Al Sharafiyah 13.8kv Relay Settings
Al Sharafiyah 13.8kv Relay Settings
DAR ENGINEERING
Instrument Transformers:
CT ratio:
-Primary 800 Amp
-Secondary 1 Amp
PT ratio:
-Primary 13,800 Volts
-Secondary 120 Volts
TELEPROTECTION SCHEME:
TIMER SETTINGS:
T1 = 0.00 sec.
T2 = 0.50 sec.
T3 = 1.00 sec.
T4 = 1.50 sec.
I-DIFF>SWITCH ON:
I-DIFF>SWITCH ON 4 x Ic (Assumed)
Current Transformer :
k_alf/k_alf_nominal = 1.00
VT DATA:
AR SETTINGS:
Dead Time Main CB 0.5SEC
Dead time follower CB 1SEC
Reclaim Time 30SEC
No of shots 1
Synch Setting
DLLB YES
LLDB NO
DLDB NO
DIFF VOLTAGE 6.5V
ANGLE 20 DEGREE
FREQ 50mHz
UV 50% P-N
OV 120% P-N
Live voltage 80% P-N
Dead voltage 40% P-N
STAGE-2
Pick up value UNDER VOLTAGE ALARM = 70% of VT (Ph - N)voltage
48.497 V
Time delay for Alaram stage-2 = 3 sec
KV
V
V
Hz
Attachments:
Annexure-A: SLD
CE-1216342 5 OF 24
CE-1216342
0
INDEX
DESCRIPTION
CE-1216342 6 OF 24
PRIMARY POWER SUBSTATION NO.8382 FOR RIYADH SITE PACKAGE-2
1- Relay : 7SL87
2- Relay Setting Base:
Basis for relay setting:
The basis for relay settings is the relay '7SL87' relay manual.
3- CT & VT PARAMETERS:
CT Ratio =
Addopted Tap =
CT Class =
Burden =
4-
Differential Protection :
4.1-
Pickup value of differential current (I-DIFF>):
The current sensitivity is set with address 1210 I-DIFF>. It is determined by the entire current flowing into a protected zone in case of a fault. Thi
regardless of how it is distributed between the ends of the protected object.
Considering the variations of voltage and frequency, the set value should be at least 2 to 3 times higher than the calculated charging current. More
should not be less than 15% of the rated operational current. The rated operational current derive from the addresses 1104 FullScaleCurr.
If no voltages are measured, the compensated charging current is taken into account in address 1224 IcSTAB/IcN. This ratio is normally 2.5, so th
to 3 times, or IcSTAB/IcN · I-DIFF>, of the determined charging current.
Our recommendation is that differential current setting should be more than Differential Current contribution by Line Charging Current plus Diffe
contribution by phase shift. The charging current compensation in address 1221 is switched Ic-comp. = ON
CRITERIA 1:
I-DIFF> = Idiff1 ( charging current)
Idiff1 ( charging current) =
UGF line Charging Current per Km , Ic =
Idiff1 ( Primary side) =
Idiff1 ( Secondary side)
CRITERIA 2:
I-DIFF> =
CE-1214841 7 OF 24
PRIMARY POWER SUBSTATION NO.8382 FOR RIYADH SITE PACKAGE-2
Hence, our setting should be maximum of the two conditions towards secondary side therefore
I-DIFF>SWITCH ON =
I-DIFF>SWITCH ON =
I-DIFF>> =
4.4- Pickup value when switching on the charge comparison (I-DIF>> SWITCHON)
If bushing transformers are used for a transformer in the protected line section, stray fluxes through the bushing transformers may occur when rec
fault. These stray fluxes may cause a distortion of the secondary current and an over-function of the charge comparison.
If bushing transformers are used, the setting value of parameter 1235 I-DIF>>SWITCHON should be 2 to 3 times the setting value of I-DIFF>>. T
DIF>>SWITCHON corresponds to the default setting of parameter 1233 I-DIFF>>. In the default setting, this parameter is therefore ineffective.
I-DIF>> SWITCHON =
2nd HARMONIC =
CE-1214841 8 OF 24
PRIMARY POWER SUBSTATION NO.8382 FOR RIYADH SITE PACKAGE-2
n Realy
1250-800-400 / 1A
800 / 1A
5P20
90-60-30 VA
25000 A
13800 V
120 V
7967.43371481684 V
69.2820323027551 V
6.96
40
into a protected zone in case of a fault. This is the total fault current
2 x Ic x L
18.408 Ampere/km
92.04 Ampere
0.11505 Ampere
CE-1214841 9 OF 24
PRIMARY POWER SUBSTATION NO.8382 FOR RIYADH SITE PACKAGE-2
0.15
0.15
4 x Ic
0.46
infinity
infinity
15.00%
CE-1214841 10 OF 24
II 13.8KV Metered Feeder OC & EF Protection Relay
1- Transformer LV OC
Relay Information : REF620
1.1-
No. of Taps = 5
Nominal Tap No. = 3
% Impedance ,Z HV-LV
Positive Sequence Impedance, Nom. Tap 8.50%
For setting of phase O/C relay we propose a value of 120% of rated current of transformer for phase faults.
a). The Phase Fault Current Setting:
ISP = 120% * Ip (Relay setting current related to primary side of CT)
ISP = 120% *104.59
ISP = 125.51A
ISS = ISP/n (Relay setting current related to secondary side of CT)
ISS = 125.51/800
ISS = 0.16A
b). The Phase Fault Time dial Setting:
TD = 0.5
Curve = ANSI Moderately Invers
c). The Phase Fault Current Setting Second Stage:
ISP = 300% * CT (Relay setting current related to primary side of CT)
ISP = 300% *800
ISP = 1056A
ISS = ISP/n (Relay setting current related to secondary side of CT)
ISS = 1056/800
ISS = 1.32A
Curve = DT
Time = 40ms
CLASSIFICATION: INTERNAL
#
II 13.8KV Metered Feeder OC & EF Protection Relay
T1 = 0.15 s
Where,
T1 = Time for trip of all associated CBs with faulty CB
CLASSIFICATION: INTERNAL
#
III 13.8KV 87BB (7SJ85) Protection Final Setting
CT Secondary 1 Amp
CT Class PX
CT Resistance 18 Ohms
2 Lead Burden
Below is the formula for calculating the total resistance of lead wires
RL = R20 · L · [1 + ά · (T – 20)], wherein
3 Relay Burden
# CLASSIFICATION: INTERNAL
III 13.8KV 87BB (7SJ85) Protection Final Setting
Applying 20% margin to the calculated setting based on SEC design based requirements
Proposed CT is suitable since the required Kneepoint voltage less than the rated value.
As per PTS the relay operating current should not be more than 100mA such that the voltage can be set in the range of 50-300V.
As per PTS the relay operating current should not be more than 100mA such that the voltage can be set in the range of 50-300V.
Pcontseries = Is2 x Rs 17 W
CT Magnetising Current
= (30 x 170) / 800x 1000 0.0064 A
Imag at US= (Imag at Vk X VKP)/Vk
Total CT Magnetising Current(for 15 nos. CT's)
= (15 x 0.0064) 0.0960 A
T.Imag = 15 X Imag at US
As per metrosil sizing, metrosil is not required.
Min Primary Operating Current Iop= N X (Ir + Ires + T.Imag+Isup) = (3600/1) x (0.1 + 0 + 0.096 + 0.0002) 706.5 A
The primary fault sensitivity is 19.62% of the CT rating at setting voltage, i.e., in between 10-20% of the CT rated current, therefore, the calculated setting is acceptable.
# CLASSIFICATION: INTERNAL
III 13.8KV 87BB (7SJ85) Protection Final Setting
Ish=(Iopr-Iop)/Ipn
Where
Iopr= Required Primary Fault sensitivity/Operating Current. =(4000-706.5)/3600 1.0978 A
Iop= Min.Primary fault sensitivity/operating Current
Ipn= CT ratio
The rms voltage developed across a resistor for maximum internal fault conditions is define as
Phalf= Vf ÷ Rs
2 =1111^2÷150 8228.01 W
The Settings.
# CLASSIFICATION: INTERNAL
PRIMARY POWER SUBSTATION NO.8382 FOR RIYADH SITE PACKAGE-2
IV 13.8KV RMU
1 CT & VT DATA
CT Primary ( Amp)
Adopted Tap ( Amp)
CT Secondary
2 PHASE & EARTH FAULT IDMT OVER CURRENT SETTING
2.1 The Phase Fault Current Setting:
The recommended Phase fault current setting = 90% of CT Rated primary Current
=0.9*400
(Isp)
Setting Current (Secondary side) =360*(1/400)
2.2 The Phase Fault TMS Setting::
For calculation of time multiplier 'TMS' following are the basis:
TMS' shall be selected based CB interupting capacity.
CB interupting capacity Ik
With 'Normal Inverse'characteristics time for relay operation:
t=0.14/(I0.02-1)
where I= Ik/Isp =25000/360
CE-1214841 16 OF 24
PRIMARY POWER SUBSTATION NO.8382 FOR RIYADH SITE PACKAGE-2
200/400 A
400 A
1A
360 Amps
0.9 Amps
25000 Amps
69.44 Amps
20
2.27 Seconds
0.11
80 Amps
0.2 Amps
25000 Amps
312.5 Amps
20
2.27 Seconds
0.11
CE-1214841 17 OF 24
V SST LV Side 64N (7SJ80) Final Setting
System details:
Transformer detail:
CT details:
Connected Burden
The effective wire burden will be calculated for a two wire connection of CT and relay according to length,
cross-section, copper resistivity and secondary nominal current:
RL = R20 . L. [1 + α(T-20)]
where
RL = Lead wire resistance
R20 = CT lead resistance per unit length
L = total length of the CT lead wires
α = Temperature coefficient of Resistance of copper conductor at inferred absolute
zero of temperature ( α = 1/234.5)
T = Final temperature of the wire (T=75 oC)
Thus
Area of Cross Section, A = 6 mm2
CT lead resistance per unit length = 0.00308 Ω/m (as per Table 2.0 in TES-P-119.28)
Temperature Coefficient of Copper, α = 0.00426439232409
The CT Accuracy Limiting Voltage (Ual) shall meet the following requirements.
Transformer % imp at 1.5 MVA = Tr. % Imp. at given base MVA x New Base MVA
Given base MVA
CLASSIFICATION: INTERNAL
#
= 222.34 V
Since the available Vk(500V) is higher than required Ual (267V), the CT is Suitably sized.
Rs = 1200 Ohms
The primary fault sensitivity is only 10% of the CT rating and the CT magnetising current has less effect on the primary fault sensitivity.
Vf = 9.62252*(10+1.50304+1200+0.05)
= 11658.2
Vp = 2 x(SQRT(2)(2 x 500*(11658.2-500))
= 6680.78
Since the calculation Vp is more than 2kV, so below metrosil type is proposed.
The Settings.
CLASSIFICATION: INTERNAL
#
PRIMARY POWER SUBSTATION NO.8382 FOR RIYADH SITE PACKAGE-2
VI 13.8KV UF SETTING
SETTINGS:
STAGE-1
Frequency Pick up value of stage-1 (f1) = 59.5 Hz
Delay time for stage-1 (Tf1) = 0.5 SEC
STAGE-2
Frequency Pick up value of stage-2 (f2) = 59.3 Hz
Delay time for stage-2 (Tf2) = 1 SEC
STAGE-3
Frequency Pick up value of stage-3 (f3) = 59.1 Hz
Delay time for stage-3 (Tf3) = 1.5 SEC
STAGE-4
Frequency Pick up value of stage-4 (f4) = 59.0 Hz
Delay time for stage-4 (Tf4) = 2 SEC
NOTE:
1. STAGE-1&2 WILL TRIP ALL OUTGOING FEEDERS IN 13.8kV SWGR
2. STAGE-3&4 WILL TRIP ALL INCOMER & BUS SECTION FEEDERS IN 13.8kV SWGR
CE-1214841 20 OF 24
PRIMARY POWER SUBSTATION NO.8382 FOR RIYADH SITE PACKAGE-2
VII 13.8KV UV SETTING
Panel 1
13.8kV UNDER VOLTAGE RELAY Panel 2
Settings:
STAGE:1
Pick up value UNDER VOLTAGE Trip = 80% of VT (Ph - N)voltage
55.426 V
Time delay for Trip stage = 5 sec
STAGE:2
Pick up value UNDER VOLTAGE Trip = 75% of VT (Ph - N)voltage
51.962 V
Time delay for Trip stage = 5 sec
STAGE:3
Pick up value UNDER VOLTAGE Trip = 70% of VT (Ph - N)voltage
48.497 V
Time delay for Trip stage = 5 sec
CE-1214841 21 OF 24
VIII 13.8KV BS RELAY SETTINGS
CT Secondary 1 Amp
CT Class PX
CT Resistance 18 Ohms
2 Lead Burden
Below is the formula for calculating the total resistance of lead wires
RL = R20 · L · [1 + ά · (T – 20)], wherein
3 Relay Burden
# CLASSIFICATION: INTERNAL
VIII 13.8KV BS RELAY SETTINGS
Applying 20% margin to the calculated setting based on SEC design based requirements
Proposed CT is suitable since the required Kneepoint voltage less than the rated value.
As per PTS the relay operating current should not be more than 100mA such that the voltage can be set in the range of 50-300V.
As per PTS the relay operating current should not be more than 100mA such that the voltage can be set in the range of 50-300V.
Pcontseries = Is2 x Rs 17 W
CT Magnetising Current
= (30 x 170) / 800x 1000 0.0064 A
Imag at US= (Imag at Vk X VKP)/Vk
Total CT Magnetising Current(for 15 nos. CT's)
= (15 x 0.0064) 0.0960 A
T.Imag = 15 X Imag at US
As per metrosil sizing, metrosil is not required.
Min Primary Operating Current Iop= N X (Ir + Ires + T.Imag+Isup) = (3600/1) x (0.1 + 0 + 0.096 + 0.0002) 706.5 A
The primary fault sensitivity is 19.62% of the CT rating at setting voltage, i.e., in between 10-20% of the CT rated current, therefore, the calculated setting is acceptable.
# CLASSIFICATION: INTERNAL
VIII 13.8KV BS RELAY SETTINGS
Ish=(Iopr-Iop)/Ipn
Where
Iopr= Required Primary Fault sensitivity/Operating Current. =(4000-706.5)/3600 1.0978 A
Iop= Min.Primary fault sensitivity/operating Current
Ipn= CT ratio
The rms voltage developed across a resistor for maximum internal fault conditions is define as
Phalf= Vf ÷ Rs
2 =1111^2÷150 8228.01 W
The Settings.
# CLASSIFICATION: INTERNAL