0% found this document useful (0 votes)
527 views5 pages

FK-5-1-12 Modular Cylinder - 227SOL With 227AMD - Rv02

The document provides a detailed description of the 227SOL re-assembled electrical actuator head and the 227AMD actuator monitoring device, which are used to electro-mechanically actuate valves. It outlines installation instructions, technical specifications, safety precautions, and compliance with various electrical codes and standards. The actuator monitoring device is essential for system supervision and must be used whenever the system is under service, with specific installation guidelines provided to ensure safety and functionality.

Uploaded by

Roberto Vargas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
527 views5 pages

FK-5-1-12 Modular Cylinder - 227SOL With 227AMD - Rv02

The document provides a detailed description of the 227SOL re-assembled electrical actuator head and the 227AMD actuator monitoring device, which are used to electro-mechanically actuate valves. It outlines installation instructions, technical specifications, safety precautions, and compliance with various electrical codes and standards. The actuator monitoring device is essential for system supervision and must be used whenever the system is under service, with specific installation guidelines provided to ensure safety and functionality.

Uploaded by

Roberto Vargas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

DATA SHEET

RE-ASSEMBLED ELECTRICAL ACTUATOR HEAD 227SOL


WITH ACTUATING MONITORING DEVICE 227AMD
Description

The purpose of this actuator head is to actuate the valves of the cylinders on which it is fitted electro-
mechanically. It will activate when the coil is energised, which will cause the solenoid to operate and actuate the
valve. This actuator can be reseted (pointer goes back to the stand by position) by threading a reset screw in its
revolving nut.
The mechanism for fitting it to the cylinder valve using a swivel nut allows it to face the right direction.
All devices are to be installed in accordance with NFPA 70 “National Electrical Code” and with local electrical
code requirements. If installation conditions require special protection, please contact Siex to discuss availability
of suitably rated enclosures.

The use of an Actuator Monitoring Device in combined operation with the electrical actuator has a required
effective date of January 1, 2016, in order to meet the requirements of NFPA 2001.
The Actuator Monitoring Device is required to be used whenever the system is under service. The actuator head
is never intended to be removed, only in case to maintenance.
If the actuator head is removed, it must be placed back in its original condition when maintenance is completed.
The device 227AMD consists in a micro pointer, it allows to electrical activation or any type of actuator head in
the installation, the micro pointer is integrated in the revolving nut of the actuator head. It is used to detect at
every moment the status of the electrical actuator or any other actuator head (connected or disconnected). When
the electrical actuator is disconnected the micro switch sends an electrical signal to the control panel displaying
status information.
227AMD can be install in all cylinders of the system because the 227AMD can be mounted in any activation head
(pneumatic, manual, electrical…) or only in cylinder with electrical actuator, could be monitorize all cylinders of
the systems. The 227AMD for electric actuator on discharge valve control head meets the requirements of NFPA
2001, UL 2166, UL 2127 and FM5600.

Connection for
Actuator head
3/4”BSP

ATTENTION Position 1
Stand by

227SOL Position 2
Activation

227AMD
CAUTION
Never put over the actuation port electric-solenoid (Mod. 227 SOL
and 227 SOLLR) when valve core 2 is assembled in to the valve

Revolving nut
3/4” BSP

Resetting screw
3/4” BSP
Valve core 2 Valve core 1

227SOL WITH 227AMD 1/5


DATA SHEET

 227SOL Re-assembled electrical actuator head

The 227SOL electrical actuator head is connected to the upper actuation port of the RGS-MAM-20/40/50/80
valve and it can be to the side port of the container valve RGS-MAM-12-1C in valve core 1. The manual
actuator head 227DM / 227DMS, the cable-operated manual actuator head 227CMC, cable-operated
manual actuator head with protective box 227CMCC, pneumatic actuator head 227CN / 227CNTK,
pneumatic-manual actuator head 227CNM and the TK-SIMPLEX or TK-COMPLEX mechanical control unit
can all be fitted to the 227SOL actuator head.

227AMD

RGS-MAM-12-1C (CO2)

Valve core 2

ATTENTION
227SOL

With holes
Valve core 1

Connection for
actuator head
3/4” BSP 227SOL
Revolving nut
3/4” BSP

227SOL

227AMD
Valve core 1

RGS-MAM-20/40/50/80

227SOL WITH 227AMD 2/5


DATA SHEET

Technical Information

Re-assembled electrical actuator head 227SOL


Code 227SOL
Actuation type Launching
Re-assembled requirements Manual force (Resetting screw)
Connection to the cylinder valve
RGS-MAM-20/40/50/80 3/4” BSP Female
RGS-MAM-11/12 (actuation port)
Protection range IP65
Nominal voltage 24V (DC)
Nominal current 0.58 A
Nominal power at 68º F (20º C) 14 W
3-pin electrical plug
Electrical connection
(2 poles + earth)

Actuator Monitoring Device 227AMD


Normally Open Normally Close
(N.O.) (N.C.)
Box
Brass 227AMD 227AMDC
Aluminium* 227AMDA 227AMDAC
227SOL / 227SOLC / 227SOLCR
227CN / 227DM / 227DMR / 227CNM
Location TK-Simplex / TK-Simplex-B / TK-Simplex-C /
TK-complex / TK-complex-B / TK-complex-C
KCTM / KCTM-R / KCTM-C
Tension 24V (DC) 0.3A
Certifications UL / FM
*This is not part of the UL listed

Installation instruction:

The process to install the 227AMD in the valves is the same as the installation of the actuator with which it
is mounted; see installation manual of the relevant extinguishing agent.
It must be threaded by hand, it is not necessary to tighten with a tool.
Once the installation and manual tightening of the actuator on the valve is finished the top safety pin can be
removed, breaking the security seal, after that the device can be rotated to the desired position, It can be
installed in any position (see image 1), loose it with a block screw and turn around the valve, It is only
necessary to unscrew a few turns, no need to remove it whole, when placed it in the desired position,
tighten the screw again (see image 2). It is advisable to store the safety pin for disassembly when
necessary.

X X

227SOL WITH 227AMD 3/5


DATA SHEET

X X

Y Y

Image 1

Safety pin

Image 2 Block screw

Circuit diagram:

Re-assembled electrical actuator head 227SOL:

1(+) 2(-)

1 D1

+ Electromagnet
24 V (DC)
- D2
2(-) 1(+)
2

Inside the connector, two diodes are located. The one connected in parallel with the winding (D2) eliminates the tension
ends that take place when disconnecting, avoiding that the electronic components can be deteriorated. The diode in
series (D1) protects the electromagnet avoiding that is damaged by tensions of inverse polarity. The non-correct
polarization of the feeding, necessarily implies the non-operation of the apparatus, therefore it is essential to respect the
feeding polarizations.
Connections of the connector:

The terminal with mark 1 corresponds to the positive of the continuous feed.
The terminal with mark 2 corresponds to the negative of the continuous feed.

227SOL WITH 227AMD 4/5


DATA SHEET

Actuator Monitoring Device 227AMD:

To install the wiring of 227AMD, the next instructions must


be followed:

1. Connect the brown leads to the supervision zone on


the Fire Alarm Control Panel.
2. The blue leads can be connected to the next
227AMD or at the End Of Line Resistor (EOLR). It´s
necessary differentiate between the electrical
activation circuit and the 227AMD circuit; they are
different, because this last is only for supervision.
They don´t share the same circuit.

This circuit diagram may change according Siex 2001 criteria.

Safety:
Before threading the electrical actuator to the activation port of the valve, check that the actuator pointer is retracted
(position 1).
If the actuator pointer is in position 2, when threading the electrical actuator, the gas extinguisher contained in the
cylinder could discharge violently, causing serious injuries to the person handling it.
Do not install the electrical actuator without holding the cylinder to the wall with its brackets.

REVOLVING NUT:
Thread it to the valve activation port.
Do not add sealant, or Teflon, or glue.
Tighten only with the hand.

To remove the electrical actuator from the valve, loosen its revolving nut by hand.
When doing this operation the valve cap must not be turned, as this will cause the contents of the cylinder to be
discharged violently, which could cause serious injuries.
Do not remove the electrical actuator unless the cylinder is attached to the wall by its brackets.

227SOL, CE and π marking:


This section meets the 73/23/CEE Low Voltage European Directive regarding the electrical material destined to use it
with determinate voltage limits and 93/68/CEE modification. The sections indicated in this guide are incorporated in set,
making up a single machine.
The use of these devices is subject to the total conformity of the equipment, which must be authorized following the
98/37/CE machinery Directive, and / or in its case, to the electromagnetic compatibility Directive.

Attention:
- Electromagnets with permanent magnets are especially contraindicated for people with pacemaker.
- People with metallic prosthesis must be aware of maintaining a minimum safety distance from any element which
generates a magnetic field.
- Certain high sensitivity electrical appliances may be affected by the electromagnetic fields produce by the appliance.
- Following the EMV 89/336 Standard (electromagnetic conformity) must be ensured by the user.
- Avoid to be in contact with the appliance when it´s working (it´s warm).

WARNING: This type of electrical actuator head 227SOL, is manufactured and approved. These products are not designed for other use or purpose. If
product user has any doubt regarding the application or product use, please contact +34 947 28 11 08. Every not approved use or application or / and any
other not approved modification of the product or its function may cause serious accidents or / and personal damages. SIEX 2001 S.L. is not responsible
for any non-approved use of the application.

IMPORTANT: SIEX 2001 S.L. reserves the right to change or modify without previous notice any data or specification due to changes or modification in
order to improve the products presented.

227SOL WITH 227AMD 5/5