Schneider Electric - Zelio-Logic - SR3B101BD
Schneider Electric - Zelio-Logic - SR3B101BD
Specifications
Main
Range of Product Zelio Logic
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product or Component Type Modular smart relay
Complementary
Local display With
Voltage state 1 guaranteed >= 15 V I1...IA and IH...IR discrete input circuit
>= 15 V IB...IG used as discrete input circuit
Voltage state 0 guaranteed <= 5 V I1...IA and IH...IR discrete input circuit
<= 5 V IB...IG used as discrete input circuit
<= 5 V
Current state 1 guaranteed >= 1.2 mA IB...IG used as discrete input circuit)
>= 2.2 mA I1...IA and IH...IR discrete input circuit)
Current state 0 guaranteed <= 0.5 mA IB...IG used as discrete input circuit)
<= 0.75 mA I1...IA and IH...IR discrete input circuit)
Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.
Operating distance 10 m between stations, with screened cable (sensor not isolated) analogue input
circuit
Electrical durability AC-12 500000 cycles 230 V, 1.5 A relay output IEC 60947-5-1
AC-15 500000 cycles 230 V, 0.9 A relay output IEC 60947-5-1
DC-12 500000 cycles 24 V, 1.5 A relay output IEC 60947-5-1
DC-13 500000 cycles 24 V, 0.6 A relay output IEC 60947-5-1
Connections - terminals Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) semi-solid
Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) solid
Screw terminals, 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) solid
Screw terminals, 2 x 0.25...2 x 0.75 mm² AWG 24...AWG 18) flexible with cable end
Environment
Immunity to microbreaks 1 ms
Ambient air temperature for -4…104 °F (-20…40 °C) in non-ventilated enclosure IEC 60068-2-1 and IEC
operation 60068-2-2
-4…131 °F (-20…55 °C) IEC 60068-2-1 and IEC 60068-2-2
GTIN 3389110549898
Returnability Yes
Country of origin US
Packing Units
Unit Type of Package 1 PCE
Contractual warranty
Warranty 18 months
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.
Environmental footprint
Use Better
Use Again
Take-back No
Dimensions Drawings
Position of Display
Analog Inputs
SR2•12••D IB…IE
SR2A201BD IB and IC
SR2D201BD IB and IC
SR2B20••D IB…IG
SR2E201BD IB…IG
SR3B10•BD IB…IE
SR3B26••D IB…IG
NOTE: Ix = IB...IG
Performance Curves
X: Current (A)
Y: Millions of operating cycles
(1) DC-12: control of resistive loads and of solid state loads isolated by opto-coupler, L/R ≤ 1 ms.
DC-13 (1)
X: Current (A)
Y: Millions of operating cycles
(1) DC-13: switching electromagnets, L/R ≤ 2 x (Ue x Ie) in ms, Ue: rated operational voltage, Ie: rated operational
current (with a protection diode on the load, DC-12 curves must be used with a coefficient of 0.9 applied to the number
in millions of operating cycles).