Esutl 2 Midterm Notes
Esutl 2 Midterm Notes
- varies by type of fixture and water pressure at - Method developed by Dr. Roy Hunter of the
the fixture. National Bureau of
Standards (now the National Institute of
Water Demand Standards and
- is defined as the volume of water requested by Technology, NIST)
users to satisfytheir needs. - is an arbitrarily chosen measure that allows all
types of plumbing
Design Load - is the maximum probable or peak fixtures to be expressed in common terms; that
instantaneous demand for domestic water by a is, a fixture having
group of fixtures. The design load is typically twice the instantaneous flow rate of a second
expressed in gpm, L/min or L/s. fixture would have a
fixture unit value twice as large.
Pressure Difference
A pressure difference must exist at a plumbing The sole purpose of the fixture unit concept is to
fixture to cause water to flow—that is, water make it possible to calculate the design load on a
pressure at the fixture must be at a higher level system composed of different types of fixtures,
than atmospheric pressure for water to flow from each having different flow rates.
the fixture. Pressure difference (ΔP) is the
driving force of fluid flow. Water Supply Fixture Unit (WSFU)
static head, in psi, ΔPstatic= -0.433Z - is a probability factor that represents each
(in English) fixture connected to the water supply system and
used to determine the total use of water within a
static head, in kPa, ΔPstatic= -9.8Z given system.
(in metric) Method 2: WSFU Design
Method 1:Simple Empirical Design Method Table Method
In the empirical design method, piping In residential and small commercial buildings,
is sized with rules of thumb based on WSFU design tables can be used to establish
observation and experience. meter and distribution pipe size based on
the total demand in WSFUs and the supply
The empirical approach is used in design of pressure (the available static pressure after static
plumbing systems for head loss). Table 13.10 represents WSFU tables
residences and similar buildings with simple used to size building supply and branch lines,
plumbing systems. and meter and service lines.
For example, the mains that serve fixture Meter and distribution pipe can be sized using
branches can be sized as follows: the following methods:
• Up to three 1 Ú2 inch branches can be served 1. Obtain minimum service water pressure for
by a 3 Ú4 inch main the location of construction. Usually this is
• Up to three 3 Ú4 inch branches or up to six 1 available through the municipal water
Ú2 inch branches can department.
be served by a 1 inch main
2. Compute the total WSFUs, including 3. Based on the maximum desired velocity (e.g.,
proposed and projected future 8ft/s or 2.4m/s) and design load (Q), solve for
plumbing fixtures. the minimum required diameter (Di-min):
3. Calculate the maximum developed length of
water piping: the In customary units, minimum required diameter
actual length of pipe between the source of (Di-min) of the pipe, in inches, is based on the
supply and the most maximum desired velocity (v) of a fluid flowing
remote fixture plus the developed length of through a pipe, in ft/s, and the volumetric flow
fittings. Developed length rate (Q) in gpm:
can be approximated by multiplying the actual Di-min = Squareroot of 0.409Q/V
length to the most In m/s:
remote fixture by 1.2 to compensate for loss of Di-min = Squareroot of 21.22Q/V
meter and fittings.
4. Select a pipe size for the appropriate pipe
Meter and distribution pipe can be sized using material (from design tables such as Table 12.9
the following methods: through 12.15, 12.17 through 12.22 in Chapter
12) with an inside diameter equal to or greater
4. Compute the static head (the pressure loss than the minimum required diameter, Di-min.
from elevation change) and subtract it from the
service water pressure. Static Head is found by Method 4: Equal Friction Design Method
multiplying the vertical height (Z), in feet or in
meters: This method is more complex and more
accurate, but usually requires several
5. Use Table 13.10 to determine the meter and iterations before pipe diameters are selected.
distribution pipe Sizing the piping using the equal friction design
sizing based on the total demand in WSFUs, method requires several iterations.
maximum developed length of water piping, and Often, it is a matter of trial and error, even for
the supply pressure (the available experienced engineers; the process
static pressure after static head loss). involves first selecting a pipe size for the
building main, which runs from the water
Method 3: Velocity Design Method system to the riser(s), and then determining the
friction loss for the pipe used from
The velocity design method entails selecting the the charts in Figures 13.6 and 13.7. The chart
smallest pipe diameter without exceeding a used will depend on the type of pipe
preestablished maximum velocity for the design roughness (material).
load in the pipe. It is typically used accurately in
a down feed system and works well in To make a pipe selection for a specific condition
preliminary design of a plumbing system using the equal friction design method:
provided the system layout is reasonably
symmetrical. This method does require an 1. Find the volumetric flow rate along the side of
investigation of pressure loss to ensure that the chart.
residual pressure at the most remote fixture is 2. Move horizontally across the chart to the pipe
adequate. diameters and, for specific nominal diameters,
note associated pressure drops and velocities.
The procedure is outlined below: 3. Select a pipe diameter having the desired
1. Sum the total number of WSFUs for hot water pressure drop (including fittings) without
and cold water. exceeding the velocity limitation requirements.
(See Table 13.7.)
2. Determine maximum probable demand in
gpm. (See Table 13.8
or Table 13.9.)
WATER SUPPLY DESIGN CONCERN pipe, fitting, pump, or valve. Over
time, this eventually manifests as
Water Velocity pinhole leaking.
If pipe diameters are small, cost is low but noise, An unsatisfactory connection or arrangement of
erosion (from high velocities), and pumping An piping that can cause non-potable water to
unsatisfactory connection or arrangement of enter the potable water system. A cross-
piping that can cause non-potable water to connection can cause used or contaminated
enter the potable water system. A cross- water to
connection can cause used or contaminated mix with the water supply.
water to
mix with the water supply. An air gap is the vertical distance through open
air between an opening in a fixture or faucet
An air gap is the vertical distance through open conveying potable water to the flood level rim of
air between an opening in a fixture or faucet a tank or fixture.
conveying potable water to the flood level rim of
a tank or fixture.costs (from high-pressure CROSS-CONNECTIONS
losses) are high. BACKFLOW
Large diameter pipes reduce noise erosion and A type of cross-connection that occurs when
pumping costs but result in high installation contaminated liquid or substance unintentionally
costs. An intermediate pipe diameter is desirable. flows backwards into distribution pipes
containing potable water.
Maximum water velocities in plumbing water
supply piping are usually limited to a range of 5 Backpressure or back siphoning is backflow
to 10 ft/s (1.5 to 3 m/s). caused by a negative pressure (vacuum) in a
potable water system.
Maximum velocities of up to 15 ft/s (4.5 m/s)
are allowed for equipment feed lines in Vacuum breaker, a device or plumbing
mechanical rooms (e.g., boiler feed lines) where assembly that when properly installed in a
noise is less of a concern. The maximum safe plumbing system prevents backflow.
velocity for thermoplastic pipe is about 5 ft/s
(1.5 m/s). VACUUM BREAKER
STC = DU . gal/DU
The House Trap – a device placed in the house
Table 13.22 provides capacities of cylindrical drain immediately inside the
storage tanks. foundation wall of the building; serves as
barrier; prevents gases which occur in the
Sanitary Drainage System public sewers from circulating through the
plumbing system.
A sanitary drainage and vent system,
sometimes referred to as the drain, waste, and
vent (DWV) system, is a network of pipes that
remove wastewater from a building.
Interceptors
Pump Drives
Close Coupled
It is on the same shaft as the pump impeller.
Drive and pump are directly connected.
The design approach is less costly and is
acceptable on small pumps where
vibration and noise are not problems.
Flexible Coupled
Minimize vibration and wear between the
pump and pump drive.
Used in typically large pumps used in
building plumbing and heating and cooling
systems.
Multispeed Drives
Have separate speed settings (e.g., high,
medium, and low) so they can be adjusted to
control speed and, thus, pump flow rate.
Variable-Speed Drives
Provide speed control over a
continuous range.
Variable speed drives control pump speed by
changing the speed of the driver and thus
flow rate.
They are the most expensive type of drive in
initial cost but the least costly to operate.
Pump Performance
1. Pump Capacity
- is the flow rate at which liquid is moved or
pushed by a pump to the desired point in the
system. It is commonly measured in either
gallons per minute (gpm), liters per minute
(L/min), or cubic meters per hour (m3 /hr).