Fire Alarm Systems | NZM 0002 A Notification Appliance Zone Module
NZM 0002 A Notification Appliance Zone
Module
www.boschsecurity.com
u Monitored control of signaling devices by voltage
polarity reversal
u Ready to go thanks to plug-and-play technology and
pluggable terminal blocks
The NZM 0002 A Notification Appliance Zone Module System Overview
provides two monitored primary lines. This enables the
connection of two separate notification appliance zone
lines.
Connection of:
• Sirens
• Strobes
• Horns
The operating status of each zone is shown by a red
and a yellow status LED.
2 | NZM 0002 A Notification Appliance Zone Module
1 2 3 4 5 6 7 8 Technical Specifications
Electrical
Input voltage 20 V DC to 30 V DC
B
O UT1
A B
IN 1
A B A
O UT2
B
IN 2
A
5 V DC ± 5 %
Max. current consumption
• Standby (2 zones) 40 mA (at 24 V DC)
• Alarm (2 zones) 65 mA (at 24 V DC)
Max. output voltage 29.5 V DC
NZM 0002 A
Max. output current for
• Power supply via rail 500 mA per notification appliance
zone line (in the event of an alarm)
• External power supply 3 A per notification appliance zone
line (in the event of an alarm)
DC BAT SYNC
• Max. cable length Dependent on type and number of
GND
GND
OUT
+ - + -
IN
connected signaling devices
Mechanics
17 18 19 20 21 22 23 24 Operating/display elements 4 LEDs (2 x red, 2 x yellow)
2 keys (LED test)
Pos. Description Connector Housing material ABS plastic, Polylac PA‑766
1/2 B OUT1/A OUT1 NAC zone 1 Housing color Satin finish, anthracite, RAL 7016
3/4 B IN1/A IN1 Dimensions Approx. 127 x 96 x 60 mm
5/6 B OUT2/A OUT2 NAC zone 2 Weight Approx. 135 g
7/8 B IN2/A IN2
Environmental conditions
17 / DC + / - External power supply
18 Permitted operating -5 °C to 50 °C
temperature
19 / BAT + / - 24 V DC input, battery voltage
20 Permitted storage -20 °C to 60 °C
temperature
21 / SYNC GND/OUT Synchronization output
22 Permitted relative humidity 95 %, non-condensing
23 / SYNC GND/IN Synchronization input Protection class as per IP 30
24 IEC 60529
Installation/Configuration Notes Ordering Information
• For operating the fire alarm system according to EN NZM 0002 A Notification Appliance Zone Module
54-13 the signaling device lines must be designed in for connecting 2 separate notification appliance zone
loop topology. lines, provides 2 monitored primary lines
Order number NZM 0002 A
Parts Included
Accessories
Qty. Components NMC 0000 A Cable HPD/NZM
Used for synchronization in accordance with UL
1 NZM 0002 A Notification Appliance Zone Module
requirements, cable length 90 cm
2 Labelling strips Order number NMC 0000 A
2 3.9 kOhm resistors