0% found this document useful (0 votes)
71 views24 pages

Liners SLOT DIFFUSERS

Linear Slot Diffusers are designed for continuous linear applications in various commercial and industrial settings, providing efficient air distribution with adjustable flow patterns. Constructed from heavy-gauged aluminum alloy, they can be used in ceilings or walls and are suitable for Variable Air Volume systems. The product features customizable options, including slot widths and lengths, and is tested for performance in accordance with industry standards.

Uploaded by

pasric
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
71 views24 pages

Liners SLOT DIFFUSERS

Linear Slot Diffusers are designed for continuous linear applications in various commercial and industrial settings, providing efficient air distribution with adjustable flow patterns. Constructed from heavy-gauged aluminum alloy, they can be used in ceilings or walls and are suitable for Variable Air Volume systems. The product features customizable options, including slot widths and lengths, and is tested for performance in accordance with industry standards.

Uploaded by

pasric
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

Linear Slot Diffusers

Technical Catalogue
Linear Slot Diffusers
Linear Slot Diffusers offer unique option for continuous linear application in ceiling of
ball rooms, auditoriums, in peripheral walls of office spaces etc. LSD is suitable for all
commercial and industrial projects which demand single or multi-slot diffusers for
ceilings, bulkheads or sidewalls for supply and exhaust air systems. It is used in ceiling
as horizontal diffuser or, in some cases, on vertical downward discharge. The ability to
produce the tight air pattern from maximum to minimum flow makes the product an
excellent choice for Variable Air Volume systems. They are constructed from heavy
gauged extruded Alumimuim alloy profiles and powder coated in standard white
finish.

Ref:GD1000LSD
Linear Slot Diffusers Introduction

SLSD/RLSD series are the exceptional option for continuous linear application as in peripheral walls
of office spaces, ball rooms and auditoriums. The ability to produce a tight air pattern from maxi-
mum to minimum flow makes our product an excellent choice for variable air volume systems.

Construction & Application

Frames/Blades Extruded heavy Gauged Aluminium alloy profile.

Finish Electrostatic Polyester powder coated system/RAL code.

Fixing Ceiling & High side wall.

Damper Hit & Miss Damper.

Shape Rectangular/Full - Half Circle.

Assembled with one to several long narrow or curved slots, commonly recognized as linear slot diffusers.

Semi concealed in permanent or suspended ceiling, which make a spectacular impression.

Used as supply, return and exhaust air terminal devices in HVAC applications.

Where high quality of air diffusion with low pressure drop and maximum attenuation of noise is to be maintained.

Adept to any designing concept of architectural engineers and contractors.

Best suitable, where a pleasant visual impact is essential, e.g in convention halls, hotels and ball rooms.

Known for consistency in maintaining desired air flow through unobstructed dispensing and pattern controlling.

EXCELAIR Air Outlets | Technical Catalogue Linear Slot Diffusers | Introduction


Linear Slot Diffusers Assembling Features

The LSD frame, slotting strips, deflector blades are made of heavy gauge, stream lined, extruded aluminum alloy which have
high corrosion resistance and rigidity.

The factory finish diffuser includes two opposed adjustable deflector blades in every row according to the number of slots, which
can be set in to deflect the air either in horizontal or vertical directions, thus 180º air flow pattern adjustment can be achieved.

Both the Supply and Return Slot Diffusers are fitted with air deflectors, so that the air flow pattern can be changed easily by
rotating the air deflectors towards the serving area.

Supply Linear Slot Diffusers(SLSD) are equipped with aluminium alloy “HIT & MISS DAMPER” which controls the air flow / volume
without affecting the airflow pattern set by the deflector blades. Return Linear Slot Diffusers are without “HIT & MISS DAMPER”
. But are fitted with normal Deflector blades.

The deflectors and the Hit & Miss dampers are painted black in accordance with RAL 9005 colour code as a standardized item.

Air deflectors and Hit & Miss Dampers are adjustable by each slot separately.

Orders can be executed for LSD consisting of 1 upto 8 slots of maximum 3000 mm length with 16mm, 19mm and 25mm width
per slot. Standard slot diffusers are supplied with 19mm slot width.

A single module unit comes capped at both ends. It also can come without end cap at both ends or at any one end.....depending
which segment of the LSD unit , whether end pieces or as part of a continuous run. Removable end caps allows extending are
shortening slot diffusers run without replacing existing pieces.

The constructional pattern enables the ceiling or wall fixed linear slot diffusers to be connected to the duct system through a
plenum box with utmost ease.

Linear slot diffusers with special geometrical shapes are also available according to the designer’s request.

All our models can be supplied with optional rubber foam gasket to prevent any air leakage and protect the walls from smudging
behind the frame.

EXCELAIR Air Outlets | Technical Catalogue Linear Slot Diffusers | Assembling Features
Linear Slot Diffusers Constructional Details

With Damper (SLSD) Without Damper (RLSD)


X X
Y Hit & Miss Damper Y

Internal Frame Internal Frame

External Frame External Frame

45 mm Air Defector 45 mm Air Defector


mm

mm
20

20
33mm 33mm
13 mm 13 mm
Z Z

Hit & Miss Damper

Internal Frame

External Frame

Dimensional Details Defectors

Straight Slot Diffusers


Slot No. of
1 2 3 4 5 6 7 8
Width (mm) Slots
X (mm) 37 68 98 128 188 219 249

16 Y (mm) 31 62 92 122 152 182 213 243


Z (mm) 81 112 142 172 202 232 263 293

X (mm) 41 76 110 144 178 212 247 281


19 Y (mm) 35 70 104 138 172 206 241 275
Z (mm) 85 120 154 188 222 256 291 325

X (mm) 46 86 125 164 203 242 282 321

25 Y (mm) 40 80 119 158 197 236 276 315


Z (mm) 90 130 169 208 247 286 326 365

CFM/FT. 10-100 20-125 30-150 40-200 50-250 60-300 70-350 80-400

X - Neck Size
Z - Face Size

EXCELAIR Air Outlets Technical Catalogue Linear Slot Diffusers Constructional Details
Linear Slot Diffusers Constructional Details

With Damper (SLSD) Without Damper (RLSD)


X X
Y Hit & Miss Damper Y

Internal Frame Internal Frame

External Frame External Frame

55 mm Air Deflector 55 mm Air Deflector


mm

mm
20

20
32mm 32mm
18 mm 18 mm
Z Z

X - Ceiling Opening Y - Neck Size Z-Front Face

Hit & Miss Damper

Internal Frame

External Frame

Dimensional Details Deflectors

Curved Slot Diffusers


Slot No. of
1 2 3 4 5 6 7 8
Width (mm) Slots
X (mm) 41 72 103 134 165 196 227 258

16 Y (mm) 35 66 97 128 159 190 221 252


Z (mm) 81 112 143 174 205 236 267 298

X (mm) 44 78 112 146 180 214 248 282


19 Y (mm) 38 72 106 140 174 208 242 276
Z (mm) 84 118 152 186 220 254 288 322

X (mm) 51 92 133 174 215 256 297 338

25 Y (mm) 45 86 127 168 209 250 291 332


Z (mm) 91 132 173 214 255 296 337 378

CFM/FT. 10-100 20-125 30-150 40-200 50-250 60-300 70-350 80-400

X - Ceiling Opening Y - Neck Size Z-Front Face

EXCELAIR Air Outlets | Technical Catalogue Linear Slot Diffusers | Constructional Details
Linear Slot Diffusers Curved Linear Slot Diffusers [CVLSD]

For an architectural semblance, our catalogue includes circular linear slot diffusers. This type will be more suitable in umbrella shaped
ceilings. Semi or full circular linear diffuser are available which for any ceiling mounting. Factory finish unit available with Hit and Miss
Damper (One Piece) and without Deflector blades.

For ordering full circular or semi circular diffuser, arch

R 0 length to be mentioned separately along with the


360
D R radius of the required diffuser. Minimum radius should
Arch length for half circular diffuser = x R be more than 2000mm.

Installation
Duct Width
Installation Screw
Y

Duct Plenum

Installation Clip

“C” Clamp

External Frame

Internal Frame

False Ceiling

18 mm

Sizes And Ceiling Opening


No. of
1 2 3 4 5 6 7 8
Slots

Slot Width (mm) 16 19 25 16 19 25 16 19 25 16 19 25 16 19 25 16 19 25 16 19 25 16 19 25

X (mm) 41 44 51 72 78 92 103 112 133 134 146 174 165 180 215 196 214 256 227 248 297 258 282 338

Y (mm) 35 38 45 66 72 86 97 106 127 128 140 168 159 174 209 190 208 250 221 242 291 252 276 332

Z (mm) 81 84 91 112 118 132 143 152 173 174 186 214 205 220 255 236 254 296 267 288 337 298 322 378

CFM/FT. 10 - 60 20 - 75 30 - 90 40 - 110 50 - 130 60 - 150 75 - 175 90- 200

X - Ceiling Opening Y - Neck Size Z-Front Face

EXCELAIR Air Outlets | Technical Catalogue Linear Slot Diffusers | Curved Linear Slot Diffusers
Linear Slot Diffusers Mitered Corners [LSD-C]

0
Side Wall - Inside Corner (C-WF-I-90 )

30
0m
m

0 mm
30

0
135

0
Ceiling Corner Fixing (C-CF-135 ) 300mm

0
Ceiling Corner Fixing (C-CF-90 )
0
90
300mm

300mm
30
0m
m
0
Side Wall - Outside Corner (C-WF-O-90 ) 0m
m
30

Note: Available in 1 to 8 slot.

EXCELAIR Air Outlets | Technical Catalogue Linear Slot Diffusers | Mitered Corners
Linear Slot Diffusers Engineering Data

Blade Settings:
The deflection blades of the supply slot linear diffuser(SLSD) can be adjusted
to provide either a horizontal or vertical air pattern. The horizontal air flow
adjustment may be set for either left or right hand throw. Resetting the blade
position leads to a change in the noise level as well as and total pressure.

Throw Data:
All throw datas are based on the results of tests of 4-feet length diffusers. To determine throws for other diffuser lengths, use correction factors as
follows:

Diffuser Active length (ft.) 1 2 3 4 6-8

Throw Correction Factor 0.6 0.8 0.9 1.0 1.3

Sound Data:
Sound data (NC values) shown in the Performance Tables are based on a room absorption of 10dB, re 10-12 Watts and a 4-feet unit test length. To
determine NC values for other lengths, add NC value to catalog data as follows:

Diffuser Active length (ft.) 2 3 4 5 6-8

Add NC Value (dB) -3.0 -1.5 0 1.0 2.0

Selection Procedure
The horizontal throw data is presented in the performance data pages with all slots supplying air in a given direction. To determine two-way throw, use
the catalog throw data for the desired quantity of air from the number of slots in each direction and reduce the throw by 20%.

Area Factor Summary

Number of Slots 16mm Slot Width 19mm Slot Width 25mm Slot Width

1 0.013 0.017 0.021


2 0.031 0.038 0.048
3 0.048 0.060 0.075
4 0.069 0.082 0.103
5 0.094 0.115 0.145
6 0.117 0.147 0.183
7 0.152 0.190 0.238
8 0.186 0.233 0.291

EXCELAIR Air Outlets | Technical Catalogue Linear Slot Diffusers | Engineering Data
Linear Slot Diffusers Product Testing

Introduction

According to the ETL - Intertek Testing Laboratories Inc, the following performance tables includes the test results conducted on the
three supply Linear Slot Diffusers. The result includes static pressure, area factor, throw and sound power level. The samples were
selected and supplied by Century Mechanical Systems Factory in April 12, 2010. Extrapolations and Interpolations were applied to
cover all range of sizes and parameters.

Test Method

The Samples were tested in accordance with the ASHRAE 70-2006 Standard “Method of Testing for Rating the Performance of Air
Outlets and Inlets”, which incorporates ADC 1062: GRD-84 test code for Grilles, Registers and Diffusers. Acoustical data were
obtained employing a Bruel & Kjaer Digital Frequency Pulse Analyzer and analyzed on a Compaq Computer. The reference sound
source used for this test was a calibrated Bruel & Kjaer Type 4204, which conforms to the above standard. The sample was installed
in the facility and supplied with measured volumes of air. The static pressure was measured 1 ½ duct diameters upstream of the inlet.

Noise Criteria(NC) ratings were determined by subtracting a room absorption of 10dB from the Sound Powder Level data. Air volumes
were calculated in CFM. Throw values were derived at terminal velocities of 150fpm, 100fpm and 50fpm.

EXCELAIR Air Outlets | Technical Catalogue Linear Slot Diffusers | Product Testing
Linear Slot Diffusers Performance Data

Supply Linear Slot Diffuser [SLSD-16]

SLSD - 16mm Slot Width:

Area
# of
Factor CFM/ft 10 20 30 40 50 60 75 90 110 130 150 175 200
Slots
(Ak)

Pt(in
0.01 0.041 0.093 0.166 0.259
wg)
Throw
1 slot Ak=0.030 3-7 7-15 10-22 13-30 16-37
(ft)

NC <15 21 32 41 49

Pt(in
0.003 0.012 0.028 0.049 0.077 0.11 0.173 0.248
wg)
Throw
2 Slot Ak=0.060 2-5 4-10 6-14 8-19 11-24 13-29 16-36 19-43
(ft)

NC <15 <15 17 25 31 36 42 48

Pt(in
0.002 0.008 0.019 0.033 0.05 0.072 0.111 0.159 0.235
wg)
Throw
3 Slot Ak=0.082 2-4 4-9 6-13 8-18 10-22 12-26 15-33 17-40 21-49
(ft)

NC <15 <15 <15 19 25 30 36 41 47

Pt(in
0.002 0.006 0.014 0.025 0.038 0.055 0.085 0.121 0.18 0.249
wg)
Throw
4 Slot Ak=0.109 1-3 3-7 4-10 6-13 7-17 9-20 11-25 13-30 16-37 19-44
(ft)

NC <15 <15 <15 <15 18 23 29 34 40 45

Pt(in
0.001 0.004 0.01 0.017 0.026 0.037 0.058 0.082 0.122 0.169 0.224
wg)
Throw
5 Slot Ak=0.136 1-3 3-6 4-9 5-12 7-15 8-18 10-22 12-27 14-33 17-39 20-45
(ft)

NC <15 <15 <15 <15 15 19 25 30 36 41 45

Pt(in
0.001 0.003 0.007 0.012 0.019 0.027 0.042 0.06 0.088 0.123 0.162 0.219
wg)
Throw
6 Slot Ak=0.163 1-3 2-5 4-8 5-11 6-13 7-16 9-20 11-24 13-30 15-35 18-40 21-47
(ft)

NC <15 <15 <15 <15 15 18 23 28 33 38 42 46

Pt(in
0.001 0.003 0.006 0.011 0.017 0.024 0.037 0.053 0.078 0.108 0.143 0.193 0.251
wg)
Throw
7 Slot Ak=0.207 1-2 2-4 3-7 4-9 5-11 6-13 7-16 9-20 11-24 13-28 14-33 17-38 19-44
(ft)

NC <15 <15 <15 <15 15 17 20 23 29 34 38 42 46

Pt(in
0.001 0.002 0.005 0.009 0.014 0.02 0.03 0.043 0.064 0.088 0.117 0.158 0.205
wg)
Throw
8 Slot Ak=0.242 1-2 2-4 3-6 3-8 4-10 5-12 7-15 8-18 10-22 11-26 13-30 15-35 17-40
(ft)

NC <15 <15 <15 <15 <15 15 18 20 25 29 33 38 41

Ak - Area Factor in Square feet per foot length Noise Criteria Values are based on room attenuation of 10dB
Pt - Total Pressure in Inches water gauge Throw values are based on face velocity of 100fpm & 50fpm
NC - Noise criteria Damper fully open position
Throw in feet

EXCELAIR Air Outlets | Technical Catalogue Linear Slot Diffusers | Performance Data
Linear Slot Diffusers Performance Data

Return Linear Slot Diffuser [RLSD-16]

RLSD - 16mm Slot Width:

# of
CFM/ft 10 20 30 40 50 60 75 90 110 130 150 175 200
Slots

Pt(in
0.013 0.05 0.113 0.201
1 slot wg)
NC <15 24 35 44
Pt(in
0.004 0.015 0.033 0.059 0.093 0.134 0.209
2 Slot wg)
NC <15 <15 19 27 33 38 45
Pt(in
0.003 0.01 0.022 0.039 0.061 0.087 0.135 0.192
3 Slot wg)
NC <15 <15 <15 21 27 32 39 44
Pt(in
0.002 0.008 0.017 0.03 0.047 0.066 0.103 0.147 0.217 0.301
4 Slot wg)
NC <15 <15 <15 15 21 26 32 37 42 47
Pt(in
0.001 0.005 0.012 0.02 0.032 0.045 0.07 0.1 0.148 0.205 0.271
5 Slot wg)
NC <15 <15 <15 15 18 22 28 33 39 43 47
Pt(in
0.001 0.004 0.008 0.015 0.023 0.033 0.051 0.072 0.107 0.148 0.196 0.265
6 Slot wg)
NC <15 <15 <15 15 18 20 25 30 36 41 45 49
Pt(in
0.001 0.003 0.007 0.013 0.02 0.029 0.045 0.064 0.094 0.131 0.173 0.234 0.304
7 Slot wg)
NC <15 <15 <15 15 18 20 23 26 32 36 40 45 48
Pt(in
0.001 0.003 0.006 0.011 0.017 0.024 0.037 0.052 0.077 0.107 0.142 0.191 0.249
8 Slot wg)
NC <15 <15 <15 <15 16 18 21 23 27 32 36 40 44

NC Data based on 10dB room attenuation. Cfm - Air volume in cubic feet per minute.
Ps - Negative static pressure in inches water gauge. NC - Noise criteria

10

EXCELAIR Air Outlets | Technical Catalogue Linear Slot Diffusers | Performance Data
Linear Slot Diffusers Performance Data

Supply Linear Slot Diffuser [SLSD-19]

SLSD - 19mm Slot Width(standard):

Area
# of
Factor CFM/ft 10 20 30 40 50 60 75 90 110 130 150 175 200
Slots
(Ak)

Pt(in
wg) 0.009 0.035 0.08 0.142 0.222 0.319
Throw
1 slot Ak=0.039 (ft) 3-6 6-13 9-19 11-26 14-32 17-39

NC
<15 <15 25 33 40 46
Pt(in
wg) 0.002 0.01 0.022 0.199 0.199 0.061 0.138 0.199 0.297
Throw
2 Slot Ak=0.078
(ft) 2-4 4-9 6-13 17-39 17-39 10-22 14-33 17-39 21-48

NC
<15 <15 <15 17 24 29 35 35 40
Pt(in
wg) 0.002 0.008 0.017 0.03 0.046 0.066 0.102 0.145 0.215
Throw
3 Slot Ak=0.117
(ft) 2-3 3-7 5-10 6-14 8-17 9-21 11-26 14-31 17-38

NC
<15 <15 <15 <15 15 20 26 31 37
Pt(in
wg) 0.001 0.005 0.01 0.018 0.028 0.04 0.062 0.089 0.132 0.183
Throw
4 Slot Ak=0.141
(ft) 1-3 3-6 4-9 5-12 7-15 8-18 10-23 12-28 15-34 18-40

NC
<15 <15 <15 <15 <15 16 22 27 33 37
Pt(in
wg) 0.001 0.003 0.007 0.012 0.019 0.027 0.042 0.06 0.089 0.123 0.163
Throw
5 Slot Ak=0.176 (ft) 1-3 2-5 4-8 5-11 6-14 7-16 9-20 11-25 13-30 16-35 18-41

NC
<15 <15 <15 <15 <15 <15 18 23 29 33 37
Pt(in
wg) 0.001 0.002 0.005 0.009 0.014 0.02 0.03 0.043 0.064 0.089 0.118 0.159 0.207
Throw
6 Slot Ak=0.211
(ft) 1-2 2-5 3-7 4-10 5-12 7-15 8-19 10-22 12-27 14-32 16-37 19-43 22-49

NC
<15 <15 <15 <15 <15 <15 17 21 26 31 35 39 43
Pt(in
wg) 0 0.002 0.004 0.007 0.01 0.015 0.023 0.032 0.048 0.066 0.088 0.118 0.154
Throw
7 Slot Ak=0.246
(ft) 1-2 2-5 3-7 4-9 5-11 6-14 8-17 9-21 11-25 13-30 15-34 18-40 20-46

NC
<15 <15 <15 <15 <15 15 18 20 24 29 33 37 41
Pt(in
wg) 0 0.001 0.003 0.005 0.008 0.011 0.018 0.025 0.037 0.052 0.069 0.093 0.121
Throw
8 Slot Ak=0.281
(ft) 1-2 2-4 3-6 4-9 5-11 6-13 7-16 8-19 10-23 12-28 14-32 16-37 19-43

NC
<15 <15 <15 <15 <15 <15 16 18 21 25 29 33 37

Ak - Area Factor in Square feet per foot length Noise Criteria Values are based on room attenuation of 10dB
Pt - Total Pressure in Inches water gauge Throw values are based on face velocity of 100fpm & 50fpm
NC - Noise criteria Damper fully open position
Throw in feet

11

EXCELAIR Air Outlets | Technical Catalogue Linear Slot Diffusers | Performance Data
Linear Slot Diffusers Performance Data

Return Linear Slot Diffuser [RLSD-19]

RLSD - 19mm Slot Width(Standard):

# of
CFM/ft 10 20 30 40 50 60 75 90 110 130 150 175 200
Slots

Pt(in 0.011 0.043 0.097 0.172 0.268 0.386


1 slot wg)
NC <15 16 28 36 42 49

Pt(in 0.003 0.012 0.027 0.048 0.074 0.107 0.167 0.241 0.36
2 Slot wg)
NC <15 <15 <15 20 26 31 37 43 49

Pt(in 0.002 0.009 0.021 0.036 0.056 0.08 0.123 0.176 0.26
3 Slot wg)
NC <15 <15 <15 <15 17 22 29 34 39

Pt(in 0.001 0.006 0.013 0.022 0.034 0.049 0.075 0.108 0.159 0.221
4 Slot wg)
NC <15 <15 <15 <15 15 18 25 30 35 40

Pt(in 0.001 0.004 0.009 0.015 0.023 0.033 0.051 0.073 0.108 0.149 0.198
5 Slot wg)
NC <15 <15 <15 <15 15 17 21 26 31 36 40

Pt(in 0.001 0.003 0.006 0.011 0.017 0.024 0.037 0.053 0.078 0.108 0.142 0.193 0.25
6 Slot wg)
NC <15 <15 <15 <15 15 17 20 23 29 33 37 42 45

Pt(in 0.001 0.002 0.005 0.008 0.012 0.018 0.027 0.039 0.058 0.08 0.106 0.143 0.186
7 Slot wg)
NC <15 <15 <15 <15 15 18 21 23 27 31 35 40 43

Pt(in 0 0.002 0.004 0.006 0.01 0.014 0.021 0.031 0.045 0.063 0.083 0.112 0.146
8 Slot wg)
NC <15 <15 <15 <15 <15 16 19 21 24 28 32 36 40

NC Data based on 10dB room attenuation. Cfm - Air volume in cubic feet per minute.
Ps - Negative static pressure in inches water gauge. NC - Noise criteria

12

EXCELAIR Air Outlets | Technical Catalogue Linear Slot Diffusers | Performance Data
Linear Slot Diffusers Performance Data

Supply Linear Slot Diffuser [SLSD-25]

SLSD - 25mm Slot Width:

Area
# of
Factor CFM/ft 10 20 30 40 50 60 75 90 110 130 150 175 200
Slots
(Ak)

Pt(in 0.007 0.027 0.06 0.107 0.168 0.241


wg)
Throw 3-6 5-12 8-18 10-24 13-30 16-36
1 slot Ak=0.046
(ft)
<15 <15 20 28 34 40
NC

Pt(in 0.002 0.008 0.017 0.031 0.048 0.069 0.108 0.155 0.232
wg)
Throw 2-4 3-8 5-12 7-16 9-20 10-24 13-30 16-35 19-43
2 Slot Ak=0.093 (ft)
<15 <15 <15 <15 19 24 30 35 41
NC

Pt(in 0.001 0.005 0.011 0.019 0.03 0.042 0.066 0.094 0.139 0.193 0.255
wg)
Throw 2-4 3-7 5-11 6-15 8-18 10-22 12-27 14-33 18-40 21-47 24-55
3 Slot Ak=0.126
(ft)
<15 <15 <15 <15 <15 18 24 29 35 39 43
NC

Pt(in 0.001 0.004 0.008 0.014 0.022 0.032 0.049 0.07 0.104 0.144 0.191 0.258 0.335
wg)
Throw 1-3 2-6 4-8 5-11 6-14 7-17 9-21 11-25 14-31 16-36 18-42 22-49 25-56
4 Slot Ak=0.167
(ft)
<15 <15 <15 <15 <15 <15 17 22 28 32 36 41 44
NC

Pt(in 0.001 0.003 0.006 0.01 0.015 0.021 0.033 0.047 0.07 0.097 0.128 0.174 0.225
wg)
Throw 1-2 2-5 3-7 4-10 5-12 7-15 8-19 10-22 12-27 14-32 16-37 19-43 22-50
5 Slot Ak=0.209
(ft)
<15 <15 <15 <15 <15 <15 15 18 24 29 33 37 41
NC

Pt(in 0 0.002 0.004 0.007 0.011 0.015 0.024 0.034 0.05 0.07 0.092 0.125 0.162
wg)
Throw 1-2 2-4 3-7 4-9 5-11 6-13 7-17 9-20 11-25 13-29 15-34 17-39 20-45
6 Slot Ak=0.251 (ft)
<15 <15 <15 <15 <15 <15 15 17 21 26 30 34 38
NC

Pt(in 0 0.001 0.003 0.005 0.008 0.011 0.018 0.025 0.037 0.052 0.069 0.093 0.12
wg)
Throw 1-2 2-4 3-6 4-8 5-10 5-12 7-16 8-19 10-23 12-27 14-31 16-36 18-42
7 Slot Ak=0.293
(ft)
<15 <15 <15 <15 <15 <15 15 18 20 24 28 32 36
NC

Pt(in 0 0.001 0.003 0.005 0.007 0.01 0.015 0.022 0.033 0.045 0.06 0.081 0.105
wg)
Throw 1-2 2-4 2-5 3-7 4-9 5-11 6-13 7-16 9-20 10-23 12-27 14-31 16-36
8 Slot Ak=0.353
(ft)
<15 <15 <15 <15 <15 <15 <15 15 18 20 23 27 31
NC

Ak - Area Factor in Square feet per foot length Noise Criteria Values are based on room attenuation of 10dB
Pt - Total Pressure in Inches water gauge Throw values are based on face velocity of 100fpm & 50fpm
NC - Noise criteria Damper fully open position
Throw in feet

13

EXCELAIR Air Outlets | Technical Catalogue Linear Slot Diffusers | Performance Data
Linear Slot Diffusers Performance Data

Return Linear Slot Diffuser [RLSD-25]

RLSD - 25mm Slot Width:

# of
CFM/ft 10 20 30 40 50 60 75 90 110 130 150 175 200
Slots

Pt(in 0.008 0.032 0.073 0.13 0.203 0.292


1 slot wg)
NC <15 <15 23 31 37 43

Pt(in 0.002 0.009 0.021 0.037 0.058 0.084 0.131 0.188 0.281
2 Slot wg)
NC <15 <15 <15 15 21 26 33 38 43

Pt(in 0.002 0.006 0.013 0.023 0.036 0.051 0.08 0.114 0.168 0.233 0.308
3 Slot wg)
NC <15 <15 <15 <15 15 20 27 32 37 42 46

Pt(in 0.001 0.005 0.01 0.017 0.027 0.039 0.06 0.085 0.126 0.175 0.231 0.312 0.406
4 Slot wg)
NC <15 <15 <15 <15 <15 15 20 25 30 35 39 43 47

Pt(in 0.001 0.003 0.007 0.012 0.018 0.026 0.04 0.057 0.085 0.117 0.155 0.21 0.273
5 Slot wg)
NC <15 <15 <15 <15 <15 15 17 21 27 31 35 40 43

Pt(in 0.001 0.002 0.005 0.008 0.013 0.019 0.029 0.041 0.061 0.084 0.112 0.151 0.196
6 Slot wg)
NC <15 <15 <15 <15 <15 15 18 20 24 29 33 37 41

Pt(in 0 0.002 0.004 0.006 0.01 0.014 0.021 0.031 0.045 0.063 0.083 0.112 0.146
7 Slot wg)
NC <15 <15 <15 <15 <15 15 18 21 23 27 31 35 39

Pt(in 0 0.001 0.003 0.005 0.008 0.012 0.019 0.027 0.039 0.055 0.072 0.098 0.127
8 Slot wg)
NC <15 <15 <15 <15 <15 <15 16 18 21 23 25 30 33

NC Data based on 10dB room attenuation. Cfm - Air volume in cubic feet per minute.
Ps - Negative static pressure in inches water gauge. NC - Noise criteria

14

EXCELAIR Air Outlets | Technical Catalogue Linear Slot Diffusers | Performance Data
Linear Slot Diffusers Ordering Requisites

1. Type

Supply Linear Slot Diffusers SLSD


Return Linear Slot Diffusers RLSD
Curved Linear Slot Diffuser CVLSD

2. Number Of Slots 1 to 8

3. Slot Width 16mm, 19mm or 25mm

4. Length In mm

5. Number Of Units In Numbers

6.Accessories

Mitered Corner Pieces(Angle’s Degree) C


Foam Rubber Gasket F
Without Accessories W/A

7. Colour

Standard Colour RAL9010


Mill Finish MF
Other Colour (RAL CODE)

Note: For ordering full or semi circular diffuser, mention separately the radius of the required diffuser or templates to be provided.

Example

1 2 3 4 5 6 7

1000mm 0
SLSD 8 19mm (Slot Width) 100 Nos. C(135 ), F RAL 9010
length

8 slots, 1000 mm length, 19mm slot width, 100 units of supply linear slot diffuser, with foam gasket, with opposite mitered corner
pieces, white RAL 9010 finish.

15

EXCELAIR Air Outlets | Technical Catalogue Linear Slot Diffusers | Ordering Requisites
Linear Slot Diffusers Notes

16

EXCELAIR Air Outlets | Technical Catalogue Linear Slot Diffusers | Notes


EXCELAIR GD1000 SERIES
Available in RAL 9010 & 9016 Colors.
All other colors are available on request.

Coyright
All rights reserved.If you are not the right recipient,
you should not disclose,copy,use or publicize the contents.

cmsglobal.com
Products from:

Tel: +971 4 3416337, Fax : +971 4 3416338


P.O Box: 60270, Dubai, United Arab Emirates
[email protected]

cm sg lo b al . co m

You might also like