Industrial Transformer Fires
Industrial Transformer Fires
Industrial
transformer
fires
Gary Howe EngTech FIFireE, President of the Norfolk and Suffolk branch of the Institution of Fire
Engineers, explores the impact of fires associated with industrial transformers, and how primary fire
risks fall on the oil itself which is used both as an insulator and coolant.
Table 1: Comparison of flash and fire points for differing oil types.
#Miscellaneous
What can fail in oil filled transformers? ♦ Current transformer issues.
Oil-filled transformers can withstand a certain number ♦ Oil leakage.
of discharges if these are not too energetic. But each ♦ Oil contamination.
discharge causes degradation of the liquid and eventually
the transformer may suffer a catastrophic failure due to this
degradation. (Society of Fire Protection Engineers, 2016)
Resilience ambition
The starting point before deciding on the type of protection
and risk mitigation measures required for transformers is
#Windings to first analyse the potential risks. This will assist with the
Insulation deterioration from: identification of critical aspects to consider. Without this
there is a risk of much time and effort being spent that is
♦ Moisture. The dielectric strength of transformer oil also
poorly focused and fails to achieve the financial protection
decreases rapidly with the absorption of moisture – as
anticipated. To define the resilience ambition, goals should
little as one part water in 40,000 parts oil (25ppm) can
be established early. The following are examples of key
reduce breakdown voltage by 50 percent ambient
points to consider:
temperature (M&I Materials, 2016)
♦ Overheating. ♦ Has the business interruption time and period to full
♦ Vibration. reinstatement been fully understood and calculated?
♦ Voltage surges. ♦ Has an emergency response plan been formulated?
♦ Mechanical stress from through-faults. ♦ Is there retention on site of critical spares?
Power Networks Tripping signals tested and verified by Power Network Company.
Electrical Site earthing. Lighting protection. Earthing resistor for each transformer is checked as part of outage
programme.
Gravel Gravel does not conduct electricity, which reduces the risk of electrical conduction in the event of
a current leak or equipment damage & in the event of an oil leak from the transformer, gravel helps
drain the oil towards the designated collection basin and acts as a fire-resistant layer.
♦ Firewalls,
♦ Spatial separation,
♦ Or other approved means for the purpose of limiting the
damage and potential spread of fire from a transformer
failure (National Fire Protection Association, 2020).
Fire walls.
♦ Where a firewall is required and provided, there are two Separation can be achieved from adjacent structures by a
potential options when seeking guidance for fire walls and 2-hour-rated firewall or by spatial separation in accordance
separation distances which is dependent on type and with Table 3. Where a firewall is provided between structures
quantity of oil. and a transformer, it should extend vertically and horizontally
♦ NFPA 850 Recommended Practice for Fire Protection for above the height of the conservator tank. A minimum height
Electric Generating Plants and High Voltage Direct Current of 1m is recommended. Whilst the minimum height above
Converter Stations (National Fire Protection Association, the conservator tank is stated as 0.3048m in NFPA 850, it is
2020) recommended that a safety margin is added to this of 0.7m to
♦ IEC BS EN IEC 61936-1:2021. allow for adverse wind conditions.
≥45,000 15 30
0.9 1.5
Dry type transformers Fire behaviour class Clearance to building surface or adjacent transformers
F0 1.5 3.0
F1 None None
Figure 1: Source: G.Howe. An example of an adequately designed Figure 2: Source: G.Howe. An example of an adequately designed fire
three-sided fire wall for a transformer located in the Netherlands. wall for a transformer located in South America. Note the height of the
Note the height of the wall above the height of the conservator tank. wall above the height of the conservator tank.
Fixed fire protection ♦ Transformer protection shall provide complete water spray
impingement on all exposed exterior surfaces.
A holistic approach should be taken in order to deal with
challenges posed by transformer fires. Conventional sprinkler ♦ Where there is insufficient space to install water spray
nozzles underneath transformers such that the water
protection or water spray fixed fire protection are historically
spray cannot directly impinge upon the bottom surfaces, it
the two forms of fixed fire protection with provenance for
shall be permitted to protect the surfaces underneath the
this application.
transformer by horizontal projection or by nozzles directed
to cool the area below the transformer projections.
Water is the most suitable and effective medium for
suppressing transformer fires due to the following attributes: ♦ The water shall be applied at a net rate not less than 0.25
gpm/ft2 [10.2 (L/min)/m2] of projected area of rectangular
♦ Heat energy absorption by large water droplets. prism envelope for the transformer and its appurtenances,
♦ Coarser sprays which penetrate the fire plume in order to and not less than 0.15 gpm/ft2 [6.1 (L/min)/m2] on the
reach the base of the fire. expected nonabsorbent ground surface area of exposure.
♦ Large water droplets penetrate flow of smoke and survive (National Fire Protection Association, 2022)
transport through hot gases.
♦ Effective surface cooling. NFPA 850
NFPA 850: Recommended Practice for Electric Generating
The following key principles should be considered: Plants and High Voltage Direct Current Converter Stations
(National Fire Protection Association, 2020)
♦ Particular care should be exercised in locating sprinkler
heads or nozzles so that they are in a position to provide ♦ Fire protection water spray systems provided for
good coverage and impingement on all exposed surfaces. transformer-rectifier sets should be designed for a density
♦ Transformer obstructions should be considered. Consider of 0.25 gpm/ft2 (10.2 mm/min) over the exposed surface of
obstructions which may shield water spray pattens. the transformer-rectifier set. Automatic sprinkler systems
♦ The worst-case hydraulic demand should be calculated. should be designed for a density of 0.25 gpm/ft2 (10.2
mm/min) over 500 ft2 (325 m2). (National Fire Protection
These aspects need to be considered by a competent person. Association, 2020)
Where applicable, recognised and robust fire protection
standards should be applied. The following additional criteria NFPA 750 Water mist
should also be considered for long term dependability and Sprinkler systems and water mist systems can inadvertently
robustness of the system: be considered as equivalent; however, this is not the case as
they perform very different roles. It’s common for promotors
♦ Power supply connections to firefighting pumps – consider
of water mist to state that water mist has equivalency with
the need for duplicate supplies - primary and secondary
sprinkler systems.
for increased robustness.
♦ Whistle in principle relying on a single firefighting pump
The design concept for sprinkler systems is historically based
might be acceptable, if impaired the firefighting system
upon a design density in mm/min over a specified area for
is then out of service. The use of duplicate pumps is best
each hazard category whereas water mist is much more
practice for long term reliability.
challenging, as water mist is different, as it requires the fire to
♦ Extended water supply duration for prolonged firefighting
drive the extinguishing process.
operations.
♦ Permanently fitted flow meter or test header facility for
There is no concept of a ‘safety factor’ which have been
pump set(s) to verify pump plate performance annually.
historically built into sprinklers systems over a long period of
time. The problem of designing a water mist system is mostly
Codes of practice
a mist transport problem. To be effective for the application of
NFPA 15 Water spray fixed systems transformers, the water mist needs:
Water spray fixed fire protection are to be designed and
installed in accordance with NFPA15: Standard for Water Spray ♦ Sufficient kinetic energy to overcome the turbulent
gases moving upwards and overcome vigorous
fixed Systems for Fire Protection (National Fire Protection
windspeed as transformers are typically located
Association, 2022)
externally.
Similar to other fixed fire protection systems additional ♦ Oil used to be a listed fire-retardant fluid. The use of higher
operational criteria may be required to satisfy the flashpoint fire-retardant fluids is beneficial if compatible
requirements of AHJ’s to provide additional resilience with operating specifications.
performance measures for water mist systems such as ♦ When calculating water supply durations from
integrity of power supply connections, increased water hydrant networks a minimum 120 min duration is
recommended to facilitate prolonged firefighting and final
extinguishment efforts.
♦ Provide fire hydrants in accordance with NFPA 291
Recommended Practice for Water Flow Testing and
Marking of Hydrants (National Fire Protection Association,
2022). Fire hydrants should be clearly identified on the
emergency plans. Ensure the hydrant network is subject to
periodic inspection, test and maintenance (ITM) including
flow testing. Results of flow tests which should record
pressure (psi) and flow (usgpm) obtained. Verification of
available pressure and flow rates is advisable, this should
be undertaken annually.
♦ Creation of a fire emergency plan in accordance with
NFPA 1660 Standard for Emergency, Continuity and Crisis
Management: Preparedness, Response and Recovery
(National Fire Protection Association, 2024)
♦ Liaison with site emergency teams to ensure they
are aware of access and facilities on site. This allows
preparation and planning for any incident.
♦ Ensure there is clear unobstructed access and suitable
hard standing areas for emergency service vehicles to
access the transformer for firefighting.
♦ Provide electrical grounding of the transformer in order to
prevent static electricity.
♦ Provide on-line monitoring of critical parameters.
♦ Critical spares for conveyors should be kept on site This case study highlights the importance of spatial
including those recommended by the original equipment separation of transformers from business-critical
manufacturer (OEM). infrastructure and the economic costs associated
with a major transformer outage. Refer to NFPA 850
On site evaluation process Recommended Practice for Fire Protection for Electric
When evaluating transformers, a competent person should Generating Plants and High Voltage Direct Current
consider the following areas as part of their site assessment: Converter Stations (National Fire Protection Association,
♦ Has the fire protection system been designed in 2020) for guidance on fire wall separation.
♦ That the air demand from the surroundings is ∙ " = 0.039 · 0.99 = 0.03897 Kgm–2
Mass rate of burning m
proportional to the stoichiometric requirements of the
∙ " X ΔHc (Drysdale, 2011)
Q: Heat release rate (HRR) = Aſ m
pyrolysis gases.
♦ That the total entrainment rate obeys the relationship Q: Heat release rate (HRR) = 30m2 · 0.03897Kgm-2 · 0.85 ·
established by Ricou and Spalding for the local 46.44MJ/Kg
entrainment rate in jets of different density than
Q: Heat release rate (HRR) = 30m2 · 0.03897Kgm-2 · 0.85 ·
the surroundings. The following relationship for
46,440KJ/Kg
dimensionless flame height was derived for the local
entrainment rate in jets of different density than the Q: Heat release rate (HRR) = 46,149.05kW
surroundings. 2
Flame height L/D= -1.02D + 0.235·Q 5
–
2
The flame height of a liquid spill or pool fire can be Flame height L/D= -1.02 · 10.5 + 0.235 · 46,149.05 5 = 6.53m
–
The correlation developed by Heskestad has been shown to Case study 3 – Generator step up
be quite robust for different fuels over a wide range of liquid transformer (GSUT)
pool fires only. The following calculation was undertaken An energy from waste site (EFW) with an integral gas
based on the specific characteristics of the transformer: turbine power station in Ireland was found to have a
Liquid quantity: 50,000L mineral oil. transformer containing 37,000L of mineral oil located
12.66m from nearby non-combustible radiative cooling
Area of pool fire: 30m2 towers, electrical equipment and critical infrastructure.
Combustion efficiency: 85%. The GSUT is only partially enclosed by a fire wall.
Heat of combustion: 46.44.7MJKg–1 (SFPE, 2016) The purpose of the exercise was to understand if the
is asymptotic mass loss rate per unit area as the pool value of radiation intensity above a specified level which
diameter increases towards infinity - 0.039 (kg m–2 s–1) would have the potential to weaken the structural steel
Kβ: optical properties of the fire plume an empirical A point source estimate of radiant flux is conceptually
constant is used which is the product of the extinction the simplest representation configurational model of
absorption coefficient k and the beam-length corrector β - a radiant source used in calculating the heat flux from
1.9 –1 (SFPE, 2016) a flame to target located outside the flame. To predict
D: Diameter: Based on a transformer compound area size a simple relationship that varies as the inverse
of 10m · 3m (30m2). Diameter = 10.5m (rounded up). square of the distance, R. For an actual point source
of radiation or a spherical source of radiation, the
∙ ”: Mass rate of burning m
m ∙"=m
∙ " ∞ (1 – e–kβD) (SFPE, 2016)
distance R is simply the distance from the point or from
∙ ” = 0.039 · (1 – e–0.7·10.5)
Mass rate of burning m the centre of the sphere to the target.
The SFPE handbook (Society of Fire Protection Engineers, In the presence of wind, the flames may not remain
2016) has been used for the primary source for the vertical. Thermal radiation to the surrounding objects
calculations. Page 3451 table A.35 lists critical heat flux and will change in the presence of a significant wind. In other
thermal response parameters of a wide range of materials. words, the flame will tilt forwards to the receiving target.
The critical heat flux intensity has been assessed as 10- In additions, the calculations do not take into account
15kW/m required for the pilot ignition of electrical cabling.
2
flying projectiles.
Heat release rate (HRR) = 61.53kW include additional resilience measures such as three-sided
fire walls, duplicate firefighting pumps, dual power supply
Indicent radiative heat flux: (12.66m from the centre line of
connections to firefighting pumps, longer duration water
the transformer):
supply capability, flow test facilities for annual testing of
0.60 · 61,530
q"// = = 8.33kW/m 2 firefighting pumps.
4 π 160.27
objective lies in mitigating the risks associated with business National Fire Protection Association, 2022. NFPA 15 Standard for Water
Spray Fixed Systems for Fire Protection, s.l.: NFPA.
interruption so that core processing activities are unaffected.
National Fire Protection Association, 2022. NFPA 291 Recommended
Practice for Water Flow Testing and Marking of Hydrants, s.l.: NFPA.
References
British Standards Institute, 2021. BS EN IEC 61936-1:2021 - TC. [Online] National Fire Protection Association, 2022. NFPA 72 National Fire Alarm
Available at: https://knowledge.bsigroup.com/products/power- and Signaling Code®, s.l.: NFPA.
installations-exceeding-1-kv-ac-and-1-5-kv-dc-ac?version=tracked National Fire Protection Association, 2024. NFPA 1660 Standard for
[Accessed 9 September 2024]. Emergency, Continuity, and Crisis Management: Preparedness,
Drysdale, D., 2011. In: An introduction to fire dyanmics 3rd edition. Response, and Recovery, s.l.: NFPA.
Chicester: Wiley, p. 235. National Fire Protection Associaton, 2023. NFPA 25 - Standard for the
FM Global, 2024. Transformers, s.l.: FM Global. Inspection, Testing, and Maintenance of Water-Based Fire Protection
Systems, s.l.: NFPA.
FPA, 2020. Water mist its complicated. s.l., FPA.
NFPA 1620, n.d. Standard for Pre-Incident Planning. s.l.:s.n.
ISO, 2000. ISO 2592:2000(en) Determination of flash and fire points -
Cleveland open cup method. [Online] SFPE, 2016. In: M. J.Hurley, ed. Society of Fire Protection Engineers
Available at: https://www.iso.org/obp/ui/#iso:std:iso:2592:ed-2:v1:en Handbook. New York: Springer, p. 402.
[Accessed 14 October 2024]. SFPE, 2016. In: M. J.Hurley, ed. Society of Fire Protection Engineers
ISO, 2016. ISO 2719:2016(EN) Determination of flashpoint - Pensky- Handbook. New York: Springer, pp. 865 - table 26.21.
martens closed cup method. [Online] Society of Fire Protection Engineers Handbook, 2016. In: M. J.Hurley, ed.
Available at: https://www.iso.org/obp/ui/#iso:std:iso:2719:ed-4:v1:en SFPE Handbook. New York: Springer, p. 402.
[Accessed 14th October 2024].
Society of Fire Protection Engineers Handbook, 2016. In: M. J.Hurley, ed.
M&I Materials, 2016. Protecting what matters in critical power SFPE Handbook. New York: Springer, pp. 865 - table 26.21.
transmission and distribution, Manchester: M&I Materials.
Society of Fire Protection Engineers Handbook, 2016. SFPE Handbook of
National Fire Protection Association, 2020. NFPA 850 Recommended Fire Protection Engineering. In: M. J.Hurley, ed. New York: Springer, pp.
Practice for Fire Protection for Electric Generating Plants and High 396-428.
Voltage Direct Current Converter Stations, s.l.: NFPA.
Society of Fire Protection Engineers, 2016. SFPE Handbook of Fire
National Fire Protection Association, 2022. NFPA 13 Standard for the Protection, New York: Springer.
Installation of Sprinkler Systems, s.l.: NFPA.
Engineer
AM AN
Findout
Find outmore
moreat:at: www.engc.org.uk/ieng
ife.org.uk/engineering-council