEC 60947-4-1
Thermal Current
[Uimp] Rated Impulse Withstand 8 kV conforming to IEC 60947-2
Voltage
Power Dissipation Per Pole 4.6 W

Mechanical Durability 40000 cycles

Electrical Durability 40000 cycles for AC-3 at 440 V In/2


40000 cycles for AC-3 at 440 V In

Maximum Operating Rate 25 cyc/h

Rated Duty Continuous conforming to IEC 60947-4-1

Connections - Terminals EverLink BTR screw connectors (top) 1 cable(s) 1.5…70 mm² - solid
EverLink BTR screw connectors (top) 1 cable(s) 1.5…50 mm² - flexible
EverLink BTR screw connectors (bottom) 1 cable(s) 2.5…95 mm² - solid
EverLink BTR screw connectors (bottom) 1 cable(s) 2.5…70 mm² - flexible

Tightening Torque 9 N.m for cable 16…95 mm²


5 N.m for cable 1.5…10 mm²

Mechanical Robustness Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6


Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
Shocks: 15 gn 11 ms conforming to IEC 60068-2-27

Phase Failure Sensitivity Yes conforming to IEC 60947-4-1

Height 155 mm

Width 81 mm

Depth 165 mm

Net Weight 1.6 kg

Colour Grey (RAL 7016)

Suitability For Isolation Yes conforming to IEC 60947-1

Environment
Standards CSA C22.2 No 60947-4-1
UL 60947-4-1
EN/IEC 60947-4-1
EN/IEC 60947-2

Product Certifications IEC


UL
CSA
CCC
EAC
ATEX
EU-RO MR

Climatic Withstand conforming to IACS E10

Ik Degree Of Protection IK07 conforming to IEC 62262

Pollution Degree 3

Ip Degree Of Protection IP40 conforming to IEC 60529

Ambient Air Temperature For -50…85 °C


Storage
Fire Resistance 960 °C conforming to IEC 60695-2-11

Operating Altitude 5000 m

Ambient Air Temperature For -25…70 °C


Operation

Packing Units
Unit Type Of Package 1 PCE

2 15-Apr-2024
Number Of Units In Package 1 1

Package 1 Height 12.5 cm

Package 1 Width 20.8 cm

Package 1 Length 22.0 cm

Package 1 Weight 1.95 kg

Unit Type Of Package 2 S03

Number Of Units In Package 2 5

Package 2 Height 30.0 cm

Package 2 Width 30.0 cm

Package 2 Length 40.0 cm

Package 2 Weight 10.15 kg

Contractual warranty
Warranty 18 months

15-Apr-2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

 Pvc Free

 Halogen Free Plastic Parts Product

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile End of Life Information

4 15-Apr-2024
Product datasheet GV4P07N

Performance Curves

Thermal-Magnetic Tripping Curves for GV4P, GV4PE, GV4PEM


Average Operating Times at 20 °C Related to Multiples of the Setting Current
Hot state

1 Class 10

2 Class 20

3 Isd = 5...13x Ir

4 Ii = 17 In

Cold state

15-Apr-2024 5
Product datasheet GV4P07N

1 Class 10

2 Class 20

3 Isd = 5...13x Ir

4 Ii = 17 In

Current Limitation on Short-Circuit for GV4P, GV4PE, GV4PEM (3-Phase 400/415 V)


Dynamic Stress
I peak = f (prospective Isc) at 1.05 Ue = 435 V

6 15-Apr-2024
Product datasheet GV4P07N

1 Maximum peak current

2 GV4P115

3 GV4P80

4 GV4P50

5 GV4P25

6 GV4P12

7 GV4P07

8 GV4P03

9 GV4P02

Thermal Limit on Short-Circuit for GV4P, GV4PE, GV4PEM


Thermal Limit in kA22s in the Magnetic Operating Zone
Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V

15-Apr-2024 7
Product datasheet GV4P07N

1 GV4P115

2 GV4P80

3 GV4P50

4 GV4P25

5 GV4P12

6 GV4P07

7 GV4P03

8 GV4P02

8 15-Apr-2024
Product datasheet GV4P07N

Dimensions Drawings

GV4 with Toggle: GV4LE, GV4PE, GV4PEM


With EverLink® Connector

With Crimp Lug Connector

GV4 with Rotary Handle: GV4L, GV4P, or GV4LE, GV4PE, GV4PEM with GV4ADN01,
GV4ADN02 Direct Mounting Rotary Handle
Dimensions

GV4L, GV4P, GV4LE, GV4PE, GV4PEM


Panel Mounting with M4 Screws

15-Apr-2024 9
Product datasheet GV4P07N

Door Cut-Out for Rotary Handle

Minimum Safety Clearance

Toggle-type, rotary handle-type: identical clearance values.


Safety Clearance (mm)
Painted Sheet Metal Bare Sheet Metal
A B C A B C

No accessory 30 0 0 40 0 5

Interphase barriers 0 0 0 0 0 5

Long terminal shield 0 0 0 0 0 5

10 15-Apr-2024
Product datasheet GV4P07N

Connections and Schema

Magnetic Motor Circuit Breakers


GV4P, GV4PE, GV4PEM

15-Apr-2024 11

You might also like