1. TECHNICAL FEATURES
1. General Features 2. Input: rectifier and battery charger
Power (kVA) 200 250 300 Power (kVA) 200 250 300
UPS Topology ON LINE – Double Conversion Input Three-phase/ 3 Ph+N
Nominal Apparent Output Power Nominal input voltage (Vac)
(kVA Cosφ 1.0) 200 250 300 400
Input voltage range (%) -20/+15
Nominal Active Output Power
(kW Cosφ 1.0) 200 250 300 Input frequency (Hz) 50 - 60
Efficiency (AC ÷ AC) (%) Input frequency range (%) ±10
@25% load Up to 94,8
@50% load Up to 95,8 Input power factor >0,99
@75% load Up to 95,8
@100% load Up to 95,3 Input current THD at nominal voltage
Efficiency (AC ÷ AC) (Eco Mode) >98%
and THDV <0,5% (%)
@25% load
Heat dissipation at rated load, VFI voltage <8
@50% load
(kW ) 9,4 11,8 14,1 <4
@75% load
<3
UPS Ambient Temperature (°C) @100% load
0 ÷ 40 < 2,5
BATTERY ambient temperature (°C) DC output voltage accuracy (%) ±1
0 ÷ +25
UPS storage temperature (°C) DC output voltage ripple (%) <1 (RMS)
-10 ÷ +70
Intermittent charging with prevailing state
BATTERY storage temperature (°C) Battery recharging characteristic of complete rest and control of the battery
-15 ÷ +40
Relative humidity % status IU (DIN 41773)
(not condensing) < 95% Maximum recharging current (A)
Altitude m <1000 (Above Sea level)
- at nominal load 30 40 40
- with DCM function (max current) 100 100 100
Power derating for altitude > 1000 m
According to “IEC62040-3”, 0,5% every 100m AC-DC converter type IGBT-based PFC
Ventilation Forced Input protection Fuses
Requested cooling air volume (m3/h) 1800 2200 2300
Nominal current absorbed from mains
Audible noise level
302 378 453
(at nominal load and battery charged) (A)
(according to IEC EN 62040-3) < 65dB
Maximum current absorbed from mains
Number of cells for standard Lead acid (at nom. load, min. mains voltage and 423 530 627
battery 360 ÷ 372 max. recharging current) (A)
Protection Degree IP20 Rectifier soft-start (walk-in) (sec) Settable from 5’’ to 30’’
Electromagnetic Compatibility EMI According to “IEC EN 62040-2” (CE marking) Rectifier sequential start-up (hold-off) Settable from 1’’ to 300’’
Safety IEC EN 62040-1
(sec)
4. Output Inverter
Power (kVA) 200 250 300
Inverter Bridge 3-Level IGBT (High Frequency PWM)
Nominal Apparent Output Power
200 250 300
(kVA Cosφ 1.0) 6. Block Diagram
Nominal Active Output Power
200 250 300
(kW Cosφ 1.0)
Efficiency (DC ÷ AC) (%)
@25% load Up to 96
@50% load Up to 97
@75% load Up to 97
@100% load Up to 98
Output 3 Phase / 4 Wires
Rated Output Voltage (selectable)
380-400-415
(Vac)
Output Voltage Stability
- Static (Balanced Load) (%) ±1
- Static (Unbalanced Load) (%) ±2
- Dynamic (Step Load 20%÷ 100% ±5
÷20%) (%)
- Output Volt. Recovery Time(after 1. Separate mains input for rectifier and bypass
step load) (ms) < 20
- IEC EN 62040-3 VFI-SS-111
2. Rectifier battery-charger
Phase Angle Accuracy (°)
3. Battery static switch
- Balanced Load ±1 4. External battery
- 100% Unbalanced Load ±1 5. Inverter
Output Frequency (selectable) (Hz) 50 / 60 6. Emergency line (bypass)
Output Frequency Stability 7. Maintenance bypass line
- Free Running Quartz Oscillator (Hz) ± 0,001
- Inverter Sync. with Mains (Hz) ± 2 (other on request)
8. Inverter (SSI) and bypass(SSB) static switch
- Slew rate (Hz/s) <1 9. Optional contact for external back-feed protection
Nominal Output Current (@ 400 Vac
output) (A) 289 361 433
OPTIONS
10 min >100%…110%
5 min> 110%...125%
Overload Capability 1. BATTERY TEMPERATURE VOLTAGE COMPENSATION
30 s >125%…150%
100 ms >150% 2. SERIAL INTERFACE RS-485 (ModBus protocol RTU)
Short Circuit Current 1st Level (A) 714 893 1071 3. SNMP ADPTER
Time of short circuit 1st Level (ms) 4. PARALLEL CARD INTERFACE KIT
70
5. LOAD-SYNC CARD INTERFACE KIT
Short Circuit Current 2nd Level (A) 439 546 655 6. ISOLATION TRANSFORMER
Time of short circuit 2nd Level (ms) 300 7. WALL MOUNTED FUSED SWITCH BOX
Current limited with electronic protection
Short Circuit Characteristic Automatic stop after 5 seconds