100MW PV Solar Grid Connected System - Project - VC1-Report

The document is a simulation report for a 100MW grid-connected solar PV project in Pakistan, detailing the system's configuration, energy production, and performance metrics. The project features 186,560 PV modules and 44 inverters, producing an annual energy output of 177.58 GWh with a performance ratio of 79.07%. The report includes various parameters such as geographical data, system losses, and monthly energy production statistics.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
56 views9 pages

100MW PV Solar Grid Connected System - Project - VC1-Report

The document is a simulation report for a 100MW grid-connected solar PV project in Pakistan, detailing the system's configuration, energy production, and performance metrics. The project features 186,560 PV modules and 44 inverters, producing an annual energy output of 177.58 GWh with a performance ratio of 79.07%. The report includes various parameters such as geographical data, system losses, and monthly energy production statistics.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

PVsyst V8.0.

PVsyst TRIAL
PVsyst - Simulation report
Grid-Connected System

Project: 100MW PV Solar Grid Connected System


Variant: 1st Simulation variant
Sheds on ground
System power: 108.2 MWp

PVsyst TRIAL
100MW Solar PV Project - Pakistan

PVsyst TRIAL

PVsyst TRIAL
Author

PVsyst TRIAL
Project: 100MW PV Solar Grid Connected System
Variant: 1st Simulation variant
PVsyst V8.0.8
VC1, Simulation date:
22/03/25 20:29
with V8.0.8

PVsyst TRIAL
Geographical Site
100MW Solar PV Project
Pakistan
Situation
Latitude
Longitude
Altitude
Time zone
Project summary

25.08 °(N)
67.95 °(E)
59 m
UTC+5
Project settings
Albedo 0.20

Weather data
100MW Solar PV Project
Meteonorm 8.2 (1996-2015), Sat=100% - Synthetic

System summary
Grid-Connected System Sheds on ground

PVsyst TRIAL
Simulation for year no 10

Orientation #1 Near Shadings User's needs


Fixed plane Linear shadings : Fast (table) Unlimited load (grid)
Tilt/Azimuth 28 / 22.4 °

System information
PV Array Inverters
Nb. of modules 186560 units Nb. of units 44 units
Pnom total 108.2 MWp Total power 88000 kWac
Pnom ratio 1.23

Results summary
Produced Energy 177.58 GWh/year Specific production 1641 kWh/kWp/year Perf. Ratio PR 79.07 %

PVsyst TRIAL
Project and results summary
General parameters, PV Array Characteristics, System losses
Near shading definition - Iso-shadings diagram
Main results
Loss diagram
Table of contents
2
3
5
6
7
Predef. graphs 8
Single-line diagram 9

PVsyst TRIAL

PVsyst TRIAL
22/03/25 PVsyst Evaluation mode Page 2/9
Project: 100MW PV Solar Grid Connected System
Variant: 1st Simulation variant
PVsyst V8.0.8
VC1, Simulation date:
22/03/25 20:29
with V8.0.8

PVsyst TRIAL
Grid-Connected System

Orientation #1
Fixed plane
Tilt/Azimuth 28 / 22.4 °
General parameters
Sheds on ground

Sheds configuration
Nb. of sheds
Identical arrays
1820 units
Sizes
Sheds spacing
Collector width
10.00
2.29
m
m
Shading limit angle Average GCR 22.9 %
Limit profile angle 7.7 ° Top inactive band 0.02 m
Bottom inactive band 0.02 m

Models used Horizon Near Shadings


Transposition Perez Free Horizon Linear shadings : Fast (table)
Diffuse Perez, Meteonorm

PVsyst TRIAL
Circumsolar separate

User's needs
Unlimited load (grid)

PV Array Characteristics
PV module Inverter
Manufacturer Generic Manufacturer Generic
Model STP-580-S-C72-Nsh Model SG2000
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 580 Wp Unit Nom. Power 2000 kWac
Number of PV modules 186560 units Number of inverters 44 units
Nominal (STC) 108.2 MWp Total power 88000 kWac
Modules 11660 string x 16 In series Operating voltage 460-850 V

PVsyst TRIAL
At operating cond. (50°C) Pnom ratio (DC:AC) 1.23
Pmpp 100.1 MWp Power sharing within this inverter
U mpp 628 V
I mpp 159253 A

Total PV power Total inverter power


Nominal (STC) 108205 kWp Total power 88000 kWac
Total 186560 modules Number of inverters 44 units
Module area 481931 m² Pnom ratio 1.23

Array losses
Array Soiling Losses Thermal Loss factor DC wiring losses
Loss Fraction 2.0 % Module temperature according to irradiance Global array res. 0.065 mΩ
Uc (const) 29.0 W/m²K Loss Fraction 1.5 % at STC

PVsyst TRIAL
Uv (wind) 0.0 W/m²K/m/s

Module Quality Loss Module mismatch losses Strings Mismatch loss


Loss Fraction -0.5 % Loss Fraction 2.0 % at MPP Loss Fraction 0.2 %

Module average degradation


Year no 10
Loss factor 0.4 %/year
Imp / Vmp contributions 80% / 20%
Mismatch due to degradation
Imp RMS dispersion 0.4 %/year
Vmp RMS dispersion 0.4 %/year

PVsyst TRIAL
22/03/25 PVsyst Evaluation mode Page 3/9
Project: 100MW PV Solar Grid Connected System
Variant: 1st Simulation variant
PVsyst V8.0.8
VC1, Simulation date:
22/03/25 20:29
with V8.0.8

PVsyst TRIAL
IAM loss factor
Incidence effect (IAM): Fresnel smooth glass, n = 1.526


1.000
30°
0.998
50°
0.981
60°
0.948
Array losses

70°
0.862
75°
0.776
80°
0.636
85°
0.402
90°
0.000

Spectral correction
FirstSolar model
Precipitable water estimated from relative humidity

Coefficient Set C0 C1 C2 C3 C4 C5
Monocrystalline Si 0.85914 -0.02088 -0.0058853 0.12029 0.026814 -0.001781

PVsyst TRIAL
Unavailability of the system
Time fraction 1.0 %
3.7 days,
System losses
Auxiliaries loss

3 periods

AC wiring losses
Inv. output line up to injection point
Inverter voltage 315 Vac tri
Loss Fraction 0.00 % at STC

PVsyst TRIAL
Inverter: SG2000
Wire section (44 Inv.) Copper 44 x 3 x 4000 mm²
Average wires length 0m

PVsyst TRIAL

PVsyst TRIAL
22/03/25 PVsyst Evaluation mode Page 4/9
Project: 100MW PV Solar Grid Connected System
Variant: 1st Simulation variant
PVsyst V8.0.8
VC1, Simulation date:
22/03/25 20:29
with V8.0.8

PVsyst TRIAL Near shadings parameter


Perspective of the PV-field and surrounding shading scene

PVsyst TRIAL
Iso-shadings diagram
Orientation #1 - Fixed plane, Tilts/azimuths: 28°/ 22.4°

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL
22/03/25 PVsyst Evaluation mode Page 5/9
Project: 100MW PV Solar Grid Connected System
Variant: 1st Simulation variant
PVsyst V8.0.8
VC1, Simulation date:
22/03/25 20:29
with V8.0.8

PVsyst TRIAL
System Production
Produced Energy 177.58 GWh/year
Main results

Specific production
Perf. Ratio PR
1641 kWh/kWp/year
79.07 %

Normalized productions (per installed kWp) Performance Ratio PR

PVsyst TRIAL
Balances and main results

GlobHor DiffHor T_Amb GlobInc GlobEff EArray E_Grid PR


kWh/m² kWh/m² °C kWh/m² kWh/m² GWh GWh ratio
January 128.3 42.0 17.89 172.9 164.1 15.71 15.52 0.830
February 140.9 46.4 21.06 175.0 166.4 15.64 15.46 0.816

PVsyst TRIAL
March 179.7 71.1 26.33 198.2 187.8 17.30 17.10 0.797
April 197.1 81.4 29.53 197.3 186.3 16.94 16.73 0.784
May 213.3 95.8 32.10 197.6 185.5 16.82 15.90 0.744
June 189.5 106.0 32.18 170.6 159.4 14.55 14.38 0.779
July 154.9 103.2 31.10 142.3 132.6 12.20 12.05 0.783
August 146.9 99.0 29.64 141.1 131.9 12.20 12.04 0.789
September 164.0 80.1 29.20 171.3 161.4 14.90 14.72 0.794
October 156.4 67.4 28.97 182.9 173.2 15.97 15.28 0.772
November 128.1 49.2 24.00 165.9 157.4 14.83 13.97 0.778
December 117.0 43.4 19.38 160.4 152.7 14.61 14.43 0.832
Year 1916.1 884.9 26.81 2075.4 1958.7 181.68 177.58 0.791

Legends

PVsyst TRIAL
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings

PVsyst TRIAL
22/03/25 PVsyst Evaluation mode Page 6/9
Project: 100MW PV Solar Grid Connected System
Variant: 1st Simulation variant
PVsyst V8.0.8
VC1, Simulation date:
22/03/25 20:29
with V8.0.8

PVsyst TRIAL 1916 kWh/m²


Loss diagram

+8.3%

-1.5%
Global horizontal irradiation
Global incident in coll. plane

Near Shadings: irradiance loss

-2.0% Soiling loss factor

-2.2% IAM factor on global


1959 kWh/m²
* 481931 m² coll. Effective irradiation on collectors

efficiency at STC = 22.45% PV conversion

PVsyst TRIAL
211.95 GWh Array nominal energy (at STC effic.)

-3.8% Module Degradation Loss ( for year #10)

-0.5% PV loss due to irradiance level

-6.6% PV loss due to temperature

+0.1% Spectral correction

+0.5% Module quality loss

-3.7% Mismatch loss, modules and strings


(including 1.5% for degradation dispersion)

-1.0% Ohmic wiring loss

PVsyst TRIAL
181.68 GWh Array virtual energy at MPP
-1.2% Inverter Loss during operation (efficiency)
0.0% Inverter Loss over nominal inv. power
0.0% Inverter Loss due to max. input current
0.0% Inverter Loss over nominal inv. voltage
0.0% Inverter Loss due to power threshold
0.0% Inverter Loss due to voltage threshold
179.48 GWh Available Energy at Inverter Output

0.0% Auxiliaries (fans, other)


0.0% AC ohmic loss
-1.1% System unavailability

PVsyst TRIAL
177.58 GWh Energy injected into grid

PVsyst TRIAL
22/03/25 PVsyst Evaluation mode Page 7/9
Project: 100MW PV Solar Grid Connected System
Variant: 1st Simulation variant
PVsyst V8.0.8
VC1, Simulation date:
22/03/25 20:29
with V8.0.8

PVsyst TRIAL Predef. graphs


Daily Input/Output diagram

PVsyst TRIAL

PVsyst TRIAL
System Output Power Distribution

PVsyst TRIAL

PVsyst TRIAL
22/03/25 PVsyst Evaluation mode Page 8/9
PVsyst V8.0.8
VC1, Simulation date:
22/03/25 20:29
with V8.0.8

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL