0% found this document useful (0 votes)
15 views15 pages

0000-EA-E-40107 - 2 - DS-LV Cables

This document is a datasheet for low voltage cables prepared by Saipem Clough Joint Venture for Perdaman Chemicals and Fertilizers, detailing specifications for outdoor and indoor cable installations at the Burrup, Australia plant. It includes environmental conditions, electrical system parameters, cable general data, and applicable standards for manufacturing and testing. The document is marked as confidential and contains proprietary information.

Uploaded by

suseedevan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
15 views15 pages

0000-EA-E-40107 - 2 - DS-LV Cables

This document is a datasheet for low voltage cables prepared by Saipem Clough Joint Venture for Perdaman Chemicals and Fertilizers, detailing specifications for outdoor and indoor cable installations at the Burrup, Australia plant. It includes environmental conditions, electrical system parameters, cable general data, and applicable standards for manufacturing and testing. The document is marked as confidential and contains proprietary information.

Uploaded by

suseedevan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 15

OWNER Contractor Job No.

: PN835057
PERDAMAN CHEMICALS AND FERTILIZERS
Doc. No. 0000-EA-E-40107
PLANT LOCATION: BURRUP, AUSTRALIA
UNIT 0000
PROJECT: PROJECT CERES
D.A. CODE E-COM Sh. 1 of 15
DATASHEET FOR LOW VOLTAGE CABLES 0 1 2
REV.

DATASHEET FOR LOW VOLTAGE CABLES

{QRCODE}

2 27-11-2023 ISSUED FOR USE N. SRIKANTH S. BALAMURUGAN R. SRINIVASAN


Rev. Date Description Prepared Checked Approved
CONFIDENTIAL
This document is prepared by Saipem Clough Joint Venture for Perdaman Chemicals and Fertilizers Pty Ltd. It contains proprietary and confidential information of Saipem Clough Joint Venture and/or of the
Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has
been disclosed.
OWNER Contractor Job No.: PN835057
PERDAMAN CHEMICALS AND FERTILIZERS
Doc. No. 0000-EA-E-40107
PLANT LOCATION: BURRUP, AUSTRALIA
UNIT 0000
PROJECT: PROJECT CERES
D.A. CODE E-COM Sh. 2 of 15
DATASHEET FOR LOW VOLTAGE CABLES 0 1 2
REV.

REVISION CONTROL SHEET

2 27-11-2023 ISSUED FOR USE


1 01-08-2023 ISSUED FOR DESIGN
0 10-05-2023 ISSUED FOR REVIEW
Revision No Date Revision Details

CONFIDENTIAL
This document is prepared by Saipem Clough Joint Venture for Perdaman Chemicals and Fertilizers Pty Ltd. It contains proprietary and confidential information of Saipem Clough Joint Venture and/or of the
Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been
disclosed.
OWNER Contractor Job No.: PN835057
PERDAMAN CHEMICALS AND FERTILIZERS
Doc. No. 0000-EA-E-40107
PLANT LOCATION: BURRUP, AUSTRALIA
UNIT 0000
PROJECT: PROJECT CERES
D.A. CODE E-COM Sh. 3 of 15
DATASHEET FOR LOW VOLTAGE CABLES 0 1 2
REV.

LV CABLES - OUTDOOR

VENDOR CONFIRMATION /
S.No DESIGN DATA U. of M. PROJECT REQUIREMENTS REV
DATA

1 AMBIENT ENVIRONMENTAL CONDITIONS

1.1 ELEVATION ABOVE SEA LEVEL m < 1000 m

1.2 INSTALLATION LOCATION (INDOOR/OUTDOOR) OUTDOOR

1.3 MAXIMUM / MINIMUM AMBIENT TEMPERATURE RANGE °C +10 TO +40

1.4 OCCASIONAL EXTREME TEMPERATURE °C +8 TO +48

1.5 DESIGN AMBIENT TEMPERATURE °C 40

1.6 RELATIVE HUMIDITY 64% Max (at 40oC)

2 ELECTRICAL SYSTEM PARAMETERS


2.1 SYSTEM VOLTAGE kV 0.4kV AC and DC
2.2 PHASES/WIRES 3/3+N+PE and P+N+PE(FOR DC)
2.3 SYSTEM FREQUENCY Hz 50

CU/PVC/SWA/PVC (MULTI CORE CABLE, ≤ 16mm2, ABOVE GROUND LAYING)


CU/PVC/AWA/PVC (SINGLE CORECABLE, ≤ 16mm2, ABOVE GROUND LAYING)
CU/PVC/NYLON/SWA/PVC (MULTI CORE CABLE, ≤ 16mm2, UNDER GROUND LAYING)
CU/PVC/NYLON/AWA/PVC (SINGLE CORECABLE, ≤ 16mm2, UNDER GROUND LAYING)
2.4 TYPE OF CABLE
CU/XLPE/SWA/PVC (MULTI CORE CABLE, >16 mm2, ABOVE GROUND LAYING)
CU/XLPE/AWA/PVC (SINGLE CORECABLE, >16 mm2, ABOVE GROUND LAYING)
CU/XLPE/NYLON/SWA/PVC (MULTI CORE CABLE, >16 mm2, UNDER GROUND LAYING)
CU/XLPE/NYLON/AWA/PVC (SINGLE CORECABLE, >16 mm2, UNDER GROUND LAYING)

2.5 PERMISSIBLE VOLTAGE VARIATION % +10 / -11


2.6 PERMISSIBLE FREQUENCY VARIATION % +/- 2

2.7 SYSTEM DESIGN LIFE years 25

3 CABLE GENERAL DATA


3.1 APPLICABLE STANDARD FOR CABLE MANUFACTURING AND TESTING AS/NZS 5000.1, AS/NZS 1125, IEC 60228, IEC 60332-3-22/ IEC 60332-1
3.2 CONDUCTOR TYPE STRANDED ANNEALED COPPER. CIRCULAR OR SHAPED CROSS SECTION.
3.3 CONDUCTOR SCREEN MATERIAL NOT APPLICABLE
3.4 CONDUCTOR CLASS CLASS 2
3.5 Uo/U (Um) AS PER TAB.1 OF IEC 60502-2 kV 0.6/1 (1.2)

3 CORE CABLES (2C+E)-RED, BLACK, GREEN-YELLOW (FOR AC CIRCUITS EG: USED FOR
LIGHTING)
3 CORE CABLES (2C+E)-RED, BLACK, GREEN-YELLOW (FOR DC CIRCUITS)
4 CORE CABLES (3C+E)-RED, WHITE, BLUE, GREEN-YELLOW
3.6 CORE IDENTIFICATION COLOURS 2
5 CORE CABLES (4C+E)-RED, WHITE, BLUE, BLACK, GREEN-YELLOW
RED OR BLACK FOR SINGLE CORE CABLES
OR CORE NUMBERING SHALL BE OF NON-FADING TYPE.
COMPLYING TO AS/NZS 5000.1
3.7 INSULATION TYPE XLPE or PVC. USE PVC ≤ 16mm2 and XLPE >16 mm2 CABLES.
3.8 INSULATION SCREEN NOT APPLICABLE
NON-HYGROSCOPIC FILLER MATERIAL TO PREVENT TRAVEL OF GAS BETWEEN
HAZARDOUS AND NON-HAZARDOUS AREAS.
3.9 FILLERS / BINDER TAPE MATERIAL
CORES LAID UP WITH EXTRUDED FILLER FOR UPTO 5 CORES. FOR 6 CORES OR MORE
WRAPPING OF POLYESTER TAPE.
3.10 BEDDING MATERIAL(INNER SHEATH) EXTRUDED PVC

3.11 WATER STOP NOT APPLICABLE

3.12 TERMITE PROTECTION ABOVE GROUND LAYING NOT APPLICABLE

3.13 UNDER GROUND LAYING NYLON 12 / DOUBLE BRASS TYPE / CHEMICAL TREATMENT (E.G TERMITEX)
3.14 ARMOURED TYPE MULTI CORE CABLES STEEL WIRE ARMOUR
3.15 SINGLE CORE CABLES ALUMINIUM WIRE ARMOUR
3.16 OUTER SHEATH COLOUR ORANGE

3.17 OUTER SHEATH EXTRUDED PVC 90DEGC

3.18 OUTER SHEATH OXYGEN INDEX MINIMUM 29%

3.19 MAXIMUM OPERATING TEMPERATURE °C 90

3.20 FINAL SHORT CIRCUIT TEMPERATURE °C 160°C for PVC and 250°C for XLPE

3.21 FIRE PERFORMANCE CHARACTERISTICS IEC 60332-3-22 CAT A

3.22 SPECIAL CONSTRUCTION UV/SUN LIGHT RESISTANT, CHEMICAL RESISTANT, MOISTURE RESISTANT

4 PHYSICAL DATA
4.1 NO. OF CORE x NOMINAL AREA TO BE DEFINED

4.2 DIAMETER OF WIRES IN EACH CONDUCTOR mm VENDOR TO SPECIFY

4.3 OVERALL DIAMETER mm VENDOR TO SPECIFY

4.4 MINIMUM BENDING RADIUS OF THE CABLE mm VENDOR TO SPECIFY

4.5 MINIMUM DRUM LENGTH m VENDOR TO SPECIFY

4.6 DRUM MAXIMUM LENGTH m VENDOR TO SPECIFY

4.7 NOMINAL INSULATION THICKNESS mm VENDOR TO SPECIFY

4.8 TOTAL WEIGHT kg/m VENDOR TO SPECIFY

4.9 COPPER WEIGHT kg/m VENDOR TO SPECIFY


4.10 MAXIMUM SHORT CIRCUIT TEMPERATRE °C VENDOR TO SPECIFY
4.11 CORE SCREEN MATERIAL VENDOR TO SPECIFY
4.12 CABLE OVERALL SCREEN MATERIAL VENDOR TO SPECIFY
4.13 ARMOUR WIRE DIAMETER mm VENDOR TO SPECIFY
4.14 UNDER ARMOUR DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.15 OVERALL CABLE DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY

4.16 ARMOUR THICKNESS mm VENDOR TO SPECIFY


4.17 CONDUCTOR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY
4.18 ARMOUR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY
4.19 NO. OF ARMOUR WIRE AS PER IEC VENDOR TO SPECIFY

5 ELECTRICAL DATA
5.1 BASIC AMPACITY IN AIR AT 30oC A VENDOR TO SPECIFY

5.2 BASIC AMPACITY IN GROUND AT 20oC 1.5K.m/W 0.8m A VENDOR TO SPECIFY

5.3 AMPACITY IN AIR AT PROJECT CONDITION A VENDOR TO SPECIFY


5.4 AMPACITY IN GROUND AT PROJECT CONDITION A VENDOR TO SPECIFY
5.5 AMPACITY IN DUCT AT PROJECT CONDITION A VENDOR TO SPECIFY
5.6 REACTANCE AT FREQUENCY 50Hz TREFOIL / FLAT Ω/km VENDOR TO SPECIFY

5.7 RESISTANCE A.C AT MAXIMUM OPERATING TEMPERATURE Ω/km VENDOR TO SPECIFY

5.8 CONDUCTOR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY


5.9 ARMOUR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.10 CABLE OVERALL SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.11 CORE SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.12 PHASE CAPACITANCE μF/km VENDOR TO SPECIFY

5.13 ZERO SEQUENCE REACTANCE Ω/km VENDOR TO SPECIFY

5.14 ZERO SEQUENCE RESISTANCE Ω/km VENDOR TO SPECIFY


5.15 ARMOUR RESISTANCE Ω/km VENDOR TO SPECIFY
o
5.16 MINIMUM INSULATION RESISTANCE AT 20 C MΩ/km VENDOR TO SPECIFY
5.17 POWER FREQUENCY TEST VOLT PER IMPULSE WITHSTAND kV VENDOR TO SPECIFY

CONFIDENTIAL
This document is prepared by Saipem Clough Joint Venture for Perdaman Chemicals and Fertilizers Pty Ltd. It contains proprietary and confidential information of Saipem Clough Joint Venture and/or of the Technologies Licensors who will safeguard their rights according
to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed.
OWNER Contractor Job No.: PN835057
PERDAMAN CHEMICALS AND FERTILIZERS
Doc. No. 0000-EA-E-40107
PLANT LOCATION: BURRUP, AUSTRALIA
UNIT 0000
PROJECT: PROJECT CERES
D.A. CODE E-COM Sh. 4 of 15
DATASHEET FOR LOW VOLTAGE CABLES 0 1 2
REV.

LV CABLES - INDOOR

VENDOR
S.No DESIGN DATA U. of M. PROJECT REQUIREMENTS REV
CONFIRMATION / DATA

1 AMBIENT ENVIRONMENTAL CONDITIONS

1.1 ELEVATION ABOVE SEA LEVEL m < 1000 m

1.2 INSTALLATION LOCATION (INDOOR/OUTDOOR) INDOOR

1.3 MAXIMUM / MINIMUM AMBIENT TEMPERATURE RANGE °C +10 TO +40

1.4 OCCASIONAL EXTREME TEMPERATURE °C +8 TO +48

1.5 DESIGN AMBIENT TEMPERATURE °C 40

1.6 RELATIVE HUMIDITY 64% Max (at 40oC)

2 ELECTRICAL SYSTEM PARAMETERS


2.1 SYSTEM VOLTAGE kV 0.4kV AC and DC
2.2 PHASES/WIRES 3/3+N+PE and P+N+PE(FOR DC)
2.3 SYSTEM FREQUENCY Hz 50

2.4 TYPE OF CABLE CU/XLPE/LSZH/LSZH

2.5 PERMISSIBLE VOLTAGE VARIATION % +10 / -11


2.6 PERMISSIBLE FREQUENCY VARIATION % +/- 2
2.7 SYSTEM DESIGN LIFE years 25

3 CABLE GENERAL DATA

AS/NZS 3013, AS/NZS 5000.1, AS/NZS 1125, IEC 60228, IEC 60332-3-22/ IEC 60332-1, IEC
3.1 APPLICABLE STANDARD FOR CABLE MANUFACTURING AND TESTING
60754-1
3.2 CONDUCTOR TYPE STRANDED ANNEALED COPPER. CIRCULAR OR SHAPED CROSS SECTION.
3.3 CONDUCTOR SCREEN MATERIAL NOT APPLICABLE
3.4 CONDUCTOR CLASS CLASS 2
3.5 Uo/U (Um) AS PER TAB.1 OF IEC 60502-2 kV 0.6/1 (1.2)

3 CORE CABLES (2C+E)-RED, BLACK, GREEN-YELLOW (FOR AC CIRCUITS EG: USED FOR
LIGHTING)
3 CORE CABLES (2C+E)-RED, BLACK, GREEN-YELLOW (FOR DC CIRCUITS)
4 CORE CABLES (3C+E)-RED, WHITE, BLUE, GREEN-YELLOW
3.6 CORE IDENTIFICATION COLOURS 2
5 CORE CABLES (4C+E)-RED, WHITE, BLUE, BLACK, GREEN-YELLOW
RED OR BLACK FOR SINGLE CORE CABLES
OR CORE NUMBERING SHALL BE OF NON-FADING TYPE.
COMPLYING TO AS/NZS 5000.1

3.7 INSULATION TYPE XLPE


3.8 INSULATION SCREEN NOT APPLICABLE
NON-HYGROSCOPIC FILLER MATERIAL TO PREVENT TRAVEL OF GAS BETWEEN
HAZARDOUS AND NON-HAZARDOUS AREAS.
3.9 FILLERS / BINDER TAPE MATERIAL
CORES LAID UP WITH EXTRUDED FILLER FOR UPTO 5 CORES. FOR 6 CORES OR MORE
WRAPPING OF POLYESTER TAPE.

3.10 BEDDING MATERIAL(INNER SHEATH) (OPTIONAL) EXTRUDED LSZH MATERIAL 2


3.11 WATER STOP NOT APPLICABLE

3.12 TERMITE PROTECTION NOT APPLICABLE


3.13 ARMOURED TYPE MULTI CORE CABLES NON-ARMOURED
3.14 SINGLE CORE CABLES NON-ARMOURED
3.15 OUTER SHEATH COLOUR ORANGE

3.16 OUTER SHEATH EXTRUDED LOW SMOKE ZERO HALOGEN TYPE

3.17 OUTER SHEATH OXYGEN INDEX MINIMUM 29%

3.18 MAXIMUM OPERATING TEMPERATURE °C 90

3.19 FINAL SHORT CIRCUIT TEMPERATURE °C 250

3.20 FIRE PERFORMANCE CHARACTERISTICS IEC 60332-3-22 CAT A

3.21 SPECIAL CONSTRUCTION CHEMICAL RESISTANT, MOISTURE RESISTANT

4 PHYSICAL DATA
4.1 NO. OF CORE x NOMINAL AREA TO BE DEFINED

4.2 DIAMETER OF WIRES IN EACH CONDUCTOR mm VENDOR TO SPECIFY

4.3 OVERALL DIAMETER mm VENDOR TO SPECIFY

4.4 MINIMUM BENDING RADIUS OF THE CABLE mm VENDOR TO SPECIFY

4.5 MINIMUM DRUM LENGTH m VENDOR TO SPECIFY

4.6 DRUM MAXIMUM LENGTH m VENDOR TO SPECIFY


4.7 NOMINAL INSULATION THICKNESS mm VENDOR TO SPECIFY
4.8 TOTAL WEIGHT kg/m VENDOR TO SPECIFY

4.9 COPPER WEIGHT kg/m VENDOR TO SPECIFY


4.10 MAXIMUM SHORT CIRCUIT TEMPERATRE °C VENDOR TO SPECIFY
4.11 CORE SCREEN MATERIAL VENDOR TO SPECIFY
4.12 CABLE OVERALL SCREEN MATERIAL VENDOR TO SPECIFY
4.13 ARMOUR WIRE DIAMETER mm VENDOR TO SPECIFY
4.14 UNDER ARMOUR DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.15 OVERALL CABLE DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.16 ARMOUR THICKNESS mm VENDOR TO SPECIFY

4.17 CONDUCTOR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY


4.18 ARMOUR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY
4.19 NO. OF ARMOUR WIRE AS PER IEC VENDOR TO SPECIFY

5 ELECTRICAL DATA
5.1 BASIC AMPACITY IN AIR AT 30oC A VENDOR TO SPECIFY

5.2 BASIC AMPACITY IN GROUND AT 20oC 1.5K.m/W 0.8m A VENDOR TO SPECIFY

5.3 AMPACITY IN AIR AT PROJECT CONDITION A VENDOR TO SPECIFY

5.4 AMPACITY IN GROUND AT PROJECT CONDITION A VENDOR TO SPECIFY


5.5 AMPACITY IN DUCT AT PROJECT CONDITION A VENDOR TO SPECIFY
5.6 REACTANCE AT FREQUENCY 50Hz TREFOIL / FLAT Ω/km VENDOR TO SPECIFY

5.7 RESISTANCE A.C AT MAXIMUM OPERATING TEMPERATURE Ω/km VENDOR TO SPECIFY


5.8 CONDUCTOR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.9 ARMOUR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY


5.10 CABLE OVERALL SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.11 CORE SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.12 PHASE CAPACITANCE μF/km VENDOR TO SPECIFY

5.13 ZERO SEQUENCE REACTANCE Ω/km VENDOR TO SPECIFY

5.14 ZERO SEQUENCE RESISTANCE Ω/km VENDOR TO SPECIFY


5.15 ARMOUR RESISTANCE Ω/km VENDOR TO SPECIFY
5.16 MINIMUM INSULATION RESISTANCE AT 20oC MΩ/km VENDOR TO SPECIFY
5.17 POWER FREQUENCY TEST VOLT PER IMPULSE WITHSTAND kV VENDOR TO SPECIFY

CONFIDENTIAL
This document is prepared by Saipem Clough Joint Venture for Perdaman Chemicals and Fertilizers Pty Ltd. It contains proprietary and confidential information of Saipem Clough Joint Venture and/or of the Technologies Licensors who will safeguard their rights according to the
civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed.
OWNER Contractor Job No.: PN835057
PERDAMAN CHEMICALS AND FERTILIZERS
Doc. No. 0000-EA-E-40107
PLANT LOCATION: BURRUP, AUSTRALIA
UNIT 0000
PROJECT: PROJECT CERES
D.A. CODE E-COM Sh. 5 of 15
DATASHEET FOR LOW VOLTAGE CABLES 0 1 2
REV.

LV CABLES FIRE RESISTANT - OUTDOOR

VENDOR
S.No DESIGN DATA U. of M. PROJECT REQUIREMENTS CONFIRMATION / REV
DATA
1 AMBIENT ENVIRONMENTAL CONDITIONS

1.1 ELEVATION ABOVE SEA LEVEL m < 1000 m

1.2 INSTALLATION LOCATION (INDOOR/OUTDOOR) OUTDOOR AND FOR EMERGENCY LIGHTING

1.3 MAXIMUM / MINIMUM AMBIENT TEMPERATURE RANGE °C +10 TO +40

1.4 OCCASIONAL EXTREME TEMPERATURE °C +8 TO +48

1.5 DESIGN AMBIENT TEMPERATURE °C 40


RELATIVE HUMIDITY o
1.6 64% Max (at 40 C)

2 ELECTRICAL SYSTEM PARAMETERS


2.1 SYSTEM VOLTAGE kV 0.4kV
2.2 PHASES/WIRES 3/3+N+PE
2.3 SYSTEM FREQUENCY Hz 50

CU/XLPE/SWA/ FR PVC (MULTI CORE CABLE, ABOVE GROUND LAYING)


CU/XLPE/AWA/FR PVC (SINGLE CORECABLE, ABOVE GROUND LAYING)
2.4 TYPE OF CABLE 2
CU/XLPE/NYLON/SWA/FR PVC (MULTI CORE CABLE, UNDER GROUND LAYING)
CU/XLPE/NYLON/AWA/FR PVC (SINGLE CORECABLE, UNDER GROUND LAYING)
2.5 PERMISSIBLE VOLTAGE VARIATION % +10 / -11
2.6 PERMISSIBLE FREQUENCY VARIATION % +/- 2

2.7 SYSTEM DESIGN LIFE years 25

3 CABLE GENERAL DATA


3.1 APPLICABLE STANDARD FOR CABLE MANUFACTURING AND TESTING AS/NZS 5000.1, AS/NZS 1125, IEC 60228, IEC 60331-21 2
3.2 CONDUCTOR TYPE STRANDED ANNEALED COPPER. CIRCULAR OR SHAPED CROSS SECTION.
3.3 MICA TAPE MICA TAPE OVER EACH CONDUCTOR
3.4 CONDUCTOR SCREEN MATERIAL NOT APPLICABLE
3.5 CONDUCTOR CLASS CLASS 2
3.6 Uo/U (Um) AS PER TAB.1 OF IEC 60502-2 kV 0.6/1 (1.2)

3 CORE CABLES (2C+E)-RED, BLACK, GREEN-YELLOW (FOR AC CIRCUITS EG: USED FOR
LIGHTING)
4 CORE CABLES (3C+E)-RED, WHITE, BLUE, GREEN-YELLOW
4 CORE CABLES (L1 L1' pilot N E)-RED, WHITE, BLACK, GREEN-YELLOW FOR EMERGENCY
3.7 CORE IDENTIFICATION COLOURS LIGHTING CABLES. 2
5 CORE CABLES (4C+E)-RED, WHITE, BLUE, BLACK, GREEN-YELLOW
RED OR BLACK FOR SINGLE CORE CABLES
OR CORE NUMBERING SHALL BE OF NON-FADING TYPE.
COMPLYING TO AS/NZS 5000.1
3.8 INSULATION TYPE XLPE
3.9 INSULATION SCREEN NOT APPLICABLE
NON-HYGROSCOPIC FILLER MATERIAL TO PREVENT TRAVEL OF GAS BETWEEN HAZARDOUS
AND NON-HAZARDOUS AREAS.
3.10 FILLERS / BINDER TAPE MATERIAL
CORES LAID UP WITH EXTRUDED FILLER FOR UPTO 5 CORES. FOR 6 CORES OR MORE
WRAPPING OF POLYESTER TAPE.
3.11 BEDDING MATERIAL(INNER SHEATH) EXTRUDED PVC 2
3.12 WATER STOP NOT APPLICABLE

3.13 TERMITE PROTECTION ABOVE GROUND LAYING NOT APPLICABLE

3.14 UNDER GROUND LAYING NYLON 12 / DOUBLE BRASS TYPE / CHEMICAL TREATMENT (E.G TERMITEX)
3.15 ARMOURED TYPE MULTI CORE CABLES STEEL WIRE ARMOUR
3.16 SINGLE CORE CABLES ALUMINIUM WIRE ARMOUR
3.17 OUTER SHEATH COLOUR ORANGE

3.18 OUTER SHEATH EXTRUDED PVC 2


3.19 OUTER SHEATH OXYGEN INDEX MINIMUM 29%

3.20 MAXIMUM OPERATING TEMPERATURE °C 90

3.21 FINAL SHORT CIRCUIT TEMPERATURE °C 250

3.22 FIRE PERFORMANCE CHARACTERISTICS FIRE RESISTANT AS PER IEC 60331-21 2


3.23 SPECIAL CONSTRUCTION UV/SUN LIGHT RESISTANT, CHEMICAL RESISTANT, MOISTURE RESISTANT

4 PHYSICAL DATA
4.1 NO. OF CORE x NOMINAL AREA TO BE DEFINED

4.2 DIAMETER OF WIRES IN EACH CONDUCTOR mm VENDOR TO SPECIFY

4.3 OVERALL DIAMETER mm VENDOR TO SPECIFY

4.4 MINIMUM BENDING RADIUS OF THE CABLE mm VENDOR TO SPECIFY

4.5 MINIMUM DRUM LENGTH m VENDOR TO SPECIFY

4.6 DRUM MAXIMUM LENGTH m VENDOR TO SPECIFY

4.7 NOMINAL INSULATION THICKNESS mm VENDOR TO SPECIFY

4.8 TOTAL WEIGHT kg/m VENDOR TO SPECIFY

4.9 COPPER WEIGHT kg/m VENDOR TO SPECIFY


4.10 MAXIMUM SHORT CIRCUIT TEMPERATRE °C VENDOR TO SPECIFY
4.11 CORE SCREEN MATERIAL VENDOR TO SPECIFY
4.12 CABLE OVERALL SCREEN MATERIAL VENDOR TO SPECIFY
4.13 ARMOUR WIRE DIAMETER mm VENDOR TO SPECIFY
4.14 UNDER ARMOUR DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.15 OVERALL CABLE DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY

4.16 ARMOUR THICKNESS mm VENDOR TO SPECIFY

4.17 CONDUCTOR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY

4.18 ARMOUR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY

4.19 NO. OF ARMOUR WIRE AS PER IEC VENDOR TO SPECIFY

5 ELECTRICAL DATA
5.1 BASIC AMPACITY IN AIR AT 30oC A VENDOR TO SPECIFY

5.2 BASIC AMPACITY IN GROUND AT 20oC 1.5K.m/W 0.8m A VENDOR TO SPECIFY

5.3 AMPACITY IN AIR AT PROJECT CONDITION A VENDOR TO SPECIFY

5.4 AMPACITY IN GROUND AT PROJECT CONDITION A VENDOR TO SPECIFY


5.5 AMPACITY IN DUCT AT PROJECT CONDITION A VENDOR TO SPECIFY
5.6 REACTANCE AT FREQUENCY 50Hz TREFOIL / FLAT Ω/km VENDOR TO SPECIFY

5.7 RESISTANCE A.C AT MAXIMUM OPERATING TEMPERATURE Ω/km VENDOR TO SPECIFY

5.8 CONDUCTOR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.9 ARMOUR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.10 CABLE OVERALL SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.11 CORE SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.12 PHASE CAPACITANCE μF/km VENDOR TO SPECIFY

5.13 ZERO SEQUENCE REACTANCE Ω/km VENDOR TO SPECIFY

5.14 ZERO SEQUENCE RESISTANCE Ω/km VENDOR TO SPECIFY


5.15 ARMOUR RESISTANCE Ω/km VENDOR TO SPECIFY
5.16 MINIMUM INSULATION RESISTANCE AT 20oC MΩ/km VENDOR TO SPECIFY
5.17 POWER FREQUENCY TEST VOLT PER IMPULSE WITHSTAND kV VENDOR TO SPECIFY

CONFIDENTIAL
This document is prepared by Saipem Clough Joint Venture for Perdaman Chemicals and Fertilizers Pty Ltd. It contains proprietary and confidential information of Saipem Clough Joint Venture and/or of the Technologies Licensors who will safeguard their rights
according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed.
OWNER Contractor Job No.: PN835057
PERDAMAN CHEMICALS AND FERTILIZERS
Doc. No. 0000-EA-E-40107
PLANT LOCATION: BURRUP, AUSTRALIA
UNIT 0000
PROJECT: PROJECT CERES
D.A. CODE E-COM Sh. 6 of 15
DATASHEET FOR LOW VOLTAGE CABLES 0 1 2
REV.

LV CABLES FIRE RESISTANT - INDOOR

VENDOR
S.No DESIGN DATA U. of M. PROJECT REQUIREMENTS CONFIRMATION / REV
DATA
1 AMBIENT ENVIRONMENTAL CONDITIONS

1.1 ELEVATION ABOVE SEA LEVEL m < 1000 m

1.2 INSTALLATION LOCATION (INDOOR/OUTDOOR) INDOOR

1.3 MAXIMUM / MINIMUM AMBIENT TEMPERATURE RANGE °C +10 TO +40

1.4 OCCASIONAL EXTREME TEMPERATURE °C +8 TO +48

1.5 DESIGN AMBIENT TEMPERATURE °C 40

1.6 RELATIVE HUMIDITY 64% Max (at 40oC)

2 ELECTRICAL SYSTEM PARAMETERS


2.1 SYSTEM VOLTAGE kV 0.4kV
2.2 PHASES/WIRES 3/3+N+PE
2.3 SYSTEM FREQUENCY Hz 50

2.4 TYPE OF CABLE CU/XLPE/LSZH/ FR LSZH

2.5 PERMISSIBLE VOLTAGE VARIATION % +10 / -11


2.6 PERMISSIBLE FREQUENCY VARIATION % +/- 2

2.7 SYSTEM DESIGN LIFE years 25

3 CABLE GENERAL DATA


3.1 APPLICABLE STANDARD FOR CABLE MANUFACTURING AND TESTING AS/NZS 5000.1, AS/NZS 1125, IEC 60228, IEC 60331-21 2
3.2 CONDUCTOR TYPE STRANDED ANNEALED COPPER. CIRCULAR OR SHAPED CROSS SECTION.
3.3 MICA TAPE MICA TAPE OVER EACH CONDUCTOR
3.4 CONDUCTOR SCREEN MATERIAL NOT APPLICABLE
3.5 CONDUCTOR CLASS CLASS 2
3.6 Uo/U (Um) AS PER TAB.1 OF IEC 60502-2 kV 0.6/1 (1.2)

3 CORE CABLES (2C+E)-RED, BLACK, GREEN-YELLOW (FOR AC CIRCUITS EG: USED FOR
LIGHTING)
4 CORE CABLES (3C+E)-RED, WHITE, BLUE, GREEN-YELLOW
4 CORE CABLES (L1 L1' pilot N E)-RED, WHITE, BLACK, GREEN-YELLOW FOR EMERGENCY
3.7 CORE IDENTIFICATION COLOURS LIGHTING CABLES. 2
5 CORE CABLES (4C+E)-RED, WHITE, BLUE, BLACK, GREEN-YELLOW
RED OR BLACK FOR SINGLE CORE CABLES
OR CORE NUMBERING SHALL BE OF NON-FADING TYPE.
COMPLYING TO AS/NZS 5000.1
3.8 INSULATION TYPE XLPE
3.9 INSULATION SCREEN NOT APPLICABLE
NON-HYGROSCOPIC FILLER MATERIAL TO PREVENT TRAVEL OF GAS BETWEEN
HAZARDOUS AND NON-HAZARDOUS AREAS.
3.10 FILLERS / BINDER TAPE MATERIAL
CORES LAID UP WITH EXTRUDED FILLER FOR UPTO 5 CORES. FOR 6 CORES OR MORE
WRAPPING OF POLYESTER TAPE.
3.11 BEDDING MATERIAL(INNER SHEATH) (OPTIONAL) EXTRUDED LSZH MATERIAL 2
3.12 WATER STOP NOT APPLICABLE

3.13 TERMITE PROTECTION ABOVE GROUND LAYING NOT APPLICABLE

3.14 UNDER GROUND LAYING NOT APPLICABLE


3.15 ARMOURED TYPE MULTI CORE CABLES UN-ARMOURED
3.16 SINGLE CORE CABLES UN-ARMOURED
3.17 OUTER SHEATH COLOUR ORANGE

3.18 OUTER SHEATH EXTRUDED LOW SMOKE ZERO HALOGEN TYPE

3.19 OUTER SHEATH OXYGEN INDEX MINIMUM 29%

3.20 MAXIMUM OPERATING TEMPERATURE °C 90

3.21 FINAL SHORT CIRCUIT TEMPERATURE °C 250

3.22 FIRE PERFORMANCE CHARACTERISTICS FIRE RESISTANT AS PER IEC 60331-21 2


3.23 SPECIAL CONSTRUCTION CHEMICAL RESISTANT, MOISTURE RESISTANT

4 PHYSICAL DATA
4.1 NO. OF CORE x NOMINAL AREA TO BE DEFINED

4.2 DIAMETER OF WIRES IN EACH CONDUCTOR mm VENDOR TO SPECIFY

4.3 OVERALL DIAMETER mm VENDOR TO SPECIFY

4.4 MINIMUM BENDING RADIUS OF THE CABLE mm VENDOR TO SPECIFY

4.5 MINIMUM DRUM LENGTH m VENDOR TO SPECIFY

4.6 DRUM MAXIMUM LENGTH m VENDOR TO SPECIFY


4.7 NOMINAL INSULATION THICKNESS mm VENDOR TO SPECIFY
4.8 TOTAL WEIGHT kg/m VENDOR TO SPECIFY

4.9 COPPER WEIGHT kg/m VENDOR TO SPECIFY


4.10 MAXIMUM SHORT CIRCUIT TEMPERATRE °C VENDOR TO SPECIFY
4.11 CORE SCREEN MATERIAL VENDOR TO SPECIFY
4.12 CABLE OVERALL SCREEN MATERIAL VENDOR TO SPECIFY
4.13 ARMOUR WIRE DIAMETER mm VENDOR TO SPECIFY
4.14 UNDER ARMOUR DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.15 OVERALL CABLE DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.16 ARMOUR THICKNESS mm VENDOR TO SPECIFY

4.17 CONDUCTOR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY


4.18 ARMOUR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY
4.19 NO. OF ARMOUR WIRE AS PER IEC VENDOR TO SPECIFY

5 ELECTRICAL DATA
5.1 BASIC AMPACITY IN AIR AT 30oC A VENDOR TO SPECIFY

5.2 BASIC AMPACITY IN GROUND AT 20oC 1.5K.m/W 0.8m A VENDOR TO SPECIFY

5.3 AMPACITY IN AIR AT PROJECT CONDITION A VENDOR TO SPECIFY

5.4 AMPACITY IN GROUND AT PROJECT CONDITION A VENDOR TO SPECIFY


5.5 AMPACITY IN DUCT AT PROJECT CONDITION A VENDOR TO SPECIFY
5.6 REACTANCE AT FREQUENCY 50Hz TREFOIL / FLAT Ω/km VENDOR TO SPECIFY

5.7 RESISTANCE A.C AT MAXIMUM OPERATING TEMPERATURE Ω/km VENDOR TO SPECIFY


5.8 CONDUCTOR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.9 ARMOUR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY


5.10 CABLE OVERALL SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.11 CORE SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.12 PHASE CAPACITANCE μF/km VENDOR TO SPECIFY

5.13 ZERO SEQUENCE REACTANCE Ω/km VENDOR TO SPECIFY

5.14 ZERO SEQUENCE RESISTANCE Ω/km VENDOR TO SPECIFY


5.15 ARMOUR RESISTANCE Ω/km VENDOR TO SPECIFY
5.16 MINIMUM INSULATION RESISTANCE AT 20oC MΩ/km VENDOR TO SPECIFY

5.17 POWER FREQUENCY TEST VOLT PER IMPULSE WITHSTAND kV VENDOR TO SPECIFY

CONFIDENTIAL
This document is prepared by Saipem Clough Joint Venture for Perdaman Chemicals and Fertilizers Pty Ltd. It contains proprietary and confidential information of Saipem Clough Joint Venture and/or of the Technologies Licensors who will safeguard
their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed.
OWNER Contractor Job No.: PN835057
PERDAMAN CHEMICALS AND FERTILIZERS
Doc. No. 0000-EA-E-40107
PLANT LOCATION: BURRUP, AUSTRALIA
UNIT 0000
PROJECT: PROJECT CERES
D.A. CODE E-COM Sh. 7 of 15
DATASHEET FOR LOW VOLTAGE CABLES 0 1 2
REV.

LV VFD CABLE - OUTDOOR

VENDOR
S.No DESIGN DATA U. of M. PROJECT REQUIREMENTS REV
CONFIRMATION / DATA

1 AMBIENT ENVIRONMENTAL CONDITIONS

1.1 ELEVATION ABOVE SEA LEVEL m < 1000 m

1.2 INSTALLATION LOCATION (INDOOR/OUTDOOR) OUTDOOR

1.3 MAXIMUM / MINIMUM AMBIENT TEMPERATURE RANGE °C +10 TO +40

1.4 OCCASIONAL EXTREME TEMPERATURE °C +8 TO +48

1.5 DESIGN AMBIENT TEMPERATURE °C 40

1.6 RELATIVE HUMIDITY 64% Max (at 40oC)

2 ELECTRICAL SYSTEM PARAMETERS

2.1 SYSTEM VOLTAGE kV 0.4kV

2.2 PHASES/WIRES 3/3+3 x PE

2.3 SYSTEM FREQUENCY Hz 50

CU/PVC/CTS/SWA/PVC (MULTI CORE CABLE, ≤ 16mm2, ABOVE GROUND LAYING)


CU/PVC/CTS/AWA/PVC (SINGLE CORECABLE, ≤ 16mm2, ABOVE GROUND LAYING)
CU/PVC/CTS/NYLON/SWA/PVC (MULTI CORE CABLE, ≤ 16mm2, UNDER GROUND LAYING)
CU/PVC/CTS/NYLON/AWA/PVC (SINGLE CORECABLE, ≤ 16mm2, UNDER GROUND LAYING)
2.4 TYPE OF CABLE
CU/XLPE/CTS/SWA/PVC (MULTI CORE CABLE, >16 mm2, ABOVE GROUND LAYING)
CU/XLPE/CTS/AWA/PVC (SINGLE CORECABLE, >16 mm2, ABOVE GROUND LAYING)
CU/XLPE/CTS/NYLON/SWA/PVC (MULTI CORE CABLE, >16 mm2, UNDER GROUND LAYING)
CU/XLPE/CTS/NYLON/AWA/PVC (SINGLE CORECABLE, >16 mm2, UNDER GROUND LAYING)

2.5 PERMISSIBLE VOLTAGE VARIATION % +10 / -11


2.6 PERMISSIBLE FREQUENCY VARIATION % +/- 2

2.7 SYSTEM DESIGN LIFE years 25

3 CABLE GENERAL DATA


3.1 APPLICABLE STANDARD FOR CABLE MANUFACTURING AND TESTING AS/NZS 5000.1; AS/NZS 1125 & IEC-60228, IEC 60332-3 Category A/ IEC 60332-1
3.2 CONDUCTOR TYPE STRANDED ANNEALED COPPER. CIRCULAR CROSS SECTION.
3.3 CONDUCTOR SCREEN MATERIAL NOT APPLICABLE
3.4 CONDUCTOR CLASS CLASS 2
3.5 Uo/U (Um) AS PER TAB.1 OF IEC 60502-2 kV 0.6/1 (1.2)

3C+3E – THREE CORE CABLES


3 CORE PHASE CORES - RED, WHITE, BLUE
3.6 CORE IDENTIFICATION COLOURS 3 SPLIT EARTH CORES - GREEN-YELLOW 2
RED OR BLACK FOR SINGLE CORE CABLES
COMPLYING TO AS/NZS 5000.1

3.7 INSULATION TYPE XLPE or PVC. USE PVC ≤ 16mm2 and XLPE >16 mm2 CABLES.
3.8 INSULATION SCREEN N/A
NON-HYGROSCOPIC FILLER MATERIAL TO PREVENT TRAVEL OF GAS BETWEEN HAZARDOUS AND NON-
HAZARDOUS AREAS.
3.9 FILLERS / BINDER TAPE MATERIAL
CORES LAID UP WITH EXTRUDED FILLER FOR UPTO 5 CORES. FOR 6 CORES OR MORE WRAPPING OF
POLYESTER TAPE.

3.10 INNER & INTERMEDIATE SHEATH EXTRUDEDE PVC SHEATHED 90DEGC

3.11 OVERALL SCREENING COPPER TAPE SCREENING COMPLYING TO EMC

3.12 BEDDING EXTRUDEDE PVC SHEATHED 90DEGC

3.13 WATER STOP NOT APPLICABLE

3.14 TERMITE PROTECTION ABOVE GROUND LAYING NOT APPLICABLE

3.15 UNDER GROUND LAYING NYLON 12 / DOUBLE BRASS TYPE / CHEMICAL TREATMENT (E.G TERMITEX)
3.16 ARMOURED TYPE OUTDOOR MULTI CORE CABLES STEEL WIRE ARMOUR
3.17 OUTDOOR SINGLE CORE CABLES ALUMINIUM WIRE ARMOUR
3.18 OUTER SHEATH COLOUR ORANGE

3.19 OUTER SHEATH EXTRUDED PVC SUITABLE FOR 90DEG C

3.20 OUTER SHEATH OXYGEN INDEX MINIMUM 29%

3.21 MAXIMUM OPERATING TEMPERATURE °C 90

3.22 FINAL SHORT CIRCUIT TEMPERATURE °C 160°C for PVC and 250°C for XLPE

3.23 FIRE PERFORMANCE CHARACTERISTICS IEC 60332-3-22 CAT A

3.24 SPECIAL CONSTRUCTION UV/SUN LIGHT RESISTANT, CHEMICAL RESISTANT, MOISTURE RESISTANT

4 PHYSICAL DATA
4.1 NO. OF CORE x NOMINAL AREA TO BE DEFINED

4.2 DIAMETER OF WIRES IN EACH CONDUCTOR mm VENDOR TO SPECIFY

4.3 OVERALL DIAMETER mm VENDOR TO SPECIFY

4.4 MINIMUM BENDING RADIUS OF THE CABLE mm VENDOR TO SPECIFY

4.5 MINIMUM DRUM LENGTH m VENDOR TO SPECIFY

4.6 DRUM MAXIMUM LENGTH m VENDOR TO SPECIFY

4.7 NOMINAL INSULATION THICKNESS mm VENDOR TO SPECIFY

4.8 TOTAL WEIGHT kg/m VENDOR TO SPECIFY


4.9 COPPER WEIGHT kg/m VENDOR TO SPECIFY
4.10 MAXIMUM SHORT CIRCUIT TEMPERATRE °C VENDOR TO SPECIFY
4.11 CORE SCREEN MATERIAL VENDOR TO SPECIFY
4.12 CABLE OVERALL SCREEN MATERIAL VENDOR TO SPECIFY
4.13 ARMOUR WIRE DIAMETER mm VENDOR TO SPECIFY
4.14 UNDER ARMOUR DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.15 OVERALL CABLE DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.16 ARMOUR THICKNESS mm VENDOR TO SPECIFY

4.17 CONDUCTOR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY


4.18 ARMOUR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY
4.19 NO. OF ARMOUR WIRE AS PER IEC VENDOR TO SPECIFY

5 ELECTRICAL DATA
5.1 BASIC AMPACITY IN AIR AT 30oC A VENDOR TO SPECIFY

5.2 BASIC AMPACITY IN GROUND AT 20oC 1.5K.m/W 0.8m A VENDOR TO SPECIFY

5.3 AMPACITY IN AIR AT PROJECT CONDITION A VENDOR TO SPECIFY

5.4 AMPACITY IN GROUND AT PROJECT CONDITION A VENDOR TO SPECIFY


5.5 AMPACITY IN DUCT AT PROJECT CONDITION A VENDOR TO SPECIFY
5.6 REACTANCE AT FREQUENCY 50Hz TREFOIL / FLAT Ω/km VENDOR TO SPECIFY

5.7 RESISTANCE A.C AT MAXIMUM OPERATING TEMPERATURE Ω/km VENDOR TO SPECIFY


5.8 CONDUCTOR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.9 ARMOUR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.10 CABLE OVERALL SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.11 CORE SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY


5.12 PHASE CAPACITANCE μF/km VENDOR TO SPECIFY

5.13 ZERO SEQUENCE REACTANCE Ω/km VENDOR TO SPECIFY

5.14 ZERO SEQUENCE RESISTANCE Ω/km VENDOR TO SPECIFY


5.15 ARMOUR RESISTANCE Ω/km VENDOR TO SPECIFY
5.16 MINIMUM INSULATION RESISTANCE AT 20oC MΩ/km VENDOR TO SPECIFY
5.17 POWER FREQUENCY TEST VOLT PER IMPULSE WITHSTAND kV VENDOR TO SPECIFY

CONFIDENTIAL
This document is prepared by Saipem Clough Joint Venture for Perdaman Chemicals and Fertilizers Pty Ltd. It contains proprietary and confidential information of Saipem Clough Joint Venture and/or of the Technologies Licensors who will safeguard their rights
according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed.
OWNER Contractor Job No.: PN835057
PERDAMAN CHEMICALS AND FERTILIZERS
Doc. No. 0000-EA-E-40107
PLANT LOCATION: BURRUP, AUSTRALIA
UNIT 0000
PROJECT: PROJECT CERES
D.A. CODE E-COM Sh. 8 of 15
DATASHEET FOR LOW VOLTAGE CABLES 0 1 2
REV.

LV VFD CABLE - INDOOR

VENDOR
S.No DESIGN DATA U. of M. PROJECT REQUIREMENTS REV
CONFIRMATION / DATA

1 AMBIENT ENVIRONMENTAL CONDITIONS

1.1 ELEVATION ABOVE SEA LEVEL m < 1000 m

1.2 INSTALLATION LOCATION (INDOOR/OUTDOOR) INDOOR

1.3 MAXIMUM / MINIMUM AMBIENT TEMPERATURE RANGE °C +10 TO +40

1.4 OCCASIONAL EXTREME TEMPERATURE °C +8 TO +48

1.5 DESIGN AMBIENT TEMPERATURE °C 40

1.6 RELATIVE HUMIDITY 64% Max (at 40oC)

2 ELECTRICAL SYSTEM PARAMETERS

2.1 SYSTEM VOLTAGE kV 0.4kV

2.2 PHASES/WIRES 3/3+3 x PE

2.3 SYSTEM FREQUENCY Hz 50

CU/XLPE/CTS/LSZH (MULTI CORE CABLE)


2.4 TYPE OF CABLE
CU/XLPE/CTS/LSZH (SINGLE CORECABLE)

2.5 PERMISSIBLE VOLTAGE VARIATION % +10 / -11


2.6 PERMISSIBLE FREQUENCY VARIATION % +/- 2
2.7 SYSTEM DESIGN LIFE years 25

3 CABLE GENERAL DATA


3.1 APPLICABLE STANDARD FOR CABLE MANUFACTURING AND TESTING AS/NZS 5000.1; AS/NZS 1125 & IEC-60228, IEC 60332-3 Category A/ IEC 60332-1. IEC 60754-1
3.2 CONDUCTOR TYPE STRANDED ANNEALED COPPER. CIRCULAR CROSS SECTION.
3.3 CONDUCTOR SCREEN MATERIAL NOT APPLICABLE
3.4 CONDUCTOR CLASS CLASS 2
3.5 Uo/U (Um) AS PER TAB.1 OF IEC 60502-2 kV 0.6/1 (1.2)

3C+3E – THREE CORE CABLES


3 CORE PHASE CORES - RED, WHITE, BLUE
3.6 CORE IDENTIFICATION COLOURS 3 SPLIT EARTH CORES - GREEN-YELLOW 2
RED OR BLACK FOR SINGLE CORE CABLES
COMPLYING TO AS/NZS 5000.1

3.7 INSULATION TYPE XLPE


3.8 INSULATION SCREEN N/A
NON-HYGROSCOPIC FILLER MATERIAL TO PREVENT TRAVEL OF GAS BETWEEN HAZARDOUS
AND NON-HAZARDOUS AREAS.
3.9 FILLERS / BINDER TAPE MATERIAL
CORES LAID UP WITH EXTRUDED FILLER FOR UPTO 5 CORES. FOR 6 CORES OR MORE
WRAPPING OF POLYESTER TAPE.
3.10 INNER & INTERMEDIATE SHEATH EXTRUDEDE LSZH

3.11 OVERALL SCREENING COPPER TAPE SCREENING COMPLYING TO EMC

3.12 BEDDING (OPTIONAL) EXTRUDEDE LSZH 2


3.13 WATER STOP NOT APPLICABLE

3.14 TERMITE PROTECTION ABOVE GROUND LAYING NOT APPLICABLE

3.15 UNDER GROUND LAYING NOT APPLICABLE


3.16 ARMOURED TYPE OUTDOOR MULTI CORE CABLES UN-ARMOURED
3.17 OUTDOOR SINGLE CORE CABLES UN-ARMOURED
3.18 OUTER SHEATH COLOUR ORANGE

3.19 OUTER SHEATH EXTRUDED LSZH

3.20 OUTER SHEATH OXYGEN INDEX MINIMUM 29%

3.21 MAXIMUM OPERATING TEMPERATURE °C 90

3.22 FINAL SHORT CIRCUIT TEMPERATURE °C 250°C

3.23 FIRE PERFORMANCE CHARACTERISTICS IEC 60332-3-22 CAT A

3.24 SPECIAL CONSTRUCTION CHEMICAL RESISTANT, MOISTURE RESISTANT

4 PHYSICAL DATA
4.1 NO. OF CORE x NOMINAL AREA TO BE DEFINED

4.2 DIAMETER OF WIRES IN EACH CONDUCTOR mm VENDOR TO SPECIFY

4.3 OVERALL DIAMETER mm VENDOR TO SPECIFY

4.4 MINIMUM BENDING RADIUS OF THE CABLE mm VENDOR TO SPECIFY

4.5 MINIMUM DRUM LENGTH m VENDOR TO SPECIFY

4.6 DRUM MAXIMUM LENGTH m VENDOR TO SPECIFY

4.7 NOMINAL INSULATION THICKNESS mm VENDOR TO SPECIFY

4.8 TOTAL WEIGHT kg/m VENDOR TO SPECIFY

4.9 COPPER WEIGHT kg/m VENDOR TO SPECIFY


4.10 MAXIMUM SHORT CIRCUIT TEMPERATRE °C VENDOR TO SPECIFY
4.11 CORE SCREEN MATERIAL VENDOR TO SPECIFY
4.12 CABLE OVERALL SCREEN MATERIAL VENDOR TO SPECIFY

4.13 ARMOUR WIRE DIAMETER mm VENDOR TO SPECIFY


4.14 UNDER ARMOUR DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.15 OVERALL CABLE DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY

4.16 ARMOUR THICKNESS mm VENDOR TO SPECIFY

4.17 CONDUCTOR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY

4.18 ARMOUR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY

4.19 NO. OF ARMOUR WIRE AS PER IEC VENDOR TO SPECIFY

5 ELECTRICAL DATA
o VENDOR TO SPECIFY
5.1 BASIC AMPACITY IN AIR AT 30 C A
o VENDOR TO SPECIFY
5.2 BASIC AMPACITY IN GROUND AT 20 C 1.5K.m/W 0.8m A

5.3 AMPACITY IN AIR AT PROJECT CONDITION A VENDOR TO SPECIFY

5.4 AMPACITY IN GROUND AT PROJECT CONDITION A VENDOR TO SPECIFY


5.5 AMPACITY IN DUCT AT PROJECT CONDITION A VENDOR TO SPECIFY
5.6 REACTANCE AT FREQUENCY 50Hz TREFOIL / FLAT Ω/km VENDOR TO SPECIFY

5.7 RESISTANCE A.C AT MAXIMUM OPERATING TEMPERATURE Ω/km VENDOR TO SPECIFY

5.8 CONDUCTOR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.9 ARMOUR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.10 CABLE OVERALL SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.11 CORE SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.12 PHASE CAPACITANCE μF/km VENDOR TO SPECIFY

5.13 ZERO SEQUENCE REACTANCE Ω/km VENDOR TO SPECIFY

5.14 ZERO SEQUENCE RESISTANCE Ω/km VENDOR TO SPECIFY


5.15 ARMOUR RESISTANCE Ω/km VENDOR TO SPECIFY
5.16 MINIMUM INSULATION RESISTANCE AT 20oC MΩ/km VENDOR TO SPECIFY
5.17 POWER FREQUENCY TEST VOLT PER IMPULSE WITHSTAND kV VENDOR TO SPECIFY

CONFIDENTIAL
This document is prepared by Saipem Clough Joint Venture for Perdaman Chemicals and Fertilizers Pty Ltd. It contains proprietary and confidential information of Saipem Clough Joint Venture and/or of the Technologies Licensors who will safeguard their rights
according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed.
OWNER Contractor Job No.: PN835057
PERDAMAN CHEMICALS AND FERTILIZERS
Doc. No. 0000-EA-E-40107
PLANT LOCATION: BURRUP, AUSTRALIA
UNIT 0000
PROJECT: PROJECT CERES
D.A. CODE E-COM Sh. 9 of 15
DATASHEET FOR LOW VOLTAGE CABLES 0 1 2
REV.

LV CONTROL CABLE - OUTDOOR

VENDOR CONFIRMATION
S.No DESIGN DATA U. of M. PROJECT REQUIREMENTS REV
/ DATA

1 AMBIENT ENVIRONMENTAL CONDITIONS

1.1 ELEVATION ABOVE SEA LEVEL m < 1000 m

1.2 INSTALLATION LOCATION (INDOOR/OUTDOOR) OUTDOOR

1.3 MAXIMUM / MINIMUM AMBIENT TEMPERATURE RANGE °C +10 TO +40

1.4 OCCASIONAL EXTREME TEMPERATURE °C +8 TO +48

1.5 DESIGN AMBIENT TEMPERATURE °C 40

1.6 RELATIVE HUMIDITY 64% Max (at 40oC)

2 ELECTRICAL SYSTEM PARAMETERS


2.1 SYSTEM VOLTAGE kV 0.4kV
2.2 PHASES/WIRES 3/3+N+PE
2.3 SYSTEM FREQUENCY Hz 50

CU/PVC/NYLON/SWA/PVC (UNDER GROUND LAYING)


2.4 TYPE OF CABLE
CU/PVC/SWA/PVC (ABOVE GROUND LAYING)

2.5 PERMISSIBLE VOLTAGE VARIATION % +10 / -11


2.6 PERMISSIBLE FREQUENCY VARIATION % +/- 2
2.7 SYSTEM DESIGN LIFE years 25

3 CABLE GENERAL DATA


3.1 APPLICABLE STANDARD FOR CABLE MANUFACTURING AND TESTING AS/NZS 5000.1, AS/NZS 1125, IEC 60228, IEC 60332-3-22
3.2 CONDUCTOR TYPE STRANDED ANNEALED COPPER. CIRCULAR SECTION
3.3 CONDUCTOR SCREEN MATERIAL NOT APPLICABLE
3.4 CONDUCTOR CLASS CLASS 2
3.5 Uo/U (Um) AS PER TAB.1 OF IEC 60502-2 kV 0.6/1 (1.2)

3 CORE CABLES (2C+E)-WHITE, GREEN-YELLOW EARTHING CORE


UPTO 50CORE CABLES (49C+E)- ALL CORES WHITE, GREEN-YELLOW EARTHING CORE.
3.6 CORE IDENTIFICATION COLOURS CORE NUMBERING SHALL BE BLACK NUMBERING ON WHITE CORE INSULATION, NON-FADING 2
TYPE.
COMPLYING TO AS/NZS 5000.1
3.7 INSULATION TYPE PVC
3.8 INSULATION SCREEN NOT APPLICABLE

NON-HYGROSCOPIC FILLER MATERIAL TO PREVENT TRAVEL OF GAS BETWEEN HAZARDOUS


AND NON-HAZARDOUS AREAS.
3.9 FILLERS / BINDER TAPE MATERIAL, IF NECESSARY.
CORES LAID UP WITH EXTRUDED FILLER FOR UPTO 5 CORES. FOR 6 CORES OR MORE
WRAPPING OF POLYESTER TAPE.

3.10 BEDDING MATERIAL(INNER SHEATH) EXTRUDED PVC

3.11 WATER STOP NOT APPLICABLE

3.12 TERMITE PROTECTION ABOVE GROUND LAYING NOT APPLICABLE

3.13 UNDER GROUND LAYING NYLON 12 / DOUBLE BRASS TYPE / CHEMICAL TREATMENT (E.G TERMITEX)
3.14 ARMOURED TYPE GALVANISED STEEL WIRE ARMOUR
3.15 OUTER SHEATH COLOUR BLACK

3.16 OUTER SHEATH EXTRUDED PVC SUITABLE FOR 90DEG C

3.18 OUTER SHEATH OXYGEN INDEX MINIMUM 29%

3.17 MAXIMUM OPERATING TEMPERATURE °C 75

3.18 FINAL SHORT CIRCUIT TEMPERATURE °C 160

3.19 FIRE PERFORMANCE CHARACTERISTICS IEC 60332-3-22 CAT A

3.20 SPECIAL CONSTRUCTION UV/SUN LIGHT RESISTANT, CHEMICAL RESISTANT, MOISTURE RESISTANT

4 PHYSICAL DATA
4.1 NO. OF CORE x NOMINAL AREA TO BE DEFINED

4.2 DIAMETER OF WIRES IN EACH CONDUCTOR mm VENDOR TO SPECIFY

4.3 OVERALL DIAMETER mm VENDOR TO SPECIFY

4.4 MINIMUM BENDING RADIUS OF THE CABLE mm VENDOR TO SPECIFY

4.5 MINIMUM DRUM LENGTH m VENDOR TO SPECIFY


4.6 DRUM MAXIMUM LENGTH m VENDOR TO SPECIFY
4.7 NOMINAL INSULATION THICKNESS mm VENDOR TO SPECIFY
4.8 TOTAL WEIGHT kg/m VENDOR TO SPECIFY
4.9 COPPER WEIGHT kg/m VENDOR TO SPECIFY
4.1 MAXIMUM SHORT CIRCUIT TEMPERATRE °C VENDOR TO SPECIFY
4.11 CORE SCREEN MATERIAL VENDOR TO SPECIFY
4.12 CABLE OVERALL SCREEN MATERIAL VENDOR TO SPECIFY
4.13 ARMOUR WIRE DIAMETER mm VENDOR TO SPECIFY
4.14 UNDER ARMOUR DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.15 OVERALL CABLE DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.16 ARMOUR THICKNESS mm VENDOR TO SPECIFY
4.17 CONDUCTOR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY
4.18 ARMOUR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY
4.19 NO. OF ARMOUR WIRE AS PER IEC VENDOR TO SPECIFY

5 ELECTRICAL DATA
5.1 BASIC AMPACITY IN AIR AT 30oC A VENDOR TO SPECIFY
o VENDOR TO SPECIFY
5.2 BASIC AMPACITY IN GROUND AT 20 C 1.5K.m/W 0.8m A

5.3 AMPACITY IN AIR AT PROJECT CONDITION A VENDOR TO SPECIFY


5.4 AMPACITY IN GROUND AT PROJECT CONDITION A VENDOR TO SPECIFY
5.5 AMPACITY IN DUCT AT PROJECT CONDITION A VENDOR TO SPECIFY
5.6 REACTANCE AT FREQUENCY 50Hz TREFOIL / FLAT Ω/km VENDOR TO SPECIFY
5.7 RESISTANCE A.C AT MAXIMUM OPERATING TEMPERATURE Ω/km VENDOR TO SPECIFY
5.8 CONDUCTOR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.9 ARMOUR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.1 CABLE OVERALL SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.11 CORE SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.12 PHASE CAPACITANCE μF/km VENDOR TO SPECIFY
5.13 ZERO SEQUENCE REACTANCE Ω/km VENDOR TO SPECIFY

5.14 ZERO SEQUENCE RESISTANCE Ω/km VENDOR TO SPECIFY


5.15 ARMOUR RESISTANCE Ω/km VENDOR TO SPECIFY
5.16 MINIMUM INSULATION RESISTANCE AT 20oC MΩ/km VENDOR TO SPECIFY
5.17 POWER FREQUENCY TEST VOLT PER IMPULSE WITHSTAND kV VENDOR TO SPECIFY

CONFIDENTIAL
This document is prepared by Saipem Clough Joint Venture for Perdaman Chemicals and Fertilizers Pty Ltd. It contains proprietary and confidential information of Saipem Clough Joint Venture and/or of the Technologies Licensors who will safeguard their
rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed.
OWNER Contractor Job No.: PN835057
PERDAMAN CHEMICALS AND FERTILIZERS
Doc. No. 0000-EA-E-40107
PLANT LOCATION: BURRUP, AUSTRALIA
UNIT 0000
PROJECT: PROJECT CERES
D.A. CODE E-COM Sh. 10 of 15
DATASHEET FOR LOW VOLTAGE CABLES 0 1 2
REV.

LV CONTROL CABLE - INDOOR

VENDOR CONFIRMATION
S.No DESIGN DATA U. of M. PROJECT REQUIREMENTS REV
/ DATA

1 AMBIENT ENVIRONMENTAL CONDITIONS

1.1 ELEVATION ABOVE SEA LEVEL m < 1000 m

1.2 INSTALLATION LOCATION (INDOOR/OUTDOOR) INDOOR

1.3 MAXIMUM / MINIMUM AMBIENT TEMPERATURE RANGE °C +10 TO +40

1.4 OCCASIONAL EXTREME TEMPERATURE °C +8 TO +48

1.5 DESIGN AMBIENT TEMPERATURE °C 40

1.6 RELATIVE HUMIDITY 64% Max (at 40oC)

2 ELECTRICAL SYSTEM PARAMETERS


2.1 SYSTEM VOLTAGE kV 0.4kV
2.2 PHASES/WIRES 3/3+N+PE
2.3 SYSTEM FREQUENCY Hz 50
2.4 TYPE OF CABLE CU/XLPE/LSZH
2.5 PERMISSIBLE VOLTAGE VARIATION % +10 / -11
2.6 PERMISSIBLE FREQUENCY VARIATION % +/- 2
2.7 SYSTEM DESIGN LIFE years 25

3 CABLE GENERAL DATA


3.1 APPLICABLE STANDARD FOR CABLE MANUFACTURING AND TESTING AS/NZS 5000.1, AS/NZS 1125, IEC 60228, IEC 60332-3-22, IEC 60754-1
3.2 CONDUCTOR TYPE STRANDED ANNEALED COPPER. CIRCULAR SECTION
3.3 CONDUCTOR SCREEN MATERIAL NOT APPLICABLE
3.4 CONDUCTOR CLASS CLASS 2
3.5 Uo/U (Um) AS PER TAB.1 OF IEC 60502-2 kV 0.6/1 (1.2)
3 CORE CABLES (2C+E)-WHITE, GREEN-YELLOW EARTHING CORE
UPTO 50CORE CABLES (49C+E)- ALL CORES WHITE, GREEN-YELLOW EARTHING CORE.
3.6 CORE IDENTIFICATION COLOURS CORE NUMBERING SHALL BE BLACK NUMBERING ON WHITE CORE INSULATION, NON- 2
FADING TYPE.
COMPLYING TO AS/NZS 5000.1
3.7 INSULATION TYPE XLPE
3.8 INSULATION SCREEN NOT APPLICABLE
NON-HYGROSCOPIC FILLER MATERIAL TO PREVENT TRAVEL OF GAS BETWEEN
HAZARDOUS AND NON-HAZARDOUS AREAS.
3.9 FILLERS / BINDER TAPE MATERIAL, IF NECESSARY.
CORES LAID UP WITH EXTRUDED FILLER FOR UPTO 5 CORES. FOR 6 CORES OR MORE
WRAPPING OF POLYESTER TAPE.
3.10 BEDDING MATERIAL(INNER SHEATH) (OPTIONAL) EXTRUDED LSZH 2
3.11 WATER STOP NOT APPLICABLE

3.12 TERMITE PROTECTION NOT APPLICABLE


3.13 ARMOURED TYPE UN-ARMOURED
3.14 OUTER SHEATH COLOUR BLACK

3.15 OUTER SHEATH EXTRUDED LOW SMOKE ZERO HALOGEN TYPE

3.16 OUTER SHEATH OXYGEN INDEX MINIMUM 29%

3.18 MAXIMUM OPERATING TEMPERATURE °C 75

3.17 FINAL SHORT CIRCUIT TEMPERATURE °C 160

3.18 FIRE PERFORMANCE CHARACTERISTICS IEC 60332-3-22 CAT A

3.19 SPECIAL CONSTRUCTION CHEMICAL RESISTANT, MOISTURE RESISTANT

4 PHYSICAL DATA
4.1 NO. OF CORE x NOMINAL AREA TO BE DEFINED

4.2 DIAMETER OF WIRES IN EACH CONDUCTOR mm VENDOR TO SPECIFY

4.3 OVERALL DIAMETER mm VENDOR TO SPECIFY

4.4 MINIMUM BENDING RADIUS OF THE CABLE mm VENDOR TO SPECIFY

4.5 MINIMUM DRUM LENGTH m VENDOR TO SPECIFY

4.6 DRUM MAXIMUM LENGTH m VENDOR TO SPECIFY


4.7 NOMINAL INSULATION THICKNESS mm VENDOR TO SPECIFY
4.8 TOTAL WEIGHT kg/m VENDOR TO SPECIFY
4.9 COPPER WEIGHT kg/m VENDOR TO SPECIFY
4.1 MAXIMUM SHORT CIRCUIT TEMPERATRE °C VENDOR TO SPECIFY
4.11 CORE SCREEN MATERIAL VENDOR TO SPECIFY
4.12 CABLE OVERALL SCREEN MATERIAL VENDOR TO SPECIFY
4.13 ARMOUR WIRE DIAMETER mm VENDOR TO SPECIFY
4.14 UNDER ARMOUR DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.15 OVERALL CABLE DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.16 ARMOUR THICKNESS mm VENDOR TO SPECIFY
4.17 CONDUCTOR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY
4.18 ARMOUR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY
4.19 NO. OF ARMOUR WIRE AS PER IEC VENDOR TO SPECIFY

5 ELECTRICAL DATA
o
5.1 BASIC AMPACITY IN AIR AT 30 C A VENDOR TO SPECIFY

5.2 BASIC AMPACITY IN GROUND AT 20oC 1.5K.m/W 0.8m A VENDOR TO SPECIFY

5.3 AMPACITY IN AIR AT PROJECT CONDITION A VENDOR TO SPECIFY


5.4 AMPACITY IN GROUND AT PROJECT CONDITION A VENDOR TO SPECIFY
5.5 AMPACITY IN DUCT AT PROJECT CONDITION A VENDOR TO SPECIFY
5.6 REACTANCE AT FREQUENCY 50Hz TREFOIL / FLAT Ω/km VENDOR TO SPECIFY
5.7 RESISTANCE A.C AT MAXIMUM OPERATING TEMPERATURE Ω/km VENDOR TO SPECIFY
5.8 CONDUCTOR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.9 ARMOUR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.1 CABLE OVERALL SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.11 CORE SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.12 PHASE CAPACITANCE μF/km VENDOR TO SPECIFY
5.13 ZERO SEQUENCE REACTANCE Ω/km VENDOR TO SPECIFY

5.14 ZERO SEQUENCE RESISTANCE Ω/km VENDOR TO SPECIFY


5.15 ARMOUR RESISTANCE Ω/km VENDOR TO SPECIFY
5.16 MINIMUM INSULATION RESISTANCE AT 20oC MΩ/km VENDOR TO SPECIFY
5.17 POWER FREQUENCY TEST VOLT PER IMPULSE WITHSTAND kV VENDOR TO SPECIFY

CONFIDENTIAL
This document is prepared by Saipem Clough Joint Venture for Perdaman Chemicals and Fertilizers Pty Ltd. It contains proprietary and confidential information of Saipem Clough Joint Venture and/or of the Technologies Licensors who will safeguard their
rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed.
OWNER Contractor Job No.: PN835057
PERDAMAN CHEMICALS AND FERTILIZERS
Doc. No. 0000-EA-E-40107
PLANT LOCATION: BURRUP, AUSTRALIA
UNIT 0000
PROJECT: PROJECT CERES
D.A. CODE E-COM Sh. 11 of 15
DATASHEET FOR LOW VOLTAGE CABLES 0 1 2
REV.

LV CONTROL CABLE - FIRE RESISTANT OUTDOOR

VENDOR
S.No DESIGN DATA U. of M. PROJECT REQUIREMENTS REV
CONFIRMATION / DATA

1 AMBIENT ENVIRONMENTAL CONDITIONS

1.1 ELEVATION ABOVE SEA LEVEL m < 1000 m

1.2 INSTALLATION LOCATION (INDOOR/OUTDOOR) OUTDOOR

1.3 MAXIMUM / MINIMUM AMBIENT TEMPERATURE RANGE °C +10 TO +40

1.4 OCCASIONAL EXTREME TEMPERATURE °C +8 TO +48

1.5 DESIGN AMBIENT TEMPERATURE °C 40

1.6 RELATIVE HUMIDITY 64% Max (at 40oC)

2 ELECTRICAL SYSTEM PARAMETERS


2.1 SYSTEM VOLTAGE kV 0.4kV
2.2 PHASES/WIRES 3/3+N+PE
2.3 SYSTEM FREQUENCY Hz 50

CU/XLPE/NYLON/SWA/FR PVC (UNDER GROUND LAYING)


2.4 TYPE OF CABLE 2
CU/XLPE/SWA/FR PVC (ABOVE GROUND LAYING)

2.5 PERMISSIBLE VOLTAGE VARIATION % +10 / -11


2.6 PERMISSIBLE FREQUENCY VARIATION % +/- 2
2.7 SYSTEM DESIGN LIFE years 25

3 CABLE GENERAL DATA


3.1 APPLICABLE STANDARD FOR CABLE MANUFACTURING AND TESTING AS/NZS 5000.1, AS/NZS 1125, IEC 60228, IEC 60331 part 21 2
3.2 CONDUCTOR TYPE STRANDED ANNEALED COPPER. CIRCULAR SECTION
3.3 MICA TAPE MICA TAPE OVER EACH CONDUCTOR
3.4 CONDUCTOR SCREEN MATERIAL NOT APPLICABLE
3.5 CONDUCTOR CLASS CLASS 2
3.6 Uo/U (Um) AS PER TAB.1 OF IEC 60502-2 kV 0.6/1 (1.2)

3 CORE CABLES (2C+E)-WHITE, GREEN-YELLOW EARTHING CORE


UPTO 50CORE CABLES (49C+E)- ALL CORES WHITE, GREEN-YELLOW EARTHING CORE.
3.7 CORE IDENTIFICATION COLOURS CORE NUMBERING SHALL BE BLACK NUMBERING ON WHITE CORE INSULATION, NON- 2
FADING TYPE.
COMPLYING TO AS/NZS 5000.1

3.8 INSULATION TYPE XLPE


3.9 INSULATION SCREEN NOT APPLICABLE

NON-HYGROSCOPIC FILLER MATERIAL TO PREVENT TRAVEL OF GAS BETWEEN


HAZARDOUS AND NON-HAZARDOUS AREAS
3.10 FILLERS / BINDER TAPE MATERIAL, IF NECESSARY.
CORES LAID UP WITH EXTRUDED FILLER FOR UPTO 5 CORES. FOR 6 CORES OR MORE
WRAPPING OF POLYESTER TAPE.

3.11 BEDDING MATERIAL(INNER SHEATH) EXTRUDED PVC 2


3.12 WATER STOP NOT APPLICABLE

3.13 TERMITE PROTECTION ABOVE GROUND LAYING NOT APPLICABLE

3.14 UNDER GROUND LAYING NYLON 12 / DOUBLE BRASS TYPE / CHEMICAL TREATMENT (E.G TERMITEX)
3.15 ARMOURED TYPE GALVANISED STEEL WIRE ARMOUR
3.16 OUTER SHEATH COLOUR BLACK

3.17 OUTER SHEATH EXTRUDED PVC 2


3.18 OUTER SHEATH OXYGEN INDEX MINIMUM 29%

3.19 MAXIMUM OPERATING TEMPERATURE °C 75

3.20 FINAL SHORT CIRCUIT TEMPERATURE °C 160

3.21 FIRE PERFORMANCE CHARACTERISTICS FIRE RESISTANT AS PER IEC 60331-21 2


3.22 SPECIAL CONSTRUCTION UV/SUN LIGHT RESISTANT, CHEMICAL RESISTANT, MOISTURE RESISTANT

4 PHYSICAL DATA
4.1 NO. OF CORE x NOMINAL AREA TO BE DEFINED

4.2 DIAMETER OF WIRES IN EACH CONDUCTOR mm VENDOR TO SPECIFY

4.3 OVERALL DIAMETER mm VENDOR TO SPECIFY

4.4 MINIMUM BENDING RADIUS OF THE CABLE mm VENDOR TO SPECIFY

4.5 MINIMUM DRUM LENGTH m VENDOR TO SPECIFY

4.6 DRUM MAXIMUM LENGTH m VENDOR TO SPECIFY

4.7 NOMINAL INSULATION THICKNESS mm VENDOR TO SPECIFY

4.8 TOTAL WEIGHT kg/m VENDOR TO SPECIFY

4.9 COPPER WEIGHT kg/m VENDOR TO SPECIFY


4.1 MAXIMUM SHORT CIRCUIT TEMPERATRE °C VENDOR TO SPECIFY
4.11 CORE SCREEN MATERIAL VENDOR TO SPECIFY
4.12 CABLE OVERALL SCREEN MATERIAL VENDOR TO SPECIFY
4.13 ARMOUR WIRE DIAMETER mm VENDOR TO SPECIFY
4.14 UNDER ARMOUR DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.15 OVERALL CABLE DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.16 ARMOUR THICKNESS mm VENDOR TO SPECIFY

4.17 CONDUCTOR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY


4.18 ARMOUR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY
4.19 NO. OF ARMOUR WIRE AS PER IEC VENDOR TO SPECIFY

5 ELECTRICAL DATA
5.1 BASIC AMPACITY IN AIR AT 30oC A VENDOR TO SPECIFY

5.2 BASIC AMPACITY IN GROUND AT 20oC 1.5K.m/W 0.8m A VENDOR TO SPECIFY

5.3 AMPACITY IN AIR AT PROJECT CONDITION A VENDOR TO SPECIFY

5.4 AMPACITY IN GROUND AT PROJECT CONDITION A VENDOR TO SPECIFY


5.5 AMPACITY IN DUCT AT PROJECT CONDITION A VENDOR TO SPECIFY
5.6 REACTANCE AT FREQUENCY 50Hz TREFOIL / FLAT Ω/km VENDOR TO SPECIFY

5.7 RESISTANCE A.C AT MAXIMUM OPERATING TEMPERATURE Ω/km VENDOR TO SPECIFY


5.8 CONDUCTOR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.9 ARMOUR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY


5.1 CABLE OVERALL SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.11 CORE SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY

5.12 PHASE CAPACITANCE μF/km VENDOR TO SPECIFY

5.13 ZERO SEQUENCE REACTANCE Ω/km VENDOR TO SPECIFY

5.14 ZERO SEQUENCE RESISTANCE Ω/km VENDOR TO SPECIFY


5.15 ARMOUR RESISTANCE Ω/km VENDOR TO SPECIFY
o VENDOR TO SPECIFY
5.16 MINIMUM INSULATION RESISTANCE AT 20 C MΩ/km

5.17 POWER FREQUENCY TEST VOLT PER IMPULSE WITHSTAND kV VENDOR TO SPECIFY

CONFIDENTIAL
This document is prepared by Saipem Clough Joint Venture for Perdaman Chemicals and Fertilizers Pty Ltd. It contains proprietary and confidential information of Saipem Clough Joint Venture and/or of the Technologies Licensors who will safeguard their rights
according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed.
OWNER Contractor Job No.: PN835057
PERDAMAN CHEMICALS AND FERTILIZERS
Doc. No. 0000-EA-E-40107
PLANT LOCATION: BURRUP, AUSTRALIA
UNIT 0000
PROJECT: PROJECT CERES
D.A. CODE E-COM Sh. 12 of 15
DATASHEET FOR LOW VOLTAGE CABLES 0 1 2
REV.

LV CONTROL CABLE - FIRE RESISTANT INDOOR


VENDOR
S.No DESIGN DATA U. of M. PROJECT REQUIREMENTS CONFIRMATION / REV
DATA
1 AMBIENT ENVIRONMENTAL CONDITIONS

1.1 ELEVATION ABOVE SEA LEVEL m < 1000 m

1.2 INSTALLATION LOCATION (INDOOR/OUTDOOR) INDOOR

1.3 MAXIMUM / MINIMUM AMBIENT TEMPERATURE RANGE °C +10 TO +40

1.4 OCCASIONAL EXTREME TEMPERATURE °C +8 TO +48

1.5 DESIGN AMBIENT TEMPERATURE °C 40

1.6 RELATIVE HUMIDITY 64% Max (at 40oC)

2 ELECTRICAL SYSTEM PARAMETERS


2.1 SYSTEM VOLTAGE kV 0.4kV
2.2 PHASES/WIRES 3/3+N+PE
2.3 SYSTEM FREQUENCY Hz 50
2.4 TYPE OF CABLE CU/XLPE/FR LSZH
2.5 PERMISSIBLE VOLTAGE VARIATION % +10 / -11
2.6 PERMISSIBLE FREQUENCY VARIATION % +/- 2
2.7 SYSTEM DESIGN LIFE years 25

3 CABLE GENERAL DATA


3.1 APPLICABLE STANDARD FOR CABLE MANUFACTURING AND TESTING AS/NZS 5000.1, AS/NZS 1125, IEC 60228, IEC 60331 part 21 2
3.2 CONDUCTOR TYPE STRANDED ANNEALED COPPER. CIRCULAR SECTION
3.3 MICA TAPE MICA TAPE OVER EACH CONDUCTOR
3.4 CONDUCTOR SCREEN MATERIAL NOT APPLICABLE
3.5 CONDUCTOR CLASS CLASS 2
3.6 Uo/U (Um) AS PER TAB.1 OF IEC 60502-2 kV 0.6/1 (1.2)
3 CORE CABLES (2C+E)-WHITE, GREEN-YELLOW EARTHING CORE
UPTO 50CORE CABLES (49C+E)- ALL CORES WHITE, GREEN-YELLOW EARTHING CORE.
3.7 CORE IDENTIFICATION COLOURS CORE NUMBERING SHALL BE BLACK NUMBERING ON WHITE CORE INSULATION, NON-FADING 2
TYPE.
COMPLYING TO AS/NZS 5000.1
3.8 INSULATION TYPE XLPE
3.9 INSULATION SCREEN NOT APPLICABLE
NON-HYGROSCOPIC FILLER MATERIAL TO PREVENT TRAVEL OF GAS BETWEEN HAZARDOUS
AND NON-HAZARDOUS AREAS.
3.10 FILLERS / BINDER TAPE MATERIAL, IF NECESSARY.
CORES LAID UP WITH EXTRUDED FILLER FOR UPTO 5 CORES. FOR 6 CORES OR MORE
WRAPPING OF POLYESTER TAPE.
3.11 BEDDING MATERIAL(INNER SHEATH) (OPTIONAL) EXTRUDED LSZH 2
3.12 WATER STOP NOT APPLICABLE

3.13 TERMITE PROTECTION NOT APPLICABLE


3.14 ARMOURED TYPE UN-ARMOURED
3.15 OUTER SHEATH COLOUR BLACK

3.16 OUTER SHEATH EXTRUDED LOW SMOKE ZERO HALOGEN TYPE

3.17 OUTER SHEATH OXYGEN INDEX MINIMUM 29%

3.18 MAXIMUM OPERATING TEMPERATURE °C 75

3.19 FINAL SHORT CIRCUIT TEMPERATURE °C 160

3.20 FIRE PERFORMANCE CHARACTERISTICS FIRE RESISTANT AS PER IEC 60331-21 2


3.21 SPECIAL CONSTRUCTION CHEMICAL RESISTANT, MOISTURE RESISTANT

4 PHYSICAL DATA
4.1 NO. OF CORE x NOMINAL AREA TO BE DEFINED
4.2 DIAMETER OF WIRES IN EACH CONDUCTOR mm VENDOR TO SPECIFY
4.3 OVERALL DIAMETER mm VENDOR TO SPECIFY

4.4 MINIMUM BENDING RADIUS OF THE CABLE mm VENDOR TO SPECIFY

4.5 MINIMUM DRUM LENGTH m VENDOR TO SPECIFY

4.6 DRUM MAXIMUM LENGTH m VENDOR TO SPECIFY


4.7 NOMINAL INSULATION THICKNESS mm VENDOR TO SPECIFY
4.8 TOTAL WEIGHT kg/m VENDOR TO SPECIFY
4.9 COPPER WEIGHT kg/m VENDOR TO SPECIFY
4.1 MAXIMUM SHORT CIRCUIT TEMPERATRE °C VENDOR TO SPECIFY
4.11 CORE SCREEN MATERIAL VENDOR TO SPECIFY
4.12 CABLE OVERALL SCREEN MATERIAL VENDOR TO SPECIFY
4.13 ARMOUR WIRE DIAMETER mm VENDOR TO SPECIFY
4.14 UNDER ARMOUR DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.15 OVERALL CABLE DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.16 ARMOUR THICKNESS mm VENDOR TO SPECIFY
4.17 CONDUCTOR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY
4.18 ARMOUR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY
4.19 NO. OF ARMOUR WIRE AS PER IEC VENDOR TO SPECIFY

5 ELECTRICAL DATA
5.1 BASIC AMPACITY IN AIR AT 30oC A VENDOR TO SPECIFY
o VENDOR TO SPECIFY
5.2 BASIC AMPACITY IN GROUND AT 20 C 1.5K.m/W 0.8m A

5.3 AMPACITY IN AIR AT PROJECT CONDITION A VENDOR TO SPECIFY


5.4 AMPACITY IN GROUND AT PROJECT CONDITION A VENDOR TO SPECIFY
5.5 AMPACITY IN DUCT AT PROJECT CONDITION A VENDOR TO SPECIFY
5.6 REACTANCE AT FREQUENCY 50Hz TREFOIL / FLAT Ω/km VENDOR TO SPECIFY
5.7 RESISTANCE A.C AT MAXIMUM OPERATING TEMPERATURE Ω/km VENDOR TO SPECIFY
5.8 CONDUCTOR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.9 ARMOUR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.1 CABLE OVERALL SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.11 CORE SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.12 PHASE CAPACITANCE μF/km VENDOR TO SPECIFY
5.13 ZERO SEQUENCE REACTANCE Ω/km VENDOR TO SPECIFY

5.14 ZERO SEQUENCE RESISTANCE Ω/km VENDOR TO SPECIFY


5.15 ARMOUR RESISTANCE Ω/km VENDOR TO SPECIFY
5.16 MINIMUM INSULATION RESISTANCE AT 20oC MΩ/km VENDOR TO SPECIFY
5.17 POWER FREQUENCY TEST VOLT PER IMPULSE WITHSTAND kV VENDOR TO SPECIFY

CONFIDENTIAL
This document is prepared by Saipem Clough Joint Venture for Perdaman Chemicals and Fertilizers Pty Ltd. It contains proprietary and confidential information of Saipem Clough Joint Venture and/or of the Technologies Licensors who will safeguard their rights
according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed.
OWNER Contractor Job No.: PN835057
PERDAMAN CHEMICALS AND FERTILIZERS
Doc. No. 0000-EA-E-40107
PLANT LOCATION: BURRUP, AUSTRALIA
UNIT 0000
PROJECT: PROJECT CERES
D.A. CODE E-COM Sh. 13 of 15
DATASHEET FOR LOW VOLTAGE CABLES 0 1 2
REV.

LV CABLES - EARTHING CABLE OUTDOOR

VENDOR CONFIRMATION /
S.No DESIGN DATA U. of M. PROJECT REQUIREMENTS REV
DATA

1 AMBIENT ENVIRONMENTAL CONDITIONS

1.1 ELEVATION ABOVE SEA LEVEL m < 1000 m

1.2 INSTALLATION LOCATION (INDOOR/OUTDOOR) OUTDOOR

1.3 MAXIMUM / MINIMUM AMBIENT TEMPERATURE RANGE °C +10 TO +40

1.4 OCCASIONAL EXTREME TEMPERATURE °C +8 TO +48

1.5 DESIGN AMBIENT TEMPERATURE °C 40

1.6 RELATIVE HUMIDITY 64% Max (at 40oC)

2 ELECTRICAL SYSTEM PARAMETERS


2.1 SYSTEM VOLTAGE kV 0.4kV
2.2 PHASES/WIRES PE 2
2.3 SYSTEM FREQUENCY Hz 50
2.4 TYPE OF CABLE CU/PVC
2.5 PERMISSIBLE VOLTAGE VARIATION % +10 / -11
2.6 PERMISSIBLE FREQUENCY VARIATION % +/- 2
2.7 SYSTEM DESIGN LIFE years 25

3 CABLE GENERAL DATA

3.1 APPLICABLE STANDARD FOR CABLE MANUFACTURING AND TESTING AS/NZS 5000.1, AS/NZS 3000, AS/NZS 1125, IEC 60228, IEC 60332-1

3.2 CONDUCTOR TYPE FLEXIBLE BUNCHED ANNEALED STRANDED COPPER


3.3 CONDUCTOR SCREEN MATERIAL NOT APPLICABLE
3.4 CONDUCTOR CLASS CLASS 5
3.5 Uo/U (Um) AS PER TAB.1 OF IEC 60502-2 kV 0.6/1 (1.2)

COLOUR: GREEN / YELLOW


3.6 CORE IDENTIFICATION COLOURS 2
COMPLYING TO AS/NZS 5000.1

3.7 INSULATION TYPE PVC 75°C


3.8 INSULATION SCREEN NOT APPLICABLE
3.9 FILLERS / BINDER TAPE MATERIAL NOT APPLICABLE
3.10 BEDDING MATERIAL(INNER SHEATH) NOT APPLICABLE

3.11 WATER STOP NOT APPLICABLE

3.12 TERMITE PROTECTION NOT APPLICABLE


3.13 ARMOURED TYPE MULTI CORE CABLES NON-ARMOURED
3.14 SINGLE CORE CABLES NON-ARMOURED
3.15 OUTER SHEATH COLOUR NOT APPLICABLE

3.16 OUTER SHEATH NOT APPLICABLE

3.17 MAXIMUM OPERATING TEMPERATURE °C 75

3.18 FINAL SHORT CIRCUIT TEMPERATURE °C 160

3.19 FIRE PERFORMANCE CHARACTERISTICS IEC 60332-3-22 CAT A

3.20 SPECIAL CONSTRUCTION UV/SUN LIGHT RESISTANT, CHEMICAL RESISTANT, MOISTURE RESISTANT

4 PHYSICAL DATA
4.1 NO. OF CORE x NOMINAL AREA TO BE DEFINED

4.2 DIAMETER OF WIRES IN EACH CONDUCTOR mm VENDOR TO SPECIFY

4.3 OVERALL DIAMETER mm VENDOR TO SPECIFY

4.4 MINIMUM BENDING RADIUS OF THE CABLE mm VENDOR TO SPECIFY

4.5 MINIMUM DRUM LENGTH m VENDOR TO SPECIFY


4.6 DRUM MAXIMUM LENGTH m VENDOR TO SPECIFY
4.7 NOMINAL INSULATION THICKNESS mm VENDOR TO SPECIFY
4.8 TOTAL WEIGHT kg/m VENDOR TO SPECIFY
4.9 COPPER WEIGHT kg/m VENDOR TO SPECIFY
4.10 MAXIMUM SHORT CIRCUIT TEMPERATRE °C VENDOR TO SPECIFY
4.11 CORE SCREEN MATERIAL NOT APPLICABLE
4.12 CABLE OVERALL SCREEN MATERIAL NOT APPLICABLE
4.13 ARMOUR WIRE DIAMETER mm NOT APPLICABLE
4.14 UNDER ARMOUR DIAMETER WITH TOLERANCE mm NOT APPLICABLE
4.15 OVERALL CABLE DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.16 ARMOUR THICKNESS mm NOT APPLICABLE
4.17 CONDUCTOR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY
4.18 ARMOUR MAXIMUM PULLING TENSION kN NOT APPLICABLE
4.19 NO. OF ARMOUR WIRE AS PER IEC NOT APPLICABLE

5 ELECTRICAL DATA
5.1 BASIC AMPACITY IN AIR AT 30oC A VENDOR TO SPECIFY

5.2 BASIC AMPACITY IN GROUND AT 20oC 1.5K.m/W 0.8m A VENDOR TO SPECIFY

5.3 AMPACITY IN AIR AT PROJECT CONDITION A VENDOR TO SPECIFY


5.4 AMPACITY IN GROUND AT PROJECT CONDITION A VENDOR TO SPECIFY
5.5 AMPACITY IN DUCT AT PROJECT CONDITION A VENDOR TO SPECIFY
5.6 REACTANCE AT FREQUENCY 50Hz TREFOIL / FLAT Ω/km VENDOR TO SPECIFY
5.7 RESISTANCE A.C AT MAXIMUM OPERATING TEMPERATURE Ω/km VENDOR TO SPECIFY
5.8 CONDUCTOR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.9 ARMOUR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.10 CABLE OVERALL SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.11 CORE SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.12 PHASE CAPACITANCE μF/km NOT APPLICABLE
5.13 ZERO SEQUENCE REACTANCE Ω/km VENDOR TO SPECIFY

5.14 ZERO SEQUENCE RESISTANCE Ω/km VENDOR TO SPECIFY


5.15 ARMOUR RESISTANCE Ω/km NOT APPLICABLE
5.16 MINIMUM INSULATION RESISTANCE AT 20oC MΩ/km VENDOR TO SPECIFY

5.17 POWER FREQUENCY TEST VOLT PER IMPULSE WITHSTAND kV VENDOR TO SPECIFY

CONFIDENTIAL
This document is prepared by Saipem Clough Joint Venture for Perdaman Chemicals and Fertilizers Pty Ltd. It contains proprietary and confidential information of Saipem Clough Joint Venture and/or of the Technologies Licensors who will safeguard their rights
according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed.
OWNER Contractor Job No.: PN835057
PERDAMAN CHEMICALS AND FERTILIZERS
Doc. No. 0000-EA-E-40107
PLANT LOCATION: BURRUP, AUSTRALIA
UNIT 0000
PROJECT: PROJECT CERES
D.A. CODE E-COM Sh. 14 of 15
DATASHEET FOR LOW VOLTAGE CABLES 0 1 2
REV.

LV CABLES - EARTHING CABLE INDOOR

VENDOR CONFIRMATION /
S.No DESIGN DATA U. of M. PROJECT REQUIREMENTS REV
DATA

1 AMBIENT ENVIRONMENTAL CONDITIONS

1.1 ELEVATION ABOVE SEA LEVEL m < 1000 m

1.2 INSTALLATION LOCATION (INDOOR/OUTDOOR) INDOOR

1.3 MAXIMUM / MINIMUM AMBIENT TEMPERATURE RANGE °C +10 TO +40

1.4 OCCASIONAL EXTREME TEMPERATURE °C +8 TO +48

1.5 DESIGN AMBIENT TEMPERATURE °C 40

1.6 RELATIVE HUMIDITY 64% Max (at 40oC)

2 ELECTRICAL SYSTEM PARAMETERS


2.1 SYSTEM VOLTAGE kV 0.4kV
2.2 PHASES/WIRES PE 2
2.3 SYSTEM FREQUENCY Hz 50
2.4 TYPE OF CABLE CU/LSZH
2.5 PERMISSIBLE VOLTAGE VARIATION % +10 / -11
2.6 PERMISSIBLE FREQUENCY VARIATION % +/- 2
2.7 SYSTEM DESIGN LIFE years 25

3 CABLE GENERAL DATA

APPLICABLE STANDARD FOR CABLE MANUFACTURING AND


3.1 AS/NZS 5000.1, AS/NZS 3000, AS/NZS 1125, IEC 60228, IEC 60754-1
TESTING
3.2 CONDUCTOR TYPE FLEXIBLE BUNCHED ANNEALED STRANDED COPPER
3.3 CONDUCTOR SCREEN MATERIAL NOT APPLICABLE
3.4 CONDUCTOR CLASS CLASS 5
3.5 Uo/U (Um) AS PER TAB.1 OF IEC 60502-2 kV 0.6/1 (1.2)

COLOUR: GREEN / YELLOW


3.6 CORE IDENTIFICATION COLOURS 2
COMPLYING TO AS/NZS 5000.1

3.7 INSULATION TYPE LOW SMOKE ZERO HALOGEN TYPE


3.8 INSULATION SCREEN NOT APPLICABLE
3.9 FILLERS / BINDER TAPE MATERIAL NOT APPLICABLE
3.10 BEDDING MATERIAL(INNER SHEATH) NOT APPLICABLE

3.11 WATER STOP NOT APPLICABLE

3.12 TERMITE PROTECTION NOT APPLICABLE


3.13 ARMOURED TYPE MULTI CORE CABLES NON-ARMOURED
3.14 SINGLE CORE CABLES NON-ARMOURED
3.15 OUTER SHEATH COLOUR NOT APPLICABLE

3.16 OUTER SHEATH NOT APPLICABLE

3.17 MAXIMUM OPERATING TEMPERATURE °C 75

3.18 FINAL SHORT CIRCUIT TEMPERATURE °C 160

3.19 FIRE PERFORMANCE CHARACTERISTICS IEC 60332-3-22 CAT A

3.20 SPECIAL CONSTRUCTION CHEMICAL RESISTANT, MOISTURE RESISTANT

4 PHYSICAL DATA
4.1 NO. OF CORE x NOMINAL AREA TO BE DEFINED

4.2 DIAMETER OF WIRES IN EACH CONDUCTOR mm VENDOR TO SPECIFY

4.3 OVERALL DIAMETER mm VENDOR TO SPECIFY

4.4 MINIMUM BENDING RADIUS OF THE CABLE mm VENDOR TO SPECIFY

4.5 MINIMUM DRUM LENGTH m VENDOR TO SPECIFY

4.6 DRUM MAXIMUM LENGTH m VENDOR TO SPECIFY


4.7 NOMINAL INSULATION THICKNESS mm VENDOR TO SPECIFY
4.8 TOTAL WEIGHT kg/m VENDOR TO SPECIFY
4.9 COPPER WEIGHT kg/m VENDOR TO SPECIFY
4.10 MAXIMUM SHORT CIRCUIT TEMPERATRE °C VENDOR TO SPECIFY
4.11 CORE SCREEN MATERIAL NOT APPLICABLE
4.12 CABLE OVERALL SCREEN MATERIAL NOT APPLICABLE
4.13 ARMOUR WIRE DIAMETER mm NOT APPLICABLE
4.14 UNDER ARMOUR DIAMETER WITH TOLERANCE mm NOT APPLICABLE
4.15 OVERALL CABLE DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.16 ARMOUR THICKNESS mm NOT APPLICABLE
4.17 CONDUCTOR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY
4.18 ARMOUR MAXIMUM PULLING TENSION kN NOT APPLICABLE
4.19 NO. OF ARMOUR WIRE AS PER IEC NOT APPLICABLE

5 ELECTRICAL DATA
5.1 BASIC AMPACITY IN AIR AT 30oC A VENDOR TO SPECIFY

5.2 BASIC AMPACITY IN GROUND AT 20oC 1.5K.m/W 0.8m A VENDOR TO SPECIFY

5.3 AMPACITY IN AIR AT PROJECT CONDITION A VENDOR TO SPECIFY


5.4 AMPACITY IN GROUND AT PROJECT CONDITION A VENDOR TO SPECIFY
5.5 AMPACITY IN DUCT AT PROJECT CONDITION A VENDOR TO SPECIFY
5.6 REACTANCE AT FREQUENCY 50Hz TREFOIL / FLAT Ω/km VENDOR TO SPECIFY
5.7 RESISTANCE A.C AT MAXIMUM OPERATING TEMPERATURE Ω/km VENDOR TO SPECIFY
5.8 CONDUCTOR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.9 ARMOUR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.10 CABLE OVERALL SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.11 CORE SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.12 PHASE CAPACITANCE μF/km NOT APPLICABLE

5.13 ZERO SEQUENCE REACTANCE Ω/km VENDOR TO SPECIFY


5.14 ZERO SEQUENCE RESISTANCE Ω/km VENDOR TO SPECIFY
5.15 ARMOUR RESISTANCE Ω/km NOT APPLICABLE
o
5.16 MINIMUM INSULATION RESISTANCE AT 20 C MΩ/km VENDOR TO SPECIFY

5.17 POWER FREQUENCY TEST VOLT PER IMPULSE WITHSTAND kV VENDOR TO SPECIFY

CONFIDENTIAL
This document is prepared by Saipem Clough Joint Venture for Perdaman Chemicals and Fertilizers Pty Ltd. It contains proprietary and confidential information of Saipem Clough Joint Venture and/or of the Technologies Licensors who will safeguard their rights
according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed.
OWNER Contractor Job No.: PN835057
PERDAMAN CHEMICALS AND FERTILIZERS
Doc. No. 0000-EA-E-40107
PLANT LOCATION: BURRUP, AUSTRALIA
UNIT 0000
PROJECT: PROJECT CERES
D.A. CODE E-COM Sh. 15 of 15
DATASHEET FOR LOW VOLTAGE CABLES 0 1 2
REV.

LV CABLES - BARE EARTHING CABLE OUTDOOR

VENDOR CONFIRMATION /
S.No DESIGN DATA U. of M. PROJECT REQUIREMENTS REV
DATA

1 AMBIENT ENVIRONMENTAL CONDITIONS


1.1 ELEVATION ABOVE SEA LEVEL m < 1000 m
1.2 INSTALLATION LOCATION (INDOOR/OUTDOOR) OUTDOOR
1.3 MAXIMUM / MINIMUM AMBIENT TEMPERATURE RANGE °C +10 TO +40
1.4 OCCASIONAL EXTREME TEMPERATURE °C +8 TO +48
1.5 DESIGN AMBIENT TEMPERATURE °C 40
1.6 RELATIVE HUMIDITY 64% Max (at 40oC)

2 ELECTRICAL SYSTEM PARAMETERS


2.1 SYSTEM VOLTAGE kV N/A 2
2.2 PHASES/WIRES N/A 2
2.3 SYSTEM FREQUENCY Hz 50
2.4 TYPE OF CABLE CU
2.5 PERMISSIBLE VOLTAGE VARIATION % +10 / -11
2.6 PERMISSIBLE FREQUENCY VARIATION % +/- 2
2.7 SYSTEM DESIGN LIFE years 25

3 CABLE GENERAL DATA

3.1 APPLICABLE STANDARD FOR CABLE MANUFACTURING AND TESTING AS/NZS 5000.1, AS/NZS 3000, AS/NZS 1125, IEC 60228

STRANDED ANNEALED BARE COPPER

STRANDED ANNEALED TIN/ NICKEL PLATED COPPER (FOR AMMONIA PLANT


3.2 CONDUCTOR TYPE
ENVIRONMENT)

SOFT DRAWIN SHALL MEET THE REQUIREMENT OF IEC 60228.

3.3 CONDUCTOR SCREEN MATERIAL NOT APPLICABLE


3.4 CONDUCTOR CLASS CLASS 2
3.5 Uo/U (Um) AS PER TAB.1 OF IEC 60502-2 kV N/A 2

4 PHYSICAL DATA
4.1 NO. OF CORE x NOMINAL AREA TO BE DEFINED

4.2 DIAMETER OF WIRES IN EACH CONDUCTOR mm VENDOR TO SPECIFY


4.3 OVERALL DIAMETER mm VENDOR TO SPECIFY
4.4 MINIMUM BENDING RADIUS OF THE CABLE mm VENDOR TO SPECIFY

4.5 MINIMUM DRUM LENGTH m VENDOR TO SPECIFY


4.6 DRUM MAXIMUM LENGTH m VENDOR TO SPECIFY
4.7 TOTAL WEIGHT kg/m VENDOR TO SPECIFY
4.8 COPPER WEIGHT kg/m VENDOR TO SPECIFY
4.9 MAXIMUM SHORT CIRCUIT TEMPERATRE °C VENDOR TO SPECIFY
4. 10 OVERALL CABLE DIAMETER WITH TOLERANCE mm VENDOR TO SPECIFY
4.11 CONDUCTOR MAXIMUM PULLING TENSION kN VENDOR TO SPECIFY

5 ELECTRICAL DATA
5.1 BASIC AMPACITY IN AIR AT 30oC A VENDOR TO SPECIFY

5.2 BASIC AMPACITY IN GROUND AT 20oC 1.5K.m/W 0.8m A VENDOR TO SPECIFY

5.3 AMPACITY IN AIR AT PROJECT CONDITION A VENDOR TO SPECIFY


5.4 AMPACITY IN GROUND AT PROJECT CONDITION A VENDOR TO SPECIFY
5.5 AMPACITY IN DUCT AT PROJECT CONDITION A VENDOR TO SPECIFY
5.6 REACTANCE AT FREQUENCY 50Hz TREFOIL / FLAT Ω/km VENDOR TO SPECIFY
5.7 RESISTANCE A.C AT MAXIMUM OPERATING TEMPERATURE Ω/km VENDOR TO SPECIFY
5.8 CONDUCTOR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.9 ARMOUR SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.10 CABLE OVERALL SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.11 CORE SCREEN SHORT CIRCUIT CURRENT kA VENDOR TO SPECIFY
5.12 PHASE CAPACITANCE μF/km NOT APPLICABLE
5.13 ZERO SEQUENCE REACTANCE Ω/km VENDOR TO SPECIFY
5.14 ZERO SEQUENCE RESISTANCE Ω/km VENDOR TO SPECIFY
5.15 ARMOUR RESISTANCE Ω/km NOT APPLICABLE
o
5.16 MINIMUM INSULATION RESISTANCE AT 20 C MΩ/km VENDOR TO SPECIFY
5.17 POWER FREQUENCY TEST VOLT PER IMPULSE WITHSTAND kV VENDOR TO SPECIFY