UPS Memopower III 1 10kVA
UPS Memopower III 1 10kVA
1kVA~10kVA
02
MEMOPOW E R - Ⅲ Se r i e s
Features
High power density
03
Technical Specifications:
MODEL MP 1k H MP 1k S MP 2k H MP 2k S MP 3k H MP 3k S
Capacity 1000VA/ 900W 2000VA/ 1800W 3000VA/ 2700W
INPUT
Nominal voltage 208/220/230/240Vac
Input voltage range 110~300Vac (176~280Vac @ 100% load)
Frequency range 40~70Hz (50/60Hz Auto-Sensing)
Power factor ≥0.99
OUTPUT
Output voltage 208/220/230/240Vac
Power factor 0.9
Voltage regulation ±1%
EFFICENCY
AC mode 88% 90% 91%
Battery mode 85% 87% 88%
BATTERY
Battery number 2 3 2 3 4 6 4 6 6 8 6
Capacity (Standard unit) 9Ah/12V
Typical recharging time 4 hours (to 90% of full capacity)
Charging voltage 27.4Vdc±1% 41.1Vdc±1% 27.4Vdc±1% 41.1Vdc±1% 54.8Vdc±1% 82.2Vdc±1% 54.8Vdc±1% 82.2Vdc±1% 82.2Vdc±1% 109.6Vdc±1% 82.2Vdc±1%
Charging current (Max) 6A/12A 1A 6A/12A 1A 6A/12A 1A
INDICATORS
LED display Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault
ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continously beeping
PHYSICAL
Dimension W x D×H (mm) 144 x 293 x 209 144 x 399 x 209 191 x 460 x 337
Net weight (kg) 4.1 9.3 12.5 10 19.5 24.5 10 24.5
ENVIRONMENT
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20~95%RH @ 0~40℃ (Non condensing)
Altitude <1500m,derating required when>1500m
Noise level <50dB at 1 Meter
STANDARDS
Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
04
MP BT 1-3kVA battery pack specification
BATTERY SYSTEM
Battery tpye VRLA (Lead acid maintenance free battery)
Typical battery recharging time 6~8 hours (to 90% of full capacity)
Typical battery life 3~5 years,depend on discharing cycle and ambient temperature
System voltage 24Vdc 36Vdc 48Vdc 72Vdc 96Vdc
Charging current (Max) 1.4A
Battery quantity 4 6 8 12 16
ENVIRONMENT
Safety CE
Operating environment 0℃~40℃
Relative humidity 0~95% (Non condensing)
Noise level <40dB at 1 Meter
Specifications are subject to change without prior notice.
Remark: MP BT08048C "MP" means series; "BT" means Battery Tower cabinet; " 08" means battery number inside the cabinet;
" 048" means the battery system voltage; "C" means the cabinet coming with charger.
05
MEM OPOW E R R T - Ⅲ S e rie s
Features
Rack/Tower convertible design
Generator compatible
Cold start
06
Technical Specifications:
MODEL MP RT 1k H MP RT 1k S MP RT 2k H MP RT 2k S MP RT 3k H MP RT 3k S
Capacity 1000VA/ 900W 2000VA/ 1800W 3000VA/ 2700W
INPUT
Nominal voltage 208/220/230/240Vac
Input voltage range 110~300Vac (176~280Vac @ 100% load)
Frequency range 40~70Hz (50/60Hz Auto-Sensing)
Power factor ≥0.99
OUTPUT
Output voltage 208/220/230/240Vac
Power factor 0.9
Voltage regulation ±1%
EFFICENCY
AC mode 89% 91% 92%
Battery mode 85% 87% 88%
BATTERY
Battery number 2 3 2 3 4 6 4 6 6 8 6
Capacity (Standard unit) 9Ah/12V
Typical recharging time 4 hours (to 90% of full capacity)
Charging voltage 27.4Vdc±1% 41.1Vdc±1% 27.4Vdc±1% 41.1Vdc±1% 54.8Vdc±1% 82.2Vdc±1% 54.8Vdc±1% 82.2Vdc±1% 82.2Vdc±1% 109.6Vdc±1% 82.2Vdc±1%
Charging current (Max) 6A/12A 1A 6A/12A 1A 6A/12A 1A
INDICATORS
LED display Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault
ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continously beeping
PHYSICAL
Dimension W x D×H (mm) 440 x 325x 86.5 440 x 460 x 86.5 440 x 600 x 86.5 440 x 460 x 86.5 440 x 600 x 86.5
Net weight (kg) 5.6 11.3 14 10.5 19.5 25 11 26
ENVIRONMENT
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20~95%RH @ 0~40℃ (Non condensing)
Altitude <1500m,derating required when>1500m
Noise level <50dB at 1 Meter
STANDARDS
Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
07
MP BR 1-3kVA battery pack specification
BATTERY SYSTEM
Battery tpye VRLA (Lead acid maintenance free battery)
Typical battery recharging time 6~8 hours (to 90% of full capacity)
Typical battery life 3~5 years,depend on discharing cycle and ambient temperature
System voltage 24Vdc 36Vdc 48Vdc 72Vdc 96Vdc
Charging current (Max) 1.4A
Battery quantity 4 6 8 12 8
PHYSICAL
Dimension W x D x H (mm) 440 x 430 x 86.5 440 x 550 x 86.5 440 x 710 x 86.5 440 x 550 x 86.5
Net weight (kg) 17.4 22.5 31.5 44 31.5
ENVIRONMENT
Safety CE
Operating environment 0℃~40℃
Relative humidity 0~95% (Non condensing)
Noise level <40dB at 1 Meter
Specifications are subject to change without prior notice.
Remark: MP BR08048C "MP" means series; "BR" means Battery Rack; "08" means battery number inside the Rack;
"048" means the battery system voltage; "C" means the Rack coming with charger.
08
MEMOPOW E R - Ⅲ Se r i e s
Features
Online double conversion with full digital control
16/18/20pcs (Settable)
Cold start
09
Technical Specifications:
OUTPUT
Output voltage 208/220/230/240Vac
Power factor 0.9
Voltage regulation ±1%
ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continously beeping
PHYSICAL
Dimension W x D×H (mm) H:191 x 460 x 337;S:191 x 460 x 720 (With wheel)
Net weight (kg) 12 69.5 13.5 71
ENVIRONMENT
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20~95%RH @ 0~40℃ (Non condensing)
Altitude <1500m,derating required when>1500m
Noise level <55dB at 1 Meter <58dB at 1 Meter
STANDARDS
Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
Specifications are subject to change without prior notice.
When output voltage is 208Vac,need to derate to 80% of the unit capacity.
10
MP BT 6-10kVA battery pack specification
MODEL MP BT40240
BATTERY SYSTEM
Battery tpye VRLA (Lead acid maintenance free battery)
Typical battery recharging time 6~8 hours (to 90% of full capacity)
Typical battery life 3~5 years,depend on discharing cycle and ambient temperature
System voltage 240Vdc
ENVIRONMENT
Safety CE
Operating environment 0℃~40℃
Relative humidity 0~95% (Non condensing)
Noise level <40dB at 1 Meter
Specifications are subject to change without prior notice.
Remark: MP BT40240 "MP" means series; "BT" means Battery Tower cabinet; "40" means battery number inside the cabinet;
"240" means the battery system voltage.
11
MEMOPOW E R Pr o - Ⅲ S e rie s
Features
N+X parallel redundancy,support maximum 4 units in parallel
(Settable)
Generator compatible
Cold start
SNMP
Design with maintenance switch (Optional)
12
Technical Specifications:
Max.voltage:220V:+25% (Optional+10%,15%,20%)
Bypass voltage range 230V:+20% (Optional+10%,15%,20%)
240V:+15% (Optional+10%)
Min.voltage:-45% (Optional-20%,-30%)
OUTPUT
Output voltage 208/220/230/240Vac
Power factor 0.9
Voltage regulation ±1%
ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continously beeping
PHYSICAL
Dimension W x D×H (mm) H:191 x 460 x 337;S:191 x 460 x 720 (With wheel)
Net weight (kg) 12.5 70 14 71.5
ENVIRONMENT
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20~95%RH @ 0~40℃ (Non condensing)
Altitude <1500m,derating required when>1500m
Noise level <55dB at 1 Meter <58dB at 1 Meter
STANDARDS
Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
Specifications are subject to change without prior notice.
When output voltage is 208Vac,need to derate to 80% of the unit capacity.
13
MP BT 6-10kVA Pro battery pack specification
MODEL MP BT40120N
BATTERY SYSTEM
Battery tpye VRLA (Lead acid maintenance free battery)
Typical battery recharging time 6~8 hours (to 90% of full capacity)
Typical battery life 3~5 years,depend on discharing cycle and ambient temperature
System voltage ±120Vdc
PHYSICAL
Dimension W x D x H (mm) 250 x 597 x 616
Net weight (kg) 122/134
ENVIRONMENT
Safety CE
Operating environment 0℃~40℃
Relative humidity 0~95% (Non condensing)
Noise level <40dB at 1 Meter
Specifications are subject to change without prior notice.
Remark: MP BT40120N "MP" means series; "BT": means Battery Tower cabinet; "40" means battery number inside the cabinet;
"120" means the battery system voltage; "N" means battery with neutral connection.
14
MEMOPOW E R R T Pr o- Ⅲ S e rie s
Features
High power density
(Settable)
Generator compatible
15
Technical Specifications:
MODEL MP RT 6k MP RT 10k
Capacity 6000VA/ 5400W 10000VA/ 9000W
INPUT
Nominal voltage 208/220/230/240Vac
Input voltage range 110~286Vac
Frequency range 40~70Hz (50/60Hz Auto-Sensing)
Power factor ≥0.99
Max.voltage:220V:+25% (Optional+10%,15%,20%)
Bypass voltage range 230V:+20% (Optional+10%,15%,20%)
240V:+15% (Optional+10%)
Min.voltage:-45% (Optional-20%,-30%)
OUTPUT
Output voltage 208/220/230/240Vac
Power factor 0.9
Voltage regulation ±1%
ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continously beeping
PHYSICAL
Dimension W x D×H (mm) 440 x 625 x 86.5
Net weight (kg) 16 18
ENVIRONMENT
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20~95%RH @ 0~40℃ (Non condensing)
Altitude <1500m,derating required when>1500m
Noise level <55dB at 1 Meter <58dB at 1 Meter
STANDARDS
Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
Specifications are subject to change without prior notice.
When output voltage is 208Vac,need to derate to 80% of the unit capacity.
16
MP BR 6-10kVA battery pack specification
MODEL MP BR20120N
BATTERY SYSTEM
Battery tpye VRLA (Lead acid maintenance free battery)
Typical battery recharging time 6~8 hours (to 90% of full capacity)
Typical battery life 3~5 years,depend on discharing cycle and ambient temperature
System voltage ±120Vdc
PHYSICAL
Dimension W x D x H (mm) 440 x 680 x 131
Net weight (kg) 58/63
ENVIRONMENT
Safety CE
Operating environment 0℃~40℃
Relative humidity 0~95% (Non condensing)
Noise level <40dB at 1 Meter
Specifications are subject to change without prior notice.
Remark: MP BR20120N "MP" means series; "BR": means Battery Rack; "20" means battery number inside the Rack;
"120" means the battery system voltage; "N" means battery with neutral connection.
17
HEADQUARTERS
Add: 4/F, No.1 Bldg.Software Park, Keji C. Rd. 2nd, Hi-Tech Industrial Zone,
Shenzhen 518057, P.R.China
Kstar reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without
incurring any obligation to make such changes and modifications on kstar products previously or subsequently sold. Kstar does not
guarantee the items of the accuracy and completeness. Version number: KSD/C&C 2020-11