Comparison Novec 1230 Vs FM 200

The document compares FM 200 and Novec 1230 fire suppression agents, highlighting key differences in chemical properties, environmental impact, and operational efficiency. FM 200 has a higher global warming potential and longer atmospheric lifetime, while Novec 1230 is easier to refill on-site and has a significantly lower environmental impact. Both agents are UL listed, but Novec 1230 offers a warranty and requires less floor space for installation.

Uploaded by

Guillermo Lozano
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
138 views3 pages

Comparison Novec 1230 Vs FM 200

The document compares FM 200 and Novec 1230 fire suppression agents, highlighting key differences in chemical properties, environmental impact, and operational efficiency. FM 200 has a higher global warming potential and longer atmospheric lifetime, while Novec 1230 is easier to refill on-site and has a significantly lower environmental impact. Both agents are UL listed, but Novec 1230 offers a warranty and requires less floor space for installation.

Uploaded by

Guillermo Lozano
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Comparison of FM 200 Vs Novec 1230

Sr. No. FM 200 Novec 1230 Comments

1 ASHREA Agent Name HFC -227 ea FK-5-1-12 Fluro ketone

2 Chemical Formula CH3CHFCF3 CF2CF2C(O)CF(CF3)2

3 State in Room temperature Gas-liquid mixture Liquid Easy to store in standard drums

4 Boiling temperature -16.4 Deg. C 49 Deg. C Liquid is easy to handle, filling at site

5 Specific heat, Kj/Kg Deg C 0.891 0.808

FM 200 refilling has to be done in filling station which may


require weeks. Novec 1230 refilling can be done at site in
6 Solubility in Water <0.001 0.06% hours, in front of the client Ins the case of Novec 1230
you don't have to worry about refilling with spurious
gases.
7 Do you require a filling pump YES NO
for refilling cylinder

8 Can the agent be filled at site


and pressurized with nitrogen NO YES

9 Is the System UL Listed/LPCB Yes Yes

10 Is factory "first fill" required Yes Yes UL listing will be void if the factory filled
to get UL Listing for systems cylinder is not imported from manufacturer

11 Ozone depletion Potential Zero Zero

12 Atmospheric Life Time 35 years 5 days FM 200 retains the absorbed radiated heat
for 35 years and hence adds to Global warming.
Novec 1230 disintegrates in sunlight within 5 days and
can
not retain heat. Novec 1230 is good
13 Global Warning potential 3500 1
Since the design concentration of Novec 1230 is 4.2% for
14 NOAEL (No Observable adverse 9% 10% Class A fire, the operator can finish the operation before
leaving the room
effect Level) percentage

15 LOAEL (Lowest observable 10.50% >10 %


adverse effect level)

16 Maximum fill density lb/ft3 72 90

17 Design Concentration at 21 Deg C 7.5% to 8.7 % 4.2% to 6 % Class A and B and C

20 years, free
replacement warranty for Novec 1230 system environmental responsibility is on the
18 Environmental warranty from manufacturer No warranty
the entire system with a manufacturer and not the end-user
new system

Is seamless cylinders required for 8 sizes of welded cylinder available. FM 200 only 2
19 Yes No
installation? semless cylinder sizes available

80 %Less than Inert 90 % less than inert gas


20 Real Estate floor space used Novec 1230 system requires least amount of floor space
gas systems systems

21 Are Refill stations available in all metros? Yes Yes

Novec 1230 Filling stations are certified by Nitin 1230, the


Are the refill stations certified by the
22 No Yes manufacturer of Novec 1230 system to ensure original
manufacturer?
components and techniques are used.

If the refilling can be done within 48 hours of the


Do you require reserve bank of cylinders for
23 Yes No discharge reserve bank of cylinders are not required.
critical asset protection?
Novec 1230 can be refilled at site being a liquid.