0% found this document useful (0 votes)
28 views11 pages

Schneider Electric - Zelio-Logic - SR3B101BD

The document provides a detailed product data sheet for the Zelio Logic modular smart relay SR3B101BD, which features 10 I/O, a local display, and 4 relay outputs. It includes specifications such as voltage ratings, input/output characteristics, environmental conditions, and compliance certifications. The product is available for a list price of 282.00 USD and is designed for various applications with a focus on sustainability and environmental impact.

Uploaded by

pradeep
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views11 pages

Schneider Electric - Zelio-Logic - SR3B101BD

The document provides a detailed product data sheet for the Zelio Logic modular smart relay SR3B101BD, which features 10 I/O, a local display, and 4 relay outputs. It includes specifications such as voltage ratings, input/output characteristics, environmental conditions, and compliance certifications. The product is available for a list price of 282.00 USD and is designed for various applications with a focus on sustainability and environmental impact.

Uploaded by

pradeep
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

Product data sheet

Specifications

modular smart relay, Zelio Logic


SR2 SR3, 10 IO, 24V DC, clock,
display, 4 relay outputs
SR3B101BD

Product availability: Stock - Normally stocked in distribution


facility

Price*: 282.00 USD

Main
Range of Product Zelio Logic

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product or Component Type Modular smart relay

Complementary
Local display With

Number or control scheme lines 0…500 FBD


0…240 ladder

Cycle time 6…90 ms

Backup time 10 years 77 °F (25 °C)

Clock drift 12 min/year 32…131 °F (0…55 °C)


6 s/month 77 °F (25 °C)

Checks Program memory on each power up

[Us] rated supply voltage 24 V

Supply voltage limits 19.2…30 V

Maximum supply current 100 mA with extensions)


100 mA without extension)

Power dissipation in W 3 W without extension


8 W with extensions

Reverse polarity protection With

Discrete input number 6 IEC 61131-2 Type 1

Discrete input type Resistive

Discrete input voltage 24 V DC

Discrete input current 4 mA

Counting frequency 1 kHz discrete input

Voltage state 1 guaranteed >= 15 V I1...IA and IH...IR discrete input circuit
>= 15 V IB...IG used as discrete input circuit

Voltage state 0 guaranteed <= 5 V I1...IA and IH...IR discrete input circuit
<= 5 V IB...IG used as discrete input circuit
<= 5 V

Current state 1 guaranteed >= 1.2 mA IB...IG used as discrete input circuit)
>= 2.2 mA I1...IA and IH...IR discrete input circuit)

Current state 0 guaranteed <= 0.5 mA IB...IG used as discrete input circuit)
<= 0.75 mA I1...IA and IH...IR discrete input circuit)

Input compatibility 3-wire proximity sensors PNP discrete input

Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.

Jan 25, 2025 1


Analogue input number 4

Analogue Input Type Common mode

Analogue input range 0...10 V


0...24 V

Temperature probe type NTC 10k 77 °F (25 °C)


NTC 1000k 77 °F (25 °C)
KTY81 210/220/221/222/250
Pt 500

Maximum permissible voltage 30 V analogue input circuit

Analogue input resolution 8 bits

LSB value 39 mV analogue input circuit

Conversion time Smart relay cycle time analogue input circuit

Conversion error +/- 5 % 77 °F (25 °C) analogue input circuit


+/- 6.2 % 131 °F (55 °C) analogue input circuit

Repeat accuracy +/- 2 % 131 °F (55 °C) analogue input circuit

Operating distance 10 m between stations, with screened cable (sensor not isolated) analogue input
circuit

Input impedance 12 kOhm IB...IG used as analogue input circuit


12 kOhm IB...IG used as discrete input circuit
7.4 kOhm I1...IA and IH...IR discrete input circuit

Number of Outputs 4 relay

Output voltage limits 24...250 V AC relay output)


5...30 V DC relay output)

Contacts type and composition NO relay output

Output thermal current 8 A for all 4 outputs relay output

Electrical durability AC-12 500000 cycles 230 V, 1.5 A relay output IEC 60947-5-1
AC-15 500000 cycles 230 V, 0.9 A relay output IEC 60947-5-1
DC-12 500000 cycles 24 V, 1.5 A relay output IEC 60947-5-1
DC-13 500000 cycles 24 V, 0.6 A relay output IEC 60947-5-1

Switching capacity in mA >= 10 mA 12 V relay output)

Operating rate in Hz 0.1 Hz at Ie)relay output


10 Hz no load)relay output

Mechanical durability 10000000 cycles relay output

[Uimp] rated impulse withstand 4 kV EN/IEC 60947-1 and EN/IEC 60664-1


voltage
Clock With

Response time 10 ms from state 0 to state 1)relay output


5 ms from state 1 to state 0)relay output

Connections - terminals Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) semi-solid
Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) solid
Screw terminals, 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) solid
Screw terminals, 2 x 0.25...2 x 0.75 mm² AWG 24...AWG 18) flexible with cable end

tightening torque 4.4 lbf.in (0.5 N.m)

Overvoltage category III conforming to IEC 60664-1

Net Weight 0.55 lb(US) (0.25 kg)

Environment
Immunity to microbreaks 1 ms

2 Jan 25, 2025


Product Certifications GOST
UL
C-tick
CSA
GL

Standards IEC 60068-2-6 Fc


IEC 61000-4-11
IEC 60068-2-27 Ea
IEC 61000-4-4 level 3
IEC 61000-4-3
IEC 61000-4-6 level 3
IEC 61000-4-2 level 3
IEC 61000-4-5
IEC 61000-4-12

IP degree of protection IP20 IEC 60529 terminal block)


IP40 IEC 60529 front panel)

Environmental characteristic EMC directive conforming to IEC 61000-6-2


EMC directive conforming to IEC 61000-6-3
EMC directive conforming to IEC 61000-6-4
EMC directive conforming to IEC 61131-2 zone B
Low voltage directive conforming to IEC 61131-2

Disturbance radiated/conducted Class B EN 55022-11 group 1

Pollution degree 2 IEC 61131-2

Ambient air temperature for -4…104 °F (-20…40 °C) in non-ventilated enclosure IEC 60068-2-1 and IEC
operation 60068-2-2
-4…131 °F (-20…55 °C) IEC 60068-2-1 and IEC 60068-2-2

Ambient Air Temperature for -40…158 °F (-40…70 °C)


Storage
Operating altitude 6561.68 ft (2000 m)

Maximum altitude transport 10000.0000000000 ft (3048 m)

Relative Humidity 95 % without condensation or dripping water

Ordering and shipping details


Category US1000I22378

Discount Schedule 000I

GTIN 3389110549898

Returnability Yes

Country of origin US

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 2.76 in (7.000 cm)

Package 1 Width 3.54 in (9.000 cm)

Package 1 Length 4.02 in (10.200 cm)

Package 1 Weight 8.360 oz (237.000 g)

Unit Type of Package 2 S03

Number of Units in Package 2 30

Package 2 Height 11.81 in (30.000 cm)

Package 2 Width 11.81 in (30.000 cm)

Package 2 Length 15.75 in (40.000 cm)

Jan 25, 2025 3


Package 2 Weight 16.731 lb(US) (7.589 kg)

Contractual warranty
Warranty 18 months

4 Jan 25, 2025


Environmental Data

Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.

Environmental Data explained

How we assess product sustainability

Environmental footprint

Carbon footprint (kg CO2 eq, Total Life cycle) 118

Environmental Disclosure Product Environmental Profile

Use Better

Materials and Substances

Packaging made with recycled cardboard Yes

Packaging without single use plastic Yes

Pro-active compliance (Product out of EU RoHS legal


EU RoHS Directive
scope)

SCIP Number Eee2fc35-1620-4b70-b1d5-206e9240044e

REACh Regulation REACh Declaration

China RoHS Regulation China RoHS declaration

WARNING: This product can expose you to chemicals


including: Lead and lead compounds, which is known to
California proposition 65 the State of California to cause cancer and birth defects
or other reproductive harm. For more information go to
www.P65Warnings.ca.gov

PVC free Yes

Use Again

Repack and remanufacture

Circularity Profile End of Life Information

The product must be disposed on European Union


WEEE markets following specific waste collection and never end
up in rubbish bins.

Take-back No

Jan 25, 2025 5


Product data sheet SR3B101BD

Dimensions Drawings

Compact and Modular Smart Relays

Mounting on 35 mm/1.38 in. DIN Rail

(1) With SR2USB01 or SR2BTC01

Screw Fixing (Retractable Lugs)

(1) With SR2USB01 or SR2BTC01

Position of Display

6 Jan 25, 2025


Product data sheet SR3B101BD

Connections and Schema

Compact and Modular Smart Relays

Connection of Smart Relays on DC Supply

(1) 1 A quick-blow fuse or circuit-breaker.


(2) Fuse or circuit-breaker.
(3) Inductive load.
(4) Q9 and QA: 5 A (max. current in terminal C: 10 A).

Discrete Input Used for 3-Wire Sensors

(1) 1 A quick-blow fuse or circuit-breaker.

Jan 25, 2025 7


Product data sheet SR3B101BD

Connection of Smart Relays on DC Supply

Analog Inputs

(1) 1 A quick-blow fuse or circuit-breaker.


(2) Ca: Analog sensor / Ta: Analog transmitter.
(3) Recommended values: 2.2 kΩ / 0.5 W (10 kΩ max.)
(4) Screened cables, maximum length 10 m / 32.80 feet.
(5) Analog inputs according to Zelio Logic smart relay type (see table below)
(6) 0-10 Vdc ANALOG
Smart Relays Analog Inputs

SR2•12••D IB…IE

SR2A201BD IB and IC

SR2D201BD IB and IC

SR2B20••D IB…IG

SR2E201BD IB…IG

SR3B10•BD IB…IE

SR3B26••D IB…IG

8 Jan 25, 2025


Product data sheet SR3B101BD

Connection of Smart Relays on DC Supply, with Discrete I/O Extension Modules

SR3B•••JD + SR3XT•••JD, SR3B•••BD + SR3XT•••BD

(1) 1 A quick-blow fuse or circuit-breaker.


(2) Ca: Analog sensor / Ta: Analog transmitter.
(3) Recommended values: 2.2 kΩ / 0.5 W (10 kΩ max.)
(4) Screened cables, maximum length 10 m / 32.80 feet.

NOTE: QF and QG : 5 A for SR3XT141••

Jan 25, 2025 9


Product data sheet SR3B101BD

Connection of Thermistor Input on DC Supply

NOTE: Ix = IB...IG

10 Jan 25, 2025


Product data sheet SR3B101BD

Performance Curves

Compact and Modular Smart Relays

Electrical Durability of Relay Outputs


(in millions of operating cycles, conforming to IEC/EN 60947-5-1)
DC-12 (1)

X: Current (A)
Y: Millions of operating cycles
(1) DC-12: control of resistive loads and of solid state loads isolated by opto-coupler, L/R ≤ 1 ms.
DC-13 (1)

X: Current (A)
Y: Millions of operating cycles
(1) DC-13: switching electromagnets, L/R ≤ 2 x (Ue x Ie) in ms, Ue: rated operational voltage, Ie: rated operational
current (with a protection diode on the load, DC-12 curves must be used with a coefficient of 0.9 applied to the number
in millions of operating cycles).

Jan 25, 2025 11