Tender Drawing
Tender Drawing
230
0.230
C9 C10 C11 0.230 0.150 0.230 0.230
4.300 3.690 1.130
2.780
TYPE DESCRIPTION NOS. SILL LVL. LINTEL LVL. LOCATION
2.700
SIZE
2.080
3.350
3.350
FW 1.80 X 2.40 M ANODIZED 2 TRACK ALUMINUM FRENCH WINDOW 03 F.F.L 2.4 BALCONY
0.150
WITH 5mm THK CLEAR GLASS SHUTTER WITH
C8 GRANITE FRAME.
0.230
2.430 ANODIZED 3 TRACK ALUMINUM FRENCH WINDOW,
W 1.50 X 1.50 M
C7 2.870 RW1 ONE SHUTTER WITH S.S MOSQUITO NET & TWO 06 0.9 2.4 BEDROOM,
WITH 5MM THK CLEAR GLASS SHUTTER WITH KITCHEN
2.870
GRANITE FRAME.
1.500
0.230
WITH 5MM THK CLEAR GLASS SHUTTER WITH
1.440 1.800 GRANITE FRAME.
1.440 1.800 V 0.60 X 0.90 M ANODIZED ALUMINUM FRAME WITH 4mm THK. 02 1.5 2.4 TOILET
4.780
FROSTED GLASS LOUVERED VENTILATORS WITH
4.780
RW1
4.130
3.130
2.400
2.400
1.500
0.230
0.230
C4
TYPE SIZE DESCRIPTION NOS. SILL LVL. LINTEL LVL. LOCATION
4.380
C5 2.830 D 1.00 X 2.10 M 35 mm THK BOTH SIDE LAMINATED MACHINE 01 F.F.L 2.10 LIVING
4.380 C6 PRESSED SOLID CORE SINGLE SHUTTER ENTRY
1.700
OPENABLE FLUSH DOOR WITH PEEP HOLE &
SAFETY CHAIN AND WITH TEAK WOOD DOOR
FRAME OF SIZE 125 mm x 75 mm.
D1 0.90 X 2.10 M 35 mm THK BOTH SIDE LAMINATED MACHINE 03 F.F.L 2.10 BEDROOM
PRESSED SOLID CORE SINGLE SHUTTER
3.500
3.500
OPENABLE FLUSH DOOR WITH R.C.C DOOR
A A FRAME OF SIZE 65 mm X 125 mm.
0.230
0.230
2.680 3.130
0.230
0.230
1.000
1.000
3.050 1.020 1.320 3.500
0.230 0.230 0.150 0.230 0.230
CONSULTANCY [email protected]
AURANGABAD | JAIPUR
SATARA PARISAR, AURANGABAD - 431001
DWG. NO. 2K18 - 06 REVISION R-0
SCALE NTS DATE 20-05-2018
PARAPET WALL LVL
v v
v v
v v
SUZU
KI
GSX
750F
SACS
SUZ
UKI
PLINTH LVL
CONSULTANCY [email protected]
AURANGABAD | JAIPUR
SATARA PARISAR, AURANGABAD - 431001
DWG. NO. 2K18 - 06 REVISION R-0
SCALE NTS DATE 20-05-2018
C9 C10 C11
11900
11785
11600
C8
8855
C7
RW1
8205
LIFT RW2
6475
RW1
C4 C5 C6
3845
C1 C2 C3
115
0
4755
4830
0
300
4645
8670
9660
9845
9960
PROJECT CONSTRUCTION OF ONE FLOOR ONE FLAT
BUILDING FOR Mr. NYATI @ NASHIK , DIST- NASHIK
C9 C10 C11
600X230 600X230 600X230
C8
600X230
C7
600X230
LIFT
C4 C5 C6
600X230 450X230 600X230
A A
C1 C2 C3
600X230 600X230 600X230
FOUNDATION PLAN
TYP. COLUMN FOOTING PLAN
THK slab
150mm
15
THK slab
0
150mm
0 10 @ 100 C/C
15 50
8 @ 200 C/C
0
8 @ 200 C/C
0
10 @ 100 C/C 50 1560
BEAM
8 @ 200 C/C
910
10 @ 100 C/C
BEAM
10 @ 100 C/C
29
15
15
29
10 @ 100 C/C
10 @ 100 C/C
910 BEAM
8 @ 200 C/C 10 @ 100 C/C
BEAM 1560
10 @ 100 C/C 8 @ 200 C/C
SECTION 1 - 1 SECTION 2 - 2
REINFORCEMENT
FOOTING FOOTING P.C.C 100THK FOOTING + 6.00
MARK TYPE 1:3:6 SIZE (L X B X D) SHORTER SIDE LONGER SIDE
+ 3.00
F-1 BOX 2800 X 2400 2600 X 2200 X 400 12T @150C/C 12T @150C/C
± 0.00
F-2 BOX 2200 X 2000 2000 X 1800 X 400 12T @150C/C 10T @150C/C
LIFT BOX 2760 X 2760 2560 X 2560 X 400 For R/F Details Refer Lift Section
GENERAL NOTES DRAWING ISSUED FOR - APPROVAL, ESTIMATION, EXECUTION, STUDY PURPOSE 13. DESHUTTERING PERIOD SHALL NOT BE LESS THAN - 18. IN NO CASE THIS DRAWING SHALL BE USED FOR ANY SIMILAR PROJECT CONSTRUCTION OF ONE FLOOR ONE FLAT
PROJECT, AT ANY OTHER PLACES
1. ALL DIMENSIONS ARE IN MM UNLESS MENTIONED OTHERWISE. 8. CLEAR COVER TO THE MAIN REINFORCEMENT SHALL BE a VERTICAL FACES OF COLUMN BEAMS & WALLS = 24 HOURS. 19. COLUMNS AND FOOTINGS ARE DESIGNED FOR PARKING + BUILDING FOR Mr. NYATI @ NASHIK , DIST- NASHIK
2. REFER THIS DRAWING ALONG WITH ARCHITECTURAL DRAWING. FOUNDATIONS - 50 MM, COLUMNS - 40 MM, BEAMS - 25 MM, SLABS - 03 FLOOR, TOTAL 4 STOREY BUILDING.
3. DO NOT SCALE THE DRAWING, REFER WRITTEN DIMENSIONS ONLY. 20 MM, RCC PARDI - 40 MM
SLAB SPANNING UPTO 3.50 M. = 7 DAYS. 20. DO NOT CAST ANY R.C.C WORK UNLESS IT IS CHECKED
4. ANY DISCREPANCY IN INFORMATION OR CO-ORDINATION IN THIS AND CONFIRMED BY ENGINEER.
9. LAP LENGTHS OR DEVELOPMENT LENGTH (LD) FOR 8T, 10T, 12T, 16T,
SLAB SPANNING OVER 3.50 M. = 14 DAYS. 21. AT DISCONTINUOUS ENDS TOP & BOTTOM BARS SHALL DRG. TITLE LAYOUT OF FOOTINGS & COLUMN SCHEDULE
DRAWING SHOULD BE BROUGHT TO THE CONSULTANTS BEFORE THE 20T, SHOULD BE 400 MM, 500 MM, 600 MM,800 MM, 1000 MM
FINAL EXECUTION OF WORKS. RESPECTIVELY. (LD=50XD) HAVE ELL BENDS.
BEAMS BOTTOM = 21 DAYS.
5. ALL WORKS SHOULD BE EXECUTED IN ACCORDANCE WITH THE GOOD 10. THE LAPS IN BARS SHALL BE STAGGERED AND AT ONE PLACE SHALL CONSULTANCY [email protected]
EXECUTION TO RELEVANT INDIAN STANDARD CODES OF PRACTICES. NOT BE MORE THAN 33.3 PERCENT AND MAXIMUM UP TO 50 16. IN BEAMS WHERE THERE ARE MORE THAN ONE LAYER OF REINF. A SPACER
6. THE GRADE OF ALL R.C.C. WORK SHALL BE M25 U.N.O. (UNLESS PERCENT. BAR SHALL BE PROVIDED BETWEEN TWO LAYER AT SPACING 1500C/C THE DIA PLEASE NOTE: CONTRACTOR/OWNER OR THEIR ENGINEER IS AURANGABAD | JAIPUR
NOTED OTHERWISE) 11. a) AVOID LAPS IN BOTTOM BARS NEAR MID SPAN. OF SUCH BARS SHALL BE EQUAL TO THE MAX. SIZE OF BAR IN THE LAYERS RESPONSIBLE FOR SITE EXECUTION AS PER STRUCTURAL DRAWINGS SATARA PARISAR, AURANGABAD - 431001
7. THE REINFORCEMENT SHALL BE T.M.T. BARS (TOR BARS) b) AVOID LAPS IN TOP BARS NEAR MID SUPPORTS. (OR) MIN. 16MM. AND FOR QUALITY OF ALL CONSTRUCTION MATERIALS AND MIX
CONFIRMING TO I.S. 1786 - FE 500. 12. ALL CONCRETE SHALL BE MACHINE MIXED AND MECHANICALLY 17. PROPER CHAIRS TO BE PROVIDED TO ENSURE SPECIFIED THICKNESS OF SLAB DESIGN USED. STRUCTURAL CONSULTANT ARE RESPONSIBLE FOR DWG. NO. 2K18 - 06 REVISION R-0
VIBRATED TO RETAIN THE TOP BARS IN PROPER POSITION & ALSO PROVIDE PROPER ONLY SAFE TRANSMITTAL OF STRUCTURAL DESIGN THOUGH THESE
COVERING & PINS FOR BEAM REINFORCEMENT DRAWINGS WITH NO FURTHER RISKS SCALE NTS DATE 20-05-2018
9960
LAYOUT OF PLINTH BEAM & DETAILS, LIFT DETAILS
C9 C10 C11
4.300 3.610 1.130
2.700
3.350
3.350
2-10 Ø
8Ø-150c/c
8Ø-150c/c
1 3 2 -16 Ø
2 -16 Ø 2 -16 Ø
(ALTH.) (ALTH.) (ALTH.)
C8 2-16 Ø 8Ø @150c/c 2-16 Ø
8Ø @150c/c 8Ø @150c/c
Section 1 - 1 Section 3 - 3
BEAM TB-3 (230X450)
4.300 C7 BEAM TB-1 (230X450)
3.240
1.500
LIFT
1000 1000 1000 1000 2-12 Ø 2-10 Ø
2 -10 Ø 2 -12 Ø 2 -10 Ø 2 -12 Ø 2 -10 Ø 2 -10 Ø
2 4 (ALTH.)
(EXTRA) (ALTH.) (EXTRA) (ALTH.) (EXTRA)
4.780
11900
11900
2-10 Ø
8Ø-150c/c
8Ø-150c/c
2.400
(ALTH.) (ALTH.) (ALTH.)
2-16 Ø 3-12 Ø
8Ø @150c/c 8Ø @150c/c 8Ø @150c/c
Section 2 - 2 Section 4 - 4
2-10 Ø
3.500
8Ø-150c/c
8Ø-150c/c
C2
9960
2-10 Ø
8Ø-150c/c
2-10 Ø
8Ø-150c/c
8Ø-150c/c
8 9 3 -12 Ø
2 -16 Ø 2 -16 Ø
(ALTH.) (ALTH.) (ALTH.)
2-16 Ø 3-12 Ø
8Ø @150c/c 8Ø @150c/c 8Ø @150c/c
Section 8 - 8 Section 9 - 9
2-10 Ø
8Ø-150c/c
8Ø-150c/c
8Ø @150c/c
3 -12 Ø
(ALTH.)
3-12 Ø
8Ø @150c/c 8Ø @150c/c
Section 11 - 11 Section 10 - 10
GENERAL NOTES DRAWING ISSUED FOR - APPROVAL, ESTIMATION, EXECUTION, STUDY PURPOSE 13. DESHUTTERING PERIOD SHALL NOT BE LESS THAN - 18. IN NO CASE THIS DRAWING SHALL BE USED FOR ANY SIMILAR PROJECT CONSTRUCTION OF ONE FLOOR ONE FLAT
PROJECT, AT ANY OTHER PLACES
1. ALL DIMENSIONS ARE IN MM UNLESS MENTIONED OTHERWISE. 8. CLEAR COVER TO THE MAIN REINFORCEMENT SHALL BE a VERTICAL FACES OF COLUMN BEAMS & WALLS = 24 HOURS. 19. COLUMNS AND FOOTINGS ARE DESIGNED FOR PARKING + BUILDING FOR Mr. NYATI @ NASHIK , DIST- NASHIK
2. REFER THIS DRAWING ALONG WITH ARCHITECTURAL DRAWING. FOUNDATIONS - 50 MM, COLUMNS - 40 MM, BEAMS - 25 MM, SLABS - 03 FLOOR, TOTAL 4 STOREY BUILDING.
3. DO NOT SCALE THE DRAWING, REFER WRITTEN DIMENSIONS ONLY. 20 MM, RCC PARDI - 40 MM
SLAB SPANNING UPTO 3.50 M. = 7 DAYS. 20. DO NOT CAST ANY R.C.C WORK UNLESS IT IS CHECKED
4. ANY DISCREPANCY IN INFORMATION OR CO-ORDINATION IN THIS AND CONFIRMED BY ENGINEER.
9. LAP LENGTHS OR DEVELOPMENT LENGTH (LD) FOR 8T, 10T, 12T, 16T,
SLAB SPANNING OVER 3.50 M. = 14 DAYS. 21. AT DISCONTINUOUS ENDS TOP & BOTTOM BARS SHALL DRG. TITLE COLUMN SCHEDULE & LIFT DETAILS
DRAWING SHOULD BE BROUGHT TO THE CONSULTANTS BEFORE THE 20T, SHOULD BE 400 MM, 500 MM, 600 MM,800 MM, 1000 MM
FINAL EXECUTION OF WORKS. RESPECTIVELY. (LD=50XD) HAVE ELL BENDS.
BEAMS BOTTOM = 21 DAYS.
5. ALL WORKS SHOULD BE EXECUTED IN ACCORDANCE WITH THE GOOD 10. THE LAPS IN BARS SHALL BE STAGGERED AND AT ONE PLACE SHALL CONSULTANCY [email protected]
EXECUTION TO RELEVANT INDIAN STANDARD CODES OF PRACTICES. NOT BE MORE THAN 33.3 PERCENT AND MAXIMUM UP TO 50 16. IN BEAMS WHERE THERE ARE MORE THAN ONE LAYER OF REINF. A SPACER
6. THE GRADE OF ALL R.C.C. WORK SHALL BE M25 U.N.O. (UNLESS PERCENT. BAR SHALL BE PROVIDED BETWEEN TWO LAYER AT SPACING 1500C/C THE DIA PLEASE NOTE: CONTRACTOR/OWNER OR THEIR ENGINEER IS AURANGABAD | JAIPUR
NOTED OTHERWISE) 11. a) AVOID LAPS IN BOTTOM BARS NEAR MID SPAN. OF SUCH BARS SHALL BE EQUAL TO THE MAX. SIZE OF BAR IN THE LAYERS RESPONSIBLE FOR SITE EXECUTION AS PER STRUCTURAL DRAWINGS SATARA PARISAR, AURANGABAD - 431001
7. THE REINFORCEMENT SHALL BE T.M.T. BARS (TOR BARS) b) AVOID LAPS IN TOP BARS NEAR MID SUPPORTS. (OR) MIN. 16MM. AND FOR QUALITY OF ALL CONSTRUCTION MATERIALS AND MIX
CONFIRMING TO I.S. 1786 - FE 500. 12. ALL CONCRETE SHALL BE MACHINE MIXED AND MECHANICALLY 17. PROPER CHAIRS TO BE PROVIDED TO ENSURE SPECIFIED THICKNESS OF SLAB DESIGN USED. STRUCTURAL CONSULTANT ARE RESPONSIBLE FOR DWG. NO. 2K18 - 06 REVISION R-0
VIBRATED TO RETAIN THE TOP BARS IN PROPER POSITION & ALSO PROVIDE PROPER ONLY SAFE TRANSMITTAL OF STRUCTURAL DESIGN THOUGH THESE
COVERING & PINS FOR BEAM REINFORCEMENT DRAWINGS WITH NO FURTHER RISKS SCALE NTS DATE 20-05-2018
FLOOR SLAB & BEAM DETAILS
C9 C10 C11
4.300 3.610 1.130
2-12 Ø 1000 1000 1000 1000 2-12 Ø
2 -12 Ø 2 -12 Ø 2 -10 Ø 2 -12 Ø 2 -10 Ø 2 -12 Ø 2 -10 Ø
(ALTH.) 1 (ALTH.) (EXTRA) (ALTH.) 2 (EXTRA) (ALTH.) (EXTRA)
2.700
2-10 Ø
3.350
3.350
8Ø-150c/c 8Ø-150c/c
Section 1 - 1 Section 2 - 2
4.300 C7 BEAM B-1 (230X600) BEAM B-2 (230X600)
3.240
1.500
LIFT
2-10 Ø 1000 1000 1000 1000 2-12 Ø 2-10 Ø
2 -10 Ø 2 -10 Ø
3 (ALTH.) 2 -10 Ø 2 -12 Ø 2 -10 Ø 2 -12 Ø 2 -10 Ø 5 (ALTH.)
4
4.780
2-10 Ø
8Ø-150c/c 8Ø-150c/c 8Ø-150c/c
3 2 -12 Ø 5 3 -12 Ø
2.400
2 -16 Ø 4 2 -16 Ø
(ALTH.) (ALTH.)
(ALTH.) (ALTH.)
2-12 Ø 2-16 Ø 3-12 Ø
8Ø @150c/c 8Ø @150c/c
8Ø @150c/c 8Ø @150c/c
Section 3 - 3 Section 4 - 4 Section 5 - 5
C4 C5 4.970
BEAM B-3 (230X600) BEAM B-4 (230X600) BEAM B-5 (230X600)
C6
3.050 2.490
3.500
0.900
3.500
2-10 Ø
8Ø-150c/c
2.370
8Ø-150c/c 8Ø-150c/c
8Ø-150c/c 8Ø-150c/c
9 10 2 -16 Ø
3 -16 Ø 3 -16 Ø 3 -16 Ø
(ALTH.)
(ALTH.) (ALTH.) (ALTH.)
3-16 Ø 2-16 Ø
8Ø @150c/c 8Ø @150c/c 8Ø @150c/c 8Ø @150c/c
Section 9 - 9 Section 10 - 10
2-10 Ø
8Ø-150c/c
8Ø-150c/c 8Ø-150c/c
11 12 13 2 -12 Ø
2 -12 Ø 2 -16 Ø 2 -16 Ø
(ALTH.) (ALTH.) (ALTH.) (ALTH.)
2-12 Ø 2-16 Ø 2-12 Ø
8Ø @150c/c 8Ø @150c/c 8Ø @150c/c 8Ø @150c/c
Section 11 - 11 Section 12 - 12 Section 13 - 13
8Ø-150c/c 8Ø-150c/c
14 3 -12 Ø 15
3 -12 Ø 3 -12 Ø
(ALTH.) (ALTH.) (ALTH.)
3-12 Ø 3-12 Ø
8Ø @150c/c
8Ø @150c/c 8Ø @150c/c 8Ø @150c/c
Section 14 - 14 Section 9 - 9
GENERAL NOTES DRAWING ISSUED FOR - APPROVAL, ESTIMATION, EXECUTION, STUDY PURPOSE 13. DESHUTTERING PERIOD SHALL NOT BE LESS THAN - 18. IN NO CASE THIS DRAWING SHALL BE USED FOR ANY SIMILAR PROJECT CONSTRUCTION OF ONE FLOOR ONE FLAT
PROJECT, AT ANY OTHER PLACES
1. ALL DIMENSIONS ARE IN MM UNLESS MENTIONED OTHERWISE. 8. CLEAR COVER TO THE MAIN REINFORCEMENT SHALL BE a VERTICAL FACES OF COLUMN BEAMS & WALLS = 24 HOURS. 19. COLUMNS AND FOOTINGS ARE DESIGNED FOR PARKING + BUILDING FOR Mr. NYATI @ NASHIK , DIST- NASHIK
2. REFER THIS DRAWING ALONG WITH ARCHITECTURAL DRAWING. FOUNDATIONS - 50 MM, COLUMNS - 40 MM, BEAMS - 25 MM, SLABS - 03 FLOOR, TOTAL 4 STOREY BUILDING.
3. DO NOT SCALE THE DRAWING, REFER WRITTEN DIMENSIONS ONLY. 20 MM, RCC PARDI - 40 MM
SLAB SPANNING UPTO 3.50 M. = 7 DAYS. 20. DO NOT CAST ANY R.C.C WORK UNLESS IT IS CHECKED
4. ANY DISCREPANCY IN INFORMATION OR CO-ORDINATION IN THIS AND CONFIRMED BY ENGINEER.
9. LAP LENGTHS OR DEVELOPMENT LENGTH (LD) FOR 8T, 10T, 12T, 16T,
SLAB SPANNING OVER 3.50 M. = 14 DAYS. 21. AT DISCONTINUOUS ENDS TOP & BOTTOM BARS SHALL DRG. TITLE LAYOUT OF FLOOR BEAM & SLAB DETAILS
DRAWING SHOULD BE BROUGHT TO THE CONSULTANTS BEFORE THE 20T, SHOULD BE 400 MM, 500 MM, 600 MM,800 MM, 1000 MM
FINAL EXECUTION OF WORKS. RESPECTIVELY. (LD=50XD) HAVE ELL BENDS.
BEAMS BOTTOM = 21 DAYS.
5. ALL WORKS SHOULD BE EXECUTED IN ACCORDANCE WITH THE GOOD 10. THE LAPS IN BARS SHALL BE STAGGERED AND AT ONE PLACE SHALL CONSULTANCY [email protected]
EXECUTION TO RELEVANT INDIAN STANDARD CODES OF PRACTICES. NOT BE MORE THAN 33.3 PERCENT AND MAXIMUM UP TO 50 16. IN BEAMS WHERE THERE ARE MORE THAN ONE LAYER OF REINF. A SPACER
6. THE GRADE OF ALL R.C.C. WORK SHALL BE M25 U.N.O. (UNLESS PERCENT. BAR SHALL BE PROVIDED BETWEEN TWO LAYER AT SPACING 1500C/C THE DIA PLEASE NOTE: CONTRACTOR/OWNER OR THEIR ENGINEER IS AURANGABAD | JAIPUR
NOTED OTHERWISE) 11. a) AVOID LAPS IN BOTTOM BARS NEAR MID SPAN. OF SUCH BARS SHALL BE EQUAL TO THE MAX. SIZE OF BAR IN THE LAYERS RESPONSIBLE FOR SITE EXECUTION AS PER STRUCTURAL DRAWINGS SATARA PARISAR, AURANGABAD - 431001
FRAMING PLAN AT COLUMN FOOTING
7. THE REINFORCEMENT SHALL BE T.M.T. BARS (TOR BARS) b) AVOID LAPS IN TOP BARS NEAR MID SUPPORTS. (OR) MIN. 16MM. AND FOR QUALITY OF ALL CONSTRUCTION MATERIALS AND MIX
CONFIRMING TO I.S. 1786 - FE 500. 12. ALL CONCRETE SHALL BE MACHINE MIXED AND MECHANICALLY 17. PROPER CHAIRS TO BE PROVIDED TO ENSURE SPECIFIED THICKNESS OF SLAB DESIGN USED. STRUCTURAL CONSULTANT ARE RESPONSIBLE FOR DWG. NO. 2K18 - 06 REVISION R-0
VIBRATED TO RETAIN THE TOP BARS IN PROPER POSITION & ALSO PROVIDE PROPER ONLY SAFE TRANSMITTAL OF STRUCTURAL DESIGN THOUGH THESE
COVERING & PINS FOR BEAM REINFORCEMENT DRAWINGS WITH NO FURTHER RISKS SCALE NTS DATE 20-05-2018