Comparison of FM 200 Vs Novec 1230
Sr. No. FM 200 Novec 1230 Comments
1 ASHREA Agent Name HFC -227 ea FK-5-1-12 Fluro ketone
2 Chemical Formula CH3CHFCF3 CF2CF2C(O)CF(CF3)2
3 State in Room temperature Gas-liquid mixture Liquid Easy to store in standard drums
4 Boiling temperature -16.4 Deg. C 49 Deg. C Liquid is easy to handle, filling at site
5 Specific heat, Kj/Kg Deg C 0.891 0.808
FM 200 refilling has to be done in filling station which may
require weeks. Novec 1230 refilling can be done at site in
6 Solubility in Water <0.001 0.06% hours, in front of the client Ins the case of Novec 1230
you don't have to worry about refilling with spurious
gases.
7 Do you require a filling pump YES NO
for refilling cylinder
8 Can the agent be filled at site
and pressurized with nitrogen NO YES
9 Is the System UL Listed/LPCB Yes Yes
10 Is factory "first fill" required Yes Yes UL listing will be void if the factory filled
to get UL Listing for systems cylinder is not imported from manufacturer
11 Ozone depletion Potential Zero Zero
12 Atmospheric Life Time 35 years 5 days FM 200 retains the absorbed radiated heat
for 35 years and hence adds to Global warming.
Novec 1230 disintegrates in sunlight within 5 days and
can
not retain heat. Novec 1230 is good
13 Global Warning potential 3500 1
Since the design concentration of Novec 1230 is 4.2% for
14 NOAEL (No Observable adverse 9% 10% Class A fire, the operator can finish the operation before
leaving the room
effect Level) percentage
15 LOAEL (Lowest observable 10.50% >10 %
adverse effect level)
16 Maximum fill density lb/ft3 72 90
17 Design Concentration at 21 Deg C 7.5% to 8.7 % 4.2% to 6 % Class A and B and C
20 years, free
replacement warranty for Novec 1230 system environmental responsibility is on the
18 Environmental warranty from manufacturer No warranty
the entire system with a manufacturer and not the end-user
new system
Is seamless cylinders required for 8 sizes of welded cylinder available. FM 200 only 2
19 Yes No
installation? semless cylinder sizes available
80 %Less than Inert 90 % less than inert gas
20 Real Estate floor space used Novec 1230 system requires least amount of floor space
gas systems systems
21 Are Refill stations available in all metros? Yes Yes
Novec 1230 Filling stations are certified by Nitin 1230, the
Are the refill stations certified by the
22 No Yes manufacturer of Novec 1230 system to ensure original
manufacturer?
components and techniques are used.
If the refilling can be done within 48 hours of the
Do you require reserve bank of cylinders for
23 Yes No discharge reserve bank of cylinders are not required.
critical asset protection?
Novec 1230 can be refilled at site being a liquid.
With Kind Regards
KD