EE206
EE206
ROPAR
DEPARTMENT OF ELECTRICAL ENGINEERING
ELECTRICAL MACHINES
LAB MANUAL
EEL206
1
PREFACE
2
SAFETY MEASURES
2. Always wear rubber sole shoes while working in the laboratory. Do not wear
slippers
4. While performing the experiment, get the circuit checked by a staff member
before you switch on the power supply
5. You will not be allowed to work alone in the laboratory. A minimum of two
students are required to conduct any experiment
6. Turn off all switches, clear all loose wires on your table before leaving the
laboratory
11. For extra time needed in case of incomplete work or exam preparation, take
time slots from laboratory coordinator
3
CONTENTS
Preface ……………………………. 2
4
EXPERIMENT NO.1
OBJECTIVE:
APPARATUS REQUIRED:
1. Voltmeters
2. Ammeters
3. Watt meters
5
4. Single phase variac
THEORY:
Parallel operation of transformers is used for load sharingand transformers are connected in
parallel on both primary and secondary side. The two transformers are connected in parallel meets
the need of common load
Satisfactory performance for parallel operation of two or more transformers require that they
have :
The currents carried by two transformers are proportional to their ratings if their numerical or
ohmic impedances are inversely proportional to those ratings , and thei per unit impedances are
equal. A difference in quality of per unit impedance(i.e. ratio of resistance to reactance) results
in divergence of phase angle of two currents ,so that one transformer will be working with a
higher and other with a lower power factor than that of the combined output
I = I1+ I2
𝒁𝟏 𝒁𝟐
S1 = 𝒁𝟏+𝒁𝟐 I and S1 =𝒁𝟏+𝒁𝟐 I
𝑾𝟏 𝑾𝟐
Cos Ø1 =𝑽𝟏𝑰𝟏and CosØ2 =𝑽𝟐𝑰𝟐
6
CIRCUIT DIAGRAM:
Figure - 1
7
PROCEDURE:
OBSERVATIONS:
Applied Voltage =
Frequency =
8
2. Short Circuit Test of two transformers
(W)
CALCULATION:
Calculation of Req,Xeq and Zeqfor both transformers as it was done in previous experiment
Calculation of power factor for both transformers under different load conditions .
9
RESULT:
Compare load distribution of both transformers (current ,active power and reactive power ) with
respect to series parameters of transformers
QUESTIONS
10
Experiment No.2: Scott Connection of Transformers
Motivation:
Sometimes two-phase electric equipment like an electric arc furnace or two-phase induction motors
used in servo applications might need a two phase supply whereas only a three-phase supply may be
available. This problem can be tackled by means of Scott connected transformer which converts a
balanced three-phase supply to a balanced two-phase supply. Such a connection can also supply a
single phase load by suitably connecting the secondary windings of the two phase system without
creating an imbalance in the three phase system.
Objectives:
To study the performance of the Scott connected transformers on no-load and full load.
kVA rating H.V Volts L.V. Volts ILoad (A) Winding type
Teaser
Transformer
Main
Transformer
Apparatus Required:
1. Voltmeters
2. Ammeters
11
4. Three phase variac
5. Resistive Loads
Theory:
With the help of a Scott connected transformer a three-phase system can be converted to a two-
phase one and vice-versa. For Scott connection two single phase transformers are needed. The
primary winding of one of the two single phase transformers should have a tapping at 50% (main
transformer) while the other should have a tapping of 86.6% in the primary (teaser transformer) as
shown in Fig.1. End B1 of the teaser transformer is connected to the mid-point M, i.e., 50% tapping
point of the main transformer. Now if a balanced three-phase supply is given to A, B and C, then the
voltages available across secondaries S1 and S2 will be equal magnitude and in phase quadrature.
Hence these two voltages will constitute a balanced two phase system.
Fig.1.
12
Fig.2.
The phasordiagram of the currents are shown above at unity power factor and at 0.707
power factor. It can be clearly seen that for a transformation ratio of 1:1 for the main and teaser
transformers, the per-phase current on the three-phase side will be 1.15 times the secondary
current.
Let equal currents I2 at unity p.f. be taken from the two secondary phases, Fig.2(a), and let
magnetizing current be neglected. There must, in each transformer, be an m.m.f. balance. In the
𝑁2
main transformer the primary balancing current is 2𝐼2 𝑁2 /√3𝑁1 = 1.15𝐼2 𝑁1
. The teaser primary
current is in phase with the star voltage AN. The total current in the main primary is the resultant of
𝑁2
two components: the first is 𝐼2 𝑁1
to balance the secondary current, the second is one-half of the
teaser primary current in either direction from S(and having a zero net m.m.f. in consequence). The
currents in lines B and C are shown in Fig. 2, taking 𝑁1 = 𝑁2 for clarity; their phasors, combining the
rectangular components 𝐼2 and 0.58𝐼2 , are co-phasal respectively with the star voltages NB and NC,
and are equal to the teaser primary current. Thus for a balanced 2-phase load of unity p.f. the 3-
phase side is balanced. Case (b) is for a balanced 2-phase load of p.f. 0.71. Again the 3-phase load is
balanced, and the main transformer loading is 15% greater than that of the teaser. Case (c) is for an
unbalanced load.
13
CIRCUIT DIAGRAM:
Fig.3.
Let V be the primary line to line voltage and N1, N2 be the no. of turns in the primary and secondary
𝑁
respectively, then the secondary voltage will be𝑉(𝑁2 ). The active number of turns in the main
1
√3
transformer’s primary N1 and the teaser transformer primary is 2
𝑁1 .
PROCEDURE:
14
4. Apply load on the transformers up to full load current. By loading the Transformers in steps
note down the VL, IL, W from multifunctional meter and Input wattmeter readings. Also, take
Input current reading on the 3-phase side. (it should be 1.15 times ILoad)
5. After taking the meter readings remove the load on the transformer.
6. Bring back the auto transformer to its minimum output position and switch off the 3- phase
supply.
OBSERVATIONS:
FORMULAS:
V1 =
I1 =
V2 =
I2 =
W1 =
15
W2 =
Input Power ( Pi ) = W1 + W2
MODEL GRAPH:
Fig.4.
GRAPHS:
RESULT:
Load Efficiency
¼ ________
½ ________
¾ ________
PRECAUTIONS:
16
Questions
17
EXP 3: TO STUDY THREE-PHASE TRANSFORMER
CONNECTIONS
Motivation:
The importance of three-phase system in generation, transmission and
distribution of power is well known. To transform the three-phase electric power from
one voltage to another, three-phase transformers are required both at the generating
and the distribution ends of a power system. It is therefore essential to learn about
the performance of three phase transformers connected in different possible
manners.
Objectives:
1. To connect the given three identical single-phase transformers in all the
possible three-phase connections.
2. To study the efficiency and voltage regulation of a star-star three-phase
transformer.
Theory:
Single-phase transformers can be connected to form 3-phase transformer
banks for 3-phase power systems. Four common methods of connecting three
transformers for 3-phase circuits are ∆-∆, Y-Y, Y-∆, and ∆-Y connections. An
advantage of ∆-∆ connection is that if one of the transformers fails or is removed
from the circuit the remaining two can operate in the open-∆ or V connection. This
way, the bank still delivers 3-phase currents and voltages in their correct phase
relationship. However, the capacity of the bank is reduced to 57.7 % (1/√3 ) of its
original value.
In the Y-Y connection, only 57.7% of the line voltage is applied to each
winding but full line current flows in each winding. The Y-Y connection is rarely used
because of difficulties with exciting-current phenomena.
The ∆-Y connection is used for stepping up voltages since the voltage is
increased by the transformer ratio multiplied by √3. The Y-∆ connection may be used
for stepping down voltages. The availability of neutral on high voltage side for
grounding is desirable in many cases. Instead of three single-phase transformers, a
three-phase bank may consist of one three-phase transformer having all six windings
on a common multi-legged core and contained in a single tank which has many
advantages like less cost, less weight, less floor space etc.
18
Figure: 3.1 Various 3-ϕ transformer connections
19
voltage C1 to C should equal zero. If not, the winding c must be reversed and open
ends can be joined after that to form the ∆-connection.
Note: the ∆-connection should never be closed until the test is first made to verify
that the voltage within the ∆ is zero. Otherwise, severe damage may occur!
Procedure:
1) Under no load conditions make ∆-Y, ∆-∆ and Y-Y connection one-by-one
and get it checked by the lab instructor
2) Make sure that the windings are connected in the proper phase relationships
3) Note down the Line Voltage (LV), Phase Voltage (PV), Line Current (LC), and
Phase Current (PC) on primary and on secondary sides in each case
4) Verify the relations between line and phase quantities in different connections.
(e.g. in star connection, LV = √3 PV and LC = PC)
20
R cc cc
M L M L
A A R’
com com
440 V pc pc
V V
50 Hz
3-φ
3-φ Y’
Y
AC Load
6) Calculate the efficiency and voltage regulation of the Y-Y connected 3-ϕ
transformer under different loading conditions.
Poutput
Efficiency = 100%
Pinput
V NL VL
Voltage Regulation = 100 %
VL
Observations:
Primary Secondary
Type of
S.No.
connection
Line Phase Line Phase
Voltage Voltage Voltage Voltage
1
21
Table 3.2: Load Test
Primary Secondary
S.No Type of Efficiency
connection %
WP LV PV LC PC WS LV PV LC PC
1
2
3
4
22
EXP 4: TO STUDY THE MAGNETIZATION AND LOAD
CHARACTERISTICS OF A SEPARATELY EXCITED DC
GENERATOR.
Motivation:
In-spite of the advantages of AC systems, DC machines continue to find use
in a wide range of industrial applications because of their flexibility and versatility.
The special features which determine the choice of a DC machine for a particular
application are the torque-speed characteristics of motors and the voltage-load
characteristics of generators. The knowledge of the limits within which these
characteristics can be varied and of the way in which such variations could be
obtained is important. Study of these features for a DC machine is accordingly the
motivation for this experiment.
Objectives:
1. To determine the Magnetization Characteristic of a separately excited DC
generator.
2. To determine the Load Characteristic of a separately excited DC generator.
Theory:
23
With the shunt generator the fall in terminal voltage with increase in load
current is more marked than with the separately excited generator because of the
decrease in field current accompanying the drop in terminal voltage. In series
generators, the flux varies widely with load because the load current is also the field
current. The terminal voltage-load current characteristic resembles the magnetization
curve but is somewhat' lower because of armature and series field resistance drops.
The causes of voltage decrease from no load to full load in a shunt generator may be
partially or completely compensated or over compensated by the augmentation of
the series field.
Circuit Diagram:
Procedure:
1. Make a list of the instruments required for the experiment, also note down the
full specifications of the given motor-generator set.
2. To determine the magnetization characteristic, make the circuit as shown in
Figure 4.1 and get it checked by the lab instructor. Do not connect the load on
the generator side.
3. To start the separately excited DC motor, first switch on the field supply of the
motor, and then gradually increase the armature voltage of the motor through
3-phase variac till the rated speed of the motor is achieved.
4. Now switch on the field supply of the generator.
5. Slowly increase Ifg from zero to rated value in steps, by varying Rfg. Note
down the corresponding Vag.
6. Record Vag vs. Ifg. This is the magnetization characteristic of the separately
excited DC generator at rated speed.
24
7. Now, decrease the Ifg from rated to zero value in steps, by varying Rfg. Again,
note down the corresponding Vag. Observe if the Vag-Ifg curve retraces the
same path & comment
8. Set the Ifg value equal to its rated value, and vary the speed of the motor by
varying the motor armature voltage through 3-phase variac
9. Increase the motor speed (N) from (say) 100 rpm to rated value, in steps and
note the corresponding Vag
10. Decrease the motor speed from rated to minimum, and note V ag
11. Record Vagvs. N for constant Ifg
12. For recording Load characteristic, connect the load bank and get the circuit
checked by the lab instructor
13. Start the motor at rated speed. Adjust Rfg such that rated field current flows in
the circuit
14. Keeping Ifgand speed constant (by adjustment of Vam or Ifm), take readings of
Vag, Iag, Vam, Iam, Ifm for different load values
15. Record Vagvs. Iag. This is called the load characteristic of the separately
excited DC generator
16. Measure armature and field winding resistances of generator appropriately
17. Plot the magnetization and load characteristics of the separately excited DC
generator
Observations:
25
Table 4.1 (b): O.C.C. of DC Generator
Rated Ifg=………..Amp
S.No. N Vag
1
2
:
8
Load current
S.No. Vag Vam Iam
(Iag)
1
2
:
8
S.No. V I R
1
2
3
4
26
EXP 5:SPEED CONTROL OF A SEPARATELY EXCITED DC
MOTOR
Motivation:
DC motors are in general much more adaptable to adjustable speed drives
than AC motors which are associated with a constant speed rotating field. Indeed
this susceptibility of DC motors to adjustment of their operating speed over wide
ranges and by a variety of methods is one of the important reasons for strong
competitive position of DC motors in modern industrial drives. It is thus necessary to
gather an idea about various speed-control methods along with their associated
characteristics.
Objectives:
1. To control the speed of a DC separately excited motor by varying the
armature terminal voltage.
2. To control the speed of a DC separately excited motor by varying the
resistance in the field.
Theory:
One of the unique features of a dc motor, which has helped it maintain its
supremacy over other electric drive systems for specific applications in industry, is its
ability to provide smooth, wide range speed control with relative ease. As we already
know, the basic equations governing the steady-state operation of a dc motor are
given by
Vt E I a Ra (5.1)
where, Vt is the terminal voltage and E, the induced back emf, is of the form
Zp
E N K
60 a (5.2)
where ‘N’ and ‘’ are the rotor speed in rpm and rad/sec, respectively and, the
constant ‘K’, is given by
27
Z p
K
2a
With no shaft load applied on the motor, the torque developed is only for
overcoming the rotational losses. Since the shunt motor operates at essentially a
constant flux, a small armature current, Ia, is only required as compared with the
rated current of the machine to meet the rotational losses. When a load torque is
applied to the motor shaft, the applied load torque causes the motor to assume that
value of speed, which yields an armature current Ia, sufficient to overcome the load
torque and the rotational losses. Hence, the relation between speed-torque is an
important characteristic of the DC motor.
Various schemes available for the speed control of DC motor can also be deduced
from equation (5.2). Vt and E, in equation (5.1) are of the same order, so that, on a
first degree of approximation, VE and thus
Vt K
This gives,
Vt
(5.3)
Expression (5.3) suggests that there can be two alternative strategies for achieving
speed control:
Let us consider the practical implications of the above alternatives. Equation (5.3)
shows that
(a) The speed (for a given torque supplied by the motor) changes linearly with
applied voltage. Since the torque developed by the motor is given by T = KIa, a
motor working with a constant field excitation and delivering a constant torque
will draw a constant current Ia whose value will be independent of the value of
the applied voltage V. This points to the fact that armature voltage control leads
to
Speed control without directly affecting the torque developed by the motor
28
(b) The speed of the motor will change in inverse proportion to the field flux or field
excitation. Also, in motors, working with constant armature voltage, controlling
of field flux will tend to change the torque developed by the motor at a given
value of armature current, thus suggesting that field control leads to
(c) Although DC machines are designed to operate with given maximum values of
armature voltage and field excitation, there exists a minimum permissible value
of field current, below which the armature current of the machine may attain
dangerously high values during normal operation
Speed
(rad/s) Load TL
0 P1
1 Motor TM
29
V1 V2 V3 V1 V2 V3
V1
V2 V1
V2
V3
V3
1 2 3
1 2 3
1
2 1
3 3 2
Torque (N-m) Torque (N-m)
30
Circuit Diagram:
Procedure:
1. Make a list of the instruments required to perform the experiment, and the
given machines, with full specifications
2. For carrying out the Armature Voltage Control of motor speed, make the
circuit as shown in Figure 5.5, and get the connections checked by the lab
instructor
3. Adjust Rfm to keep Ifm at fixed rated value
4. Through 3-phase variac, vary Vam from zero to rated value
5. Measure Iam and N at different Vam
6. To carry out Field Control, bringIfm at rated value
7. Bring Vam from zero to half of rated value (about 200 V) and keep it fixed
8. Slowly reduce Ifm in steps to increase speed N, using Rfm
9. Measure Iam and N at different Ifm
10. Plot the Vamvs N (Fixed Ifm) and Ifmvs N (Fixed Vam) characteristics
31
Observations:
..
..
32
EXP 6: Speed control of a 3-phase induction motor using
variable frequency drive. Torque-Speed characteristics under
constant and variable torque loads with fixed V/f
Objectives:
• Calculation of friction and windage losses using variable frequency drive at no load
• Torque speed characteristics (with constant value of V/f ratio & V, f variable) under
constant torque load
• Torque speed characteristics (with constant value of V/f ratio & V, f also fixed) under
variable torque load
Circuit Diagram:
Figure: 6.1
Theory:
The rotational speed of the induction motor can be controlled in a step-less way over a wide
range by changing the supply frequency.
V = E1 = 2π × k w1 × N ph1 × f × φ r 6.1
As per Eqn. (6. 1) the resultant air-gap flux per pole is given by
1 V
φr = ⋅ 6.2
4.44 × kw1 × N ph1 f
Therefore, in order to avoid saturation in stator and rotor cores which would cause
sharp increase in magnetization current, the flux ϕr must be kept constant as f is varied. To
achieve this, it follows from Eqn. 6.2, that when f is varied, V must also be varied such that
(V/ f) remains constant. Variable (V, f) supply from constant (V, f) supply can be arranged by
the frequency controller-inverter arrangement shown in Figure 6.1. The chief attraction of
employing induction motor for speed control is its ruggedness, low cost and maintenance-free
operation as compared to de motor. Because of the cost of the inverter involved in the
induction motor speed-control scheme, the DC motor scheme as of today is more economical.
However, the induction motor scheme is a strong candidate for speed control and is likely to
take over in the near future with further improvement and cost reduction in drive technology.
Procedure:
1. Note down the specification of the machine under test; make the connections as
shown in Figure: 6.1 and get it checked by the lab instructor.
2. Apply the required voltage and frequency to 3-phase induction motor for the three
cases mentioned in objective.
3. Record the applied voltage, frequency, no-load current, speed and I/P power coming
from W1 and W2 etc as required for each case. (Tables 6:1, 6:2, 6:3)
4. Calculate the friction and windage losses from first case (No load test).
5. Obtain Speed vs Input voltage curve for no-load and Speed vs Torque curves in the
other two cases.
Observation Tables:
Table 6.2: Constant Torque Load (Iag = 3 A fixed), V/f = 8.5 (fixed)
Objectives:
a) To perform open and short circuit tests on a synchronous generator and determine its
synchronous impedance (i) neglecting saturation and (ii) considering saturation.
b) To make an equivalent circuit of the generator using the synchronous impedance
values determined in (a) (for both (i) and (ii)).
c) To determine and draw the terminal voltage versus load current characteristics of the
generator for unity P.F load using the equivalent circuit determined in (b). Also to
determine voltage regulation of the generator for unity power factor load.
Theory:
Synchronous impedance 𝑍𝑠 can be determined by open and short circuit tests on the
generator. The generator is run at its rated speed. Open circuit characteristic (OCC) of
generator is the plot of its terminal voltage against its field current. This is also called the
magnetization characteristic of the machine. Short circuit characteristic (SCC) is the plot of
generator short circuit current versus its field current.
Where, AB is the short circuit current corresponding to the field current OA.
The generator impedance adjusted for saturation is
Note that the values as determined above are approximate because to consider exactly the
effect of armature reaction mmf, it is necessary to determine the orientation of armature
reaction mmf in the machine (the reactance of the magnetic path depends on the orientation
of the resultant mmf due to main field and armature reaction in machines with salient poles),
and magnitude of the mmf (since this decides the level of saturation in the magnetic circuit).
These are not accurately taken into account in the two ways mentioned for finding
synchronous impedance. Synchronous reactance is given by
where, 𝑅𝑎 is the effective resistance of the armature. 𝑅𝑎 can be measured for DC conditions
(using voltmeter-ammeter method) and the result multiplied by a factor of 1.6 to get a good
estimate of the effective value of the AC resistance. We can now write an equivalent circuit
for the generator in terms of a constant voltage behind the synchronous impedance. Voltage
regulation is defined as
�𝐸𝑝ℎ �−�𝑉𝑝ℎ �
𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝑟𝑒𝑔𝑢𝑙𝑎𝑡𝑖𝑜𝑛 = �𝐸𝑝ℎ �
7.4
where �𝐸𝑝ℎ � and �𝑉𝑝ℎ � denote, respectively, the phase values of no-load and full-load terminal
voltages (any one phase to neutral voltage), for constant field excitation, rated speed and with
�𝐸𝑝ℎ � = rated voltage of the machine.
Circuit Diagram:
Figure 7.2
Procedure:
1. Note the nameplate detail of the machines (generator and prime mover) for the
experiment and make the circuit as shown in Figure 7.2.
2. Keep generator output open circuited and connect a voltmeter between any one phase
and neutral.
3. Start the prime mover (DC motor) and bring the speed to rated value (1500 rpm) for
alternator. Keep the speed constant at this value during the experiment. Note down the
generator terminal voltage through the voltmeter and field current for rated value of.
4. Short any two phases of generator and connect an ammeter between remaining phase
and shorted phases as shown below.
5. Start the prime mover as usual and bring it to the rated speed of alternator. Keep the
speed constant at this value during the experiment.
6. Do not go beyond the full load current of alternator. Start with alternator field circuit
resistance in maximum position. Note down the appropriate meter readings including
generator phase current and field current.
Load Test at unity Power Factor
Objective:
Theory:
In power stations a number of alternators run in parallel. All the alternators are
synchronized with a common bus-bar. The load is connected across the bus-bar. In the
event of increased demand of load on a power station, additional generating sets are
required to be connected in parallel with the bus-bar. Before an alternator can be
connected in parallel with another alternator it should be synchronized.
Synchronization can be done by using a synchro-scope or by three-lamp method. The
following conditions are to be fulfilled before connecting an alternator in parallel with
others:
(a) The voltage of the incoming alternator should be the same as the running
alternator voltage.
(b) The frequency of voltage of the incoming alternator should be the same as the
running alternator voltage frequency.
(c) The phase sequence of the voltages of the incoming alternator to be connected in
parallel should be the same as that of the running alternator.
(d) At the instant when the synchronizing switch is closed, the voltages of the
incoming alternator should be in time-phase with the running alternator voltage.
In other words, there are five conditions that must be met before the synchronization
process takes place. The alternator must have equal line voltage, frequency, phase
sequence, phase angle and waveform to that of the system to which it is being
synchronized. Waveform and phase sequence are fixed by the construction of the
generator and its connections to the system, but voltage, frequency and phase angle
must be controlled each time a generator is to be connected to a grid.
Three light bulbs are connected between the three phases of generator and the grid.
Here two lamps are connected in series as the maximum voltage which will appear
across the lamps will be the line voltage, i.e., 400 V (for a 400 V machine). As lamps
are generally rated for 230 V, for safety reasons, two lamps are connected in series.
Procedure I:
2. Start the DC motor and bring its speed to the synchronous speed of the generator
(1500-rpm). Adjust the field excitation of the generator so that rated voltage (400V,
L-L) is obtained.
3. Switch on the AC mains and adjust the variac so that line voltage is 400 V. Let the
phase sequence of the generator terminals RYB be the same as that of the respective
terminals of the mains, RYB. The voltage phasors for this condition are shown in Fig
8.2. If the generator frequency is slightly more than that of the bus, then the phasors
R1, Y1 and B1 move anti-clockwise relative to R2, Y2, and B2. The voltages across
the lamps L1, L2, L3 (which are indicated by the phasors R1R2, Y1Y2, and B1B2)
will increase & decrease simultaneously and therefore, the three lamps will brighten
up and darken at the same time.
Figure 8.2
4. If the phase sequences are R1Y1B1 and R2 B2Y2, the phase diagram of voltages
will be as shown in Fig 8.3. For this condition the voltages across lamps given by
phasors R1R2, Y1Y2 and B1B2 are not equal to each other at the instant shown.
Therefore the lamps go through their zero voltage one after the other. The phase
sequences are thus different and can be corrected by interchanging any two terminals
either on the generator side or on the bus side. When such a change is made, both the
three-phase mains and the DC supply should be switched off.
Figure 8.3
5. With the phase sequence corrected, if there is a large difference between the
frequency of the generator and that of the bus, the lamps will brighten & darken in
quick succession. By adjusting the speed of the generator, this rapidity can be
reduced, which indicates that the frequencies are coming closer and the lamps will
brighten up & darken slowly. The correct moment of synchronization in this method
is when all the lamps are completely dark, at which time all the voltages of the bus
are exactly in phase with the corresponding voltages of the generator. At this
moment the synchronizing switch S is closed and the generator is synchronized with
the mains.
Procedure II:
1. For the alternator connected to infinite busbars and operating at unity p.f, it is then said to be
normally excited. Suppose that excitation of the alternator is increased (overexcited) while the power
input to the prime mover is unchanged. The active power output (W or kW) of the alternator will
thus remain unchanged i.e., active component of current is unaltered. The overexcited alternator will
supply lagging current (and hence lagging reactive power) to the infinite busbars (mains bus). This
action can be explained by the m.m.f. of armature reaction. When the alternator is overexcited, it
must deliver lagging current since lagging current produces an opposing m.m.f. to reduce the over-
excitation. Thus an overexcited alternator supplies lagging current in addition to the constant active
component of current. Therefore, an overexcited alternator will operate at lagging power factor.
Note that excitation does not control the active power but it controls power factor of the
current supplied by the alternator to the infinite busbars. Fig 8.4 shows the phasor diagram of an
overexcited alternator connected to infinite busbars. The angle δ between E (Stator voltage)
and V (Mains bus voltage) is called torque angle. It is also the angle between the
rotor and stator fields. Is is the stator current. The angle θ is the phase of Is with
respect to V, and hence the power factor is cos θ.
2. Now suppose that excitation of the alternator is decreased below normal excitation
(under-excitation) while the power input to the prime mover is unchanged. Therefore, the active
power output (W or kW) of the alternator will remain unchanged i.e., active component of current is
unaltered. The underexcited alternator supplies leading current (and hence leading reactive power) to
the infinite busbars. It is because when an alternator is under excited, it must deliver leading current
since leading current produces an aiding m.m.f. to increase the underexcitation. Thus an
underexcited alternator supplies leading current in addition to the constant active component of
current. Therefore, an underexcited alternator will operate at leading power factor. Fig 8.5 shows the
phasor diagram of an underexcited alternator connected to infinite busbars.
3. Dependence of power factor on prime mover field excitation is noted and the value
of If for unity p.f is found out.
Procedure III:
OBJECTIVE:
To perform no-load , blocked rotor and load tests on 1-phase induction motor (split phase and
capacitor start) and determine:
(a) The parameters for the equivalent circuit
(b) Compute the performance of motor from the parameters and compare with the experimental
results
THEORY:
1-phase induction motors are constructed much the same way as poly-phase induction motors
expect that their stators have 1-phase winding and the rotor is normally a squirrel cage rotor. The
poly-phase motors are self-starting, while 1-phase motors are not, since its torque when at rest is
zero. In order to start 1-phase induction motor some means are required. The various types of 1-
phase induction motors are: split phase, capacitor motor (capacitors start and capacitor run motor),
shaded pole and repulsion start. There are two theories for the analysis of 1-phase induction motor,
i.e.
(1) Cross field theory
(2) Revolving field theory
Based upon revolving phase theory, the equivalent circuit of a 1-phase induction motor with only
main winding effective is shown in figure 9.1 where
In blocked rotor test, a reduced voltage is applied to main winding only, such that a full required
current is flowing in the main winding. The reduced voltage applied Es , the rated input current ls and
the input power Ps are recorded. At rotor standstill, s is unity and the equivalent circuit takes the
form shown in Fig 9.3 below.
Just after the blocked rotor test, D.C resistance of main winding R1dc is measured to get the value at
operating temperature.
The total no-load power input is used up as stator copper loss, 𝐼𝑜2 𝑅1 , backward field resistance
copper loss 𝐼𝑜2 𝑅2𝑏 ⁄2, forward field excitation (iron) loss and backward field excitation loss. Under
no-load conditions, the magnitude of the backward rotating field is very small, and therefore the
backward iron loss may be neglected.
Voltage across the forward exciting circuit = 𝑉𝑓 = 𝐸𝑜 − 𝐼𝑜 {𝑅1 + 𝑗𝑋1 + 𝑗𝑋2𝑏 + (𝑅2𝑏 ⁄2)}
Also, 𝐵𝑏 = 𝐵𝑓 , 𝐺𝑏 = 𝐺𝑓 . Thus, all the parameters of the equivalent circuit pertaining to running
condition (no-load) are known.
If Zsc is equivalent impedance of the machine during blocked rotor test, 𝑍𝑠𝑐 = 𝐸𝑠 ⁄𝐼𝑠
Also if,
Then,
𝑅𝑠𝑐 = 𝑃𝑠 ⁄𝐼𝑠2
From these relationships, Rsc and Xsc may be obtained. As the blocked rotor test is performed at
reduced voltage, the exciting current and core loss during this test are very small and may be
neglected. In terms of equivalent circuit, this assumption means that the excitation branch
admittance is zero. Further, at s=1, frequency of the currents on the account of both the forward
field and the backward field are same. Under this condition, therefore, 𝑅2𝑓 = 𝑅2𝑏 = 𝑅2𝑐 (say), the
equivalent circuit of Fig 9.3 then takes the form shown in Fig 9.5 below.
If X2 is total rotor reactance (= X2f + X2b) then Xl + X2 = Xsc. It is not possible to separate Xl and X2 , but
it is customary to consider Xl = X2 = Xsc/2. Under blocked rotor condition, it is easy to visualize that
X2f = X2b, hence,
𝑋2𝑓 = 𝑋2𝑏 = 𝑋2 ⁄2
The effective value of main winding resistance at line frequency is usually 1.1 to 1.3 times the dc
value, the actual ratio depending upon conductor configuration etc.
Thus,
𝑅1 = (1.1 𝑡𝑜 1.3)𝑅1𝑑𝑐
𝑅𝑠𝑐 = 𝑅1 + 2𝑅2𝑐
Where
Under normal running conditions, the forward field-slip is small, and therefore the rotor resistance
for this field will be very nearly dc resistance, i.e. R2c divided by a suitable factor to reduce it to its dc
value. The factor has a value in the range 1.2 to 1.4 (say 1.3). Therefore,
With respect to the backward field, the frequency of the rotor currents under running conditions is
approximately twice the line frequency. Effective rotor resistance with respect to the backward field
at this high frequency is generally 1.6 to 1.8 times R2dc. Therefore, R2b = (1.6 to 1.8) say R2b = 1.7R2dc.
Thus from known values of R1, blocked-rotor-data and suitable choice of factors for converting
effective resistance into dc resistance and vice versa, R2f , R2b , X2f , X2b and X1 are obtained.
The equivalent circuit derived in this experiment is based on number of approximations. R2f and
R2b are the effective values of the resistances which change with slips. However for the normal range
of running speeds (s = 1-5%). These effective values may be assumed to remain constant. The
leakage reactance is assumed to be equally divided between rotor and stator whereas actually it
may not be so. The factors for convening effective values of resistance into dc values and vice versa
are arbitrary and cannot be determined. By far the most important assumption is that the friction
and windage losses (Fig 9.7), which are mechanical, are combined with the other losses in calculating
the loss conductance’s, Gf and Gb. For more accurate analysis, friction, and windage loss should be
subtracted from the mechanical power developed, and should not be included along with excitation
losses.
Load Test:
8. Now connect the DC generator as shown in Fig 9.8 above
9. Apply rated voltage to the motor and run the generator under no–load condition with its
field resistance in maximum position
10. Note down the readings of input AC power, input AC current, output DC voltage, output DC
current and speed of the motor
11. Now increase the load in steps up to which rated current flows in the induction motor. Note
down all the meter readings
Applied voltage:______ V
DC-Generator current DC-Generator
Input AC power Input AC current Speed
(Iag) voltage (Vag)
Results and Discussions:
1. (a) Plot no-load power input as function of applied voltage in case of no-load test and obtain
from there the no load current, lo and power input Po corresponding to rated voltage.
(b) Extrapolate the curve of Po upto zero applied voltage to obtain the friction and windage
loss as shown in Fig 9.7
2. Complete the parameters of the equivalent circuit
3. From the equivalent circuit, compute input current, input power, efficiency, torque when
the motor is running from rated voltage with slip of 5% and therefore compare its
performance with practical values from load test
4. From load test data plot Torque vs slip characteristics for different voltage levels
EXP 10: No-load, blocked rotor tests on 3-phase squirrel cage
induction motor and write its equivalent circuit referred to
the stator.
Objective:
To perform no load, blocked rotor and load test on a 3- phase, squirrel cage, induction motor
and write its equivalent circuit referred to the stator.
Circuit Diagram:
Figure 10.1
Procedure:
1. Write down the motor nameplate details and make circuit as shown in Fig 10.1.
2. Conduct a no-load test at the rated voltage and note down the line current and input
power to the motor. Use the appropriate range of meters. Start with variac in zero
position.
3. Conduct a blocked rotor test by a blocking the rotor from rotating. Use the same
circuit as in Fig 10.1 with meters changed to appropriate ones. Before switching on,
make sure that the variac is in zero position.
4. Measure the dc resistance of the stator (value of dc resistance ≈ 3.85 Ω/phase).
5. Gradually change the variac position to obtain rated current input to motor. Note
down the line voltage and input power to the motor.
Observation Table:
Motor Motor N
Sl No W1 W2 Vag Iag
Voltage Current (rpm)
1
2
:
:
8