analog controller
analog controller
Modern implementation of controller action is provided by computers using software to perform the
required math operations. Prior to the widespread use of computers, analog electronic circuits and
pneumatic systems provided controller action. Some control system implementations still use analog
electronics for special purposes and there remains a vast array of equipment in continued use in the
process industry
General features
An analog controller is a device that implements the controller modes described previously, using
analog signals to represent the loop parameters. The analog signal may be in the form of an electric
current or a pneumatic air pressure. The controller accepts a measurement expressed in terms of
one of these signals, calculates an output for the mode being used, and outputs an analog signal of
the same type. Because the controller does solve equations, we think of it as an analog computer.
The controller must be able to add, subtract, multiply, integrate, and find derivatives. It does this by
working with analog voltages or pressures.
Analog controllers are usually designed to fit into a panel assembly as a slide in/out module, as
shown in Figure 1. The front displays all necessary information and provides adjustment capability
for the operator. When the unit is pulled out partway but still connected, other, less frequently
required adjustments are available. When the controller is pulled still further out, an extension cable
can be disconnected and the entire unit removed from the panel for replacement, if necessary.
Front Panel
The front panel of an analog controller displays information for operators and allows adjustment of
the setpoint. Figure 1 shows a typical front panel. The setpoint knob moves a sliding scale under the
fixed setpoint indicator. Thus, a fixed span of measurement above and below the setpoint is visible,
as indicated by the measurement-value indicator.
The error is the difference between the setpoint indicator and the measurement meter. The display
is typically expressed in percentage of span (4 to 20 mA or 3 to 15 psi). The lower meter shows the
controller output, again expressed in percentage of span. Of course, the output is actually 4 to 20
mA or 3 to 15 psi, so that 0% would mean 4 mA,
for example. There is often a switch on the front panel by which the controller can be placed in a
manual control, which means that the output can be adjusted independently of the input using the
output-adjust knob. In automatic mode, this knob has no effect on the output. Connections to the
controller are made through electrical or pneumatic cables connected to the rear of the unit.
On the side of the controller, when partially pulled out, knobs are available to adjust operation of
the controller modes. On this panel, as shown in Figure 1, the proportional, integral (reset), and
derivative (rate) gains can be adjusted. In addition, filtering action and reverse/direct operation can
often be selected.
Electronic controllers
In the following treatment of electronic methods of realizing controller modes, emphasis is on the
use of op amps as the primary circuit element. Discrete electronic components also are used to
implement this function, but the basic principles are best illustrated using op amp circuits. Op amp
circuits other than the ones described also can be developed
Error Detector
The detection of an error signal is accomplished in electronic controllers by taking the difference
between voltages. One voltage is generated by the process signal current passed through a resistor.
The second voltage represents the setpoint. This is usually generated by a voltage divider using a
constant voltage as a source.
Single Mode
The following systems and op amp circuits illustrate methods of implementing the pure modes of
controller action.
Two-Position
The inertia of the mercury tends to keep the system in that position until the temperature increases
to a value above the setpoint temperature. This provides the required neutral zone to prevent
excessive cycling of the system
A method using op amp implementation of ON/OFF control with adjustable neutral zone is given in
Figure 5. For this circuit, we assume that if the controller input voltage, V, reaches a value VH, then
the comparator output should go to the ON state, which is defined as some voltage, Vo. When the
input voltage falls below a value, the comparator output should switch to the OFF state, which is
defined as 0 V. The comparator output switches states when the voltage on its input, V1, is equal to
the setpoint value, Vsp. Analysis of this circuit shows that the high (ON) switch voltage is
Proportional Mode
Proportional Mode
If we consider both the controller output and error to be expressed in terms of voltage, we see that
Equation (14) is simply a summing amplifier. The op amp circuit in Figure 7 shows such an electronic
proportional controller. In this case, the analog electronic equation for the output voltage is
This must now be expressed in terms of the voltage gain, Gp , in Equation (3). The relationship
between GP and K is given by,
Integral Mode
Previously, we saw that the integral mode was characterized by an equation of the form
The values of R and C can be adjusted to obtain the desired integration time. The initial controller
output is the integrator output at t = 0. As we noted earlier, the integration time constant
determines the rate at which controller output increases when the error is constant. If is made too
large, the output rises so fast that overshoots of the optimum setting occur and cycling is produced.
The actual value of G1, and therefore of R and C, is determined from K1 and the input and output
voltage ranges. One way to do this is to recognize that the integral gain says that an input error of
1% must produce an output that changes as K1 percent per second. Another way is to know that if an
error of 1% lasts for 1 s, the output must change by percent.
Derivative Mode
The derivative mode is never used alone because it cannot provide a controller output when the error
is zero. Nevertheless, we show here how it is implemented with op amps so it can be combined with
other modes. The control mode equation was given earlier as
In principle, this mode could be implemented by the op amp circuit presented earlier. Indeed, the
theoretical transfer function for this circuit given in Equation (6) looks just like Equation (9.18) with
appropriate identifications in terms of circuit elements:
where the input voltage has been set equal to the controller error voltage.
From a practical perspective, this circuit cannot be used because it tends to be unstable; that is, it
may begin to exhibit spontaneous oscillations in the output voltage. The reason for this instability is
the very large gain at high frequencies where the derivative is very large
To study this effect, let us assume that the input voltage is given by a sinusoidal voltage oscillating
with some frequency, f; then .
This equation shows that the magnitude of the output voltage increases linearly with frequency. So,
in principle, as the frequency goes to infinity, so does the output! Clearly this is unacceptable in our
control system. A little high-frequency noise will cause large excursions in output voltage.
In order to make a practical circuit, a modification is provided that essentially “clamps” the gain
above some frequency to a constant value. We make sure that the clamped frequencies are well
above anything that could occur in the actual control system. This way, the circuit provides a
derivative output in the frequencies of practical interest but simply acts like a fixed-gain amplifier at
higher frequencies. Figure 9 shows that the simple modification is to place a resistor in series with
the capacitor.
The actual transfer function for this circuit can be shown to be given by
You can see that the output depends upon the derivative of the input voltage, but there is now an
extra term involving the derivative of the output voltage. Essentially, we have a first-order
differential equation relating input and output voltage
Proportional-Integral
A simple combination of the proportional and integral circuits provides the proportional-integral
mode of controller action. The resulting circuit is shown in Figure 10. For this case, the relation
between input and output is most easily found by applying op amp circuit analysis. We get (including
the inverter)
The adjustments of this controller are the proportional band through GP = R2/R1, and the integration
gain through G1 = 1/R2C
Proportional-Derivative
A powerful combination of controller modes is the proportional and derivative modes. This
combination is implemented using a circuit similar to that shown in Figure 11. Analysis shows that
this circuit responds according to the equation
where the quantities are defined in the figure and the output inverter has been included.
Then the condition becomes as usual, 2πfmaxRC = 0.1. Assuming this criterion has been met, the
equation for the proportional-derivative response becomes
PID (Three-Mode) The ultimate process controller is the one that exhibits proportional, integral, and
derivative response to the process-error input. This mode is characterized by the equation
The zero-error term of the proportional mode is not necessary because the integral automatically
accommodates for offset and nominal setting. This mode can be provided by a straight application of
op amp circuits, resulting in the circuit of Figure 12.
It must be noted, however, that it is possible to reduce the complexity of the circuitry of Figure 12
and still realize the three-mode action, but in these cases an interaction results between derivative
and integral gains.
We will use the circuit of Figure 12 because it is easy to follow in illustrating the principles of
implementing this mode. Analysis of the circuit shows that the output is
➢The outward appearance of a pneumatic controller is typically the same as that for the electronic
controller. The same readout of setpoint, error, and controller output appears, and adjustments of
gain, rate, and reset are available.
➢The working signal is most typically the 3- to 15-psi standard pneumatic process-ontrol signal,
usually derived from a regulated air supply of 20 to 30 psi.
➢The pneumatic controller is based on the nozzle/flapper described previously as the basic
mechanism of operation, much as the op amp is used in electronics.
Mode Implementation
Proportional
A proportional mode of operation can be achieved with the system shown in Figure 13. Operation is
understood by noting that if the input pressure increases, then the input bellows forces the flapper
to rotate to close off the nozzle. When this happens, the output pressure increases so that the
feedback bellows exerts a force to balance that of the input bellows. A balance condition then occurs
when torques exerted by each about the pivot are equal, or
Because the bellows are usually of fixed geometry, the gain is varied by changing the lever arm
length. In this simple representation, the gain is established by the distance between the bellows. If
this separation is changed, the forces are no longer balanced, and for the same pressure a new
controller output will be formed, corresponding to the new gain.
Proportional-Integral
This control mode is also implemented using pneumatics by the system shown in Figure 14. In this
case, an extra bellows with a variable restriction is added to the proportional system. Suppose the
input pressure shows a sudden increase. This drives the flapper toward the nozzle, increasing output
pressure until the proportional bellows balances the input as in the previous case.
The integral bellows is still at the original output pressure, because the restriction prevents pressure
changes from being transmitted immediately.
As the increased pressure on the output bleeds through the restriction, the integral bellows slowly
moves the flapper closer to the nozzle, thereby causing a steady increase in output pressure (as
dictated by the integral mode). The variable restriction allows for variation of the leakage rate, and
hence the integration time
This controller action can be accomplished pneumatically by the method shown in Figure 15. A
variable restriction is placed on the line leading to the balance bellows. Thus, as the input pressure
increases, the flapper is moved toward the nozzle with no impedance, because the restrictions
prevent an immediate response of the balance bellows. Thus, the output pressure rises very fast and
then, as the increased pressure leaks into the balance bellows, decreases as the balance bellows
moves the flapper back away from the nozzle. Adjustment of the variable restriction allows for
changing the derivative time constraint.
Three-Mode
The three-mode controller is actually the most common type produced, because it can be used to
accomplish any of the previous modes by setting of restrictions. This device is shown in Figure 16,
and, as can be seen, it is simply a combination of the three systems presented. By opening or closing
restrictions, the three-mode controller can be used to implement the other composite modes.
Proportional gain, reset time, and rate are set by adjustment of bellows separation and restriction
size
To illustrate some of the facets involved in setting up a process-control loop, it would be valuable to
follow through some hypothetical examples. The following examples assume that a process-control
loop is required, and that the controller operation must be provided by electronic analog circuits