Ug03i S
Ug03i S
USER'S MANUAL
<UG SERIES SX-BUS Communications>
TYPES: UG03I-S
UG02I-S
FEH357a
Preface
Thank you very much for purchasing the Fuji UG Series Programmable Operation Display.
This manual describes how to use the SX-bus interface type.
This manual will help you understand the outline information and to master it efficiently by
giving examples in each chapter.
In addition to this manual, the following manuals on the UG Series are available. Please
ask your nearest dealer for the appropriate manuals and read them too.
Notes
(1) No part of this manual may be reproduced in any form without the prior permission of the
publisher.
(2) The contents of this manual, including the specifications, are subject to change without notice
for the purposes of improvement.
(3) This manual was prepared with the utmost care. However, if you find any ambiguity, errors,
etc., please contact any of our sales offices that are listed at the end of this manual. When you
do so, be sure to quote the manual number given on the cover of this manual.
Record of Revisions
The manual number is shown at the bottom right of the front cover.
Printing Date Reference No. Revised Contents
August, 2001 FEH357 1st Edition printed
Preface
Record of Revisions
Contents
1. General ............................................................................. 1-1
2. Specifications ................................................................... 2-1
2.1 Applicable Models .............................................................................2-1
Applicable PLCs .............................................................................................. 2-1
Applicable PODs .............................................................................................. 2-1
2.2 Communication Specifications .......................................................... 2-2
2.3 Available Areas of PLC Internal Memory ............................................2-3
3. Setting & Wiring of POD .................................................... 3-1
3.1 Mounting the Interface Unit ..............................................................3-1
When UG03I-S is used ..................................................................................... 3-1
When UG02I-S is used ..................................................................................... 3-3
3.2 Cable Connection and Station Number Setting .................................. 3-4
3.3 External Dimensions........... ..............................................................3-5
SX bus interface unit ...................................................................................... 3-5
External dimensionswhen mounted on POD .................................................... 3-5
4. Screen Data Editing .......................................................... 4-1
4.1 Select PLC Type ................................................................................4-1
4.2 Communication Parameters ..............................................................4-2
5. Registration on PLC Side(Setting with D300win) ............... 5-1
5.1 Registration of POD ..........................................................................5-1
5.2 Registration of System Fall-Soft startup Operation ........................... 5-3
General
General
General
• This type of SX Bus I/F unit enables high-speed data transmission with MICREX-SX
Series PLCs.
• The POD updates the display when there is a change in the read data (POD PLC).
The read data is the content of the PLC addresses assigned to the display elements,
such as the current status of the lamps and counters, which are created on the
individual screen the POD displays.
When a POD switch or counter setting element is operated, the POD sends a write
command to the PLC and writes the output data in the PLC internal memory which
corresponds to the operation data.
These operations are automatically performed by POD, and therefore it is unnecessary
to create a communications program on the PLC side.
POD
Read command (example): Monitor all the data displayed on the screen
1-1
General
1-2
Specifications
Specifications 2
Applicable Models
2.1 Applicable Models
Applicable PLCs
The following PLC models are applicable:
Applicable PODs
Be sure to use the following type of communication unit according to the type of POD
you use.
* UG420H-Ex (EL display type) and UG320HD (handy type) cannnot be used.
2-1
Specifications
Item Specification
Transmission line Dedicated cable *1 Total length 25 m
Connectable sets Number of PODs connectable in same
configuration via SX bus: 8 sets *2
Transmission rate 25Mbps
PLC connecting range CPU in same configuration *3
*2 Though maximum 8 sets of POD can be connected in one configuration, the total
when including the following modules must be 16 sets or less.
• P-link module (NP1L-PL1)
• PC card interface module (NP1F-PC2)
• PE-link module (NP1L-PE1)
• Memory card interface module (NP1F-MM1)
• General-purpose communication module (NP1L-RS1/RS2/RS4)
2-2
Specifications
• Memory area is specified basically by variable name linkage. For more information
about variable name linkage, refer to “UG Series Manual <Variable Name
Cooperation>” (FEH363).
• ■ in the above table is SX station No. (1 to 238).
• in the above table is CPU No. (0 to 7).
• Figures for the memory range in the above table are when individual area is set to the
maximum. Actual range depends on “CPU memory size” defined on the PLC side.
• TYPE is used when memory is indirectly specified using macros from the POD
editor.
• When memory is indirectly specified using macros from the POD editor, be sure to
define CPU No. in the extension code.
• Input and output memories (%I, Q) cannot be indirectly specified using macros from
the POD editor.
2-3
Setting and Wiring of POD
3
3.1 Mounting the Interface Unit
• Remove the dust preventive seal from the I/F unit connector (UG30 Series : CN5,
UG20 Series : See the figure below) on the backside of the POD, mount the I/F unit
and fix it with 3 mounting screws.
UG530/UG430 UG330 UG520/UG420 UG320
CN6
CN6
LAN
(+)
DC 24V
L
(-)
CN5 100-
240VAC
N
MEMORY
NC MJ2 MJ1
CN5 MEMORY
CF
CN1
CF
24VDC
- + PRINTER
CN1
MJ1 MJ2
CN2
CN1
100-240VAC
LAN CN1 MJ1 MJ2 PRINTER
L N
MJ2 MJ1
UG221
CN2
+
24VDC
-
Connector for I/F unit
MJ1
CN2 CN1
• For UG30 and UG320/221 , insert the spacer (supplied with the unit) before mounting
the unit. Be sure to check the orientation of the spacer.
• Wire the communication cable. When the POD becomes a termination, be sure to use
a loop-back plug.
• Mount the ferrite core that is supplied with the unit on the communication cable to be
connected to the IN connector of the POD. The ferrite core should be mounted as
near to the POD as possible.
3-1
Setting and Wiring of POD
Available models
UGx30H-xx4
UG520H-xC4ZE UG520H-xC4MZE UG420H-xC4ZE
UG420H-xC4MZE UG320H-SC4ZE UG221H-xx *
* UG221 of the following and later hardware versions are supported.
UG221H-TC4 -> Version 1 UG221H-SC4 -> Version 2
UG221H-LC -> Version 1 UG221H-TC4D -> Version 4
UG221H-SC4D -> Version 6 UG221H-LC4D -> Version 5
The hardware version of the unit is indicated in the third digit from the extreme left of
the serial number shown on the backside of the unit.
Mounting procedure
When mounting UG03I-S on UG221 for CE specification, connect the FG terminal of
UG221 to the FG terminal of UG03I-S using the FG cable supplied with the unit.
FG cable
MJ2 MJ1
3-2
Setting and Wiring of POD
• After removing the dust preventive seal which is stuck on the rear of the POD, mount
the I/F unit at the position shown in the figure below and fix it with the 4 mounting
screws (M3 8) supplied with the unit.
I/F unit
Mounting screws*
(4 positions)
(+)
DC24V
(-)
CN2 CN1
MJ2 MJ1
POD
• Connect the insulated cable with the ground terminal on the POD.
• Wire the communication cable. When the POD becomes a termination, be sure to use
a loop-back plug.
3-3
Setting and Wiring of POD
• UG03I-S • UG02I-S
2 Station No. setting switch
F0 1 2 012
E EF
3456
BCD
3456
BCD
78 9A 78 9A
SW1 SW2
IN OUT
SW1 SW2
IN OUT
1 SX bus connector
• Be sure to connect the cable that comes from OUT connector to the IN connector
of the mating device.
Communication is impossible if this cable is connected between OUT connectors
or between IN connectors.
• For connection, be sure to use the dedicated SX bus extension cable.
(For more information about the SX bus extension cable, refer to “2-2
Communication Specifications”.)
2 Station number setting switch
• This switch is used to set local station number on the SX bus. SW1 sets the high-
order digit of station number while SW2, the low-order digit.
Turn the rotary switches with a screwdriver to set a station number in the range
from 00 to FF (hexadecimal).
The station number that is set on the POD side (with the above
setting switches) must be the same as the station number that is set
on the PLC side (using the [System_Definition] function of
D300win). Communication is not normally performed if different
station number is set.
For more information about the registration with D300win, refer to
“5.1 Registration of POD”.
Example:
When station number is set to 10 (h) (by setting SW1 to “1” and
SW2 to “0”) on the POD side, “SX bus station number (N)” that is
set by D300win on the PLC side must be “16”.
3-4
Setting and Wiring of POD
External Dimensions
167.4
150.5
SW1 SW2
SW1 SW2 IN OUT
IN OUT
13.6
14.9 37.8
98 25
. UG30 Series
.UG330H .UG430H .UG530H
87.1 93 93
72
66.1 72
21 21 21
165
215.2
245.2
6.6
8
8
3-5
Setting and Wiring of POD
. UG20 Series
UG520 UG420
312 288
92.3
95.8
16
16
11.5 114.5 8 110
141.5 126
245.2
240
215.2
270
334
310
UG320 UG221
220 173.6
25
25
66.1
53.3
6
85 85 6
130.8
138.8
175
165
230 182.5
UG220
173.6
28.5
I/F unit
50
5
138.8
130.8
182.5
3-6
Setting for Creating Screens
This section describes the items to be set for SX Bus communications when creating
screens with the editor (personal computer).
For more information about the way to set or use UG00S-CW , refer to user’s manual
[Function] (FEH376) .
4
To create screen data for SX bus interface, use UG00S-CW , or Ver.
Click [System Setting ], then click [PLC Type] . Select [FUJI ; MICREX-SX ] on the
[Select PLC Type] dialog.
4-1
Setting for Creating Screens
For setting of [Comm. Parameter...] under [System Setting], differences from other
communication methods are:
2 Connection
Needs not be set in this case. When 1:n connection (multiple sets of POD) is used,
definition is made on the PLC side (D300win) as well as at individual SX bus station
on the POD side.
For more information, refer to user’s manual [Function] (FEH376).
3 Parity, etc.
Need not be set.
4-2
Registration on PLC Side
This section describes how to set the PLC side program loader (D300win) in order to
register the POD system that performs communication via SX bus interface. For other
information about D300win, including operation method, refer to user’s manual
[D300win <Reference> ] (FEH251).
5
5.1 Registration of POD
Registration of POD
The procedure to register the system configuration in which one set of POD is
connected to SPH300 Series via SX bus interface is described below.
Power
supply
5-1
Registration on PLC Side
(2) The system definition window is opened. On this window, click [Base] and then
the [Insert] icon.
Note: In the following case, [Individual type module] cannot be selected in the [Module
attribute type] box:
→ [Individual type module] cannot be selected on the [Module Insert] dialog
unless the [Base] icon is clicked (selected) in above step (2).
5-2
Registration on PLC Side
POD is treated as a module with station number setting switch. Therefore, “System
Fail-Soft Startup Operation Definition” is useful.
(1) On the system definition window, click [System Property] and then the 5
[Property] button.
For more information about fail-soft startup operation mode, refer to user’s manual
<Instruction>, MICREX-SX Series SPH (FEH200).
5-3
Fuji Electric Co., Ltd.
ED & C.Drive Systems Company