The document provides technical specifications for the SIRIUS 3RV2011-1AA20 circuit breaker, designed for motor protection with a CLASS 10 A-release. It includes details on electrical endurance, operational parameters, and installation requirements, highlighting its suitability for various applications. The circuit breaker features a maximum operating voltage of 690 V and is rated for a current of 1.6 A, with additional protective functions and certifications.

Uploaded by

jrubil074
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
23 views8 pages

3RV20111AA20 Datasheet en

The document provides technical specifications for the SIRIUS 3RV2011-1AA20 circuit breaker, designed for motor protection with a CLASS 10 A-release. It includes details on electrical endurance, operational parameters, and installation requirements, highlighting its suitability for various applications. The circuit breaker features a maximum operating voltage of 690 V and is rated for a current of 1.6 A, with additional protective functions and certifications.

Uploaded by

jrubil074
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Data sheet 3RV2011-1AA20

Circuit breaker size S00 for motor protection, CLASS 10 A-release


1.1...1.6 A N-release 21 A Spring-type terminal Standard switching
capacity

Product brand name SIRIUS


Product designation Circuit breaker
Design of the product For motor protection
Product type designation 3RV2

General technical data


Size of the circuit-breaker S00
Size of contactor can be combined company-specific S00, S0
Product extension
● Auxiliary switch Yes
Power loss [W] total typical 6W
Surge voltage resistance rated value 6 kV
maximum permissible voltage for safe isolation
● in networks with grounded star point between 400 V
main and auxiliary circuit
● in networks with grounded star point between 400 V
main and auxiliary circuit
Protection class IP
● on the front IP20
● of the terminal IP20

3RV2011-1AA20 Subject to change without notice


Page 1/8 06/20/2019 © Copyright Siemens
Shock resistance
● acc. to IEC 60068-2-27 25g / 11 ms
Mechanical service life (switching cycles)
● of the main contacts typical 100 000
● of auxiliary contacts typical 100 000
Electrical endurance (switching cycles)
● typical 100 000
Certificate of suitability according to ATEX directive DMT 02 ATEX F 001
2014/34/EU
Protection against electrical shock finger-safe
Reference code acc. to DIN EN 81346-2 Q

Ambient conditions
Installation altitude at height above sea level
● maximum 2 000 m
Temperature compensation -20 ... +60 °C
Relative humidity during operation 10 ... 95 %

Main circuit
Number of poles for main current circuit 3
Adjustable pick-up value current of the current- 1.1 ... 1.6 A
dependent overload release
Operating voltage
● rated value 690 V
● at AC-3 rated value maximum 690 V
Operating frequency rated value 50 ... 60 Hz
Operating current rated value 1.6 A
Operating current
● at AC-3
— at 400 V rated value 1.6 A
Operating power
● at AC-3
— at 230 V rated value 250 W
— at 400 V rated value 550 W
— at 500 V rated value 750 W
— at 690 V rated value 1 100 W
Operating frequency
● at AC-3 maximum 15 1/h

Auxiliary circuit
Number of NC contacts for auxiliary contacts 0
Number of NO contacts for auxiliary contacts 0
Number of CO contacts
● for auxiliary contacts 0

3RV2011-1AA20 Subject to change without notice


Page 2/8 06/20/2019 © Copyright Siemens
Protective and monitoring functions
Product function
● Ground fault detection No
● Phase failure detection Yes
Trip class CLASS 10
Design of the overload release thermal
Operational short-circuit current breaking capacity
(Ics) at AC
● at 240 V rated value 100 kA
● at 400 V rated value 100 kA
● at 500 V rated value 100 kA
● at 690 V rated value 100 kA
Maximum short-circuit current breaking capacity (Icu)
● at AC at 240 V rated value 100 kA
● at AC at 400 V rated value 100 kA
● at AC at 500 V rated value 100 kA
● at AC at 690 V rated value 100 kA
Breaking capacity short-circuit current (Icn)
● at 1 current path at DC at 150 V rated value 10 kA
● with 2 current paths in series at DC at 300 V 10 kA
rated value
● with 3 current paths in series at DC at 450 V 10 kA
rated value
Response value current
● of instantaneous short-circuit trip unit 21 A

UL/CSA ratings
Full-load current (FLA) for three-phase AC motor
● at 480 V rated value 1.6 A
● at 600 V rated value 1.6 A
Yielded mechanical performance [hp]
● for single-phase AC motor
— at 230 V rated value 0.1 hp
● for three-phase AC motor
— at 460/480 V rated value 0.75 hp
— at 575/600 V rated value 0.75 hp

Short-circuit protection
Product function Short circuit protection Yes
Design of the short-circuit trip magnetic
Design of the fuse link for IT network for short-circuit
protection of the main circuit
● at 500 V gL/gG 20 A
● at 690 V gL/gG 16 A

3RV2011-1AA20 Subject to change without notice


Page 3/8 06/20/2019 © Copyright Siemens
Installation/ mounting/ dimensions
Mounting position any
Mounting type screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
Height 106 mm
Width 45 mm
Depth 97 mm
Required spacing
● with side-by-side mounting
— forwards 0 mm
— Backwards 0 mm
— upwards 50 mm
— downwards 50 mm
— at the side 0 mm
● for grounded parts
— forwards 0 mm
— Backwards 0 mm
— upwards 50 mm
— at the side 30 mm
— downwards 50 mm
● for live parts
— forwards 0 mm
— Backwards 0 mm
— upwards 50 mm
— downwards 50 mm
— at the side 30 mm

Connections/Terminals
Product function
● removable terminal for auxiliary and control No
circuit
Type of electrical connection
● for main current circuit spring-loaded terminals
Arrangement of electrical connectors for main current Top and bottom
circuit
Type of connectable conductor cross-sections
● for main contacts
— single or multi-stranded 2x (0,5 ... 4 mm²)
— finely stranded with core end processing 2x (0.5 ... 2.5 mm²)
— finely stranded without core end 2x (0.5 ... 2.5 mm²)
processing
● at AWG conductors for main contacts 2x (20 ... 12)
Design of screwdriver shaft Diameter 3 mm

3RV2011-1AA20 Subject to change without notice


Page 4/8 06/20/2019 © Copyright Siemens
Size of the screwdriver tip 3,0 x 0,5 mm

Safety related data


B10 value
● with high demand rate acc. to SN 31920 5 000
Proportion of dangerous failures
● with low demand rate acc. to SN 31920 50 %
● with high demand rate acc. to SN 31920 50 %
Failure rate [FIT]
● with low demand rate acc. to SN 31920 50 FIT
T1 value for proof test interval or service life acc. to 10 y
IEC 61508
Display version
● for switching status Handle

Certificates/approvals
General Product Approval For use in hazardous locations

Declaration of Conformity Test Certificates Marine / Shipping


Miscellaneous Type Test Certific- Special Test Certi-
ates/Test Report ficate

Marine / Shipping other


Confirmation

other Railway
Vibration and Shock

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs

3RV2011-1AA20 Subject to change without notice


Page 5/8 06/20/2019 © Copyright Siemens
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2011-1AA20
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2011-1AA20
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RV2011-1AA20
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2011-1AA20&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RV2011-1AA20/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV2011-1AA20&objecttype=14&gridview=view1

45 96.9
53.5
106

3RV2011-1AA20 Subject to change without notice


Page 6/8 06/20/2019 © Copyright Siemens
3RV2011-1AA20 Subject to change without notice
Page 7/8 06/20/2019 © Copyright Siemens
1/L1

3/L2

5/L3
-F

I> I> I>


2/T1

4/T2

6/T3

last modified: 06/19/2019

3RV2011-1AA20 Subject to change without notice


Page 8/8 06/20/2019 © Copyright Siemens