The document outlines the design of shear reinforcement for a concrete slab to resist punching shear around an interior square column, following ACI 318 guidelines. It provides calculations for concrete shear strength, required area of reinforcement, and termination distances for shear reinforcement. The results indicate that shear reinforcement is required, with a specified area of 0.88 in² and a termination distance of 28.8 inches from the column face.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
32 views2 pages

Output

The document outlines the design of shear reinforcement for a concrete slab to resist punching shear around an interior square column, following ACI 318 guidelines. It provides calculations for concrete shear strength, required area of reinforcement, and termination distances for shear reinforcement. The results indicate that shear reinforcement is required, with a specified area of 0.88 in² and a termination distance of 28.8 inches from the column face.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Punching Shear Strength of Slab with Shear Reinf

ACI 318
Page: 1

Design Shear Reinforcement for Slab which to resist Punching Stress around Interior Square Column
As per ACI318-11 Chapter 11

2d

b1 a√2
d/2 c d/2

φVc/2

d/2
Critical Section for s
Punching Shear Action

a c

System
Column Dimension, c= 12.0 in
Thickness of Concrete Slab, h= 7.5 in
Concrete Cover, co= 1.5 in
Effective Depth of Concrete Section, d= h - co = 7.5 - 1.5 = 6.0 in
Bar Diameter of Shear Reinforcement, Dia= 0.375 in

Load
Ultimate Shear Force, Vu= 120.0 kips

Material Properties
Concrete Strength, f'c= 4000 psi

Yield Strength of Reinforcement, fy= 60000 psi

Shear Strength Reduction Factor (According to Cl.9.3.2 of ACI318), Φ= 0.75


Modification Factor for Lightweight Concrete, λ= 1.00

Determine Concrete Shear Strength


b1= c+d = 18.0 in

Perimeter of Critical Section, b0= 4 * b1 = 72.0 in


Nominal Shear Strength provided by Concrete (According to Eq. 11-33 of ACI318),
Vc= 4 * λ * √ f'c * b0 * d / 1000 = 109.3 kips

Punching Shear Reinforcement is : IF(Vu>Φ∗Vc;"Required";"Not Required") = Required

Determine Area of Shear Reinforcement


Minimum Effective Depth of Slab with Shear Reinforcement (According to Cl.11.11.3 of ACI318),
Punching Shear Strength of Slab with Shear Reinf
ACI 318
Page: 2

dmin= MIN(6;16*Dia ) = 6.0 in

Effective Depth of Slab : IF(d>dmin;"Should Increase";"OK") = OK


Maximum Shear Strength of Slab with Shear Reinforcement (According to Cl.11.11.3.2 of ACI318),
Vn= 6 * √ f'c * b0 * d / 1000 = 163.9 kips

Validity : IF(Vu>Φ*Vn;"Not Valid";"Valid") = Valid


Shear Strength provided by Concrete with Shear RFT (According to Cl.11.11.3.1 of ACI318),
Vci= 2 * λ * √ f'c * b0 * d / 1000 = 54.6 kips

Nominal Shear Strength provided by Reinforcement (According to Eq. 11-2 of ACI318),


V u - Φ * V ci
Vs= = 105.4 kips
Φ
Spacing of Provided Bars, s= 3.0 in
V s * s * 1000
Required Area of Reinforcement, Av= = 0.88 in2
fy * d

Required Area of Reinforcement for each side of Column, Av_side= Av / 4 = 0.22 in2

Perimeter of Critical Section where Shear Reinforcement may be terminated,


V u * 1000
b'0= = 210.8 in
Φ * 2 * λ * √ f'c * d
Distance from Column Face where Shear Reinforcement may be terminated,

a= ( )√
b'0
4
-c / 2 = 28.8 in

Design Summary

Required Area of Reinforcement, Av= Av = 0.88 in2


Distance from Column Face where Shear Reinforcement may be terminated: a = 28.8 in