Chapter Two Symmetrical Faults
Chapter Two Symmetrical Faults
2
Introduction:
Sometime sabotage also results in creating faults. Contamination of
insulators may also result in a fault. Sometimes, small animals like rats,
lizards enter switch gear to create faults. Thus, symmetrical faults can also be
defined as:
Def:- A fault in which all three phase are shorted to one another and to
ground is known as three phase short circuit fault or symmetrical faults.
A three phase short circuit occurs rarely but it is most severe type of fault
involving largest currents. For this reason the balanced short circuit
calculations are performed to determine these large currents to be used to
determine the rating of the circuit breakers.
Faults can cause system to become unstable. Hence, it is necessary that
upon the occurrence of fault , the faulty section should be disconnected as
rapidly as possible in order that the normal operation of the rest of the
system is not affected. If this is not done, the equipment may be damaged
and the power supply is disrupted.
The relays should immediately detect the existence of the fault and initiate
circuit breaker operation to disconnect the faulty section.
3
Introduction:
Purpose of Fault Analysis
The purpose of fault analysis is to determine the values of voltages and
currents at different points of the system during the fault. Such an analysis
enables us to select appropriate protective schemes, relays, and circuit
breakers in order to save the system from the abnormal condition within
minimum time.
Note:- The assumptions for short circuit calculations are same as for per
unit system reactance diagram.
Limitation of Fault Current
When a short circuit occurs at any
point in a system, the short-circuit
current is limited by the impedance of
the system up to the point of fault.
Hence, the knowledge of the
impedances of various equipment and
circuits in the line of the system is
very important for the determination
of short-circuit currents. 4
Introduction:
Experience in the operation of transmission lines have shown that ultra-
high speed reclosing breakers successfully reclose after most faults. Of
those cases where reclosure is not successful, many are caused by
permanent faults where reclosure would be impossible regardless of the
interval between opening and reclosing.
Experiences has shown that between 70% and 80% of transmission line
faults are single line to ground faults, which arise from the flashover of only
one line to the tower and ground. Roughly 5% of all faults involve all three
phases. These are the so called symmetrical three phase faults.
Typical relative frequencies of occurrence of different kinds of faults in a
power system (in order of decreasing severity) are:
Type of Fault Percentage Occurrence
Three phase (3 ɸ) Faults 5%
Double line to ground (LLG) faults 10%
Double Line or Line to Line (LL) faults 15%
Single Line to ground faults 70%
5
Short Circuit Capacity:
The short circuit capacity of a bus network is defined as:
Def:-“The product of the magnitudes of the prefault voltage and the fault
current”.
The short circuit capacity is also known as the fault level. Mathematically
SCC V o I F VA
Where, V0 = the prefault voltage in Volts,
IF = the short circuit current in amperes.
For a solid fault, the fault impedance ZF = 0, and the fault current is given
by:
IF = VT / ZT
Where
VT =Thevenin voltage per phase in volts and
ZT =Thevenin impedance in ohms.
In our case VT = V0, therefore,
SCC 1 VT I F VT VT / ZT VT / ZT
2
VA / phase …Equation (A)
6
Short Circuit Capacity:
We know that,
SB
ZT p.u ZT ……………………Equation (B)
V 2B
Where,
Sb =Base volt-amperes in VA,
Vb = Base voltage in volts, ZT p.u = Thevenin impedance in per unit.
If VT is chosen as base voltage, VT = Vb. Therefore, Equation (B) can be
written as:
SB
ZT p.u ZT 2
V T
V 2T S
B …………………Equation (C)
ZT Z T p.u
Combining Equations (A) and (C)
SCC 1 Sb / Z T ( p.u ) VA / phase
SCC 3 ( Sb ) 3 / Z T ( p.u ) MVA
7
Sudden Short Circuit At the Armature Terminals
of Three Phase Synchronous Generator:
Consider the Figure which shows the equivalent circuit of three phase
generator on no load, running at its synchronous speed and carrying a
constant field current. It can be noticed that the equivalent circuit resembles
to series RL circuit.
Now, suppose, suddenly, the three phases of
the synchronous generator are short
circuited. The short circuit in each phase
consists of a steady state AC component and
a transient DC offset.
The synchronous generator offers time
varying reactance which changes from X’’d to
X’d and finally to Xd.
The currents which flow in different parts of a power system immediately
after the occurrence of a fault differ from those flowing a few cycles later just
before circuit breakers are called upon to open the line on both sides of the
fault. All of these current differ widely from the currents which would flow
under steady state conditions.
8
Sudden Short Circuit At the Armature Terminals
of Three Phase Synchronous Generator:
The synchronous generator during short circuit has a characteristic time
varying behaviour.
In the event of a short circuit, the flux per pole undergoes dynamic change
with associated transients in damper and field windings.
The reactance of the circuit model of the machine changes in the first few
cycles from a low sub-transient reactance to a higher transient value, finally
setting at a still higher synchronous (steady state) value.
Depending upon the arc interruption time of circuit breakers, a suitable
reactance value is used for the circuit model of synchronous generators for
short circuit analysis.
The current flowing immediately after a fault occurs in a power network is
determined by the impedances of the network components and the
synchronous machines.
The initial symmetrical rms fault current can be determined by
representing each machine by its sub-transient reactance in series with its
sub-transient internal voltage.
9
Sudden Short Circuit At the Armature Terminals
of Three Phase Synchronous Generator:
Figure shows the short circuit for one phase of a synchronous generator
with DC offset component neglected. The dashed envelope is called the
symmetrical short circuit armature current. The wave may be divided into
three distinct time periods.
Figure: Symmetrical short circuit current for one phase of synchronous generator
10
Sudden Short Circuit At the Armature Terminals
of Three Phase Synchronous Generator:
Sub-transient Period:
The period lasts for only about 2 cycles. During this period the current
decays very rapidly.
Transient Period:
The transient period lasts for about 20 to 30 cycles. During this period the
current decreases somewhat slowly.
Steady State Period:
The current reaches its steady state value.
Sub-transient Current:
The rms value of initial current (that is, the current at the instant of short
circuit) is called sub transient current I’’.
The corresponding reactance of the winding is called the direct-axis sub-
transient reactance X’’d. This reactance is essentially due to the presence of
damper winding.
11
Sudden Short Circuit At the Armature Terminals
of Three Phase Synchronous Generator:
Transient Current:
The rms value of current after two cycles to 30 cycles is called transient
current I’.
The corresponding reactance of the winding is called the direct-axis
transient reactance X’d. This reactance is essentially due to the presence of
field winding.
Steady State Current:
The rms value of
current after 20 cycles
is called steady state
current ( I ).
The corresponding
reactance of the
winding is called the
direct-axis transient
reactance Xd.
12
Selection of Circuit Breakers:
The electric utility company furnishes data to a customer who must
determine the fault current in order to specify circuit breakers properly for
an industrial plant or industrial power distribution system connected to the
utility system at a certain point.
Up to this point, we have devoted most of our attention to the sub-transient
current called the initial symmetrical current, which does not include the DC
component.
Inclusion of the DC component results in a rms value of current
immediately after the fault, which is higher than the sub-transient current.
For oil circuit breakers above 5 kV, the sub-transient current multiplied by
1.6 is considered to be the rms value of the current whose disruptive forces
the breaker must withstand during the first half cycle after the fault occurs.
This current is called Momentary current.
This interrupting current is of course lower than the momentary current
and depends on the speed of the breaker such as 8, 5, 3 or 2 cycles, which is
a measure of the time from the occurrence of the fault to the extinction of the
arc.
13
Selection of Circuit Breakers:
Two of the rated circuit breaker ratings which require the computation of
short circuit current are:
Rated momentary current and
Rated symmetrical interrupting current.
Symmetrical short circuit current is obtained by using the sub-transient
reactances for synchronous machines.
Momentary current (rms) is then calculated by multiplying the symmetrical
momentary current by a factor of 1.6 to account for the presence of DC-off
set current.
The DC off set value to be added to obtain the current to be interrupted is
accounted for by multiplying the symmetrical short circuit current by a
factor as tabulated below:
Circuit Breaker Speed Multiplying Factor
8 cycles or slower (0.16 seconds) 1.0
5 cycles (0.1 seconds) 1.1
3 cycles (0.06 seconds) 1.2
2 cycles (0.04 seconds) 1.4 14
Selection of Circuit Breakers:
The rated interrupting time of a circuit breaker is the period between the
instant of energizing the trip circuit and the arc extinction on an opening
operation.
Preceding this period is the tripping delay time which is usually assumed
to be ½ cycle for relays to pick up.
Obviously the rated MVA interrupting capacity of a circuit breaker is to be
more than (or equal to ) the Short circuit MVA required to be interrupted.
15
Reactor Control of Short Circuit Currents:
A reactor is a coil of number of turns designed to have a large inductance
as compared to its ohmic resistance.
With the fast expanding power system, the fault level (i.e. the power
available to flow into a fault) is also rising.
The circuit breakers connected in the power system must be capable of
dealing with maximum possible short-circuit currents that can occur at their
points of connection.
Generally, the reactance of the system under fault conditions is low and
fault currents may rise to a dangerously high value.
If no steps are taken to limit the value of these short-circuit currents, not
only will the duty required of circuit breakers be excessively heavy, but also
damage to lines and other equipment will almost certainly occur.
In order to limit the short-circuit currents to a value which the circuit
breakers can handle, additional reactances known as reactors are connected
in series with the system at suitable points.
Advantages:
Reactors limit the flow of short-circuit current and thus protect the
equipment from overheating as well as from failure due to destructive
mechanical forces. 16
Reactor Control of Short Circuit Currents:
Troubles are localised or isolated at the point where they originate without
communicating their disturbing effects to other parts of the power system.
This increases the chances of continuity of supply.
They permit the installation of circuit breakers of lower rating.
Location of Reactors:
Short circuit current limiting reactors may be connected in series:
With each generator Note:- The information about Bus-bar
With each feeder and can be found in Power system Analysis
by V. K. Mehta, Chapter 16, Topic 16.4 Bus
With Bus-bars.
bar arrangements Page Number 391.
Types of Reactors:
Depending upon the location of reactors, following are the main types of
Reactors
Generator Reactors
Feeder Reactors
Bus-bar Reactors
Each installation has its own particular demands which must be carefully
considered before a choice of reactor location can be made.
17
Ring System:
Under normal operation, each generator supplies feeder connected to its
own section and there will be no current through the reactors.
Thus, there is no voltage drop or power loss or very little power loss in the
reactor during normal operation. Generally, one feeder is fed from one
generator only.
The principal advantage of the system is that if a fault occurs on any feeder,
only that bus bar section is affected to which it is connected. The other
sections continue to operate normally.
One generator (to which the particular feeder is connected) mainly feeds
the fault current while the current fed from other generators is small due to
the presence of reactors.
Therefore, only that section of bus-bar is affected to which the feeder is
connected, the other sections being able to continue in normal operation
Tie-Bar System:
In this system, the generators are connected to the common bus-bar (tie-
bar) through the reactors but the feeders are fed from the generator side of
the reactors.
The tie-bar system is better and more flexible than the ring system. 18
Tie-Bar System:
In the ring system, the short circuit current due to a fault on any bus bar
section, is fed from the generators connected to other sections through one
reactor, whereas in the tie-bar system the current flows through two reactors
in series.
Therefore this system requires only half the reactance compared to the ring
system.
Disadvantages:
The Tie-bar system has the disadvantage that it requires an additional bus-
bar i.e. the tie-bar. 19
Selection of Base kVA & Its Importance:
The common kVA rating assumed for calculation of per unit or short circuit
current is known as base kVA.
The value of this base kVA is quite unimportant and may be :
Equal to that of the largest plant
Equal to the total plant capacity
Any arbitrary value
The fact is that the value of base kVA does not affect the actual short circuit
current.
Whatever value of base kVA we may choose, the actual value of short-
circuit current will be the same.
It can be proved with the help of an example as shown in the next slides
20
This example is taken from Book Principles of
Example Power System by V K Mehta, Chapter 17, Topic 17.4
Solution:
Suppose we have chosen 2500 kVA and 5000 kVA, two common base kVA.
Now first, short circuit current is calculated with 2500 kVA as below:
21
Solution:
ISC Calculation at 2500 kVA as Base kVA:
On this base value, reactance's of the various elements in the system are
calculated as below:
New Per unit Reactance of Generator G:
2
1110 2500 103
3
X j 0.1 3
j 0.1 p.u
1110 2500 10
G( p.u )new 3
Base kVA 5000 1000 5000 5000
I
SC( Base) 43.74 A
3 VBase 3 66 1000 3 66 114.3153
Actual Short Circuit Current ISC : Equation …2
I I I 2.22 43.74 97.1 A
SC( Actual ) SC( p.u ) SC( Base)
Hence, it can be observed from Equation 1 & 2 that actual
value of short circuit current does not depend upon the base
kVA. However, in the interest of simplicity, numerically
convenient value of base kVA should be chosen. Answer 24
Example
A three phase transmission line operating at 33 kV and having a resistance
and reactance of 5 ohms and 20 ohms respectively is connected to a
generating station bus bar through a 15 MVA step-up transformer which has
a reactance of 0.06 p.u. connected to bus bar are two generators, one 10 MVA
having 0.1 p.u reactance and another 5MVA having 0.075 p.u reactance.
Calculate the short circuit MVA and the fault current when a three phase
short circuit occurs:
(a) At the high voltage terminals of transformer
(b) At the load end of the transmission line. Select 15MVA and 11kV as the
base values.
(c) Which fault will have higher value of current.
25
Solution:
We know that the formula for new per unit impedance is given by:
2
base kVgiven base kVA new
Z Z ( p.u ) old
( p.u )new
base kVnew base kVA given
The total impedance from the generator side up to the point of fault FA is
given by: j 0.15 j 0.225
Z ( j 0.15) || ( j 0.225) j 0.06 j 0.06
Total ( p.u ) j 0.15 j 0.225
j 2 0.03375
Z j 0.06 1 0.03375 j 0.06
Total ( p.u ) j 0.375 j 0.375
( j ) 0.03375
Z
Total( p.u)
j 0.06 p.u j 0.09 j 0.06 p.u j 0.15 p.u
0.375 28
Solution:
The short circuit MVA fed into the fault at FA:
S Base 15 10 6 15 10 6 15 10 6 15 100 10 6
S Actual 100 MVA
Z p.u j 0.15 0.15 15 / 100 15
The fault current at point FA is given by:
Actual kVA 100 10 6 100 103 100 103
I SC 1.7495 103 1749 .5 A
3 VActual 3 33 10 3
3 33 57.1576
30
Solution:
The total impedance from the generator side up to the point of fault FB is
given by:
Z ( j 0.15) || ( j 0.225) j 0.06 0.06887 j 0.2754
Total ( p.u )
Z
Total ( p.u )
j 0.09 j 0.06 0.06887 j 0.2754 0.06887 j 0.4254
Z 0.06887 2 j 0.4254 2 0.431 p.u Note: To calculate short circuit
Total ( p.u ) MVA, impedance in polar form
The short circuit MVA fed into the fault at FA: is used. However, alternatively,
if impedance in rectangular
S Base 15 10 6 15 10 6 form is used, then short circuit
S Actual 34.8 MVA MVA is obtained by
Z p.u j 0.431 0.431 rationalizing the impedance.
The fault current at point FB is given by:
Solution
(a) Short circuit current fed by the Alternator:
The formula for new per unit impedance is given by:
34
Solution: Let 10MVA and 6.6 kV be the base values.
2
base kVgiven base kVA new
Z Z ( p.u ) old
( p.u )new
base kVnew base kVA given
Base kVA 10 10 6 10 103 10 103
I
SC( Base) 3 VBase
174.95 A
3 33 10 3
3 33 57.157
I I I
SC ( Actual ) SC ( p.u ) SC ( Base)
I 1.157 174.95
SC ( Actual )
I 202.4 A
SC ( Actual ) Answer
38
Example For Practice:
This example is taken from Book
Power System Analysis by
P.S.R.Murty. Chapter 6, Example 6.17.
39
Solution:
(a) Short Circuit MVA at LV side of Transformer:
Let 15,000 kVA as base kVA
The formula for new per unit impedance is given by:
2
base kVgiven base kVA new
Z Z ( p.u ) old
( p.u )new
base kVnew base kVA given
The short circuit MVA is given by:
S Base 15,000 10 3
S SC 250 MVA
Z p.u 0.06
For the radial network shown in Figure, a three phase fault occurs at F.
determine the fault current.
41
Solution: Let 100 MVA and 11 kV as chosen as base values.
(a) Short Circuit Current at End of Feeder:
The formula for new per unit impedance is given by:
2
base kVgiven base kVA new
Z Z ( p.u ) old
( p.u )new
base kVnew base kVA given
The formula to find per unit impedance of transmission line is given by:
SB Base kVA
Z p.u Z ohms 2 Z ohms
V B ( Base kV ) 2
The values are given for per kilometre. Hence, for 30 kilometre, we have to
multiply it with 30.
100 106 100
3 2 30 (0.27 j0.36 )
Z Line ( p.u ) 30 (0.27 j0.36 )
(33 10 ) 1089
Z Line ( p.u ) 30 (0.27 j0.36) 0.09183 (8.1 j10.8) 0.09183
Z Line ( p.u ) 0.744 j 0.99 p.u 43
Solution:
New Per unit Impedance of Transformer T2:
2
33 10 100 106
3
Z j 0.08 3
j 0.08 1 20 j1.6 p.u
T ( p.u)new
2 33 10 5 10 6
The impedance value of cable is given for per kilometre. Hence, for 3
kilometre, we have to multiply it with 3 as below:
100 106 100
Z Cable ( p.u ) 3 (0.135 j0.08) 3 (0.135 j 0.08 )
(6.6 103 ) 2 43.56
ZCable ( p.u ) 3 (0.135 j0.08) 2.295 (0.405 j0.24) 2.295
ZCable ( p.u ) 0.93 j 0.55 p.u 44
Solution:
The equivalent per unit single line diagram with fault at point F is shown as
below:
It can be observed that since the system is on no load prior to occurrence
of the fault, the voltages of the two generators are identical (in phase and
magnitude) and are equal to 1.0 p.u. the generator circuit can thus be
replaced by a single voltage source in series with the parallel combination
of generator reactance's as shown above. 45
Solution:
The total impedance up to the fault point is given as:
Z ( j1.5) || ( j1.25) j1.0 0.744 j 0.99 j1.6 0.93 j 0.55
Total ( p.u)
j1.5 j1.25
Z j1.0 0.744 j 0.99 j1.6 0.93 j 0.55
Total ( p.u ) j1.5 j1.25
j 21.875
Z j1.0 0.744 j 0.99 j1.6 0.93 j 0.55
Total ( p.u ) j 2.75
Z (1) ( j ) 0.681 j1.0 0.744 j 0.99 j1.6 0.93 j 0.55
Total ( p.u )
Z j 0.681 j1.0 0.744 j 0.99 j1.6 0.93 j 0.55
Total ( p.u )
Z 1.674 j 4.82 p.u 1.674 2 j 4.82 2 5.170.8 p.u
Total ( p.u )
The per unit short circuit current is given by:
47
This example is taken from Book Modern Power System
Example: Analysis by D.P.Kothari. Chapter 9, Example 9.4.
48
Solution: Let 50 MVA and 6.6 kV as chosen as base values.
(a) Short Circuit MVA at Far End of Feeder:
The formula for new per unit impedance is given by:
2
base kVgiven base kVA new
Z Z ( p.u ) old
( p.u )new
base kVnew base kVA given
51
Solution:
It can be noticed from the equivalent circuit that j0.1 and j0.12 are in series,
similarly, j0.2 and j0.24 are in series. Hence, these can be combined to get
one value as j0.22 and j0.44 p.u respectively. The modified equivalent per
unit single line diagram with fault at point F is shown as below:
The total impedance
from the generator to the
fault point is given as:
This example is the modification of previous example. The aim is to analyse the advantage
of reactor. Hence, in this example, reactors are not used. 55
Solution: Let 50 MVA and 6.6 kV as chosen as base values.
(a) Short Circuit MVA at Far End of Feeder:
The formula for new per unit impedance is given by:
2
base kVgiven base kVA new
Z Z ( p.u ) old
( p.u )new
base kVnew base kVA given
57
Solution:
The total impedance from the generator to the fault point is given as:
Z ( j 0.2) || ( j 0.1) || ( j 0.125) 0.069 j 0.138
Total ( p.u )
j 0.2 j 0.1
Z || ( j 0.125) 0.069 j 0.138
Total ( p.u ) j 0.2 j 0.1
j 2 0.02
Z || ( j 0.125) 0.069 j 0.138
Total ( p.u ) j 0.3
Z (1) ( j ) 0.0667 || ( j 0.125) 0.069 j 0.138
Total ( p.u )
Z j 0.0667 || ( j 0.125) 0.069 j 0.138
Total ( p.u )
j 0.0667 j 0.125 j 2 0.00833
Z 0.069 j 0.138 0.069 j 0.138
Total ( p.u ) j 0.0667 j 0.125 j 0.1916
Z (1) ( j ) 0.04346 0.069 j 0.138 j 0.04346 0.069 j 0.138
Total ( p.u )
Thank You
59