Relato Ref Systems
Relato Ref Systems
A A
P
MAIN
CHILLER
OFFICE
PRODUCTION AREA
A
CHILLER
MACHINE
AREA
B B
R
ENGINEERING
CONTROL
C
ROOM
C
ROOM
K
D D
I
LABORATORY
N
E E
G
ENTRANCE
DOCKING AREA
DOCKING AREA
MAIN
STORAGE AREA
F F
PR
OV
IN
CI
AL
RO
AD
SOLAR
DRYER
PR
O
VI
N
W E C
IA
L
R
O
A
D
M3
SITE LOCATION LAYOUT
1 1 SCALE NTS TOPAS
S IMPACT SCHOOL
PRODUCTION AREA
OFFICE ROOM
CONTROL
ROOM
LABORATORY
HALLWAY AREA HALLWAY AREA
ROOM
ENTRANCE
DOCKING AREA
DOCKING AREA
MAIN
STORAGE
AREA
P
C. PIPE PENETRATION THRU WALLS OR FLOOR SLAB.
D. CONDENSATE PIPING OF FAN COIL UNITS FOR PROPER DISPOSAL.
MAIN
CHILLER
E. CONCRETE PAD REQUIREMENTS FOR VARIOUS AIR-CONDITIONING AND
OFFICE VENTILATION EQUIPMENT.
F. ACTUAL LOCATIONS OF AIR-CONDITIONING AND VENTILATION EQUIPMENT.
PRODUCTION AREA
A
2.0 THE MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL
AIR-CONDITIONING AND VENTILATION DUCTWORK AS INDICATED ON THE PLANS AND
DRAWINGS INCLUDING ALL NECESSARY REQUIREMENT CONNECTIONS.
CHILLER
3.0 THE MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL THE COMPLETE
MACHINE
REFRIGERANT PIPING INCLUDING INSULATION, HANGERS, SUPPORTS AND
AREA
NECESSARY EQUIPMENT CONNECTIONS.
R
100 mm or MORE INSULATION PIPE 4.0 THE MECHANICAL CONTRACTOR SHALL COORDINATE WITH THE SUPPLIER OF
MULTI-SPLIT TYPE AIR-CONDITIONING UNIT FOR PROPER SIZING OF REFRIGERANT
ESCUTCHEON PLATE GALVANIZED STEEL PIPE SLEEVE
ENGINEERING WITH 1/2" MINIMUM ANNULAR SUCTION AND LIQUID AS WELL AS BRANCH SIZE JOINTS FROM ONE FAN COIL UNIT
CONTROL
STAINLESS STEEL
SPACE WITH INSULATION (FCU) TO ANOTHER.
ROOM REMOVE THE COVER PLATE SCREW TO
ROOM
HAVE ACCESS TO THE TERMINAL BOARD
K
PIPE 5.0 ALL DIMENSIONS ARE EXPRESSED IN MILLIMETRS UNLESS OTHERWISE
INDICATED.
600 mm or MORE
600 mm or MORE 6.0 LOCATION OF CONTROL THERMOSTAT, LOCAL CONTROL PANEL (BUILDING)
AND OTHER SENSORS SHALL BE A CONTRACTOR RESPONSIBILITY TO ENSURE AN
20mm CONDENSATE PIPE THRU WALL VAPOR BARRIER SEALING EFFICIENT OPERATIONS OF THE SYSTEM.
PIPE INSULATION COMPOUND 1/2" THICK BOTH ENDS
I
(WHERE REQUIRED)
7.0 ALL NECESSARY GOVERNMENT PERMITS SHALL BE SECURED AND PAID AT
OAKUM PACKING FOR BARE PIPE
AUTO LOUVER (VERTICAL) WALL AND INSULATION FOR INSULATED
THE EXPENSE OF THE MECHANICAL CONTRACTOR.
LABORATORY
N
9.0 MANUFACTURER AND MODEL NUMBER SPECIFIED IS NOT MANDATORY
EQUIPMENT FOR INSTALLATION, IT IS ONLY THE BASIS OF SPECIFICATION FOR THE
SELECTION OF THE EQUIPMENT.
G
200 mm or MORE WALLS AND OR AS DIRECTED BY THE PROJECT ENGINEER OR IN-CHARGE.
SCALE NTS 11.0 ALL MECHANICAL WORKS INCLUDED HEREIN SHALL BE INSTALLED IN
ACCORDANCE WITH THE LATEST REQUIREMENTS OF THE PHILIPPINE NATIONAL
BUILDING CODE AND THE LOCAL AUTHORITY.
200 mm or MORE
ENTRANCE
DOCKING AREA
DOCKING AREA
12.0 THE MECHANICAL CONTRACTOR SHALL SUBMIT THREE (3) SETS OF AS-BUILT
PLAN DULY SIGNED AND SEALED BY A REGISTERED PROFESSIONAL MECHANICAL
CONNECTING CABLE
MAIN
ENGINEER PRIOR TO THE COMPLETION OF THE ENTIRE PROJECT.
6.4 mm
(38") Ø
(41") Ø
9.5 mm (38") Ø ID
x 3/8" WALL
6.4 mm (41") Ø ID
SCALE NTS
x 3/8" WALL
CEMENT FILL
CONCRETE EDGE
THREAD ROD
CEILING
TYPICAL DETAIL OF FCU CEILING CASSETTE PIPE PENETRATION THROUGH ROOF SLAB VERTICAL RISERS SUPPORT DETAIL TYPICAL FCU CONDENSATE DRAIN CONNECTION DETAIL
SCALE NTS@A3 SCALE NTS@A3 SCALE NTS@A3 SCALE NTS@A3