Swe Taw Min Than Aye Design Book
Swe Taw Min Than Aye Design Book
CONTENTS
PREPARED BY
SWELDAW-MINTHANAYE
1
ELECTRICAL DESIGN WITH CALCULATION
2
Major electrical equipments for building electrical system
· Transformers
· Diesel generators
· Transfer switches(A AND MANUAL TRANFER SWITH)
· Automatic voltage regulator
· Load bank
Load center
· Power factor correction capacitors
· UPS
· Bus ducts & bus bars
· Motors & pumps
· Light fixtures,air con,socket outlets,fridges,water cooler
· Switchgear
· Disconnecting switches
· Wires and cables
· Raceway
· Grounding materials
· Lightning materials
· TVSS (transient voltage suppression systems)(overvoltage)
· Wiring devices
· Cable trays and ladders, conduits, trunkings (wireway, cable management)
· Measuring devices
· Control devices
· Protection devices
Constitution of power distribution
3
Floor plan
4
A/C planing
5
6
7
SINGLE LINE DIAGRAM
8
9
10
Table 4.14 - Cable factors (terms) for conduit and trunking
Type of Conductor c.s.a. Factor for Factor for trunkingpvc Factor for trunking thermosetting
conductor (mm²) conduit insulation insulation
11
12
13
Standard ampere rating of breaker (IEE rule)
Mcb-.5,1,2,3,4,5,6,8,10,13,16,20,25,32,40,50,63A
Mccb-25,32,50,63,80,100,125,160,200,250,315,400,500
-630,800,1000,1250,1600,
Acb-400,630,800,1000,1250,1600,2000,2500,3200,4000,5000,, -6300
Vcb-800,1200,1600,2000, 2500,3000/3150,4000
14
15
Definition of AF(ampere rating of circuit breaker frame size)
16
MCB (Miniature Circuit Breaker)
CHARACTERISTICS
17
How to setting Overload Relay protection?
Basically to setting the overload value,we refer to this formula :
1) IB ≤ In ≤ IZ
2) I2 ≤ 1,45 x IZ
Note:
IZ = Current carrying capacity of conductor or cable or Motor
18
19
NSX630N circuit breaker equipped with a 400 A Micrologic 6.3E overcurrent trip relay, set at 0.9, will have a trip-
current setting:
Trip currents
Real life performance is rather more complex than simply tripping when rated current is exceeded.
The thermal element is slow acting, and responds to sustained overload currents of at minimum 1.13-1.45 x rated current
The magnetic element responds rapidly to substantial fault currents
MCBs don't trip at a sustained low level overload currents, BS EN 60898 requires a MCB to carry upto 1.13 times its
nominal current rating indefinitely
BS EN 60898 also requires a current of 1.45 (or more) times the nominal capacity to result in a trip. Currents between these
thresholds may or may not cause a trip depending on external influences such as temperature etc. Note these are minimum
performance requirements required for MCBs designed to meet the British Standard. Actual products can perform better than this
20
21
22
23
IEC 60228 is the International Electrotechnical Commission's international standard on conductors of insulated
cables. Among other things, it defines a set of standard wire cross-sections:
24
25
26
27
BUILDING ELECTRICAL DISTRIBUTION
28
29
30
31
Electrical Load Calculation
32
33
34
\
35
36
37
38
SHORT CIRCUIT DESIGN WITH CALCULATION
39
40
41
42
Rated Oil-immersed Cast-resin
Power
(kVA) Usc (%) Rtr (mΩ) Xtr (mΩ) Ztr (mΩ) Usc (%) Rtr (mΩ) Xtr (mΩ) Ztr (mΩ)
43
1,000 6 2.3 10.3 10.6 6 1.9 10.4 10.6
44
45
46
47
LIGHTING DESIGN WITH CALCULATION
48
49
50
51
52
53
54
55
56
57
Illuminance level
58
59
Determination of LLMF
60
(REF- CIBSE- chartered institute of building services engineering)
Determination of LSF
61
Determination of LMF, dirty environment
62
(REF- CIBSE- chartered institute of building services engineering)
63
64
determination of luminaire dust depreciation(LDD)
65
Determination of room surface dirt depreciation (RSDD)
66
Ballast factor(showing lamp and ballast combination)
(REF-SYLVANIA ballast technology and specification guide)
Room 30 20 9 AML=50 FC
Pc =80% hcc =0.0
67
Obtain effective ceiling cavity reflectance (pcc) pcc =( 80%)
68
69
70
71
EARTHING DESIGN WITH CALCULATION
Fault protection
72
73
74
75
Metal-To-Metal Touch Voltage: shock situation due to either hand-to-hand or hand-to-feet contact,
Transferred Voltage: shock situation due to hand-to-feet contact, occurred when a person standing within
the substation area touches a conductor grounded at a remote point,
Extended Transferred Voltage: shock situation due to hand-to-feet contact, occurred when or a person
standing at a remote point touches a conductor connected to the substation grounding grid.
76
Table 5.6 - Supplementary bonding conductor sizes
Circuit protective
Supplementary bonding conductor size
conductor size
77
78
79
80
81
82
83
84
(
85
R is the resistance to earth in ohms,
ρ is the resistivity of the soil, in Ω-m,
L is the length of electrode, in feets,
D is the diameter of the rod in inches
Example#1:
For a vertical rod electrode having 20mm diameter and 3 m length, calculate the resistance to earth noting that
soil resistivity is 50 Ω-m.
Solution:
The resistance to earth of a vertical rod electrode is given by the following equation:
Example#2:
For a vertical rod electrode having 25mm diameter and 2 m length, calculate the resistance to earth noting that
soil resistivity is 30 Ω-m.
Solution:
The resistance to earth of a vertical rod electrode (R) in ohms is given by the following equation:
86
87
88
The Earth Resistance of Single Rod or Pipe electrode is calculated as per BS 7430:
R=ρ/2×3.14xL (loge (8xL/d)-1)
Where ρ=Resistivity of Soil (Ω Meter),
L=Length of Electrode (Meter),
D=Diameter of Electrode (Meter)
Example:
Calculate Isolated Earthing Rod Resistance.
The Earthing Rod is 4 Meter Long
12.2mm Diameter
Soil Resistivity 500 Ω Meter
R=500/ (2×3.14×4) x (Loge (8×4/0.0125)-1) =156.19 Ω.
Example:
Calculate Total Earthing Rod Resistance of 200 Number arranges in Parallel having 4 Meter Space
of each and if it connects in Hollow Square arrangement. The Earthing Rod is 4 Meter Long and
having 12.2mm Diameter, Soil Resistivity 500 Ω.
First Calculate Single Earthing Rod Resistance
89
R=ρ/2×3.14xL (loge (8xL/d)-1)
R=500/ (2×3.14×4) x (Loge (8×4/0.0125)-1) =136.23 Ω
Now Calculate Total Resistance of Earthing Rod of 200 Number in Parallel condition.
a=500/(2×3.14x136x4)=0.146
Ra (Parallel in Line) =136.23x (1+10×0.146/200) =1.67 Ω.
If Earthing Rod is connected in Hollow Square than Rod in Each side of Square is 200=(4n-1) so
n=49 No.
Ra (In Hollow Square) =136.23x (1+9.4×0.146/200) =1.61 Ω.
90
The first method is to measure the impedance of the supply by determining its voltage regulation, that is, the
amount by which the voltage falls with an increase in current. For example, consider an installation with a
no-load terminal voltage of 240 V. If, when a current of 40 A flows, the voltage falls to 238 V, the volt drop
will be due to the impedance of the supply.
91
92
93
94
95
LIGHTNING DESIGN WITH CALCULATION
The three basic methods recommended for determining the position of the air termination
system components are:
external areas of the structure with heights more than the radius of corresponding rolling sphere
96
Introduction To Design Calculations Of Lightning Protection Systems
It is very important before explaining the design calculations of lightning protection systems to
highlight some important topics or expressions that will be used in these calculations. These
topics can be listed as follows:
97
Protection angle method
98
Shapes of Protection Zones Provided By Protection Angle Method
99
Protection Levels According to Height and α Angles
100
Protective range of rolling sphere method
101
The Rolling Sphere Method Protection Applications
The rolling sphere methods can be used for the following applications:
102
1. Rolling sphere method with rod air-terminations,
2. Rolling sphere method and mesh/catenary conductors,
3. Rolling sphere method and Tall structures.
When rods are to be used as the air-termination for the protection of plane surfaces the following
formula can be used:
4. d = 2 √ (2rh – h2)
Where:
103
104
105
106
Rolling Sphere Method And Tall Structures
107
108
MESH METHOD
109
effective at capturing lightning flashes than mesh
conductors installed upon, or just above structure
surface. For example; Rod air-terminations of height in
the region of 0.5 m are preferable to shorter rods or
conductors on the building surface.
The Protection Angle The protection angle method can only be used with
limited vertical distances (limited height).
Method (PAM)
The mesh method is more suitable for the protection of
The Mesh Method flat/plane surfaces.
Meshed conductors used as air-terminations should not be confused with the mesh method. While the mesh method
requires the use of surface mounted meshed conductors (a grid) to protect flat surfaces, the rolling sphere and
protection angle method can also be used to determine protection provided by elevated meshed conductors to
protect a variety of compound surfaces. The below Table shows the Suitability Of Air-Termination Forms and
Design Methods.
Protection Method
Air-Termination
Rolling Protection
Mesh Method
Sphere Angle
Rod √√√ √√
Meshed conductors – (on structure
√(1)
surface)
Meshed conductors – (elevated
√√ √√
from structure)
Catenary wires √√ √√
Note (1): Mesh method is appropriate for the evaluation of the protection of the bound flat
surface. Rolling sphere and protection angle methods can be used to determine protection of
adjacent areas.
According to IEC 62305-3, Based on the class of the lightning protection system, the below table indicate
Maximum values with each class for:
Class Of LPS
Rolling Sphere Radius
(Lightning Mesh Size (M) Protection Angle
(M)
Protection Level)
I 20 5x5 See below figure
II 30 10 x 10
110
III 45 15 x 15
IV 60 20 x 20
:
Protection Angle with corresponding height and Class of LPS
Lightning protection
Class of LPS
level (LPL)
I I (highest protection)
II II
III III
IV IV (lowest protection)
h (m) 20 30 45 60
Protection level Mesh Width d (m)
R (m) α0 α0 α0 α0
I 20 25 * * * 5
II 30 35 25 * * 10
III 45 45 35 25 * 15
IV 60 55 45 35 25 20
111
First: According to IEC 62305-3
Typical Distance
Class of LPS between down
conductors
I 10 m
II 10 m
III 15 m
IV 20 m
At least two down conductors shall be provided on any kind of structure, including
steeples.
Structures exceeding 76 m (250 ft) in perimeter shall have a down conductor for every 30
m (100 ft) of perimeter or fraction thereof.
Lower roofs or projections that are located within a zone of protection shall not be
required to be included in the perimeter measurement.
The number of down conductors depends upon the building area or upon its
circumference in such away that the minimum numbers of down conductors is (2).
A building with area not exceeding 100 m2 or its perimeter up to 30m or less, the number
of down conductor = one.
For buildings with height <30 m, the minimum number resulted from one of the following
two methods:
112
2 2
1. One down conductors for first 100m in addition of one conductor for each 300m or a part
of it.
2. One down conductor for each 30m of building perimeter.
For buildings with height ≥30 m, the minimum number of down conductor is given in the
following Table#2:
Number of
Area of building in m2
down conductors
100 - 400 2
400 - 700 3
700 - 1000 4
1000 - 1300 5
1300 – 1600 6
1600 - 1900 7
Table#2
Example#2:
If the total perimeter of intermediate school = 625 mt, Find the Minimum required number of
down conductors by the rules of thumb method if the intermediate school height < 30 m?
Solution:
Since intermediate school height < 30 m , then use One down conductor for each 30m of building
perimeter.
113
Llightning protection of ESE
114
115
116
117
SHORT CIRCUIT RATING FOR PVC INSULATED CABLES
118
119
120
121
122
123
124
125
126
.
127
,
128
129