0% found this document useful (0 votes)
77 views12 pages

Datasheet DRL 24V75W1AZ

The LYTE DIN Rail Power Supply DRL-75W series offers a universal AC input voltage range, high efficiency up to 90%, and operates in temperatures from -10°C to +50°C. It features built-in overcurrent protection, compliance with various safety standards, and is suitable for inductive and capacitive loads. The series includes multiple models with different output voltages and is designed for reliable performance in industrial applications.

Uploaded by

zakariaafoun
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
77 views12 pages

Datasheet DRL 24V75W1AZ

The LYTE DIN Rail Power Supply DRL-75W series offers a universal AC input voltage range, high efficiency up to 90%, and operates in temperatures from -10°C to +50°C. It features built-in overcurrent protection, compliance with various safety standards, and is suitable for inductive and capacitive loads. The series includes multiple models with different output voltages and is designed for reliable performance in industrial applications.

Uploaded by

zakariaafoun
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

TECHNICAL DATASHEET

LYTE DIN Rail Power Supply


DRL-75W series / DRL-V75W1AZ

Highlights & Features


• Universal AC input voltage range
• Built-in constant current circuit for reactive loads
• Up to 90% efficiency
• Full power from -10°C to +50°C @ 230 Vac with -30°C Cold Start
• Compliance to SEMI F47 @ 200 Vac
• Limited Power Source (LPS) certified (DRL-24V75W1AZ &
DRL-48V75W1AZ)

Safety Standards

CB Certified for worldwide use

Model Number: DRL-V75W1AZ


Unit Weight: 0.22 kg (0.49 lb)
Dimensions (H x W x D): 123.6 x 27 x 102 mm
(4.87 x 1.06 x 4.02 inch)

General Description
Delta’s LYTE DIN rail power supply series is designed for price sensitive users who require basic yet reliable power output for general
industrial applications. The convection-cooled LYTE series operates between 20°C to +70°C, providing 100% output power from -10°C
to +50°C at 230 Vac. The overcurrent protection is designed to operate in constant current mode, which makes the LYTE series suitable
for inductive and capacitive load applications. The product is certified according to safety standards IEC 60950-1 & IEC/EN/UL 62368-1.
Electromagnetic radiated and conducted emissions are certified according to EN 55032, Class B; and, the product is RoHS compliant for
environmental protection.

Model Information
LYTE DIN Rail Power Supply

Model Number Input Voltage Range Rated Output Voltage Rated Output Current
DRL-12V75W1AZ 12 Vdc 6.25 A
DRL-24V75W1AZ 85-264 Vac (120-375 Vdc) 24 Vdc 3.125 A
DRL-48V75W1AZ 48 Vdc 1.57 A

Model Numbering
DR L– V 75W 1 A Z 
DIN Rail Product Type Output Voltage Output Single Phase LYTE Series Z – Plastic case Blank – No coating
L – LYTE Family 12 – 12 V Power with Standard without DC OK R – With coating
24 – 24 V Bracket relay contact
48 – 48 V

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
1 www.DeltaPSU.com (December 2023, Rev. 09)
TECHNICAL DATASHEET

LYTE DIN Rail Power Supply


DRL-75W series / DRL-V75W1AZ

Specifications

Model Number DRL-12V75W1AZ☐ DRL-24V75W1AZ☐ DRL-48V75W1AZ☐

Input Ratings / Characteristics

Nominal Input Voltage 100-240 Vac


Input Voltage Range 85-264 Vac
Nominal Input Frequency 50-60 Hz
Input Frequency Range 47-63 Hz
DC input Voltage Range*1 120-375 Vdc
Input Current 1.4 A typ. @ 115 Vac, 0.9 A typ. @ 230 Vac
Efficiency at 100% Load 87.5% typ. @ 230 Vac 89% typ. @ 230 Vac 90% typ. @ 230 Vac
Max Inrush Current (Cold Start) 50 A typ. @ 230 Vac
Leakage Current < 1 mA @ 240 Vac
*1 Power supply can operate at DC input voltage, please connect +pole to L, -pole to N and PE terminal to an earth wire or to the machine ground.

Output Ratings / Characteristics*2

Nominal Output Voltage 12 Vdc 24 Vdc 48 Vdc


Factory Set Point Tolerance 12 Vdc ± 2% 24 Vdc ± 2% 48 Vdc ± 1%
Output Voltage Adjustment Range 10.8-13.2 Vdc 21.6-26 Vdc 43.2-52.8 Vdc

Output Current 6.2 5A 3.125 A 1.57 A


Output Power 75 W 75 W 75.36 W
Line Regulation < 0.5% (@ 85-264 Vac, 100% load)
Load Regulation < 1% (0-100% load)
PARD*3 (20 MHz) < 120 mVpp @ > -10°C to +70°C < 120 mVpp @ > -10°C to +70°C < 240 mVpp @ > -10°C to +70°C
< 360 mVpp @ ≤ -10°C to -30°C < 360 mVpp @ ≤ -10°C to -30°C < 480 mVpp @ ≤ -10°C to -30°C
Rise Time 30 ms typ. @ nominal input (100% load)
Start-up Time 1200 ms typ. @ 115 Vac (100% load)
1000 ms typ. @ 230 Vac (100% load)
Hold-up Time 16 ms typ. @ 115 Vac (100% load)
60 ms typ. @ 230 Vac (100% load)
Dynamic Response ± 10% @ 115 Vac & 230 Vac input, 0-50%, 50-100% load
(Overshoot & Undershoot O/P Voltage)
(Slew Rate: 2.5 A/μS, 50% duty cycle @ 100 Hz & 1 kHz)
Start-up with Capacitive Loads 5,000 µF Max 5,000 µF Max 4,000 µF Max
*2 For power de-rating from -10°C to -20°C, and 40°C to 70°C @ 115 Vac & 50°C to 70°C @ 230 Vac, and Vin < 100 Vac, see power de-rating on page 3.
*3 PARD is measured with an AC coupling mode, 5cm wires, and in parallel to end terminal with 0.1 μF ceramic capacitor & 47 μF electrolytic capacitor. PSU need to burn in
around 5 minutes when AMB ≤ 0°C

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
2 www.DeltaPSU.com (December 2023, Rev. 09)
TECHNICAL DATASHEET

LYTE DIN Rail Power Supply


DRL-75W series / DRL-V75W1AZ

Model Number DRL-12V75W1AZ☐ DRL-24V75W1AZ☐ DRL-48V75W1AZ☐

Mechanical

Case Cover / Chassis Plastic


Dimensions (H x W x D) 123.6 x 27 x 102 mm (4.87 x 1.06 x 4.02 inch)
Unit Weight 0.22 kg (0.49 lb)
Indicator Green LED (DC OK)
Cooling System Convection
Terminal Input 3 Pins (Rated 300 V / 16 A)
Output 4 Pins (Rated 300 V / 16 A)
Wire Input AWG 18-12
Output AWG 22-12
Mounting Rail Standard TS35 DIN Rail in accordance with EN 60715
Noise (1 Meter from power supply) Sound Pressure Level (SPL) < 25 dBA

Environment

Surrounding Air Operating -20°C to +70°C (-30°C Cold Start)


Temperature Storage -40°C to +85°C
Power De-rating Temperature -10°C to -20°C de-rate power by 1% / °C
> 40°C de-rate power by 1.67% / °C @ 115 Vac
> 50°C de-rate power by 2.5% / °C @ 230 Vac
Input
< 100 Vac de-rate power by 1.33% / Vac
Voltage
Operating Humidity 5 to 95% RH (Non-Condensing)
Operating Altitude 0 to 5,000 Meters (16,400 ft.)
Shock Test Non- IEC 60068-2-27, Half Sine Wave: 50 G for duration of 11 ms; 3 times per direction,
Operating 9 times in total
Operating IEC 60068-2-27, Half Sine Wave: 10 G for duration of 11 ms; 1 time in X axis
Vibration Non- IEC 60068-2-6, Random: 5 Hz to 500 Hz; 2.09 Grms;
Operating 20 min per axis for all X, Y, Z directions
Operating IEC 60068-2-6, Sine Wave: 10 Hz to 500 Hz @ 19.6 m/s² (2 G peak);
displacement of 0.3 5mm; 10 min per cycle, 60 min for X direction
Over Voltage Category II
Pollution Degree 2

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
3 www.DeltaPSU.com (December 2023, Rev. 09)
TECHNICAL DATASHEET

LYTE DIN Rail Power Supply


DRL-75W series / DRL-V75W1AZ

Model Number DRL-12V75W1AZ☐ DRL-24V75W1AZ☐ DRL-48V75W1AZ☐

Protections

Overvoltage < 18 V, SELV Output, < 33.6 V, SELV Output, < 62.4 V, SELV Output,
Latch Mode Latch Mode Latch Mode
Overload / Overcurrent 105 - 133% of rated load 105 - 133% of rated load 105 - 133% of rated load
current, Constant current current, Constant current current, Constant current
limit, Auto-recovery limit, Auto-recovery limit, Auto-recovery
Over Temperature Latch Mode
Short Circuit Hiccup Mode, Non-Latching
(Auto-Recovery when the fault is removed)
Internal Fuse at L pin F5AH
Degree of Protection IP20
Protection Against Shock Class I with PE*4 connection
*4 PE: Primary Earth

Reliability Data

MTBF Telcordia > 700,000 hrs I/P: 100 Vac, O/P: 100% load, Ta: 25°C
SR-332
Expected Cap Life Time 10 years (115 Vac & 230 Vac, 50% load @ 40°C)

Safety Standards / Directives

Electrical Safety CB scheme IEC 62368-1, IEC 60950-1, IEC 61010-1


TUV Bauart EN 62368-1
UL/cUL UL 62368-1, UL 61010-1/-2-201
BSMI CNS14336-1
EAC TP TC 004/2011
KC K 60950-1
Limited Power Source CB scheme IEC 62368-1 (For DRL-24V75W1AZ & DRL-48V75W1AZ)
(LPS)
CE In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
UKCA In conformance with Electrical Equipment (Safety) Regulations 2016 and Electromagnetic
Compatibility Regulations 2016
Galvanic Isolation Input to 3.0 KVac
Output
Input to 2.0 KVac
Ground
Output to 0.5 KVac
Ground

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
4 www.DeltaPSU.com (December 2023, Rev. 09)
TECHNICAL DATASHEET

LYTE DIN Rail Power Supply


DRL-75W series / DRL-V75W1AZ

Model Number DRL-12V75W1AZ☐ DRL-24V75W1AZ☐ DRL-48V75W1AZ☐

EMC

Emissions (CE & RE) CISPR 32, EN/BS EN 55032, EN/BS EN 55011, AS/NZS CISPR32: Class B;
GB9254.1
Compliance with: EN/BS EN 61000-6-3
Component Power EN/BS EN 61204-3
Supply for General Use
Immunity EN/BS EN 55035, EN/BS EN 55024
Compliance with: EN/BS EN 61000-6-1
Electrostatic IEC 61000-4-2 Level 4 Criteria A1)
Discharge Air Discharge: 15 kV
Contact Discharge: 8 kV
Radiated Field IEC 61000-4-3 Level 2 Criteria A1)
80 MHz – 1 GHz, 3 V/M with 1 kHz tone / 80% modulation
Electrical Fast IEC 61000-4-4 Level 3 Criteria A1)
Transient / Burst 2 kV
Surge IEC 61000-4-5 Level 4 Criteria A1)
Common Mode3): 4 kV
Differential Mode4): 2 kV
Conducted IEC 61000-4-6 Level 2 Criteria A1)
150 kHz – 80 MHz, 3 Vrms
Power Frequency IEC 61000-4-8 Level 2 Criteria A1)
Magnetic Fields 3 A/m
Voltage Dips and IEC 61000-4-11 0% of 115 Vac, 12 ms Criteria A1)
Interruptions 40% of 115 Vac, 200 ms Criteria B2)
70% of 115 Vac, 500 ms Criteria A1)
0% of 115 Vac, 5000 ms Criteria B2)
0% of 240 Vac, 12 ms Criteria A1)
40% of 240 Vac, 200 ms Criteria A1)
70% of 240 Vac, 500 ms Criteria A1)
0% of 240 Vac, 5000 ms Criteria B2)
Harmonic Current IEC/EN/BS EN 61000-3-2, Class A; GB17625.1
Emission
Voltage Fluctuation and IEC/EN/BS EN 61000-3-3
Flicker
Voltage Sag Immunity 80% of 200 Vac 160 Vac, 1000 ms Criteria A1)
SEMI F47 – 0706 70% of 200 Vac 140 Vac, 500 ms Criteria A1)
50% of 200 Vac 100 Vac, 200 ms Criteria A1)
1) Criteria A: Normal performance within the specification limits
2) Criteria B: Temporary degradation or loss of function which is self-recoverable
3) Asymmetrical: Common mode (Line to earth)
4) Symmetrical: Differential mode (Line to line)

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
5 www.DeltaPSU.com (December 2023, Rev. 09)
TECHNICAL DATASHEET

LYTE DIN Rail Power Supply


DRL-75W series / DRL-V75W1AZ

Block Diagram
DRL-☐V75W1AZ☐

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
6 www.DeltaPSU.com (December 2023, Rev. 09)
TECHNICAL DATASHEET

LYTE DIN Rail Power Supply


DRL-75W series / DRL-V75W1AZ

Device Description

1) Input terminal block connector


2) Output terminal block connector
3) DC voltage adjustment potentiometer
4) DC OK LED (Green)
5) Universal mounting rail system

Dimensions
H x W x D: 123.6 x 27 x 102 mm (4.87 x 1.06 x 4.02 inch)

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
7 www.DeltaPSU.com (December 2023, Rev. 09)
TECHNICAL DATASHEET

LYTE DIN Rail Power Supply


DRL-75W series / DRL-V75W1AZ

Engineering Data
Output Load De-rating VS Surrounding Air Temperature Note

110 1. Power supply components may degrade, or


be damaged, when the power supply is
100
Percentage of Max Load (%)

continuously used outside the shaded region,


90 refer to the graph shown in Fig. 1.
80 2. If the output capacity is not reduced when the
70 surrounding air temperature > 40°C (115 Vac)
or > 50°C (230 Vac), the device will run into
60 Over Temperature Protection. When
50 activated, power supply will latch off, until the
40 surrounding air temperature is lowered or the
load is reduced as far as necessary to keep
30
the device in working condition, and require
20 removal/re-application of input AC voltage in
10 order to restart.
0 3. In order for the device to function in the
manner intended, it is also necessary to keep
-20 -10 0 10 20 30 40 50 60 70
a safety distance as recommended in the
Surrounding Air Temperature (°C) safety instructions while the device is in
operation.
230 Vac - - - 115 Vac
4. Depending on the surrounding air temperature
and output load delivered by the power
supply, the device can be very hot!
Fig. 1 De-rating for Vertical Mounting Orientation 5. If the device has to be mounted in any other
-10°C to -20°C de-rate power by 1% / °C orientation, please contact info@deltapsu.com
> 40°C de-rate power by 1.67% / °C @ 115 Vac for more details.
> 50°C de-rate power by 2.5% / °C @ 230 Vac

Output Load De-rating VS Input Voltage

110 ◼ No output power de-rating for the input


100 voltage from 100 Vac to 264 Vac
90
80
70
Load (%)

60
50
40
30
20
10
0
85 100 120 140 160 180 200 240 264
Input Voltage (Vac)

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
8 www.DeltaPSU.com (December 2023, Rev. 09)
TECHNICAL DATASHEET

LYTE DIN Rail Power Supply


DRL-75W series / DRL-V75W1AZ

Assembly & Installation

The power supply unit (PSU) can be mounted on 35 mm DIN rails in accordance with EN 60715. The device should be installed with
input terminal block at the bottom.

Each device is delivered ready to install.

Mounting Dismounting

Fig. 2.1 Mounting Fig. 2.2 Dismounting

Snap on the DIN rail as shown in Fig. 2.1: To uninstall,


1. Pull the unit’s DIN rail latch OUT. 1. Pull the unit’s DIN rail latch OUT.
2. Tilt the unit slightly upwards, hook the top end onto the DIN 2. Tilt the bottom part of the unit out.
rail and push downwards until stopped. 3. Push the unit up and pull out from the DIN rail.
3. Position the bottom front end against the DIN rail.
4. Push the unit’s latch DIN rail IN to lock.

In accordance to EN 60950 / UL 60950 and EN 62368 / UL 62368, flexible cables require ferrules.
Use appropriate copper cables designed to sustain operating temperature of at least 60°C / 75°C or more to fulfill UL requirements.

Safety Instructions
◼ Vertical Mounting
• ALWAYS switch mains of input power OFF before connecting and disconnecting the input
voltage to the unit. If mains are not turned OFF, there is risk of explosion / severe damage.
• To guarantee sufficient convection cooling, keep a distance of 50 mm (1.96 inch) above
and below the device as well as a lateral distance of 10 mm (0.39 inch) to other units.
• Note that the enclosure of the device can become very hot depending on the surrounding air
temperature and load of the power supply. Risk of burns!
• The main power must be turned off before connecting or disconnecting wires to the terminals.
• DO NOT insert any objects into the unit.
• Hazardous voltages may be present for up to 5 minutes after the input mains voltage is
disconnected. Do not touch the unit during this time.
• The power supplies are built in units and must be installed in a cabinet or room (condensation
free environment and indoor location) that is relatively free of conductive contaminants.

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
9 www.DeltaPSU.com (December 2023, Rev. 09)
TECHNICAL DATASHEET

LYTE DIN Rail Power Supply


DRL-75W series / DRL-V75W1AZ

Functions
◼ Graph illustrating the Start-up Time, Rise Time, and Hold-up Time

Start-up Time
The time required for the output voltage to reach 90% of its final steady state set value, after the input voltage is applied.

Rise Time
The time required for the output voltage to change from 10% to 90% of its final steady state set value.

Hold-up Time
Time between the collapse of the AC input voltage, and the output falling to 95% of its steady state set value.

Inrush Current Dynamic Response


Inrush current is the peak, instantaneous, input current measured The power supply output voltage will remains within ±10% of its
and, occurs when the input voltage is first applied. For AC input steady state value, when subjected to a dynamic load from 0% to
voltages, the maximum peak value of inrush current will occur 50% and 50% to 100% of its rated current.
during the first half cycle of the applied AC voltage. This peak value
decreases exponentially during subsequent cycles of AC voltage. ◼ 50% duty cycle / 5 Hz to 100 Hz

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
10 www.DeltaPSU.com (December 2023, Rev. 09)
TECHNICAL DATASHEET

LYTE DIN Rail Power Supply


DRL-75W series / DRL-V75W1AZ

Overload & Overcurrent Protections (Continuous Current) Overvoltage Protection (Latch Mode)
The power supply’s Overload (OLP) and Overcurrent (OCP) The power supply’s overvoltage circuit will be activated when its
Protections will be activated when output current is 105~133% of internal feedback circuit fails. The output voltage shall not exceed
IO (Max load). Upon such an occurrence, the VO (output voltage) its specifications as described in “Protections” section. Power
will start to droop. Once the power supply has reached its supply will latch off, and require removal/re-application of input AC
maximum power limit, the protection will be activated; and, the voltage in order to restart.
power supply will operate in continuous current. The power supply
will recover once the cause of OLP or OCP is removed, and I O The power supply should be latch.
(output current) is back within the specified range.

Over Temperature Protection (Latch Mode)


As described in load de-rating section, the power supply also has
Over Temperature Protection (OTP). In the event of a higher
operating temperature at 100% load; or, when the operating
temperature is beyond what is recommended in the de-rating
Short Circuit Protection (Auto-Recovery) graph, the OTP circuit will be activated. When activated, power
supply will latch off, until the surrounding air temperature drops to
The power supply’s output Short Circuit Protection function also
its normal operating temperature or the load is reduced as
provides protection against short circuits. When a short circuit is
recommended in the de-rating graph. Removal/re-application of
applied, the output current will operate in “Hiccup mode”. The
input AC voltage will then be required in order to restart.
power supply will return to normal operation after the short circuit
is removed.

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
11 www.DeltaPSU.com (December 2023, Rev. 09)
TECHNICAL DATASHEET

LYTE DIN Rail Power Supply


DRL-75W series / DRL-V75W1AZ

Others
Attention
Delta provides all information in the datasheets on an “AS IS” basis and does not offer any kind of warranty through the information for
using the product. In the event of any discrepancy between the information in the catalog and datasheets, the datasheets shall prevail
(please refer to www.DeltaPSU.com for the latest datasheets information). Delta shall have no liability of indemnification for any claim
or action arising from any error for the provided information in the datasheets. Customer shall take its responsibility for evaluation of using
the product before placing an order with Delta.

Delta reserves the right to make changes to the information described in the datasheets without notice.

Manufacturer and Authorized Representatives Information


Manufacturer
Thailand Taiwan
Delta Electronics (Thailand) PCL. Delta Electronics, Inc.
909 Pattana 1 Rd., Muang, Samutprakarn, 10280 Thailand 3 Tungyuan Road, Chungli Industrial Zone, Taoyuan County
32063, Taiwan

Authorized Representatives
The Netherlands United Kingdom
Delta Greentech (Netherlands) B.V. Delta Electronics Europe Limited
Zandsteen 15, 2132 MZ Hoofddorp, The Netherlands 1 Redwood Court, Peel Park Campus,
East Kilbride, Glasgow, G74 5PF, United Kingdom

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
12 www.DeltaPSU.com (December 2023, Rev. 09)