0% found this document useful (0 votes)
14 views4 pages

EPRMC0400

The document provides specifications for the PERKINS Series Diesel Generator Sets, detailing standby and prime power ratings, engine and alternator specifications, and optional equipment. It emphasizes the generators' compliance with various quality standards and their suitability for emergency, prime, and continuous operation power needs. Additionally, it outlines features such as sound-proof canopies, genset controllers, and safety protection systems.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
14 views4 pages

EPRMC0400

The document provides specifications for the PERKINS Series Diesel Generator Sets, detailing standby and prime power ratings, engine and alternator specifications, and optional equipment. It emphasizes the generators' compliance with various quality standards and their suitability for emergency, prime, and continuous operation power needs. Additionally, it outlines features such as sound-proof canopies, genset controllers, and safety protection systems.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

E PR MC 0400 [email protected] | www.emsa.gen.

tr

E PR MC 0400
PERKINS Series
Diesel Generator Sets
STANDBY kVA 400
kW 320
PRIME kVA 350
kW 280

Water Cooled 50 hz Easy maintenance Modular type sound-


proof canopy

3 phase Diesel Warning system for Remote control


decreasing fuel with system
electronic fuel level
sender

Emergency Standby Power: Emergency standby power,


QUALITY STANDARDS
provided by diesel generators, acts as a backup during power
outages. These generators kick in swiftly during emergencies, Our generators are manufactured in compliance with VDE 0530,
ensuring continuity for critical operations. Ideal for homes, BSE 4999 BS5000, IEC 34, EN12601; EN60204-1; TS ISO 8528-1
businesses, and industries, their usage duration should be … -13; EN12100-1; EN12100-2; EN61000-6-4; EN61000-6-2;
limited to prevent wear. Strict standards like NFPA 110 ensure EN61000-4-11; EN61000-4-6; EN61000-4-5; EN61000-4-2;
their reliability. EN55011; EN55016-2-1; EN55016-2-3; EN61000-3-2;
EN61000-3-3; EN55014-1; EN61000-6-2; EN61000-4-3;
Prime Rated Power: Prime rated power generators serve as
EN61000-4-4; EN61000-4-8; EN61000-4-11; TS EN ISO 3744; TS
primary power sources, especially in remote locations. These
EN ISO 3746; TS EN 60034-1; TS EN 60034-22; TS EN ISO 3046;
diesel generators handle varying loads over extended periods,
BS 5514; NEMA MG 21; IEC 60034, BS 4999/5000 and TS EN
making them perfect for sites without grid access. Commonly
60947-1..4 standards.
mobile, they're crucial for mining, construction, and energy
industries, offering consistent, prime-rated power supply. We have ISO 9001-2015, ISO 14001-2015, ISO 45001-2018 and
ISO 1002-2006 management system certificates from Kiwa, an
Continuous Operation Power: Continuous operation
accredited independent quality organization.
generators offer non-stop, stable power output, especially where
grid access is inconsistent or expensive. These generators Our generators up to 400 kw are manufactured in compliance
operate at a consistent 100% load, making them indispensable with 2000/14/EC European noise emission directive and certified
for remote mining, military, or farming sites. Unlike prime-rated from Ente Certificazione Macchine.
generators, they don’t vary in power, ensuring unwavering power
delivery. We also have TS ISO 8528-4, TS ISO 8528-5, TS EN
13501-1+A1:2013 flame retardancy and TTS EN ISO 9227
certificates against anti-corrosion together with CE Declaration.

Emsa reserves the right to make changes in model, technical specifications, color, equipment &
accessories without prior notice.
1
E PR MC 0400 [email protected] | www.emsa.gen.tr

Engine Specifications

PERKINS series heavy duty diesel engine Oil discharge valve and extention pipe
4 cycle, water cooling system, turbocharged - intercooler Industrial type silencer, exhaust spiral or compensator
induction Maintenance free battery
Electronic governor system Engine block water heater (in automatic models)
12/24 volt self-starter and charger alternator Diesel gen-set maintenance and operating instructions and
Changeable air, fuel and oil filter electrical circuit diagram
Flexible fuel pipe

MODEL 2206A-E13TAG2 GOVERNOR TYPE Electronic


POWER STANDBY kW 349 Induction TURBOCHARGED - INTERCOOLER
PRIME kW 305 COMBUSTION SYSTEM DIRECT
SPEED (rpm) 1500 Cooling System WATER
Cycle 4 FUEL CONSUMPTION 100% OF PRIME 71
DISPLACEMENT (lt) 12.5 (lt/h) POWER
NUMBER OF CYLINDERS 6, in line 75% OF PRIME 54
BORE AND STROKE 130 x 157 POWER
COMPRESSION RATIO 16,3 : 1 50% OF PRIME 37
POWER
TOTAL LUBRICATION SYSTEM CAPACITY (lt) 40
TOTAL COOLANT CAPACITY (lt) 51.4

Alternator Specifications

Brushless, single bearing, flexible disc 4 poles alternator for Electronic automatic voltage regulator
harmonic failure Stator 2/3 step for harmonic failure
H type isolation class The alternator windings are protected by insulating varnish
IP 21-23 protection class against oil and acid
Self exciter

BRAND MECC ALTE Phase 3


MODEL ECO40-1S/4 A.V.R. DER-1A
FREQUENCY (HZ) 50 VOLTAGE REGULATION (+/-) ± 1%
POWER (KVA) 440 INSULATION SYSTEM Class H
DESIGN 4 pole, brushless PROTECTION IP23
CONNECTION TYPE Star RATED POWER FACTOR 0.8
VOLTAGE (V) 400 WEIGHT COMP. ALTERNATOR (KG) 1049

Genset Controllers

Datakom SMART 500-MK2

The SMART 500-MK2 is a cost effective genset controller


ready for BMS integration and internet monitoring

Emsa reserves the right to make changes in model, technical specifications, color, equipment &
accessories without prior notice.
2
E PR MC 0400 [email protected] | www.emsa.gen.tr

OPTIONAL GENSET CONTROLLERS OPTIONAL

Datakom SMART 200 Datakom D500 Datakom D500-GSM DEEPSEA 6120 DEEPSEA 7320 ComAp AMF25

Datakom Datakom Datakom Datakom DEEPSEA DEEPSEA ComAp


SMART SMART D500 D500 6120 7320 AMF25
200 500-MK2 GSM
AUTOMATIC MAINS MONITORING ✔ ✔ ✔ ✔ ✔ ✔ ✔
MANUEL START ✔ ✔ ✔ ✔ ✔ ✔ ✔
REMOTE START ✔ ✔ ✔ ✔ ✔ ✔ ✔
REMOTE MONITORING WITH SIM CARD OPTIONAL OPTIONAL OPTIONAL ✔ ✖ OPTIONAL OPTIONAL

1 ADITIONAL OPTION (HORN, OIL-FUEL ✖ OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL
HEATER ETC.)
LIGHT WARNING AND MIMIC DIAGRAM ✔ ✔ ✔ ✔ ✔ ✔ ✔
BATTERY CHARGER ✔ ✔ ✔ ✔ ✔ ✔ ✔
RS-485 COMMUNICATION OPTIONAL OPTIONAL ✔ ✔ ✖ ✔ OPTIONAL

ETHERNET (TCP-IP) COMMUNICATION ✖ ✔ ✔ ✔ ✖ OPTIONAL OPTIONAL

GENSET CONTROLLERS FOR SYNCHRONIZATION SYSTEMS OPTIONAL

Next generation synchronizing genset controller capable of every communication and functionality.

DEEPSEA 8610 DEEPSEA 8620 DEEPSEA 8660 ComAp InteliGen ComAp InteliGen 200
BaseBox

Emsa reserves the right to make changes in model, technical specifications, color, equipment &
accessories without prior notice.
3
E PR MC 0400 [email protected] | www.emsa.gen.tr

Canopy

Modular type sound-proof canopy Lockable doors on both sides of canopy


Canopy installation executed with screw and nut, without Emergency stop button
welding process Transparent panel inspection window
Epoxy and polyester powder painted canopy Insulation details: Non-flammeable acoustic foam
Weatherproof canopy rating is IP 23 Nano tech cleaning system
Canopy designed for easy maintenance Container optional

Dimensions 1600x4050x2615 * Dimensions 1500x3600x2116


(W x L x H) mm (W x L x H) mm
Weight (Kg) 3846 Weight (Kg) 3192

Fuel tank capacity (lt) 819 Fuel tank capacity (lt) 819
Internal type Internal type

External type

SILENCER OPTIONS CANOPY OPTIONS

Standard industrial type Standard canopy


Critical type Super silent canopy
Hospital type Extra super silent canopy (thicker insulation)

GEN-SET SAFETY PROTECTION & ALARMS

High water temperature Over current load


Low oil pressure High & low genset voltage
High & low engine speed Start/stop failure
Low radiator water level

OPTIONAL EQUIPMENTS

Charge ammeter 3 pole/4 pole automatic transfer panel (A.T.S.)


Moulded case circuit braker (in automatic models) Fuel and oil heater
Hospital/Critical type silencer Alternator heater
Modular type sound-proof canopy Automatic fuel filling system
Mobile - trailer Fuel-water seperator filter
Synchronization control panel for 2-16 gensets PMG warning system

Emsa reserves the right to make changes in model, technical specifications, color, equipment &
accessories without prior notice.
4

You might also like