PDS T-806 10/17_V1
PENTENS T-806
High Performance Pumpable Non-Shrink Grout
Description Technical & Physical Data
PENTENS T-806 High Performance Pumpable
Form Premixed Powder
Non-Shrink Grout is a pumpable and ready-to-use rich
Colour Natural Grey
blend of cements and shrinkage compensating agents,
Aggregate Size 1.3 mm maximum
requiring only the addition of water to produce a
free-flowing and high strength grout. Compressive Strength
(n/mm²)
Water Content (Lts) 3.8 4.1
Uses 1 day > 35 > 30
PENTENS T-806 is suitable for use in grouting works
3 days > 60 > 50
with clearance of 6mm or more, such as:
7 days > 75 > 60
● Machine or equipment foundations
28 days > 85 > 75
● Structural columns
Density 2.10 g/cm³
● Cable ducts
Water Absorption % < 1.0%
● Concrete anchors
(ASTM C 413)
● Honeycomb repair
Tensile Strength 3.5
● Crane rails
(N/mm²) (ASTM C 190)
● Concrete anchors
● Cavities repair Initial Set Time +/- 45 min
● Recesses Expansion 0.1 ~ 2%
(ASTM C 827)
Open Time (mins) 20
Advantages Mixing Ratio Guide Consistency Water (litre)
PENTENS T-806 is an economical and easy-to-use
(per 25kg of Grout)
material requiring only the simple addition of water.
Flowable 4.0 – 4.4
Other beneficial properties are:
Pourable 3.6 – 4.0
■ Easy to mix and use.
Application Criteria Max thickness : 55mm
■ Low permeability.
(per grout) Min thickness : 6mm
■ Dense and non-shrink (1 step expansion).
Shelf Life / Storage 12 months in unopened
■ Excellent bond strength.
original bags and when
■ Chloride free.
■ Pumpable. stored in a dry, cool place.
■ Non-toxic. Packaging 25kg /bag
■ Rapid strength development.
■ Excellent work time. Important Notes
■ Good flow. 1. Apply to only clean surfaces which should be free
from water and leakages.
2. Minimum ambient and substrate temperature is 5ºC.
Typical Yield during curing stage. The quantity of aggregates should
not exceed 1-part aggregates to 1-part PENTENS
Flowable Pourable T-806 by weight. Other precautions such as the use of
Consistency Consistency chilled water, insulation of the formwork or baseplate
PENTENS T-806 74 x 25 kg bag 76 x 25 kg bag may be required. Please contact PENTENS Technical
Water 310 litres 303 litres Department for assistance.
Volume Mortar 1 m³ 1 m³
Curing
If formwork type repair is used, leave the formwork in
Instruction for Use place for at least 72 hours. Upon removal of the
formwork, apply wet burlap with plastic or chemical
Surface Preparation
curing agent to the exposed surface or other approved
Concrete surfaces should be clean, sound and free
curing methods.
from oil, grease, laitance and loose adhering particles.
Cleaning
Metal surfaces (iron and steel) should be free from Clean all tools and equipment with water immediately
scale, rust, oil and grease. All adsorbent surface must after use. Hardened mortar can only be mechanically
be well saturated with clean water but free from surface removed.
water prior to the application of PENTENS T-806.
Safety
Mixing Impervious gloves and barrier cream should be used
Place about 80% of the premeasured clean water (refer when handling these products. Eye protection should
to data sheet) into a clean container and gradually add be worn. In case of contact with eyes, rinse thoroughly
the whole bag of PENTENS T-806 while continuously with plenty of water for 15 minutes and seek medical
mixing. Add remaining water until the desired advice if symptoms persist. If contact with skin
consistency is obtained. Mix for 3 to 4 minutes with a occurs, it must be removed before curing takes place.
slow speed drill (maximum 500 RPM). Wash off with an industrial skin cleanser followed by
plenty of soap and water. Do not use solvent. Material
Application releases acetic acid during cure. Ensure adequate
After mixing, stir lightly with a spatula for a few ventilation when using these products.
seconds to release any entrapped air. Grout should be
placed within 25 minutes of mixing, The grout is then
poured immediately into the prepared formwork, pour
continuously from one side of the formwork until the
grout appears at the opposite side of the grout area.
When carrying out baseplate grouting, ensure
sufficient pressure head is maintained for
uninterrupted mortar flow. For formwork repair, the
prepared formwork must be firmly in place and kept
watertight.
When placing grout over a large area, it is important to
maintain a continuous flow throughout. Work
sequence must be properly organized to ensure an
uninterrupted flow. For sections thicker than 75mm or
for large grouting area, it is necessary to mix the
PENTENS T-806 with graded 10mm silt free
aggregates to minimize temperature rise generated
UFON NANO-CHEMICAL LTD. DONG JI (M) SDN. BHD.
8F, No.2, Lane 348, Sec 2, Chung-Shang Road, No.4, Jalan BP 4/1, Bandar Bukit Puchong,
Chung Ho City, Taipei Hsien, Taiwan, R.O.C. 47120 Puchong, Selangor, Malaysia.
Tel: +886 2 2240 0220 Fax: +886 2 2242 6536 Tel: +603 8066 8287 Fax: +603 8066 9287
URL: www.pentens.com URL: www.pentens.com.my
E-mail:
[email protected] E-mail:
[email protected]