Tdoct0747g Eng
Tdoct0747g Eng
MANUAL
Strain Gauge Converter
KFD2-WAC2-(Ex)1.D
ISO9001
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
With regard to the supply of products, the current issue of the following document is applicable: The
General Terms of Delivery for Products and Services of the Electrical Industry, published by the
Central Association of the Electrical Industry (Zentralverband Elektrotechnik und Elektroindustrie
(ZVEI) e.V.) in its most recent version as well as the supplementary clause: "Expanded reservation
of proprietorship"
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Table of contents
7.4.7 kg/unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7.5 Triggers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
1
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Table of contents
2
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Symbols used in this document
Note
2 Overview
The devices of the K-System from Pepperl+Fuchs are used to transmit signals between field devices
and the process control system or control.
Devices with the "Ex" code in their type identifiers are suitable for connection to field devices in the
hazardous area. The field current circuits of these devices are intrinsically safe and are galvanically
isolated from the not intrinsically safe circuits. The devices thus represent an electrical isolation
between the hazardous area and the secure area.
Devices without an Ex code can be used for signal transmission between field devices in the secure
area and the process control system or the control.
281129 2015-07
3
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Safety instructions
3 Safety instructions
The converters KFD2-WAC2-(Ex)1.D may only be operated by trained personnel in a
manner corresponding to this operating manual.
Warning
Protection of operating personnel and the installation is only guaranteed if the devices
are used according to their specifications. Any use other than that described in the
manual endangers the safety and functionality of the device and the system in which it is
installed.
Warning
281129 2015-07
4
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Explosion protection
The devices may only be installed, connected and adjusted by electrical professionals
outside the explosion hazardous area.
Warning
If malfunctions cannot be avoided, place the devices out of service and protect them
from accidental use. The devices may only be repaired directly by the manufacturer
Pepperl+Fuchs. Any opening or change in the units are dangerous and are therefore not
to be performed. They void any warranty.
Warning
Responsibility for adhering to local safety regulations and directives is held by the
operator.
Note
4 Explosion protection
For primary explosion protection, that is, measures to avoid or restrict the
production of a dangerous, explosive atmosphere, please consult the
P P P CP P P P P P P P P P ION
5
explosion protection handbook when this is available.
This text will be adapted to the new issue of the
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Mounting and connection
The devices of the K-System from Pepperl+Fuchs and thus also the converters
KFD2-WAC2-(Ex)1.D can be mounted on a 35 mm standard rail corresponding
to EN 50022. The devices must be snapped onto the rail vertically, and never
slanted or tipped to the side.
Further mounting alternatives, e. g. using the Power Rail, can be found in the
operating instructions for the K-System on our Internet page www.pepperl-
fuchs.com/pa (under Product search, enter *WAC2*).
40 115
Dimensions of the
KFD2-WAC2-(Ex)1.D in mm
1 2 3 4 5 6
1 PWR
IN /
CH K
1 2
OUT
111
118
ESC
OK
RS232
7 8 9 10 11 12
13 14 15 16 17 18
19 20 21 22 23 24
281129 2015-07
6
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Mounting and connection
5.2 Connection
4 - 6 - 2 - 1 + 5 + 3 +
281129 2015-07
7
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Mounting and connection
8
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Mounting and connection
9
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Display mode and error messages
10
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Parameterisation mode of the control panel
7.1.1 Invocation
From any menu option of the parameterisation mode, you can return to the display mode by (if
281129 2015-07
necessary repeatedly) pressing the ESC key. If 10 minutes elapse without a key being pressed in
parameterisation mode, the device switches automatically back to display mode.
11
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Parameterisation mode of the control panel
7.1.2 Password
You can protect the parameterisation from unauthorised changes by means of a password (see
section 7.8; at the delivery of the WAC2, the password is inactive).
If the password protection is active, you can view the different settings in the parameterisation mode,
but not change them before entering the password. On the first attempt to make a change, the device
immediately prompts for a password.
The password must be entered for each transition from display mode to parameterisation mode, once
each time.
The password cannot be changed. It is 1234.
The password is entered as follows:
12
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Parameterisation mode of the control panel
OK
Output Relay 1
ESC
OK
Relay 2 Mode of operation
ESC ESC
Iout
ESC
281129 2015-07
13
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Parameterisation mode of the control panel
OK
Parameter current value, flashing
ESC
, : ESC
OK
14
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Unit
7.2 Unit
The following figure shows the menu for the unit. The menu options of the lowest menu level are
surrounded by a bold box. The unit is used for the measured value display (net and gross) and for all
respective settings in the parameterisation mode.
Unit —— kg*
cbm (m³)
pcs (pieces)
* If more than 9999 kg are entered, the unit changes automatically from kg on t!
The WAC2 makes measurements in mV. For information on the conversion into other units, see
section 7.3.1 and 7.4.4, for information on setting the tare, i. e. conversion of gross into net, see
section 7.5.
281129 2015-07
15
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Sensor
7.3 Sensor
The following figures show the menus for the input parameters. The menu options of the lowest menu
level are surrounded by a bold box. Menu options that are only displayed if you have selected certain
parameter values elsewhere are highlighted in grey.
2V
3V
4V
5V
fast
281129 2015-07
16
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Sensor
Off
Calibration (7.4)
Trigger 1 (7.5)
Trigger 2 (7.5)
281129 2015-07
17
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Sensor
Please note that mechanical influences have not yet been taken into account (e. g. acting of forces on
the weighing cell other than perfectly vertically) so that the weighing device does not achieve its
optimum accuracy.
To take into account mechanical influences a calibration of the fully installed weighing
device using defined loads is unavoidable (see section 7.4.4).
Note
281129 2015-07
18
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Sensor
Without adjustment (see section 7.4), the gross value is calculated as follows:
Measured value in mV Cell rating
Gross value = ------------------------------------------------------------------------------- --------------------------
Sensitivity Excitation voltage kg/unit
For information on selecting the unit, see section 7.2, for information on the kg/unit parameter, see
section 7.4.7.
This results in the following assignment: 0 mV is converted into 0 unit, the maximum sensor signal (=
sensitivity x excitation voltage) is converted into the maximum cell load of the selected unit, interim
values are converted proportionally.
Unit
Maximum cell load
= Cell rating/(kg/unit)
0 mV
0 Maximum sensor signal
= Sensitivity x Excitation voltage
Note
• If you have selected the On setting for Sensor failure, a check for sensor breakage is performed after
each measurement (terminals 1 and 2). Possibly, the WAC2 returns the error message Err CELL.
Unless this check is enabled the WAC2 might process uncontrolled input values until the sensor
failure has been detected.
281129 2015-07
19
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Sensor
Hinweis
• By means of Smoothing, you influence the reaction of the WAC2 to strongly fluctuating measured
values.
The WAC2 processes the smoothed value instead of the current measured value. With an adjusted
smoothing time of 0 sec, the input value is processed directly. The largest smoothing is reached with
the attitude 10 sec. Note please that with increasing smoothing also the response time of the WAC2
is reduced.
Smoothing is designed as a first-order low-pass filter. The smoothing time is the time required by the
output signal to get from 10 % to 90 % after a jump stimulation.
281129 2015-07
20
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Calibration
7.4 Calibration
The following figure shows the menu levels following the Calibration menu option. The menu options of
the lowest menu level are surrounded by a bold box. Menu options that are only displayed if you have
selected certain parameter values elsewhere are highlighted in grey.
Execute —— yes
no
Execute —— yes
no
Execute —— yes
no
21
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Calibration
7.4.4 Adjust
The adjust is an exact defined excitation of the cell, e. g. by an exactly known weight. The WAC2
requires both the value of the adjust in the selected unit (see section 7.2) and the
generated input signal in mV:
• First enter the adjust value in the selected unit kg, N, cbm or pcs under Weight. If you have selected
the unit %, the adjust value must be entered in the unit that was selected before the unit was set to %.
• After excitation of the sensor (applying the weight), select Execute and then Yes. This determines
the adjust value in mV. The tare (see section 7.5) is set to 0, gross value and net value correspond
to the adjust value in the selected unit.
For determining the adjust value in mV by means of the triggers, i. e. without using the control
281129 2015-07
22
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Calibration
Adjust
0 mV
0 Zero point Adjust
281129 2015-07
23
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Calibration
7.4.6 Range
This parameter is required for evaluations in the unit %.
• Under Set displays, enter the value that is to correspond to the gross value 100 % in the (before
selecting %) selected unit kg, N, cbm or pcs (see section 7.2). Values between 0 and the maximum
cell load are possible (see section 7.3.1).
• Alternatively, you can select Execute and then Yes after excitation of the cell (e. g. after applying a
corresponding weight). This stores the current measured value as Range.
After a change to the unit %, the gross value is calculated as follows:
Gross value without change to %
Gross value in % = -------------------------------------------------------------------------------------- 100 %
Range
7.4.7 kg/unit
• This menu option is only displayed if N, cbm or pcs has been selected as unit (see section 7.2) or if
% has been selected as unit and N, cbm or pcs has been selected previously.
• The entered value determines the conversion of kg into
N (approx. 1/9.81 = 0.102)
cbm (known from the application or to be determined by weighing)
pcs (known from the application or to be determined by weighing).
• If % has been selected as unit, the factor for converting kg into the previously selected unit must be
entered.
• If an adjust into a unit other than kg is performed, the value kg/unit must be entered before the
adjust. After changing the value kg/unit, a new adjust is required.
281129 2015-07
24
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Triggers
7.5 Triggers
The following figure shows the menus for trigger 1 and trigger 2. The menu options of the lowest menu
level are surrounded by a bold box. For information on the binary inputs, see also section 5.2.
Trigger 1 —— Tare Trigger 2 —— Tare
Adjust Adjust
Zero Zero
Binary input for trigger 1: terminals 13/14 Binary input for trigger 2: terminals 15/14
• In the case of the Tare setting, a signal of at least 100 ms at the binary input results in the current
measured value of the WAC2 being stored as the (new) value for the tare. As usual, the following
applies:
net value = gross value - tare
• In the case of the Adjust setting, a signal of at least 100 ms at the binary input results in the current
measured value of the WAC2 being adopted as the value for the adjust (see section 7.4.4).
• In the case of the Zero setting, a signal of at least 100 ms at the binary input results in the current
measured value of the WAC2 being adopted as the value for the zero point (see section 7.4.1).
Storing the adjust and the zero point by means of the triggers only makes sense, for example, if you
want to avoid operational actions on the WAC2.
281129 2015-07
25
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Relays
7.6 Relays
The following figure shows the menus for the output parameters.
Output —— Relay 1 —— Trip alarm (7.6.1)
From the Relay 1 and Relay 2 menu options, you can use the OK key to get to a menu in which you can
enter individual parameters for the selected relay. Both menus are structured in the same way and are
thus only described once.
The activated function of a relay (Trip alarm or Fault indication) is marked by On. If you want to activate
a different function, first call this function using the and keys. Then press the OK key twice. After
the first OK you can cancel with ESC.
281129 2015-07
26
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Relays
Max
Active
Net
281129 2015-07
27
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Relays
Off
Off
28
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Relays
Measured value
Max
Max - hysteresis
Min + hysteresis
Min
Time
Trip mode Max, operating mode Active:
energised
de-energised
If you have selected Net, the value of the maximum cell load minus the current tare (see
section 7.5) is the maximum value for the trip point and hysteresis.
29
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Relays
• As the representation of the operating behaviour in section 7.6.2 shows, the following must apply:
for the trip mode Max: trip point - hysteresis 0
for the trip mode Min: trip point + hysteresis upper limit of the trip point
The limits are automatically determined by the WAC2.
• The hysteresis should be > 1 % of the trip point in order to prevent rapid switching of the relay.
7.6.4 Delay
If you set a time > 0 sec, you prevent short-time violations of the trip value from triggering an alarm.
• The relay only switches if the trip point is exceeded/fallen short of for a period that is longer than the
delay time.
• The relay only switches back if the trip point -/+ hysteresis is fallen short of/exceeded for a period
that is longer than the delay time.
• If the trip point is exceeded/fallen short of for a short time, this does not have any effects.
The following figure shows the operating behaviour for the trip mode Max, operating mode Active.
Measured
value
Max
Max - hysteresis
Time
Delay Delay
281129 2015-07
30
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Relays
Off
A relay with the function Fault indication is energised in normal operation. If the device detects a fault
(see section 6), the relay is de-energised.
281129 2015-07
31
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Current output
The following figures show the menu levels following the Iout menu option. The menu options of the
lowest menu level are surrounded by a bold box.
4 - 20 NE 43
12.20 -/+mA
0 - 20 mA (b)
Net
32
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Current output
Max
Hold
Up/down
Inverted
33
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Current output
7.7.2 Characteristic
The settings have the following meaning (for Inverted normal, see section 7.7.1):
0
Measured
value
- 20.0
- 20.5
- 1.25 % 0 100 % = span 101.25 %
This setting converts the measured value 0 into -20 mA (i. e. into 20 mA in the case of changed polarity
at the terminals 7 and 8; see section 5.2), the span (see section 7.7.1) is converted into +20 mA
(terminal 7 -, terminal 8 +), interim values are calculated proportionally.
For values below the measured value 0, the output current decreases linearly to a minimum of
-20.5 mA (-1.25 % of the measurement range). Further underflows cannot be evaluated (output
-20.5 mA). If the span is exceeded, the output current increases linearly to a maximum of +20.5 mA
(101.25 % of the measurement range). Further increases cannot be evaluated (output +20.5 mA).
Selected setting 4 - 20 NE 43
mA
20.5
20.0
4.0
3.8
0
- 1.25 % 0 100 % = span ~ 103 % Measured
value
281129 2015-07
34
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Current output
This setting converts the measured value 0 into 4 mA, the span (see section 7.7.1) is converted into
20 mA, interim values are calculated proportionally.
For values below the measured value 0, the output current decreases linearly to a minimum of 3.8 mA
(-1.25 % of the measurement range). Further underflows cannot be evaluated (output 3.8 mA). If the
span is exceeded, the output current increases linearly to a maximum of 20.5 mA (approx. 103 % of the
measurement range). Further increases cannot be evaluated (output 20.5 mA).
0
Measured
- 12.0 value
- 12.5
~ - 1.6 % 0 100 % = span ~ 102 %
This setting converts the measured value 0 into -12 mA (i. e. into 12 mA in the case of changed polarity
at the terminals 7 and 8; see section 5.2), the span (see section 7.7.1) is converted into +20 mA
(terminal 7 -, terminal 8 +), interim values are calculated proportionally.
For values below the measured value 0, the output current decreases linearly to a minimum of
-12.5 mA (approx. -1.6 % of the measurement range). Further underflows cannot be evaluated (output
12.5 mA). If the span is exceeded, the output current increases linearly to a maximum of 20.5 mA
(approx. 102 % of the measurement range). Further increases cannot be evaluated (output 20.5 mA).
281129 2015-07
35
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Current output
0
0 100 % = span 102.5 % Measured
value
This setting converts the measured value 0 into 0, the span (see section 7.7.1) is converted into 20 mA,
interim values are calculated proportionally.
Values below the measured value 0 cannot be evaluated (output 0 mA). If the span is exceeded, the
output current increases linearly to a maximum of 20.5 mA (102.5 % of the measurement range).
Further increases cannot be evaluated (output 20.5 mA).
36
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Service
7.8 Service
The following figure shows the menus for the service parameters. The menu options of the lowest menu
level are surrounded by a bold box.
Off
De (German)
no
RS 485: Set the address of the WAC2 for communication via the RS 485 interface here (see section 8).
Reset: If yes is flashing and you press the OK key, all settings of the WAC2 will be reset to factory
settings (see section 7.9; exceptions: language and password activation). All entries which you have
ever made in parameterisation mode and the adjust will be lost.
281129 2015-07
37
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Factory settings
38
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Editing device data: Factory settings
39
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
RS 485 interface
8 RS 485 interface
The WAC2 can be connected to an RS 485 2-wire bus via the terminals 19 ... 21 or via the Power Rail
(see section 5.2). In principle, such a bus is structured as follows:
+5V
WAC2
21 19
390
B line/+ Connection cable 5 m max.
40
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
RS 485 interface
Requests via the RS 485 interface are not suitable for time-critical or safety-critical
applications.
Warning
The WAC2 can request the following information via the RS 485 interface e. g. from a PC or a PLC (with
3 decimal places each):
• Net measured value (in the set unit, see section 7.2)
• Gross measured value (in the set unit, see section 7.2)
• mV measured value (see section 7.2)
• Output value current output (in mA, see section 7.7.2)
41
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
RS 485 interface
Command 1st byte 2nd byte 3rd byte 4th byte 5th byte 6th byte
Null 0 0 0 0 0 0
Check_1 Address 1 Checksum
Get_value_ch1 Address BHex Checksum
Get_value_ch2 Address CHex Checksum
Get_value_ch3 Address 10Hex Checksum
Get_current Address DHex Checksum
Command 1st byte 2nd byte 3rd byte 4th byte 5th byte 6th byte
Check_1 Address 9 Checksum
Get_value_ch1 Address Value Checksum
Get_value_ch2 Address Value Checksum
Get_value_ch3 Address Value Checksum
Get_current Address Value Checksum
Explanations:
• Address: The address must be calculated as follows: 128 + setting under Service RS 485 (see
section 7.8). Values from 128 + 0 to 128 + 31, i. e. from 10000000Bin to 10011111Bin, are possible.
• Checksum: The checksum is calculated as follows: 100Hex - (1st byte + ... + penultimate byte of the
code), e. g. for Check_1 for address 17: 100Hex - (91Hex + 1) = 6EHex = 01101110Bin
• The figure 9 in the response to Check_1 refers to the device type WAC2.
• Value: in the signed long data format (4 bytes or 2 bytes)
281129 2015-07
42
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Example
9 Example
The weight of a lorry load is to be calculated. The empty weight of the lorry can be between 7.5 t and
15 t, the load to be measured can be up to 20 t. To prevent an overloading of the lorry an alarm is to be
triggered at a weight above 20.5 t.
The lorry rests on 4 weighing cells which have been connected in parallel at the input of the WAC2.
Each weighing cell has the following data:
• Supply voltage 5 V
• Sensitivity 2 mV/V
• Maximum load: 15 t
• Internal resistance: 350
The mass of the lorry weighing scales is 10 t.
9.1 Unit
The weight is to be displayed in the unit tons. In the menu Unit kg must be set. If the weight reaches
281129 2015-07
43
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Example
Because the lorry scale rests on 4 measuring cells the parameters of each individual measuring cell
must be combined: The following entries must be made in the menu Sensor:
• Supply voltage:
Here the resulting total resistance of the parallel connection of the 4 sensors must be taken into
account. If the resulting resistance of the sensors connected in parallel falls below 100 , a lower
supply voltage must be selected due to the maximum available current. The maximum permitted
supply voltage is calculated as follows:
Total resistance x 49 mA = maximum supply voltage
4 measuring cells with each 350 = 87.5
87.5 x 49 mA = 4.2875 V
Set the supply voltage to 4 V.
The maximum permitted total resistance of the sensors is 10 k.
• Sensitivity:
The sensitivity of the individual cells can be accepted 1:1.
Example:
4 cells with 2 mV/V each, entry in Sensitivity = 2 mV/V
• Cell data:
Max. cell load: The cell load of the individual sensor must be multiplied by the number of sensors.
Example:
4 sensors with 15 t each, entry in Cell load = 60 tons).
Explanation:
If e. g. only one cell is loaded at its individual maximum load it will output its maximum voltage. The
other 3 sensors are connected to this voltage and become consumers; this puts a load on the
voltage source and results in a voltage drop. Only if all 4 cells are loaded at their respective
maximum loads will they output their respective maximum voltages equally which is then measured
in parallel by the WAC2. All uneven loads between those two extremes behave linear, therefore the
parallel connection can be considered as a single measuring cell.
281129 2015-07
44
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Example
One trigger input must be parameterised as "Tare" to enable a subsequent zero point setup (see
section 9.4 (offline calibration) and 9.6)
9.4 Calibration
45
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Example
However, because the total mass to be measured is greater, the range must also be entered|.
Under Input > Calibration > Range > Set the weight to be measured must be entered, in the example
35 t. With this setting the value 100 % will be displayed at 35 t if the unit is changed to %.
The WAC2 has now been calibrated including the whole measuring chain.
9.5 Outputs
Current output
The current output must only represent the net value (the weight of the load). In the menu Output >
Iout > Gross/Net the option Net must therefore be selected.
The adjustable range relates to the maximum cell load. Because the maximum cell load is not reached
with a full tank (full lorry = 20 t, maximum cell load = 60 t) the value 20 t must be entered here.
Relay outputs
To prevent overloading a relay must be triggered as a limit value relay if 20.5 t is exceeded. This
means that the relay must be parameterised as a limit value switch with the switching direction "Max";
as a switching point the 20.5 t must be entered. As hysteresis a value of approx. 1 % of the range is
recommended, i. e. 250 kg (0.25 t). The relay must energise once the switching point has been
exceeded, the direction of action must therefore be entered as "active".
To prevent the relay from switching during the lorry entering the scales a time of 60 s can be entered
under the menu item Relay > Trip alarm > Delay. Limit overruns of less than 60 s duration will then be
ignored.
9.6 Operation
An empty lorry enters the scales. After short-circuiting the inputs of the trigger input previously
parameterised as "Tare" a zero point calibration is carried out. The lorry is then loaded and the WAC2
displays only the weight of the load.
At the current output the weight of the load is represented by 4 mA for the empty lorry and 20 mA for
the fully loaded lorry.
Via the RS 485 interface the weight of the load (net weight) can be queried by a PLS via the command
Get_value_ch_1 and be processed numerically.
281129 2015-07
46
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Notes
281129 2015-07
47
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Notes
281129 2015-07
48
Strain Gauge Converter KFD2-WAC2-(Ex)1.D
Notes
281129 2015-07
49
PROCESS AUTOMATION –
PROTECTING YOUR PROCESS
Worldwide Headquarters
Pepperl+Fuchs GmbH
68307 Mannheim · Germany
Tel. +49 621 776-0
E-Mail: [email protected]
For the Pepperl+Fuchs representative
closest to you check www.pepperl-fuchs.com/contact
www.pepperl-fuchs.com