User Manual: Electronic Control and Protection System CET 4
User Manual: Electronic Control and Protection System CET 4
and Protection
System CET 4 User Manual
User Information
Important User Because of the variety of uses for the products described
Information in this publication, those responsible for the application
and use of this control equipment must satisfy themselves
that all necessary steps have been taken to assure that each
application and use meets all performance and safety
requirements, including any applicable laws, regulations,
codes and standards.
!
or circumstances that can lead to personal injury
or death, property damage or economic loss.
!
equipment!
2. In accordance with the applicable rules, work on
electrical equipment or means of production may only
be carried out by competent electricians or suitably
trained persons guided and supervised by a competent
electrician.
3. The electrical equipment of a machine / plant must be
inspected / tested. Deficiencies such as loose
connections or scorched cables must be eliminated
immediately.
!
features supervision and protection functions which
can switch the devices of automatically and thereby
bring motors to standstill. Motors can be brought to
standstill also by mechanical blockage. Furthermore,
mains failures and voltage fluctuations can also cause
switching off.
5. In case of fuctional disturbances the machine / plant
must be switched off and protected immediately! The
elimination of disturbances must be organized without
delay!
6. The elimination of a disturbance may cause the motor
to start running again by itself. This may endanger
persons or damage equipment. The user is obliged to
take the necessary safety measures against this type of
occurrence so that any danger is precluded.
7. Sufficient safety distance to the CET 4 must be
maintained where wireless equipment (walkie-talkies,
cordless and mobile phones) is used.
Section Page
Why Have an Electronic Control and Protection System? . . . . 1-1
Operational Demands of the Motor/Drive . . . . . . . . . . . . . . . . . 1-2
Temperature Rise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Motor Operating Characteristics . . . . . . . . . . . . . . . . . . . . . . . 1-2
Current and Temperature Curves . . . . . . . . . . . . . . . . . . . . . . 1-3
Limiting Temperatures, Insulation Classes . . . . . . . . . . . . . . . 1-5
Insulation Aging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Rotor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Operational Requirements for the Installation . . . . . . . . . . . . . 1-6
Personnel Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
CET 4 as an Automation Component . . . . . . . . . . . . . . . . . . . . 1-7
1.5 P Power
I Pv
⎯
25 50 75 100 125
P
⎯ [%]
Pe
Operating characteristics of an AC motor as a function of load. Between no load and half load, the losses increase
only slightly with rising load. Between half load and rated load, the change in efficiency is minimal, and the power
factor approaches its maximum. The losses increase approximately proportional to the load. Above rated load, the
losses increase more rapidly than the load.
Figure 1.3
IA Starting current I
tA Starting time
Ie Rated service current
1.6 2 IA
2 2 Ie
t Time
2 2 IA
tA
Temperature rise in a motor winding. During the starting time (tA), the
temperature of the winding rises very rapidly; at the end of start-up,
the temperature drops temporarily because heat is transferred to the
laminated core.
EM EM Average motor
%
100 life
ϑG Temperature
70 limit of the
insulation
50
25
0 ϑG
+5K +10K +15K +20K
1.6 CET 4 as an The CET 4 electronic control and protection system detects
Automation abnormal operating condition and faults in a motor branch
circuit. The data made available by the CET 4 can be used
Component for operational control and optimization of the installation.
Section Page
System Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Modular Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Operating Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Ambient Condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Nominal Rated Voltages Ue . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Electrical Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Main Current Transformers (CTs) for the Motor Circuit . . . . . . 2-9
Core Balance Current Transformer (CT) . . . . . . . . . . . . . . . . . 2-10
Recommended Data for Core Balance Current Transformer 2-10
Short-circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Choosing a circuit breaker or fuse and associated contactor . 2-10
Reaction to Failure of the Supply Voltage . . . . . . . . . . . . . . . 2-11
Failure of Supply Voltage > 30 ms . . . . . . . . . . . . . . . . . . . 2-11
Recovery of the Supply Voltage . . . . . . . . . . . . . . . . . . . . . 2-11
Automatic Recognition of Converter Module . . . . . . . . . . . . . 2-12
The CET 4 regularly checks . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
2.2.2 Installation
The CET 4 can be either flush mounted in an enclosure
door, or surface mounted to the enclosure mounting plate
using a panel mounting frame.
Current converter modules, CWE 4, can be surface
mounted.
Option:
CLV 4 for low-voltage motors
CMV 4 for medium
high-voltage motors
Communication
Communication
Network
A1 (-) -
Supply Operation LCD
A2 (+) +
Y11 Warning/Trip
Y12 Emergency start
Y13 Disable settings CET4
95/96
Controller Main relay MR
CWE 4 97/98
Figure 2.2 Block Diagram
Y21
Remote reset Basic function 13/14 Alarm relay AL
Y22
CET 4
M Y31
3~ 24 VAC/DC #1 Control
Y32
Y41 inputs
24 VAC/DC #2
Y42
ϑ amb
F Phase
L1 L1
sequence 53/54 Auxiliary relay #4
L2 L2 CLV4
Chapter 2 Description of the Equipment
Choice
Publication 825-5.025.610.910-02
CMV
1T1/1T2/1T3 PT 100 #1…#6 CMV4
Stator /
…6T1/6T2/6T3 (RTD)
bearing temperature
7T1/7T2/7T3 PT 100 #7 PC
Ambient temperatur
(RTD)
Network
Communication Interface
Chapter 2 Description of the Equipment
2.3 Operating Elements The CET 4 electronic motor protection system is very easy
to operate. With six membrane keys and the LCD, all
functions, data, and tests can be entered, executed, or
displayed. On the single-line LCD, all available data and
functions are displayed.
➌ ➍
➎ ➏
➐
CWE 4-180
CWE
Primary Detection Circuit CWE 4-20 CWE 4-630
4-2.5
CWE 4-630N
Motor Circuit
as per IEC, SEV, VDE 0660 400 VAC 660 VAC 1 000 VAC
as per CSA, UL 240 VAC 600 VAC 600 VAC
Control Circuit
Main relay (MR) 95. . .98, supply A1, A2
Phase sequence protection L1, L2, L3
as per IEC 947 400 VAC
as per SEV 380 VAC
as per UL, CSA 240 VAC
Alarm relay (AL) 13/14
Auxiliary relay #1, #4, #5
as per IEC 947 400 VAC
as per SEV 250 VAC
as per UL, CSA 240 VAC
Auxiliary relays #2, #3 50 VAC / 30 VDC
Control inputs #1, #2 24 VAC/DC
2.4.4 Standards
EMC
Noise emission as per EN 50 081-1 and as per EN 50 081-2
Noiseproof as per EN 50 082-1 and as per EN 50 082-2
Standards
IEC 947-4, CSA C22.2 No.14, UL 508
Approvals
CE, UL-Listed, CSA,
PTB: Physikalisch-Technische Bundesanstalt (Germany). Testing insti-
tute. Certfication requiered for motor protection in explosion hazard
areal (e.g. Chemikal-, Petrochemical-Installations).
2.4.5 Supply
50/60 Hz, 22 ... 24, 33 ... 36, 44 ... 48
Nominal supply 110 ... 120, 220 ... 240,
voltage Us 380 ... 415, 440 VAC
24 ... 48, 72 ... 120 VDC
Permissible voltage AC 0.85 ... 1.1 US
fluctuation DC 0.80 ... 1.1 US
Power consumption AC 13 VA, DC 10 W max.
With the appropriate supply cable rating,
Short-circuit protection
the supply module is short-circuit proof.
Range of gauges:
CET 4 plug-in
0.5 ... 2.5 mm2, single wire (AWG No. 20...14)
terminals
0.5... 1.5 mm2, double wire (AWG No. 20...16)
as per UL AWG No. 22 ... 14
as per VDE nominal gauge 1.5 mm2
Main circuit
Terminals: 2 x 2.5 mm2/1 x 4 mm2
CWE 4-2.5 /
CWE 4-20 (2 x .0039 in2 / 1 x .006 in2)
2 x AWG No. 20 ... 14 /1 x AWG No. 20 ... 12
Aperture or busbars:
CWE 4-180
Wire ∅ 19 mm max. 20/16 x 4 mm
CWE 4-630(N) Bus bars: 25 x 8 mm
The rating of the fuse or contactor must also allow for the
prospective short-circuit current. The CWE 4 converter
modules are short-circuit proof.
Section Page
Menu Overview, Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Menu Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
ACTUAL VALUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
SET VALUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
RECORDED VALUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Selecting the Setting / Display Mode . . . . . . . . . . . . . . . . . . 3-5
Setting the Operation Parameters (Set Values) . . . . . . . . . . . 3-6
Indications of Recorded Values (Statistics) . . . . . . . . . . . . . . 3-9
Test Button <Test> . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Function Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
Protective Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
Warning Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Control Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Functions of the Basic Unit CET 4 . . . . . . . . . . . . . . . . . . . . . . 3-15
Thermal Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
Adjustable Ratio of Cooling Constants . . . . . . . . . . . . . . . . . . 3-17
Indication of the Time to Tripping . . . . . . . . . . . . . . . . . . . . . 3-17
Indication of the Time until the Thermal Trip can be Reset . . 3-17
Adjustable Setting Characteristic . . . . . . . . . . . . . . . . . . . . . 3-17
Protection Against Thermal Overload . . . . . . . . . . . . . . . . . . 3-19
Asymmetry (Phase Unbalance) and Phase Failure . . . . . . . . . 3-20
High Overload and Jam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
Underload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-23
Earth (Ground) Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-25
Earth (Ground) Fault Protection by the Holmgreen Method
= Residual Method (Solidly Earthed Networks) . . . . . . . . . 3-25
Earth (Ground) Fault Protection with a Core Balance c.t. . . . 3-26
Earth (Ground) Fault Protection in High-voltage Systems . . 3-28
Isolated or High-impedance Earth Networks . . . . . . . . . . . 3-29
Neutralized Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-30
Schematic Representation of Various Network Configurations and
Earth (Ground) Fault Locations . . . . . . . . . . . . . . . . . . . . . . 3-30
Limiting the Number of Starts per Hour (Start Lockout) . . . . . 3-33
Monitoring the Starting Time . . . . . . . . . . . . . . . . . . . . . . . . 3-34
Warm Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-35
Emergency Override of Thermal Trip (Emergency Start) . . . . 3-38
LED Alarm and Trip Indicator . . . . . . . . . . . . . . . . . . . . . . . . 3-39
Connection of the Main Relay (MR) . . . . . . . . . . . . . . . . . . . . 3-39
Connection of the Alarm Relay (AL) . . . . . . . . . . . . . . . . . . . . 3-40
Alarm Relay AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-40
Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-41
Function of the CST 4 Option Card . . . . . . . . . . . . . . . . . . . . . 3-41
Short-circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-41
Earth (Ground) Fault Protection with a Core Balance c.t. . . . . 3-43
Stalling During Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-43
Thermistor Input PTC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-45
Rockwell Automation Publication 25.610.910-02 EN 3-1
Chapter 3 Functions
Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-46
Analog Output for Thermal Load or
Motor Temperature (PT100 max.) . . . . . . . . . . . . . . . . . . . . . 3-46
Analog Output for Motor Current . . . . . . . . . . . . . . . . . . . . . . 3-48
Control Inputs #1 and #2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-48
Switching to a Second Rated Current . . . . . . . . . . . . . . . . . . 3-50
Functions of CLV 4 Option Card . . . . . . . . . . . . . . . . . . . . . . . 3-51
Phase Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-51
Phase Failure (based Voltage Measurement) . . . . . . . . . . . . . 3-52
Star-Delta (Wye-Delta) Starting . . . . . . . . . . . . . . . . . . . . . . . 3-52
Functions of CMV 4 Option Card . . . . . . . . . . . . . . . . . . . . . . 3-53
Temperature Sensor PT100, #1 ... #6 (RTD) . . . . . . . . . . . . . 3-53
Temperature Sensor PT100, #7 (RTD) . . . . . . . . . . . . . . . . . 3-54
ATTENTION: All parameters can be set,including functions of option boards that are not
! mounted therefore. These warning- and trip functions are not operational!
SET
Actual
Change mode by
pressing Set
Recorded
Values
SET VALUES
Actual Change
Set
Recorded Enter
35 AMP
FULL LOAD CURR
Actual Change
Set
Recorded Enter
35 AMP
Actual Change
Set
Recorded Enter
Display Example
LCD Range Description
ACTUAL VALUES
Actual Change
Set
Recorded Enter
I MOTOR 00 %IE
Actual Change
Set
Recorded Enter
Display Example
LCD Range Description
0.00 …
I MOTOR ... A 49.99
Motor current in A
50 …
24 000
•
• –
•
For a complete list of parameters, see Chapter 6.
RECORDED VALUES
Actual Change
Set
Recorded Enter
2 h 28 min
SINCLE LAST TRIP
Actual Change
Set
Recorded Enter
•
•
•
Applications
The Recorded Values mode provides:
• Analysis of motor faults and production interruptions
• Analysis of premature motor failures
• A means of determining maintenance jobs on
switchgear, motor, and the installation
CET 4
Change
Test
Enter
Settings Reset
Resetting
Automatic: The trip becomes inactive when the Test
button is no longer pressed.
Example: Asymmetry
1. When in the Set Values mode, access the selected
output relay:
LCD:
ASYMMETRY TRIP
AUX RELAY #2
4. After the set trip delay expires, the CET 4 must trip.
LCD: :
AS TRIP TIME
_ _ _sec
Resetting
Cancel the trip by pressing Reset.
Resetting
As soon as the Test button is no longer pressed.
Functions Tripping
Setting Factory Factory Relays ➌ Factory
Factory Delay
Range Setting Setting Selection Setting
Setting Range
CET 4 Basic Unit
Thermal overload On – – – – MR MR
Asymmetry
On 5 ... 80 % 35 % 0.5...25 sec. 2.5 sec. All MR
(phase failure)
High overloading/Jam On 1 ... 6 Ie 2.4 Ie 0.1 ... 5 sec. 0.5 sec. All MR
Underload Off 25 ... 100 % 75 % 1 ... 60 sec. 10 sec. All MR
Underload delayed enable On – – 0 ... 240 sec. 0 sec. –
Earth (ground) fault (Holmgreen) On 10 ... 100 % 50% 0.1 ... 5 sec. 0.5 sec. All MR
Starting time monitor Off – – 1 ... 240 sec. 10 sec. All MR
Limited starts per hour Off 1 ... 10 2 – – All MR
CST 4
Short-circuit Off 4 ... 12 Ie 10 Ie 20... 990 ms 50 ms #1 #1
Earth (ground) fault
Off 5 mA ... 50 A 1A 0.1 .... 5 sec. 0.5 sec. All MR
(core balance c.t.)
Stalling during start ➊ Off – – – – All ➊ MR ➊
Thermistor input (PTC) Off – – – 800 ms All MR
CLV 4
Phase sequence
Off – – – 1 sec. All MR
(motor supply)
Phase failure (motor supply) Off – – – 2 sec. All MR
CMV 4
PT100 input #1 ... #6 (RTD) MR, AL
Off 50 ... 200 °C 50 °C – <8 sec. MR
(stator, bearings) #1 ... 3
PT100 input #7 (RTD) ➋ Off – – – – – –
➊ Via external speedometer (control input #1), output relay as for high overload.
➋ Allowing for the ambient temperature in the thermal image.
➌ Only one relay per function can be selected: MR = Main relay, AL = Alarm relay, Auxiliary relay #1 ... #5.
!
such that associated alarms are actuated before a
trip occurs.
Functions Tripping
Setting Factory Factory Relays ➊ Factory
Factory Delay
Range Setting Setting Selection Setting
Setting Range
CET 4 Basic Unit
Thermal utilization (%Δϑ
Off 50 ... 99 % 75 % – – AL, #1 ... 5 AL
load)
Asymmetry (% Ie) Off 5 ... 80 % 20 % – – AL, #1 ... 5 AL
High overloading (x Ie) Off 1 ... 6 Ie 2 Ie – – AL, #1 ... 5 AL
Underload Off 25 ... 100 % 75 % – – AL, #1 ... 5 AL
CST 4
Earth (ground) fault
Off 5 mA ... 50 A 500 mA – – AL, #1 ... 5 AL
(core balance c.t.)
CMV 4
PT100 input #1 ... #6 (RTD)
Off 50 ... 200 °C 50 °C – – AL, #1 ... 5 AL
(stator, bearings)
➊ Only one relay per function can be selected: MR = Main relay, AL = Alarm relay, Auxiliary relay #1 ... #5.
Functions Tripping
Setting Factory Factory Relays ➊ Factory
Factory Delay
Range Setting Setting Selection Setting
Setting Range
CET 4 Basic Unit
Warm start (% of "cold" trip) Off 50...100 % 70 % 4...60 min 60 min – –
Emergency override of
Off Jumper term. Y11-Y12 – – – –
thermal trip
CST 4
Analog output assigned to: 4 ... 20 mA
- thermal utilization 0 ... 100 %
On – – – – –
- PT100 max. temperature 50 ... 200 °C
- I Motor 0... 200 % Ie
CST 4, Control Input #1: (24 VAC/DC; 8 mA)
One of three functions can be
selected:
1) Pickup delay, relay #2 Off – – 0...240 sec. 1 sec. – #2
1) Dropout delay, relay #2 – – – 0...240 sec. 2 sec. – #2
high over-
2) Speed switch Off – – – – –
load relay
PCu PFe
≈ (IM2 + kIG2)
R1
C1 S1
C2
R2 R3
ϑ amb
Setting Parameters
Rated Current Detection Module ➋
CWE 4-2.5 CWE 4-20 CWE 4-180 CWE 4-630 CWE 4-630N
0.5 ... 2.5 A 2.5 ... 20 A
160 ... 630 A
Setting Range (2 000 A) (2 000 A) 20 ... 180 A 160 ... 630 A
➌
➊ ➊
Factory Setting 20 A 20 A 20 A 20 A 20 A
Setting
0.01 ... 2 A 0.1 ... 2 A 1A 2A 2A
Increments
➊ Up to 2 000 A, if primary CT‘s are used.
➋ -5 to 60 °C (23 to 140 °F)
➌ UL / CSA 160 ... 434 A
Warning Trip
Response Level ➋
Setting Range 55 ... 99 % –
Factory Setting 75 % 100 %
Setting Increments 1%
Output Relay
Selection AL, #1 ... #5 –
Factory Setting AL MR
Function
Factory Setting Off On
➋ Thermal utilization %
fR fR Reduction
1.0
factor for motor
output
0.9 ΔU Voltage
asymmetry in
0.8
percent
ΔU
0.7
0 1 2 3 4 5 [%]
Application
• Conveying systems
• Mills
• Mixers
• Crushers
• Saws, etc.
I
Ie
≥ 1.2
1
2.4
2
1.1
t
tv
4 5
Setting Parameters
Warning ➊ Trip ➊
Response Level
Setting Range 1 ... 6 Ie 1 ... 6 Ie
Factory Setting 2 Ie 2.4 Ie
Setting Increments 0.2 Ie 0.2 Ie
Tripping Delay
Setting Range – 1 ... 5 sec. ±0.04 sec.
Factory Setting – 0.5 sec. ±0.04 sec.
Setting Increments – 0.1 sec.
Output Relay
Selection (Relays) AL, #1 ... #5 MR, AL, #1 ... #5
Factory Setting AL MR
Function
Factory Setting Off On
➊-5 to 60 °C (23 to 140 °F)
Application
• Submersible pumps
• Fans
• Conveyor systems
• Detection of features in mechanical transmission
system
I
Ie
1
2
Ie
IT
3 3
t
tA tp tv
ts tp
Setting Parameters
Warning ➊ Trip ➊
Response Level
Setting Range ➋ 25 ... 100 % Ie
Factory Setting ➋ 75 %
Setting Increments ➋ 5%
Tripping Delay
Setting Range – 1 ... 60 sec. -0.2 sec./ +0.4 sec.
Factory Setting – 10 sec.
Setting Increments – 1 sec.
Delayed Activation of Underload Protection
Setting Range – 1 ... 240 sec. +0.4 sec./ +0.8 s
Factory Setting – 0 sec.
Setting Increments – 1 sec.
Output Relay
Selection (Relays) AL, #1 ... #5 MR, AL, #1 ... #5
Factory Setting AL MR
Function
Factory Setting Off On
➊ -5 to 60 °C (23 to 140 °F)
➋ For warning, the set Response Level is that for tripping.
L1 L2 L3
1 2
3 4
5 6
P1 S1 P1 S1 P1 S1
CWE 4 CET 4
P2 S2 P2 S2 P2 S2
I0
M1 3~
Setting Parameters
Trip ➊
Response Level
Setting Range 10 ... 100 %
Factory Setting 50 %
Setting Increments 10 %
Tripping Delay
Setting Range 0.1 ... 5 sec. ±0.2 sec.
Factory Setting 0.5 sec. ±0.2 sec.
Setting Increments 0.1 sec.
Output Relay
Selection (Relays) MR, AL, #1 ... #5
Factory Setting MR
Function
Factory Setting On
➊ -5 to 60 °C (23 to 140 °F)
Figure 3.13
Example of two-phase current detection and core balance c.t. for
sensitive earth (ground) fault protection (three-phase current detection
is also possible)
L1 L2 L3
1 2
5 6
P1 S1 P1 S1
CWE 4 CET 4
P2 S2 P2 S2
3 4
S1
·
S2
M1 3~
Application
• High-voltage motors
• Installations in a difficult environment, with moisture,
dust, etc. (e.g., mines, gravel pits, cement factory,
mills, woodworking shops, water pumping stations,
waste water treatment)
Setting Parameters
Core Balance c.t.
Current ratio
Setting Range 1 ... 2 000
Factory Setting 100
Setting steps 1
M1 3 AC
T CET 4
1 K1
U2 U1
2
3
U3
CN IE CM
M1 3 AC
T CET 4
1 K1
U2 U1
2
3
U3
L R CN IE CM
M1 3 AC
T CET 4
1 K1
U2 U1
2
3
U3
CN IE CM
M1 3 AC
T CET 4
1 K1
U2 U1
2
3
U3
L R CN IE CM
M1 3 AC
T CET 4
1 K1 U2 U1
2
3
IE
CN CM U3
Function
When the set number of starts is reached and the motor is
switched off, a new start is prevented. Depending on its
setting, either the main relay changes to "Fault," or the
selected auxiliary is activated.
As soon as a new start is permissible, the start lockout is
automatically reset.
I
I
Ie
Ie
I II
t
tw 60 min.
I First start
II Second start
tw The selected relay (MR, or #1... #5) remains in the tripped
position until 60 min. have expired. If an additional start is
allowed, the number of starts can be increased by one.
Setting Parameters
Setting Limited Number of Starts
Setting Range 1 ... 10 starts/hour
Factory Setting 2 starts/hour
Setting Increments 1
Output Relay
Selection (Relays) MR, AL, #1 ... #5
Factory Setting MR
Function
Factory Setting Off
Function
The starting time of the motor is monitored. If starting has
not finished by the set time, the installation can be switched
off.
This monitoring is independent of the thermal state of the
motor.
The beginning of a start is recognized by the CET 4, as
such when the motor current reaches 1.2 Ie. Starting is
deemed to have been completed when the motor current is
less than 1.1 Ie.
Applications
• Installations in which an elevated load or stalling of
the drive have to be detected during the starting stage,
in order to avoid serious damage. Possible causes:
overloaded installation, defective bearings, or
transmission elements.
≥1.2 Ie 1
3
2
≤1.1 Ie
tv
Function
The motor windings may be heated for a short time above
the permissible temperature limit. This applies
particularly to rotor-critical motors. The temperature that
is permitted for this short period is approximately 250 °C
and is thus appreciably higher than the continuous
operating temperature of 100 ... 150 °C. This means that
a motor warm from running has a relatively long
permissible starting time. This property of the motor can
be utilized with the CET 4. The CET 4 is factory-set for
one warm start per hour. The tripping time is then 70 %
of that from cold. The function warm start is switched off
in the factory. As additional protection for the motor, too
many warm starts can be prevented by the function
"limiting the number of starts per hour."
I
IA
1 2 3 4
Ie
t
ϑ
ϑ1
ϑe
t
t1 tw tw
tw
!
tions must be complied with, especially regarding
the minimum wait between two starts
Applications
The Warm Start function can be used in any installation
that may have to be re-started immediately after a voltage
interruption.
• Chemical process and production plants (e.g., mixers,
centrifuges, pumps, conveyor systems)
Setting Parameters
Figure 3.23 Multiple of the Set Current Ie (= Ib)
10
4
a Time/current characteristic from
cold when setting the tripping
time t6xIe = 30 sec.
3
10
b Time/current characteristic from
cold on the normal
10
4
f Time/current characteristic
after preloading with Ie when
tripping t6xIe is set to 10 sec.
Release Time (s)
3
10
g Time/current for warm start
when restarting after uninter-
10
2
b
rupted operation and 35 ...
g 100 % temperature rise
f
30
20
Tripping time "warm“ = 70 %
10 of tripping time "cold“.
6
4
2
1
1 2 3 4 6 8 10 • Ie
Suggested Procedure
Procedure when PT100 and PTC are not used:
1. Momentarily bridge terminals Y11-Y12 (voltage free
contact). A spring return key switch is recommended.
2. LCD flashes "EMERGENCY START."
3. If the thermal release has tripped, it can now be reset.
4. If the maximum number of starts per hour has been
reached, the counter has one start deducted.
5. Start the motor.
6. As soon as the motor starts, the stator winding memory
will be set to zero (copper losses only).
.
SET VALUES
PTC TRIP
OFF
Non-Fail-Safe Mode
Supply Off Supply On Supply On and Trip
Non-Fail-Safe Mode
Supply Off Supply On Supply On and
Warning
Examples
Warning Factory Setting
Thermal Utilization 75 %
Asymmetry 20 %
High Overload 2 Ie
Underload 75 %
All these functions Off
Kinds of Reset
• Manual reset - Press the reset button on the CET 4 for
at least 200 ms
• Remote reset - Short circuit terminals Y2l/Y22
• Automatic reset - In the mode "set values," set
automatic reset for:
-Thermal trip
-PTC trip
-PT100 trip
Reset Conditions
• Thermal - As soon as the temperature rise has dropped
to the preset reset threshold.
• PTC detector - As soon as the temperature is below
the reset threshold
• PT100 detector - As soon as the temperature is below
the tripping threshold.
• Asymmetry/Phase failure - Manual or remote reset
possible
• All other trips - Can be reset immediately.
Setting Parameters
Setting Range Manual/Automatic
Factory Setting Manual
Reset Threshold of the Thermal Trip
Setting Range 10 ... 100 %
Factory Setting 70 %
Setting Increments 5%
I Q1M Circuit-breaker
1 (tripping relay)
2 3 I Current curve
IA Pickup value
IA Ie Rated service
current
Ie tv Tripping delay 50 ms
t
to Operating time of the
breaker
CET 4 tLB Arc duration
Relais #1
1 Short-circuit
Relais MR
2 Contact separation
3 Short-circuit
Q1M interruption
tv tQ tLB tBL Relay MR blocked at
tBL ≥12 Ie
Application
• Medium/high-voltage motors
!
protection must not be used for switching off the
contactor.
Function
If the motor stalls during the starting phase, the motor heats
up very rapidly, and after the permissible stalling time,
reaches the temperature limit of the insulation. Large, low-
voltage motors, and especially medium/high voltage
motors often have short, admissible stalling times,
although their starts may be considerably longer.
Accordingly, the permissible stalling time must be set
higher on the CET 4. With an external speedometer or zero
speed switch, the CET 4 recognizes that stalling has
occurred during starting, and it switches the motor off
immediately. Thus, the motor and the driven installation
is not exposed to unnecessary or inadmissible stress from
stalling.
Ie
t
tv
Setting Parameters
Trip
Tripping Delay
Same time as set for the function
Factory Setting "High overload/Jam" (see 3.4.8.)
(settable only there).
Actuation
Message from zero speed switch to control input #1
Motor Running 24 VAC/DC at control input #1
Motor Standstill 0 VAC/DC at control input #1
Output Relay
Same relay as for function
Selection (Relays) "High overload an Jam" (see 3.4.8.)
(settable only there).
Function
Factory Setting Off
Function
The thermistor detectors (PTCs) are embedded in the stator
winding of the motor. They monitor the actual temperature
of the winding. Influences independent of the motor
current, such as ambient temperature, obstructed cooling,
etc., are taken into account.
Applications
As additional protection for:
• Motors above 7.5 kW (10 HP)
• High ambient temperatures, dusty environment
• Varying loads
• Plugging, etc.
Setting Parameters
Sensor Measuring Circuit
Max resistance of the PTC chain when cold 1.5 kΩ
Max. number of sensors as per IEC 34-11-2 6
Pickup value at δA = -5 .... +60 °C 3.3 kΩ ±0.3 kΩ
Dropout value at δA = -5 ... +60 °C 1.8 kΩ ±0.3 kΩ
Delay on pickup 800 ms ±200 ms
Pickup value when short-circuit in Sensors circuit
≤15 Ω
at δA = -5 ... +60 °C
Measuring voltage as per IEC 34-11-2 < 2.5 VDC
Measuring Lead
Minimum Cross-section [mm2] 0.5 0.75 1.0 1.5 2.5
[AWG No.] 20 18 17 16 14
Maximum Length [m] 200 300 400 600 1 000
[ft.] 656 984 1 312 1 968 3 280
Method of Installation ➊ up to 100 m (328 ft.) twisted, unscreened
Output Relay
Selection (relays) MR, AL, #1 ... #5
Factory Setting MR
Function
Factory Setting Off
4000
1330
550
250
100
R [Ω]
20
10
-20°C TNF-20K TNF+15K
0°C TNF- 5K TNF+ 5K
TNF
Technical data
Output 4 ... 20 mA (IEC 381-1) at -5 ... +60 °C (23 to 140 °F)
Load 0 ... 300 Ω
Application
• Local indication for continuous supervision of the
load on motor and installation.
ϑmax
ϑG
ϑK
5 10 15 20 mA
4 17.2
200˚C
50˚C
5 10 15 20 mA
4
% Ie
200
100
5 10 15 20 mA
4 12
Actuation
24 VAC or 24 VDC; 8 mA
Input #1 Pick values:
On: 12 ... 36 V
Input #2 Off: <2 V
Output Relay
On-delay ton toff = 0
On-off-delay
ton toff
On-off-delay
ton
toff
Applications
• Time-graded on and off setting
• Delaying the transfer of alarm and trip messages
Application
• Two-speed motors
• Briefly increased loading of the motor and installation
• Maximum loading when the ambient temperature
varies appreciably. Examples: Exposed water pumps,
different conveying capacitie during daytime and at
night.
Applications
• Mobile installations (e.g., refrigerated transporters,
construction machines)
• Installations that can be displaced as enclosed units
(e.g., mobile crushers, conveyor belts, saws)
• A reversed phase sequence must be expected after a
repair.
Setting Parameter
Tripping Delay
Factory Setting 1 sec.
Output Relay
Selection (Relays) MR, AL, #1 ... #5
Factory Setting MR
Function
Factory Setting Off
Function
A phase failure is recognized by measuring the voltages
before the switchgear and thus with the motor at standstill.
(With phase failure protection where the phase currents are
measured, the motor first has to be switched on, although
it cannot start with only two phases.)
Setting Parameters
Tripping Delay
Factory Setting 2 sec.
Output Relay
Selection (Relays) MR, AL, #1 ... #5
Factory Setting MR
Function
Factory Setting Off
Motor on
off
I
⎯
Ie
Ιe
Motor current
t
Star operation,
relay #4
Delta operation,
relay #5 Changeover delay 80 ms 80 ms
Setting Parameters
Star (Wye) Max. Star (Wye)
Setting Delta Relay
Relay Operation
Setting Range – – 1 ... 240 sec.
Factory Setting Relay #4 Relay #5 10 sec.
Setting Steps – – 1 sec.
Function
Factory Setting – Off Off
Applications
• Large low voltage motors
• Medium/high-voltage motors
• At high ambient temperatures
• When cooling is obstructed.
!
"Warning" must be lower than the level for
"Trip."
PT100 PROT
ON
LCD of CET 4:
Tambient ... °C
Tamb IN TH IMAGE
ON
Setting Parameters
Insulation Class
Selection B, E, F
Factory Setting B
Function
Factory Setting Off
Application
• With large temperature variation (day/night)
• Outdoor installations:
-Pumps
-Conveyors
-Crushers
-Saws
22.5˚ 22.5˚
90
˚
CET4
22.5˚
4.2.3 CET 4 for Surface Mounting
Figure 4.3 CET 4 Mounted into Panel Mounting Frame CET 4-FPM
Hinge
Dimensions in mm (inches)
øe
ød
d3
b
b
d1 ➊
➌
➊ Mounted on DIN-rail
EN 50 022-35 e2 e2 c1
➋
øe
ød
d3
b
d1
e2 e2 ø e1 c1
d2 c
a
Mounting depth: 55 mm
(2-3/16“)
➊➊
➋
➋ ➌
➌ ➍
➍ ➎
➎
➏
➏
➐➐
➊ CET 4-housing
➋ Option CMV 4 or CLV 4
➌ Communication board
➍ Option CST 4
➎ Board with basic unit
➏ Rear cover
➐ Screws
The data of the output circuits and control inputs are dealt
with in Chapter 2, Technical Data. Throughout this
manual, the contacts of the output relays are shown in their
normal working position (i.e., the CET 4 control voltage
is switched on, no warning, no trip).
!
must be performed by qualified personnel, taking
local codes into account.
Converter module
CWE 4-2.5
CWE 4-20
Cable with plugs CWE 4-180
CWE 4-630
CWE 4-630N
Converter module
CWE 4-2.5
CWE 4-20
Converter module
CWE 4-2.5
CWE 4-20
Supply AC or DC
No fuse needed
Remote reset: ➋
Push button, key-switch
External Internal
External Internal
➊ Method of installation: up to 100 m (328 ft.) twisted, unscreened
➋ Methods of actuaction, see chapter 9.
Auxiliary relay #4
IEC 400 VAC/125 VDC
UL/CSA240 VAC/125 VDC
Auxilary relay #5
IEC 400 VAC/125 VDC
UL/CSA240 VAC/125 VDC
External Internal
External Internal
Tamb IN TH IMAGE
OFF
Method of installation:
• Short links (up to 10 m) laid separate from power
cables need no screening.
• Longer leads must be screened/shielded
-Separately screened: connect screens to individual
T2 (ex. 1T2, 2T2. . .)
-Common screening: connect screen to T2,
and all T2 together (ex. 1T2, 2T2. . .)
Section Page
Menu Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
SET VALUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Main Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Special Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Operating Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
CET 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
CST 4 Option Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
CLV 4 Option Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-14
CMV 4 Option Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15
Communication Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-17
Relay Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-17
Clear Recorded Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
Reset Settings to Factory Settings (Default Values) . . . . . . . . 5-18
With the four operating keys on the front of the unit, all
operating parameters can easily be set or altered at any
time. The procedure is described in Chapter 3.
Maximum permissible
LOCKED ROT TIME 1 ... 600 locked-rotor time of motor
10 sec from cold
➊ AS WARNING On/Off
Asymmetry warning
5-7/ ➊ OFF OFF On/Off
! before it is inactivated.
OC WARNING Overcurrent/locked-rotor
On/Off
OFF OFF warning On/Off
Overcurrent/locked-rotor
OC WARNING All except
warning
ALARM RELAY main relay
Assignment of output relay
➋ UL WARNING On/Off
Underload warning
5-14/ ➊ OFF OFF On/Off
Underload warning,
assignment of output relay
UL WARNING All except
(warning level is equal to
ALARM RELAY main relay
tripping level, without
tripping delay)
Warm Start
Setting
LCD Description
Range
5-15/ ➋ Warm start
5-14/ ➊ ➌ WARM STARTING On/Off
On/Off
OFF
5-9/ ➊ OFF
Special Settings
Setting
LCD Description
Range
electri-
Main output relay in
MAIN RELAY cally held /
electrically held or non-
ELECTR. HELD non-fail-
fail-safe connection
safe
electri-
Alarm relay in non-fail-safe
ALARM RELAY cally held /
or
NON-FAIL-SAFE non-fail-
electrically held connection
safe
5…
Earth (ground) fault trip
EF C TRIP LEVEL 999 mA
(core balance transformer)
1A 1.00 …
Tripping level
50.00 A
Earth (ground) fault trip
EF C TRIP TIME 0.1 ... 5 (core balance transformer)
0.50 sec Tripping delay
Earth (ground) fault
EF CORE TRIP warning (core balance
All relays
MAIN RELAY transformer)
Assignment of output relay
Earth (ground) fault
➋ EF C WARNING On/Off warning (core balance
5-11/ ➊ OFF OFF transformer) On/Off
5…
Earth (ground) fault
EF C WARN LEVEL 999 mA
warning (core balance
500 mA 1.00 …
transformer) Tripping level
50.00 A
Earth (ground) fault
EF C WARNING All except
warning (core balance
ALARM RELAY main relay
transformer)
Control Input #1
Setting
LCD Description
Range
Phase Failure
Setting
LCD Description
Range
Phase failure
PHASE LOSS TRIP On/Off (based on motor supply
5-15/ ➊ ➌ OFF voltage) On/Off
Setting
LCD Description
Range
Star-delta starting
STAR AUX REL #4 Relay#4 Assignment of star output
relay
Star-delta starting
DELTA AUX REL #5 Relay#5 Assignment of delta out-
put relay
Star-delta starting
5-8 ➌ ➋ STAR TIME
10 sec
1 ... 240
Max. time on star
Setting
LCD Description
Range
Setting
LCD Description
Range
Setting
LCD Description
Range
Bulletin 825-M*
station number
STATION NUMBER 0 ... 63 (DeviceNet)
02 0 ... 63 (R I/O)
1 ... 247 (MODBUS)
1 ... 126 (PROFIBUS)
Baud-Rate
0 ... 2 (DeviceNet)
BAUD RATE 0 ... 23 (R I/O)
04 0 ... 182 (MODBUS)
0 ... 4 (PROFIBUS)
Setting
LCD Description
Range
Control of relays #2 and #3
REL #2-3 VIA COM No / Yes via communication
NO allowed
Setting
LCD Description
Range
Setting
LCD Description
Range
Not reset
FACTORY SETTINGS Reset/Not reset to factory
to/
NOT RESET TO NOT RESET TO settings
All reset to
Setting
LCD Description
Range
Section Page
Checking the Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Checking the Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Checking the Installation with the Control Voltage On . . . . . . . 6-2
Switching on the Control Voltage . . . . . . . . . . . . . . . . . . . . . . 6-2
Checking the Set Parameters . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Motor Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Locked Rotor or Starting Current . . . . . . . . . . . . . . . . . . . . . . . 6-4
Locked Rotor Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Programming, Set-up, and Operation . . . . . . . . . . . . . . . . . . . . 6-6
Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
Operating Checking the Actual Values . . . . . . . . . . . . . . . . . . . 6-6
Methods
• CET 4 in Set Values mode
Example
% (Ie) x Ie 85 x 140 A
Service current = = = 119 A
100 100
1 2 3 4
IA 10
⎯
Ie
8
6
4
3
1
0.2 0.4 1 2 4 10 20 40 100 200 kW
PN
1 Approximate value for 2-pole motors , speed 3 000 rpm
2 Approximate value for 4-pole motors , speed 1 500 rpm
3 Approximate value for 6-pole motors , speed 1 000 rpm
4 Approximate value for 8-pole motors , speed 750 rpm
PN Rated output power in service
Example:
Known starting time of the motor is tA = 15 sec.
Locked-rotor time to be set:
tA 15
approximately ---------- = ------- = 11 sec
1.4 1.4
-Set the locked rotor time so that the CET 4 does not
trip (< 100%) with the least favorable service load,
e.g., at the end of a heavy start. Note that for this
procedure, the motor must be of adequate size for
the intended application.
6.4.1 Starting
6.4.2 Operating
0.00 …
I MOTOR ... A 49.99
Motor current in ... A
50 …
24 000
Motor current as a
I MOTOR ... % Ie 0 / 20 … percentage of rated
999
service current (Ie)
Motor current I 1 (phase
I 1 ... % Ie 0 / 20 …
L1), percentage of rated
1 200
service current (Ie)
Motor current I 2 (phase
I 2... % Ie 0 / 20 …
L2), percentage of rated
1 200
service current (Ie)
Motor current I 3 (phase
I 3... % Ie 0 / 20 …
L3), percentage of rated
1 200
service current (Ie)
Section Page
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Checking without Test Equipment . . . . . . . . . . . . . . . . . . . . . . 7-1
Functional Check with the <Test> Button . . . . . . . . . . . . . . . . 7-1
Indication of Recorded Values . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
List of Recorded Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Checking with Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
CET 4 Test Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
Test with Three-phase Current Source . . . . . . . . . . . . . . . . . 7-5
Test with Single-phase Current Source . . . . . . . . . . . . . . . . 7-6
7.3 Checking without 7.3.1 Functional Check with the <Test> Button
Test Equipment With the motor at standstill, the functions of the thermal
protection, all alarms, trips, and tripping times can be
checked with the aid of the <Test> button. See page 3-10
for the specific procedures.
SINCE 1PRV START Time since one start prior to last start
--- h -- min in hours, minutes
SINCE 2 PRV START Time since two starts prior to last start
--- h -- min in hours, minutes
SINCE 4 PRV START Time since four starts prior to last start
--- h -- min in hours, minutes
SINCE 1 PRV TRIP Time since one trip prior to last trip in
--- h -- min hours, minutes
SINCE 2 PRV TRIP Time since two trips prior to last trip in
--- h -- min hours, minutes
SINCE 3 PRV TRIP Time since three trips prior to last trip
--- h -- min in hours, minutes
SINCE 4 PRV TRIP Time since four trips prior to last trip in
--- h -- min hours, minutes
CAUSE 1 PRV TRIP Cause of one trip prior to last trip, e.g.,
ASYMMETRY TRIP asymmetry
! by qualified personnel.
Three-phase Ie
Connections
(if current < rated motor current:
e.g., 20 A when using CWE 4-180
! by qualified personnel.
Ie
Connection
Connection
Note: The test current may not flow through the core
balance transformer.
Section Page
Alarm, Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Procedure when Alarm/Warning Picks Up . . . . . . . . . . . . . . . . 8-2
Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
Possible Causes and Actions . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
Procedure if "Warning" does not reset . . . . . . . . . . . . . . . . . . 8-9
How to get rid of Warning? . . . . . . . . . . . . . . . . . . . . . . . 8-10
Procedure if "TRIP" can not be reset . . . . . . . . . . . . . . . . . . . 8-10
a). Thermal Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10
Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10
b). Other Trips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10
Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10
Cause for this Condition . . . . . . . . . . . . . . . . . . . . . . . . . . 8-11
How to Reset ? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-11
Example: Asymmetry
When an asymmetry condition occurs and the related
threshold is reached, the following responses occur:
• LED flashes
• LCD:
AS WARNING
Actions
If the installation can be shut down without loss of
production or without affecting safety:
• Switch off the installation
• Search for the fault and repair it
!
flashing), switching off the warning function is not
allowed. (see page 8-9)
Example: Asymmetry
Faults in the motor or the installation can develop and lead
to the set threshold being rapidly exceeded. When this
occurs and the related threshold is reached, the following
responses occur:
• LED lights
• LCD:
ASYMMETRY TRIP
Actions
Determine the trip cause and correct the problem before
re-starting the motor installation.
!
switching off the protection function is not
allowed. (see page 8-10)
Indication
• LCD
Does not display the type of the Warning (LCD
active)
• Red LED
Flashing
Indication
• LCD
"THERMAL TRIP"
• Red LED
On
How to Reset ?
The motor must have cooled down to the pre-set level,
before the reset is possible:
Indication
• LCD
Does not display the type of the trip (LCD active)
• Red LED
ON
How to Reset ?
• Go to "RECORDED VALUES" mode
• Go to "CAUSE LAST TRIP"
e.g.. "ASYMMETRY TRIP"
• Go to "SET VALUES" mode
• Go to tripped Protection Function
e.g. "ASYMMETRY TRIP"
• Switch Protection Function on
e.g. "ASYMMETRY TRIP" "ON"
• Reset Trip
Red LED goes off
• Switch Protection Function off, if not required
!
instructions and the technical data for the
contactors, auxiliary relays etc.
K1 Contactor
F1 Electronic control and
protection system CET 4
S1 On push button
S0 Off push button
Us Control voltage
H1 Indicator "Contactor closed“
H2 Indicator "CET 4 tripped“
MR Main output relay
AL Alarm relay
H3 Indicator "Alarm/Warning“
!
well ar the technical data of the used contactor
must be considered.
CET 4 settings: L1 L2 L3
Ls
FULL LOAD CURR FLC x 0.5774 [A]
1)
1 3 5 1 3 5 1 3 5
A1 A1 A1
K1H K2D K3Y
A2 A2 A2
2 4 6 2 4 6 2 4 6
LOCKED ROT CURR
IBLΔ (... x Ie )
U1 CWE 4 CET 4 F1
LOCKED ROT TIME tBLΔ (... sec.)
U1 V1 W1 Converter module U1
M
CWE 4-2.5
START TIME 3~ CWE 4-20
>tstartY (... sec.) CWE 4-180
U2 V2 W2
CWE 4-630
CWE 4-630N
K1 Contactor
F1 Electronic control and protec-
tion system CET 4 with option
CLV 4
S1 On push button
S0 Off push button
Us Control voltage
H1 Indicator “Contactor closed“
H2 Indicator “CET 4 tripped“
MR Main output relay
AL Alarm relay
H3 Indicator “Alarm/Warning“
Variants
• Two-phase current evaluation
• Two-phase current evaluation and earth (ground) fault
protection with core balance transformer
Converter module U1
CWE 4-2.5
CWE 4-20
QM Circuit-breaker
QA Shunt trip coil
K1 Contactor
F1 Electronic control and protection
system CET 4
S1 On push button
S0 Off push button
Us Control voltage
H1 Indicator "Contactor closed“
H2 Indicator "CET 4 tripped“
(except for short-circuit protection
MR Main output relay
AL Alarm relay
H3 Indicator "Alarm/Warning“
#1 Aux. relay, short-circuit indication
Figure 9.7
230 V AC / DC
L1 L2 L3
27 k / 5 W
1 3 5
Y41
I II
Y42
M
3~
L1 L2 L3 220 V AC / DC
27 k / 5 W
24 V AC/DC / 8 mA
- +
I
Y41
Speed I < 20 A
II Motor supply cables loop n-times through
Y42 CWE 4-180 until n x Ie ≥ 20 A
1 3 5
CWE 4- Current setting CET 4: n x Ie (I)
180
2 4 6 Speed II > 20 A
a b c
Motor supply cables loop once through
CWE 4-180
M Current setting CET 4: Ie (II)
3~
a b c
Secondary circuit
9.8 Separately Separately ventilated motors, which are also cooled when
Ventilated Motors stationary, behave thermally as when running.
Consequently, the cooling ratio must be set to "1."
LCD:
COOL-CONST RATIO
1.00
Primary Transformer T1
... A/5 A or ... A/1 A (Selection see Chapter 2,
Technical Data, for setting see Chapter 5)
Core balance transformer T2:
Earth- / Ground Current 5 mA ... 60 A
Current ratio of core bal. c.t. 1 ... 2 000:1
Output from core bal. c.t. 0 ... 500 mA
Settings Display