9bSUN2000-150K-MG0 Datasheet

The SUN2000-150K-MG0 is a smart PV controller with a maximum efficiency of 98.8% and features such as arc fault protection, PID recovery, and smart string level disconnector. It supports a maximum input voltage of 1,100 V and has seven MPP trackers, with a nominal AC active power of 150,000 W. The device is designed for various operating conditions, with a protection degree of IP66 and compliance with multiple international standards.

Uploaded by

tyc1986
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
40 views2 pages

9bSUN2000-150K-MG0 Datasheet

The SUN2000-150K-MG0 is a smart PV controller with a maximum efficiency of 98.8% and features such as arc fault protection, PID recovery, and smart string level disconnector. It supports a maximum input voltage of 1,100 V and has seven MPP trackers, with a nominal AC active power of 150,000 W. The device is designed for various operating conditions, with a protection degree of IP66 and compliance with multiple international standards.

Uploaded by

tyc1986
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

SUN2000-150K-MG0

Smart PV Controller

PV Ground-Fault
Arc Fault Protection PID Recovery
Protection

Smart String Level Smart Connector


MBUS
Disconnector Temperature Detector

Efficiency Curve Circuit Diagram


SUN2000-150K-MG0 @400 V
Efficiency [%]
100%

99%

98%

97%

96%

95%

94%

93%

92%

91%

90%
0%
20% 40% 60% 80% 100%
625 V 720 V 850 V
Load [%]

• This datasheet only shows Preliminary Version, the information may change. Please contact with HW local supplier for the latest version

SOLAR.HUAWEI.COM/
SUN2000-150K-MG0
Technical Specification

Technical Specification SUN2000-150K-MG0

Efficiency
Max. efficiency 98.6% @400V, 98.8% @480V
European efficiency 98.4%

Input
Max. Input Voltage 1 1,100 V
Max. Current per MPPT 48A
Max. Current per Input 23A
Max. Short Circuit Current per MPPT 66A
Start Voltage 200 V
MPPT Operating Voltage Range 2 200 V ~ 1,000 V
Number of MPP trackers 7
Max. input number per MPP tracker 3

Output
Nominal AC Active Power 150,000 W
Max. AC Apparent Power 165,000 VA
Max. AC Active Power (cosφ=1) 165,000 W
Nominal Output Voltage 380 V/400 V/480Vac
Rated AC Grid Frequency 50 Hz / 60 Hz
Nominal Output Current 227.9 A @380 V, 216.5 A @400 V, 180.4A @480Vac
Max. Output Current 253.2 A @380 V, 240.5 A @400 V, 200.5A @480Vac
Adjustable Power Factor Range 0.8 leading... 0.8 lagging
alternating current THDi <1%

Protection
Anti-islanding Protection Yes
AC Overcurrent Protection Yes
DC Reverse-polarity Protection Yes
PV-array String Fault Monitoring Yes
DC Surge Arrester Type II
AC Surge Arrester Type II
DC Insulation Resistance Detection Yes
Residual Current Monitoring Unit Yes
Smart String Level Disconnector Yes
Arc Fault Protection Yes
Terminal Temperature Detection Yes
PID Recovery Yes
PV Ground-Fault Protection Yes

Communication
Display LED indicators; WLAN adaptor + FusionSolar APP
RS485 Yes
USB Yes
Smart Dongle-4G Smart Dongle – 4G / WLAN (Optional)
Monitoring BUS (MBUS) Yes (isolation transformer required)

General Data
Dimensions (W x H x D) 1,000 x 710 x 395 mm
Weight (without mounting plate) ≤ 99 kg
Operating Temperature Range -25°C ~ 60°C
Cooling Method Smart Air Cooling
Max. Operating Altitude 4,000 m (13,123 ft.)
Relative Humidity 0 ~ 100%
DC Connector Amphenol HH4
AC Connector Waterproof Connector + OT/DT Terminal
Protection Degree IP66
Topology Transformerless

Standard Compliance (more available upon request)


Certificate EN 62109-1/-2, IEC 62109-1/-2, IEC 62116, IEC 61727, IEC 60068, IEC 61683
Grid Connection Standards VDE-AR-N4105, EN 50549-1, EN 50549-2, RD 661, RD 1699, C10/11
• This datasheet only shows Preliminary Version, the information may change. Please contact with HW local supplier for the latest version
* 1 The maximum input voltage is the upper limit of the DC voltage. Any higher input DC voltage would probably damage inverter.
* 2 Any DC input voltage beyond the operating voltage range may result in inverter improper operating.