0% found this document useful (0 votes)
203 views19 pages

UPS Memopower III 1 10kVA

Shenzhen KSTAR Science & Technology Co., Ltd, founded in 1993, specializes in UPS systems and data center solutions, serving over 90 countries. The MEMOPOWER-Ⅲ Series offers a range of UPS models from 1kVA to 10kVA with features like online double conversion, wide input voltage range, and multiple communication interfaces. The series includes various models with different capacities and battery configurations, designed for high efficiency and reliability in critical infrastructure applications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
203 views19 pages

UPS Memopower III 1 10kVA

Shenzhen KSTAR Science & Technology Co., Ltd, founded in 1993, specializes in UPS systems and data center solutions, serving over 90 countries. The MEMOPOWER-Ⅲ Series offers a range of UPS models from 1kVA to 10kVA with features like online double conversion, wide input voltage range, and multiple communication interfaces. The series includes various models with different capacities and battery configurations, designed for high efficiency and reliability in critical infrastructure applications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 19

MEMOPOWER-Ⅲ Series

1kVA~10kVA

Stock code 002518


CO MPANY PR OFI L E

Founded in 1993, Shenzhen KSTAR

Science & Technology Co., Ltd (Stock

Code: 002518) is a National Torch Plan

Key High-tech Enterprise, and also a

pioneer of UPS industrial and a total

solution provider for Data Center Critical

Infrastructure & Photovoltaic Inverter

Systems in Mainland China. KSTAR is

fully committed to the R&D and has been

providing high-quality products with full

service to over 90 countries and regions

worldwide, leading the industrial

development with innovation.


MEMOPOWER-Ⅲ Series

1 MEMOPOWER-Ⅲ (1-3kVA, 0.9) 3

2 MEMOPOWER RT-Ⅲ (1-3kVA, 0.9) 6

3 MEMOPOWER-Ⅲ (6-10kVA, 0.9) 9

4 MEMOPOWER Pro-Ⅲ (6-10kVA, 0.9) 12

5 MEMOPOWER RT Pro-Ⅲ (6-10kVA, 0.9) 15

02
MEMOPOW E R - Ⅲ Se r i e s

1:1 Phase PF 0.9 (PF 0.8/1.0 optional) Power range:1kVA~3kVA

3 kinds of LCD can be selected

Colourful LCD Gray LCD Blue LCD

Battery cabinet Optimized battery configuration


(Optional) 7Ah/9Ah (12V)

Features
High power density

Online double conversion with full digital control

Wide input voltage range:110~300Vac

Input power factor 0.99 with PFC

Selectable output voltage: 208/220/230/240Vac SNMP

Smart charger design for optimized battery performance

Maximum charging current can be expanded to 12A (Long run unit)

Emergency power off function (EPO)


Dry contact
ECO mode operation for energy saving card
Generator compatible

Cold start Rear panel

Intelligent fan speed regulation

Load segment settable (Optional)

Versatile LCD human-computer interface

Multiple communication interface:RS232 (USB/EPO/Dry contact

/SNMP card optional) Optional socket

Multiple protection function:short-circuit,overload,overheat, battery

overcharge and overdischarge,output low voltage and fan fault alarm

03
Technical Specifications:

MODEL MP 1k H MP 1k S MP 2k H MP 2k S MP 3k H MP 3k S
Capacity 1000VA/ 900W 2000VA/ 1800W 3000VA/ 2700W
INPUT
Nominal voltage 208/220/230/240Vac
Input voltage range 110~300Vac (176~280Vac @ 100% load)
Frequency range 40~70Hz (50/60Hz Auto-Sensing)
Power factor ≥0.99

OUTPUT
Output voltage 208/220/230/240Vac
Power factor 0.9
Voltage regulation ±1%

Output Line Mode 46~54Hz or 56~64Hz


frequency Bat. Mode (50/60±0.1%)Hz
Crest factor 3:1
≤3% Linear load
Harmonic distortion (THDv)
≤5% Non linear load
AC mode to Bat.Mode 0ms
Transfer time
Inverter to Bypass 4ms (Typical)
Output waveform Pure Sinewave

EFFICENCY
AC mode 88% 90% 91%
Battery mode 85% 87% 88%
BATTERY
Battery number 2 3 2 3 4 6 4 6 6 8 6
Capacity (Standard unit) 9Ah/12V
Typical recharging time 4 hours (to 90% of full capacity)
Charging voltage 27.4Vdc±1% 41.1Vdc±1% 27.4Vdc±1% 41.1Vdc±1% 54.8Vdc±1% 82.2Vdc±1% 54.8Vdc±1% 82.2Vdc±1% 82.2Vdc±1% 109.6Vdc±1% 82.2Vdc±1%
Charging current (Max) 6A/12A 1A 6A/12A 1A 6A/12A 1A

INDICATORS
LED display Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault

LCD display Input voltage,Input frequency,Output voltage,Output frequency,Load percentage,


Battery voltage,Inner temperature& Remaining battery backup time

ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continously beeping

PHYSICAL
Dimension W x D×H (mm) 144 x 293 x 209 144 x 399 x 209 191 x 460 x 337
Net weight (kg) 4.1 9.3 12.5 10 19.5 24.5 10 24.5

ENVIRONMENT
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20~95%RH @ 0~40℃ (Non condensing)
Altitude <1500m,derating required when>1500m
Noise level <50dB at 1 Meter

STANDARDS
Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8

Specifications are subject to change without prior notice.


When output voltage is 208Vac,need to derate to 80% of the unit capacity.

04
MP BT 1-3kVA battery pack specification

MODEL MP BT04024C MP BT06036C MP BT08048C MP BT12072C MP BT16096C

BATTERY SYSTEM
Battery tpye VRLA (Lead acid maintenance free battery)
Typical battery recharging time 6~8 hours (to 90% of full capacity)
Typical battery life 3~5 years,depend on discharing cycle and ambient temperature
System voltage 24Vdc 36Vdc 48Vdc 72Vdc 96Vdc
Charging current (Max) 1.4A
Battery quantity 4 6 8 12 16

Capacity 9Ah/12V (7Ah/12V optional)


PHYSICAL
Dimension W x D x H (mm) 144 x 399 x 209 191 x 460 x 337
Net weight (kg) 13.5 18.5 28.5 38.5 47.5

ENVIRONMENT
Safety CE
Operating environment 0℃~40℃
Relative humidity 0~95% (Non condensing)
Noise level <40dB at 1 Meter
Specifications are subject to change without prior notice.
Remark: MP BT08048C "MP" means series; "BT" means Battery Tower cabinet; " 08" means battery number inside the cabinet;
" 048" means the battery system voltage; "C" means the cabinet coming with charger.

05
MEM OPOW E R R T - Ⅲ S e rie s

1:1 Phase PF 0.9 (PF 1.0 optional) Power range1kVA~3kVA

3 kinds of LCD can be selected

Colourful LCD Gray LCD Blue LCD

Battery cabinet Optimized battery configuration


(Optional) 7Ah/9Ah (12V)

Features
Rack/Tower convertible design

Online double conversion with full digital control

Wide input voltage range:110~300Vac

Input power factor 0.99 with PFC

Selectable output voltage: 208/220/230/240Vac

Smart charger design for optimized battery performance

Maximum charging current can be expanded to 12A (Long run unit)


Multifunctional The LCD panel can
Emergency power off function (EPO) bracket be rotated

ECO mode operation for energy saving

Generator compatible

Hot-Swappable battery design

Cold start

Intelligent fan speed regulation

Load segment settable (Optional)

Versatile LCD human-computer interface

Multiple communication interface:RS232 (USB/EPO/Dry contact

/SNMP card optional)

Multiple protection function:short-circuit,overload,overheat, battery


Dry contact SNMP
overcharge and overdischarge,output low voltage and fan fault alarm Optional socket card

06
Technical Specifications:

MODEL MP RT 1k H MP RT 1k S MP RT 2k H MP RT 2k S MP RT 3k H MP RT 3k S
Capacity 1000VA/ 900W 2000VA/ 1800W 3000VA/ 2700W
INPUT
Nominal voltage 208/220/230/240Vac
Input voltage range 110~300Vac (176~280Vac @ 100% load)
Frequency range 40~70Hz (50/60Hz Auto-Sensing)
Power factor ≥0.99

OUTPUT
Output voltage 208/220/230/240Vac
Power factor 0.9
Voltage regulation ±1%

Output Line Mode 46~54Hz or 56~64Hz


frequency Bat. Mode (50/60±0.1%)Hz
Crest factor 3:1
≤3% Linear load
Harmonic distortion (THDv)
≤5% Non linear load
AC mode to Bat.Mode 0ms
Transfer time
Inverter to Bypass 4ms (Typical)
Output waveform Pure Sinewave

EFFICENCY
AC mode 89% 91% 92%
Battery mode 85% 87% 88%
BATTERY
Battery number 2 3 2 3 4 6 4 6 6 8 6
Capacity (Standard unit) 9Ah/12V
Typical recharging time 4 hours (to 90% of full capacity)
Charging voltage 27.4Vdc±1% 41.1Vdc±1% 27.4Vdc±1% 41.1Vdc±1% 54.8Vdc±1% 82.2Vdc±1% 54.8Vdc±1% 82.2Vdc±1% 82.2Vdc±1% 109.6Vdc±1% 82.2Vdc±1%
Charging current (Max) 6A/12A 1A 6A/12A 1A 6A/12A 1A

INDICATORS
LED display Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault

LCD display Input voltage,Input frequency,Output voltage,Output frequency,Load percentage,


Battery voltage,Inner temperature& Remaining battery backup time

ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continously beeping

PHYSICAL
Dimension W x D×H (mm) 440 x 325x 86.5 440 x 460 x 86.5 440 x 600 x 86.5 440 x 460 x 86.5 440 x 600 x 86.5
Net weight (kg) 5.6 11.3 14 10.5 19.5 25 11 26

ENVIRONMENT
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20~95%RH @ 0~40℃ (Non condensing)
Altitude <1500m,derating required when>1500m
Noise level <50dB at 1 Meter

STANDARDS
Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8

Specifications are subject to change without prior notice.


When output voltage is 208Vac,need to derate to 80% of the unit capacity.

07
MP BR 1-3kVA battery pack specification

MODEL MP BR04024C MP BR06036C MP BR08048C MP BR12072C MP BR08096C

BATTERY SYSTEM
Battery tpye VRLA (Lead acid maintenance free battery)
Typical battery recharging time 6~8 hours (to 90% of full capacity)
Typical battery life 3~5 years,depend on discharing cycle and ambient temperature
System voltage 24Vdc 36Vdc 48Vdc 72Vdc 96Vdc
Charging current (Max) 1.4A
Battery quantity 4 6 8 12 8

Capacity 9Ah/12V (7Ah/12V optional)

PHYSICAL
Dimension W x D x H (mm) 440 x 430 x 86.5 440 x 550 x 86.5 440 x 710 x 86.5 440 x 550 x 86.5
Net weight (kg) 17.4 22.5 31.5 44 31.5

ENVIRONMENT
Safety CE
Operating environment 0℃~40℃
Relative humidity 0~95% (Non condensing)
Noise level <40dB at 1 Meter
Specifications are subject to change without prior notice.
Remark: MP BR08048C "MP" means series; "BR" means Battery Rack; "08" means battery number inside the Rack;
"048" means the battery system voltage; "C" means the Rack coming with charger.

08
MEMOPOW E R - Ⅲ Se r i e s

1:1 Phase PF 0.9 (PF 0.8 optional) Power range6kVA~10kVA

3 kinds of LCD can be selected

Colourful LCD Gray LCD Blue LCD

Battery cabinet Optimized battery configuration


(Optional) 7Ah/9Ah (12V)

Features
Online double conversion with full digital control

Optimization battery group, the quantity of battery:

16/18/20pcs (Settable)

Wide input voltage range:110~286Vac

Input power factor 0.99 with PFC

Wide input frequency range

Selectable output voltage: 208/220/230/240Vac


Relay card
Generator compatible

ECO mode operation for energy saving

Self-testing when UPS startup

Multiple communication interface:RS232/USB/EPO(Dry contact


SNMP
/SNMP card optional)

Cold start

Design with maintenance switch (Optional)

Intelligent fan speed regulation

Multiple protection function:short-circuit,overload,overheat, battery

overcharge and overdischarge,output low voltage and fan fault alarm

09
Technical Specifications:

MODEL MP 6k H MP 6k S MP 10k H MP 10k S


Capacity 6000VA/ 5400W 10000VA/ 9000W
INPUT
Nominal voltage 208/220/230/240Vac
Input voltage range 110~286Vac
Frequency range 40~70Hz (50/60Hz Auto-Sensing)
Power factor ≥0.99
Max.voltage:230~264Vac
Bypass voltage range
Min.voltage:176~220Vac

OUTPUT
Output voltage 208/220/230/240Vac
Power factor 0.9
Voltage regulation ±1%

Output Line Mode ±10% of the rated frequency


frequency Bat. Mode (50/60±0.1%)Hz
Crest factor 3:1
≤2% Linear load
Harmonic distortion (THDv)
≤5% Non linear load
AC mode to Bat.Mode 0ms
Transfer time
Inverter to Bypass 5ms (Typical)
Output waveform Pure Sinewave
Line Mode Load≤105% long time running; ≤125% last 10min; ≤130% last 30s; >130% turn to bypass mode immediately
Overload
Bypass Mode 40A (Breaker) 63A (Breaker)
Efficiency 93.5%
BATTERY
Battery voltage 192/216/240Vdc (Adjustable) ,without neutral
Capacity (Standard unit) 9Ah/12V (7Ah/12V optional)
Typical recharging time 6~8 hours (to 90% of full capacity)
Charging current 1A (Standard unit); Long run unit Max.current 8A (Charging current can be set according to battery capacity)
INDICATORS
LED display Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault
Input voltage,Input frequency,Output voltage,Output frequency,Load percentage,
LCD display
Battery voltage,Inner temperature& Remaining battery backup time

ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continously beeping

PHYSICAL
Dimension W x D×H (mm) H:191 x 460 x 337;S:191 x 460 x 720 (With wheel)
Net weight (kg) 12 69.5 13.5 71
ENVIRONMENT
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20~95%RH @ 0~40℃ (Non condensing)
Altitude <1500m,derating required when>1500m
Noise level <55dB at 1 Meter <58dB at 1 Meter

STANDARDS
Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
Specifications are subject to change without prior notice.
When output voltage is 208Vac,need to derate to 80% of the unit capacity.

10
MP BT 6-10kVA battery pack specification

MODEL MP BT40240

BATTERY SYSTEM
Battery tpye VRLA (Lead acid maintenance free battery)
Typical battery recharging time 6~8 hours (to 90% of full capacity)
Typical battery life 3~5 years,depend on discharing cycle and ambient temperature
System voltage 240Vdc

Battery quantity 2 * 20 PCS

Capacity 7Ah/9Ah (12V)


PHYSICAL
Dimension W x D x H (mm) 250 x 597 x 616
Net weight (kg) 122/134

ENVIRONMENT
Safety CE
Operating environment 0℃~40℃
Relative humidity 0~95% (Non condensing)
Noise level <40dB at 1 Meter
Specifications are subject to change without prior notice.
Remark: MP BT40240 "MP" means series; "BT" means Battery Tower cabinet; "40" means battery number inside the cabinet;
"240" means the battery system voltage.

11
MEMOPOW E R Pr o - Ⅲ S e rie s

1:1 Phase PF 0.9 (PF 1.0 optional) Power range6kVA~10kVA

3 kinds of LCD can be selected

Colourful LCD Gray LCD Blue LCD

Battery cabinet Optimized battery configuration


(Optional) 7Ah/9Ah (12V)

Features
N+X parallel redundancy,support maximum 4 units in parallel

Online double conversion with full digital control

Optimization battery group, the quantity of battery: ±8/±9/±10pcs

(Settable)

Wide input voltage range:110~286Vac Parallel board

Wide input frequency range

Selectable output voltage: 208/220/230/240Vac

Generator compatible

ECO mode operation for energy saving

Self-testing when UPS startup Relay card

Multiple communication interface:RS232/USB/EPO(Dry contact

/SNMP card optional)

Maximum charging current up to 10A

Cold start
SNMP
Design with maintenance switch (Optional)

Multiple protection function:short-circuit,overload,overheat, battery

overcharge and overdischarge,output low voltage and fan fault alarm

12
Technical Specifications:

MODEL MP Pro 6k H MP Pro 6k S MP Pro 10k H MP Pro 10k S


Capacity 6000VA/ 5400W 10000VA/ 9000W
INPUT
Nominal voltage 208/220/230/240Vac
Input voltage range 110~286Vac
Frequency range 40~70Hz (50/60Hz Auto-Sensing)
Power factor ≥0.99

Max.voltage:220V:+25% (Optional+10%,15%,20%)
Bypass voltage range 230V:+20% (Optional+10%,15%,20%)
240V:+15% (Optional+10%)
Min.voltage:-45% (Optional-20%,-30%)

OUTPUT
Output voltage 208/220/230/240Vac
Power factor 0.9
Voltage regulation ±1%

Output Line Mode ±1%/±2%±/±4%/±5%/±10% of the rated frequency (Optional)


frequency Bat. Mode (50/60±0.1%)Hz
Crest factor 3:1
≤2% Linear load
Harmonic distortion (THDv)
≤5% Non linear load
AC mode to Bat.Mode 0ms
Transfer time
Inverter to Bypass 0ms
Output waveform Pure Sinewave
Line Mode Load≤110% last 60min; ≤125% last 10min; ≤150% last 1min;>150% turn to bypass mode immediately
Overload
Bypass Mode 40A (Breaker) 63A (Breaker)
Efficiency 93.5%
BATTERY
Battery voltage ±96/±108/±120Vdc (Adjustable)
Capacity (Standard unit) 9Ah/12V (7Ah/12V optional)
Typical recharging time 6~8 hours (to 90% of full capacity)
Charging current 1A (Standard unit); Long run unit Max.current 10A (Charging current can be set according to battery capacity)
INDICATORS
LED display Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault
Input voltage,Input frequency,Output voltage,Output frequency,Load percentage,
LCD display
Battery voltage,Inner temperature& Remaining battery backup time

ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continously beeping

PHYSICAL
Dimension W x D×H (mm) H:191 x 460 x 337;S:191 x 460 x 720 (With wheel)
Net weight (kg) 12.5 70 14 71.5
ENVIRONMENT
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20~95%RH @ 0~40℃ (Non condensing)
Altitude <1500m,derating required when>1500m
Noise level <55dB at 1 Meter <58dB at 1 Meter

STANDARDS
Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
Specifications are subject to change without prior notice.
When output voltage is 208Vac,need to derate to 80% of the unit capacity.

13
MP BT 6-10kVA Pro battery pack specification

MODEL MP BT40120N

BATTERY SYSTEM
Battery tpye VRLA (Lead acid maintenance free battery)
Typical battery recharging time 6~8 hours (to 90% of full capacity)
Typical battery life 3~5 years,depend on discharing cycle and ambient temperature
System voltage ±120Vdc

Battery quantity 2 * ±10 PCS

Capacity 7Ah/9Ah (12V)

PHYSICAL
Dimension W x D x H (mm) 250 x 597 x 616
Net weight (kg) 122/134

ENVIRONMENT
Safety CE
Operating environment 0℃~40℃
Relative humidity 0~95% (Non condensing)
Noise level <40dB at 1 Meter
Specifications are subject to change without prior notice.
Remark: MP BT40120N "MP" means series; "BT": means Battery Tower cabinet; "40" means battery number inside the cabinet;
"120" means the battery system voltage; "N" means battery with neutral connection.

14
MEMOPOW E R R T Pr o- Ⅲ S e rie s

1:1 Phase PF 0.9 (PF 1.0 optional) Power range6kVA~10kVA

3 kinds of LCD can be selected

Colourful LCD Gray LCD Blue LCD

Battery cabinet Optimized battery configuration


(Optional) 7Ah/9Ah (12V)

Features
High power density

Rack/Tower convertible design

N+X parallel redundancy,support maximum 4 units in parallel


Parallel board Relay card
Online double conversion with full digital control

Optimization battery group, the quantity of battery: ±8/±9/±10pcs

(Settable)

Wide input voltage range:110~286Vac

Wide input frequency range

Generator compatible

ECO mode operation for energy saving


SNMP
Self-testing when UPS startup

Multiple communication interface:RS232/USB/EPO(Dry contact

/SNMP card optional)

Parallel kit default

Maximum charging current up to 10A

Cold start Multifunctional The LCD panel can


bracket be rotated
Intelligent fan speed regulation

Multiple protection function:short-circuit,overload,overheat, battery

15
Technical Specifications:

MODEL MP RT 6k MP RT 10k
Capacity 6000VA/ 5400W 10000VA/ 9000W
INPUT
Nominal voltage 208/220/230/240Vac
Input voltage range 110~286Vac
Frequency range 40~70Hz (50/60Hz Auto-Sensing)
Power factor ≥0.99

Max.voltage:220V:+25% (Optional+10%,15%,20%)
Bypass voltage range 230V:+20% (Optional+10%,15%,20%)
240V:+15% (Optional+10%)
Min.voltage:-45% (Optional-20%,-30%)

OUTPUT
Output voltage 208/220/230/240Vac
Power factor 0.9
Voltage regulation ±1%

Output Line Mode ±1%/±2%±/±4%/±5%/±10% of the rated frequency (Optional)


frequency Bat. Mode (50/60±0.1%)Hz
Crest factor 3:1
≤2% Linear load
Harmonic distortion (THDv)
≤5% Non linear load
AC mode to Bat.Mode 0ms
Transfer time
Inverter to Bypass 0ms
Output waveform Pure Sinewave
Line Mode Load≤110% last 60min; ≤125% last 10min; ≤150% last 1min; >150% turn to bypass mode immediately
Overload
Bypass Mode 40A (Breaker) 63A (Breaker)
Efficiency 94%
BATTERY
Battery voltage ±96/±108/±120Vdc (Adjustable)
Capacity (Standard unit) 9Ah/12V (7Ah/12V optional)
Typical recharging time 6~8 hours (to 90% of full capacity)
Charging current 1A (Standard unit); Long run unit Max.current 10A (Charging current can be set according to battery capacity)
INDICATORS
LED display Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault
Input voltage,Input frequency,Output voltage,Output frequency,Load percentage,
LCD display
Battery voltage,Inner temperature& Remaining battery backup time

ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continously beeping

PHYSICAL
Dimension W x D×H (mm) 440 x 625 x 86.5
Net weight (kg) 16 18
ENVIRONMENT
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20~95%RH @ 0~40℃ (Non condensing)
Altitude <1500m,derating required when>1500m
Noise level <55dB at 1 Meter <58dB at 1 Meter

STANDARDS
Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
Specifications are subject to change without prior notice.
When output voltage is 208Vac,need to derate to 80% of the unit capacity.

16
MP BR 6-10kVA battery pack specification

MODEL MP BR20120N

BATTERY SYSTEM
Battery tpye VRLA (Lead acid maintenance free battery)
Typical battery recharging time 6~8 hours (to 90% of full capacity)
Typical battery life 3~5 years,depend on discharing cycle and ambient temperature
System voltage ±120Vdc

Battery quantity 1* ±10 PCS

Capacity 7Ah/9Ah (12V)

PHYSICAL
Dimension W x D x H (mm) 440 x 680 x 131
Net weight (kg) 58/63

ENVIRONMENT
Safety CE
Operating environment 0℃~40℃
Relative humidity 0~95% (Non condensing)
Noise level <40dB at 1 Meter
Specifications are subject to change without prior notice.
Remark: MP BR20120N "MP" means series; "BR": means Battery Rack; "20" means battery number inside the Rack;
"120" means the battery system voltage; "N" means battery with neutral connection.

17
HEADQUARTERS
Add: 4/F, No.1 Bldg.Software Park, Keji C. Rd. 2nd, Hi-Tech Industrial Zone,
Shenzhen 518057, P.R.China

CONTACT FACTORIES ADDRESS


Tel: +86-755-86169858 Add: Kstar Industrial Park, Guangming Hi-Tech Industrial Zone, Shenzhen, P.R.China.
Fax: +86-755-86168482 Add: Kstar Industrial Park, Fumin Industrial Zone, Guanlan Town, Shenzhen, P.R.China.
Website:www.kstar.com E-mail: [email protected] Add: Kstar Industrial Park, Zhongkai Hi-Tech Industrial Zone, Huizhou, P.R. China.

Kstar reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without
incurring any obligation to make such changes and modifications on kstar products previously or subsequently sold. Kstar does not
guarantee the items of the accuracy and completeness. Version number: KSD/C&C 2020-11

You might also like