RBU-3H24 Greenheck
RBU-3H24 Greenheck
Tag: MK-1
Quantity: 1
Printed Date: March 8, 2024
Model: RBU-3H24
Propeller Upblast Belt Drive Exhaust Fan
Standard Construction Features: Galvanized housing with butterfly dampers. Propeller, fabricated
steel. Belt driven motor in the air stream.
1.5 1.5
Fan Configuration
a
FR
e
PM
ar
d
0.9 0.9
de
a
sh
Performance 0.6 0.6
in
e
r at
Requested Volume (CFM) 6,000 e
0.3 t op 0.3
Actual Volume (CFM) 6,000 no
Do System
Total External SP (in. wg) 0.35
0 0
Fan RPM 1,338 0 1 2 3 4 5 6 7 8 9
Drive Loss (%) 10 Volume (CFM) x 1000
Operating Power (bhp) 0.87
Startup Power (bhp) 0.87 Fan curve
FEI 1.45 Brake horsepower curve
Air Stream Temp (F) 70 Operating Point SP
Start-up Temp (F) 70 Operating Bhp point
Air Density (lbs/ft^3) 0.065 Max system curve
Elevation (ft) 3698 System curve
Static Efficiency (%) 42
Outlet Velocity (ft/min) 1,833
Sound
Motor Octave Bands (hz) LwA dBA Sones
62.5 125 250 500 1000 2000 4000 8000
Size (hp) 1
V/C/P 460/60/3 Inlet 85 85 86 85 82 79 74 70 87 76 25
NEC FLA (Amps) 2.1
Min Circuit Ampacity (MCA) 2.6
Max Overload Production (MOP) 15
Greenheck Fan Corporation certifies that the model shown herein
is licensed to bear the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance with AMCA
Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program.The AMCA
certified ratings seal applies to sound and air performance and FEI
ratings only.Performance certified is for installation type A: Free
inlet, free outlet.Power rating includes transmission
losses.Performance ratings do not include the effects of
appurtenances.The sound ratings shown are loudness values in
hemispherical sones at 1.5 m (5 ft) in a hemispherical free field
calculated per ANSI/AMCA Standard 301.Values shown are for
Installation Type A: free inlet hemispherical sone levels.dBA levels
are not licensed by AMCA International. The AMCA Certified
Ratings Seal for Sound applies to inlet sone ratings only.
FLA - based on tables 150 or 148 of National Electric Code 2002. Actual
motor FLA may vary, for sizing thermal overload, consult factory.
MCA and MOP values shown only account for the motor, not accessories
(damper actuator, field supplied VFD, etc.).