The document is a test certificate for various low-tension circuit breakers used by Gujarat Fluorochemicals Limited, detailing tests conducted on different dates in 2025. Each section includes specifications such as make, type, rated voltage, and current, along with test results for insulation resistance, coil resistance, contact resistance, and operational checks. All tested circuit breakers passed the inspections with no abnormalities reported.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
18 views39 pages
GFL Dahej-3
The document is a test certificate for various low-tension circuit breakers used by Gujarat Fluorochemicals Limited, detailing tests conducted on different dates in 2025. Each section includes specifications such as make, type, rated voltage, and current, along with test results for insulation resistance, coil resistance, contact resistance, and operational checks. All tested circuit breakers passed the inspections with no abnormalities reported.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 39
TEST CERTIFICATE OF LT CIRCUIT BREAKER
Client GUJARAT FLUOROCHEMICAL LIMITED, DAHEJ Tested on 08.03.2025
Plant PVDF EV LINE – 02 SUB – STATION Tested by ABZ Location P – 19 I/C – 1(INCOMER – 1) 415 LTP
1.0 Name Plate details :
1.1 Make : SIEMENS 1.2 Breaker type : WA124000M 1.3 Serial No. : 0E/230301600001 1.4 Rated voltage : 690V 1.5 Rated current : 4000A 1.6 No. of Pole :4 1.7 Breaking Current : 75kA 1.8 Short Time Current : 75 kA 1 s
2.0 Insulation Resistance Test :
Insulation Resistance Close condition Test @ 500 V RY YB BR RE YE BE NE RN YN BN Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G >1G
Insulation Resistance Open condition
Test @ 500 V RR` YY` BB` NN` Values in Ω >1G >1G >1G >1G
3.0 Coil Resistance Measurement :
Coil resistance of Motor Closing Coil Tripping Coil Values in Ω 8.11 10.11 9.12
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Neutral Values in μΩ 9.1 10.1 10.2 11.5
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 44 32 08 Y 44 32 08 B 44 32 08 N
6.0 Operation Counter Reading :
Before After 00329 00332 7.0 Control circuit and operational checks : Sr. No Description Remarks 7.1 Manual charging of spring OK 7.2 Mechanical Closing and Tripping OK 7.3 Electrical Closing and Tripping OK 7.4 Mechanical interlocks of breaker OK 7.5 Charging of spring through motor OK 7.6 Electrical interlocks of breaker OK 7.7 Abnormality, if any NONE
8.0 Maintenance and general check – up :
Sr. No Description Remarks 8.1 Inspection for physical damage OK 8.2 Breaker aux. switch contact healthiness OK 8.3 Spring charging mechanism operation OK 8.4 Cleaning and tightness of breaker bolts OK 8.5 Breaker rack – in and rack – out OK 8.6 Alignment of breaker OK 8.7 Earthing connection OK 8.8 Greasing of moving parts OK 8.9 Abnormality, if any NONE
9.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF LT CIRCUIT BREAKER Client GUJARAT FLUOROCHEMICAL LIMITED, DAHEJ Tested on 08.03.2025 Plant PVDF EV LINE – 02 SUB – STATION Tested by ABZ Location P – 1 INCOMER – 2 415 LTP
1.0 Name Plate details :
1.1 Make : SIEMENS 1.2 Breaker type : WA124000M 1.3 Serial No. : 0E/230119500149 1.4 Rated voltage : 690V 1.5 Rated current : 4000A 1.6 No. of Pole :4 1.7 Breaking Current : 75kA 1.8 Short Time Current : 75 KA 1 s
2.0 Insulation Resistance Test :
Insulation Resistance Close condition Test @ 500 V RY YB BR RE YE BE NE RN YN BN Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G >1G
Insulation Resistance Open condition
Test @ 500 V RR` YY` BB` NN` Values in Ω >1G >1G >1G >1G
3.0 Coil Resistance Measurement :
Coil resistance of Closing Coil Tripping Coil Moter Winding Values in Ω 10.3 10.11 9.33
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Neutral Values in μΩ 16.6 9.7 11.2 11.7
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 45 31 09 Y 45 31 09 B 45 31 09 N 6.0 Operation Counter Reading : Before After 00342 00347
7.0 Control circuit and operational checks :
Sr. No Description Remarks 7.1 Manual charging of spring OK 7.2 Mechanical Closing and Tripping OK 7.3 Electrical Closing and Tripping OK 7.4 Mechanical interlocks of breaker OK 7.5 Charging of spring through motor OK 7.6 Electrical interlocks of breaker OK 7.7 Abnormality, if any NONE
8.0 Maintenance and general check – up :
Sr. No Description Remarks 8.1 Inspection for physical damage OK 8.2 Breaker aux. switch contact healthiness OK 8.3 Spring charging mechanism operation OK 8.4 Cleaning and tightness of breaker bolts OK 8.5 Breaker rack – in and rack – out OK 8.6 Alignment of breaker OK 8.7 Earthing connection OK 8.8 Greasing of moving parts OK 8.9 Abnormality, if any NONE
9.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF LT CIRCUIT BREAKER Client GFL DAHEJ Tested on 08.03.2025 Plant PVDF LINE-2 SUB STATION Tested by ABZ Location P-1F1 APFC-1(I/C PCC 15F1) 415V LT PANEL
1.0 Name Plate details :
1.1 Make : SIEMENS 1.2 Breaker type : WL1120005 1.3 Serial No. : 006641430320003 1.4 Rated voltage : 690V 1.5 Rated current : 2000A 1.6 No. of Pole :4 1.7 Breaking Current : 75kA 1.8 Short Time Current : 75 KA 1 s
2.0 Insulation Resistance Test :
Insulation Resistance Close condition Test @ 500 V RY YB BR RE YE BE NE RN YN BN Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G >1G
Insulation Resistance Open condition
Test @ 500 V RR` YY` BB` NN` Values in Ω >1G >1G >1G >1G
3.0 Coil Resistance Measurement :
Coil resistance of Closing Coil Tripping Coil Moter Winding Values in Ω 9.11 11.3 9.18
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Neutral Values in μΩ 16.6 15.5 14.9 15.8
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 41 31 08 Y 41 32 08 B 41 32 08 N 6.0 Operation Counter Reading : Before After 00011 00015
7.0 Control circuit and operational checks :
Sr. No Description Remarks 7.1 Manual charging of spring OK 7.2 Mechanical Closing and Tripping OK 7.3 Electrical Closing and Tripping OK 7.4 Mechanical interlocks of breaker OK 7.5 Charging of spring through motor OK 7.6 Electrical interlocks of breaker OK 7.7 Abnormality, if any NONE
8.0 Maintenance and general check – up :
Sr. No Description Remarks 8.1 Inspection for physical damage OK 8.2 Breaker aux. switch contact healthiness OK 8.3 Spring charging mechanism operation OK 8.4 Cleaning and tightness of breaker bolts OK 8.5 Breaker rack – in and rack – out OK 8.6 Alignment of breaker OK 8.7 Earthing connection OK 8.8 Greasing of moving parts OK 8.9 Abnormality, if any NONE
9.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF LT CIRCUIT BREAKER Client GUJARAT FLUOROCHEMICAL LIMITED, DAHEJ Tested on 07.03.2025 Plant PVDF EV LINE – 02 SUB – STATION Tested by ABZ Location P – 09 BUS COUPLER 415 V LT PANEL
1.0 Name Plate details :
1.1 Make : SIEMENS 1.2 Breaker type : WA124000M 1.3 Serial No. : 0E/230120500058 1.4 Rated voltage : 690V 1.5 Rated current : 4000A 1.6 No. of Pole :4 1.7 Breaking Current : 75kA 1.8 Short Time Current : 75 KA 1 s
2.0 Insulation Resistance Test :
Insulation Resistance Close condition Test @ 500 V RY YB BR RE YE BE NE RN YN BN Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G >1G
Insulation Resistance Open condition
Test @ 500 V RR` YY` BB` NN` Values in Ω >1G >1G >1G >1G
3.0 Coil Resistance Measurement :
Coil resistance of Closing Coil Tripping Coil Moter Winding Values in Ω 9.07 9.18 10.11
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Neutral Values in μΩ 13.3 8.8 12.1 15.1
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 57 35 06 Y 57 35 06 B 57 35 06 N 57 35 06
6.0 Operation Counter Reading :
Before After 00155 00159 7.0 Control circuit and operational checks : Sr. No Description Remarks 7.1 Manual charging of spring OK 7.2 Mechanical Closing and Tripping OK 7.3 Electrical Closing and Tripping OK 7.4 Mechanical interlocks of breaker OK 7.5 Charging of spring through motor OK 7.6 Electrical interlocks of breaker OK 7.7 Abnormality, if any NONE
8.0 Maintenance and general check – up :
Sr. No Description Remarks 8.1 Inspection for physical damage OK 8.2 Breaker aux. switch contact healthiness OK 8.3 Spring charging mechanism operation OK 8.4 Cleaning and tightness of breaker bolts OK 8.5 Breaker rack – in and rack – out OK 8.6 Alignment of breaker OK 8.7 Earthing connection OK 8.8 Greasing of moving parts OK 8.9 Abnormality, if any NONE
9.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF LT CIRCUIT BREAKER Client GFL DAHEJ Tested on 08.03.2025 Plant PVDF LINE-2 SUB STATION Tested by ABZ Location 7F1 APFC-2(I/C PCC 8F1) 415V LT PANEL
1.0 Name Plate details :
1.1 Make : SIEMENS 1.2 Breaker type : WL112000S 1.3 Serial No. : 006641430304000 1.4 Rated voltage : 690V 1.5 Rated current : 2000A 1.6 No. of Pole :4 1.7 Breaking Current : 75kA 1.8 Short Time Current : 75 KA 1 s
2.0 Insulation Resistance Test :
Insulation Resistance Close condition Test @ 500 V RY YB BR RE YE BE NE RN YN BN Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G >1G
Insulation Resistance Open condition
Test @ 500 V RR` YY` BB` NN` Values in Ω >1G >1G >1G >1G
3.0 Coil Resistance Measurement :
Coil resistance of Closing Coil Tripping Coil Moter Winding Values in Ω 12.7 12.1 13.7
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Neutral Values in μΩ 9.81 9.71 10.7 12.4
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 48 37 09 Y 48 37 09 B 48 37 09 N 48 37 09
6.0 Operation Counter Reading :
Before After 00036 00041 7.0 Control circuit and operational checks : Sr. No Description Remarks 7.1 Manual charging of spring OK 7.2 Mechanical Closing and Tripping OK 7.3 Electrical Closing and Tripping OK 7.4 Mechanical interlocks of breaker OK 7.5 Charging of spring through motor OK 7.6 Electrical interlocks of breaker OK 7.7 Abnormality, if any NONE
8.0 Maintenance and general check – up :
Sr. No Description Remarks 8.1 Inspection for physical damage OK 8.2 Breaker aux. switch contact healthiness OK 8.3 Spring charging mechanism operation OK 8.4 Cleaning and tightness of breaker bolts OK 8.5 Breaker rack – in and rack – out OK 8.6 Alignment of breaker OK 8.7 Earthing connection OK 8.8 Greasing of moving parts OK 8.9 Abnormality, if any NONE
9.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF LT CIRCUIT BREAKER Client GUJARAT FLUOROCHEMICAL LIMITED, DAHEJ Tested on 09.03.2025 Plant PVDF LINE – 02 PROCESS MCC 01 Tested by A Location P 1F2, PVDF EV PROCESS DB I/C PCC 13F1 415 V LTP
1.0 Name Plate details :
1.1 Make : SCHNEIDER 1.2 Breaker type : NW16HA 1.3 Serial No. : 10223530270 1.4 Rated voltage : 690V 1.5 Rated current : 1600A 1.6 No. of Pole :4 1.7 Breaking Current : 65kA 1.8 Short Time Current : 65 KA 1 s
2.0 Insulation Resistance Test :
Insulation Resistance Close condition Test @ 500 V RY YB BR RE YE BE NE RN YN BN Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G >1G
Insulation Resistance Open condition
Test @ 500 V RR` YY` BB` NN` Values in Ω >1G >1G >1G >1G
3.0 Coil Resistance Measurement :
Coil resistance of Closing Coil Tripping Coil Moter Winding Values in Ω 9.48 9.51 9.46
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Neutral Values in μΩ 16.2 15.8 15.6 15.2
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 55 24 01 Y 55 24 01 B 55 24 01 N 55 24 01 6.0 Control circuit and operational checks : Sr. No Description Remarks 6.1 Manual charging of spring OK 6.2 Mechanical Closing and Tripping OK 6.3 Electrical Closing and Tripping OK 6.4 Mechanical interlocks of breaker OK 6.5 Charging of spring through motor OK 6.6 Electrical interlocks of breaker OK 6.7 Abnormality, if any NONE
7.0 Maintenance and general check – up :
Sr. No Description Remarks 7.1 Inspection for physical damage OK 7.2 Breaker aux. switch contact healthiness OK 7.3 Spring charging mechanism operation OK 7.4 Cleaning and tightness of breaker bolts OK 7.5 Breaker rack – in and rack – out OK 7.6 Alignment of breaker OK 7.7 Earthing connection OK 7.8 Greasing of moving parts OK 7.9 Abnormality, if any NONE
8.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF LT CIRCUIT BREAKER Client GFL DAHEJ Tested on 09.03.2025 Plant PVDF EV NORMEL MCC Tested by ABZ Location I/C 11F1 PCC PANEL
1.0 Name Plate details :
1.1 Make : SCHNEIDER 1.2 Breaker type : NW08HA 1.3 Serial No. : 10231770005 1.4 Rated voltage : 690V 1.5 Rated current : 800A 1.6 No. of Pole :4 1.7 Breaking Current : 65kA 1.8 Short Time Current : 65 KA 1 s
2.0 Insulation Resistance Test :
Insulation Resistance Close condition Test @ 500 V RY YB BR RE YE BE NE RN YN BN Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G >1G
Insulation Resistance Open condition
Test @ 500 V RR` YY` BB` NN` Values in Ω >1G >1G >1G >1G
3.0 Coil Resistance Measurement :
Coil resistance of Closing Coil Tripping Coil Moter Winding Values in Ω 9.5 11.6 22.3
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Neutral Values in μΩ 11.2 13.13 13.1 14.6
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 55 23 08 Y 55 23 08 B 55 23 08 N 6.0 Control circuit and operational checks : Sr. No Description Remarks 6.1 Manual charging of spring OK 6.2 Mechanical Closing and Tripping OK 6.3 Electrical Closing and Tripping OK 6.4 Mechanical interlocks of breaker Remark 6.5 Charging of spring through motor OK 6.6 Electrical interlocks of breaker Remark 6.7 Abnormality, if any NONE
7.0 Maintenance and general check – up :
Sr. No Description Remarks 7.1 Inspection for physical damage OK 7.2 Breaker aux. switch contact healthiness OK 7.3 Spring charging mechanism operation OK 7.4 Cleaning and tightness of breaker bolts OK 7.5 Breaker rack – in and rack – out OK 7.6 Alignment of breaker OK 7.7 Earthing connection OK 7.8 Greasing of moving parts OK 7.9 Abnormality, if any NONE
8.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF LT CIRCUIT BREAKER Client GUJARAT FLUOROCHEMICAL LIMITED, DAHEJ Tested on 08.03.2025 Plant PVDF EV LINE – 02 SUB – STATION Tested by ABZ Location P – 15 APFC – 1 415 V LT PANEL
1.0 Name Plate details :
1.1 Make : SIEMENS 1.2 Breaker type : WA122500M 1.3 Serial No. : 0E/230209600032 1.4 Rated voltage : 690V 1.5 Rated current : 2500A 1.6 No. of Pole :3 1.7 Breaking Current : 75kA 1.8 Short Time Current : 75kA 1s
2.0 Insulation Resistance Test :
Insulation Resistance Close Condition Open Condition Test @ 500 V RY YB BR RE YE BE RR’ YY’ BB’ Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G
3.0 Coil Resistance Measurement :
Coil resistance of Motor Closing Coil Tripping Coil Values in Ω 8.11 11.2 8.93
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Values in μΩ 12.2 11.3 9.7
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 54 40 11 Y 54 40 11 B 54 40 11
6.0 Operation Counter Reading :
Before After 00071 00074 7.0 Control circuit and operational checks : Sr. No Description Remarks 7.1 Manual charging of spring OK 7.2 Mechanical Closing and Tripping OK 7.3 Electrical Closing and Tripping OK 7.4 Mechanical interlocks of breaker OK 7.5 Charging of spring through motor OK 7.6 Electrical interlocks of breaker OK 7.7 Abnormality, if any NONE
8.0 Maintenance and general check – up :
Sr. No Description Remarks 8.1 Inspection for physical damage OK 8.2 Breaker aux. switch contact healthiness OK 8.3 Spring charging mechanism operation OK 8.4 Cleaning and tightness of breaker bolts OK 8.5 Breaker rack – in and rack – out OK 8.6 Alignment of breaker OK 8.7 Earthing connection OK 8.8 Greasing of moving parts OK 8.9 Abnormality, if any NONE
9.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF LT CIRCUIT BREAKER Client GUJARAT FLUOROCHEMICAL LIMITED, DAHEJ Tested on 09.03.2025 Plant PVDF EV LINE – 02 SUB – STATION Tested by ABZ Location P – 13 EV PROCESS DB 415 V LT PANEL
1.0 Name Plate details :
1.1 Make : SIEMENS 1.2 Breaker type : WA111250M 1.3 Serial No. : 0E/230208600001 1.4 Rated voltage : 690V 1.5 Rated current : 1250A 1.6 No. of Pole :3 1.7 Breaking Current : 66kA 1.8 Short Time Current : 66kA 1s
2.0 Insulation Resistance Test :
Insulation Resistance Close Condition Open Condition Test @ 500 V RY YB BR RE YE BE RR’ YY’ BB’ Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G
3.0 Coil Resistance Measurement :
Coil resistance of Motor Closing Coil Tripping Coil Values in Ω 8.96 9.63 9.60
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Values in μΩ 12.8 11.8 12.7
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 49 32 09 Y 49 32 09 B 49 32 09
6.0 Operation Counter Reading :
Before After 00081 00084 7.0 Control circuit and operational checks : Sr. No Description Remarks 7.1 Manual charging of spring OK 7.2 Mechanical Closing and Tripping OK 7.3 Electrical Closing and Tripping OK 7.4 Mechanical interlocks of breaker OK 7.5 Charging of spring through motor OK 7.6 Electrical interlocks of breaker OK 7.7 Abnormality, if any NONE
8.0 Maintenance and general check – up :
Sr. No Description Remarks 8.1 Inspection for physical damage OK 8.2 Breaker aux. switch contact healthiness OK 8.3 Spring charging mechanism operation OK 8.4 Cleaning and tightness of breaker bolts OK 8.5 Breaker rack – in and rack – out OK 8.6 Alignment of breaker OK 8.7 Earthing connection OK 8.8 Greasing of moving parts OK 8.9 Abnormality, if any NONE
9.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF LT CIRCUIT BREAKER Client GUJARAT FLUOROCHEMICAL LIMITED, DAHEJ Tested on 08.03.2025 Plant PVDF EV LINE – 02 SUB – STATION Tested by ABZ Location P – 16 DG INCOMER 415 LTP
1.0 Name Plate details :
1.1 Make : SIEMENS 1.2 Breaker type : WA122500M 1.3 Serial No. : 0E/230209600029 1.4 Rated voltage : 690V 1.5 Rated current : 2500A 1.6 No. of Pole :3 1.7 Breaking Current : 75kA 1.8 Short Time Current : 75kA 1s
2.0 Insulation Resistance Test :
Insulation Resistance Close Condition Open Condition Test @ 500 V RY YB BR RE YE BE RR’ YY’ BB’ Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G
3.0 Coil Resistance Measurement :
Coil resistance of Motor Closing Coil Tripping Coil Values in Ω 9.27 10.43 10.37
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Values in μΩ 9.6 12.7 15.1
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 54 36 05 Y 54 36 05 B 54 36 05
6.0 Operation Counter Reading :
Before After 00108 00112 7.0 Control circuit and operational checks : Sr. No Description Remarks 7.1 Manual charging of spring OK 7.2 Mechanical Closing and Tripping OK 7.3 Electrical Closing and Tripping OK 7.4 Mechanical interlocks of breaker OK 7.5 Charging of spring through motor OK 7.6 Electrical interlocks of breaker OK 7.7 Abnormality, if any NONE
8.0 Maintenance and general check – up :
Sr. No Description Remarks 8.1 Inspection for physical damage OK 8.2 Breaker aux. switch contact healthiness OK 8.3 Spring charging mechanism operation OK 8.4 Cleaning and tightness of breaker bolts OK 8.5 Breaker rack – in and rack – out OK 8.6 Alignment of breaker OK 8.7 Earthing connection OK 8.8 Greasing of moving parts OK 8.9 Abnormality, if any NONE
9.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF LT CIRCUIT BREAKER Client GUJARAT FLUOROCHEMICAL LIMITED, DAHEJ Tested on 07.03.2025 Plant PVDF EV LINE – 02 SUB – STATION Tested by ABZ Location P – 17 SED – 3 (HEATER – 02) 415 V LT PANEL
1.0 Name Plate details :
1.1 Make : SIEMENS 1.2 Breaker type : WA11800M 1.3 Serial No. : OE/230208500195 1.4 Rated voltage : 690V 1.5 Rated current : 800A 1.6 No. of Pole :3 1.7 Breaking Current : 66kA 1.8 Short Time Current : 66kA 1s
2.0 Insulation Resistance Test :
Insulation Resistance Close Condition Open Condition Test @ 500 V RY YB BR RE YE BE RR’ YY’ BB’ Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G
3.0 Coil Resistance Measurement :
Coil resistance of Motor Closing Coil Tripping Coil Values in Ω 8.61 8.65 8.73
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Values in μΩ 11.3 11.5 11.7
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 46 35 10 Y 46 35 10 B 46 35 11
6.0 Operation Counter Reading :
Before After 00089 00093 7.0 Control circuit and operational checks : Sr. No Description Remarks 7.1 Manual charging of spring OK 7.2 Mechanical Closing and Tripping OK 7.3 Electrical Closing and Tripping OK 7.4 Mechanical interlocks of breaker OK 7.5 Charging of spring through motor OK 7.6 Electrical interlocks of breaker OK 7.7 Abnormality, if any NONE
8.0 Maintenance and general check – up :
Sr. No Description Remarks 8.1 Inspection for physical damage OK 8.2 Breaker aux. switch contact healthiness OK 8.3 Spring charging mechanism operation OK 8.4 Cleaning and tightness of breaker bolts OK 8.5 Breaker rack – in and rack – out OK 8.6 Alignment of breaker OK 8.7 Earthing connection OK 8.8 Greasing of moving parts OK 8.9 Abnormality, if any NONE
9.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF LT CIRCUIT BREAKER Client GUJARAT FLUOROCHEMICAL LIMITED, DAHEJ Tested on 08.03.2025 Plant PVDF EV LINE – 02 SUB – STATION Tested by ABZ Location P – 11 EV PROCESS MCC LT PANEL
1.0 Name Plate details :
1.1 Make : SIEMENS 1.2 Breaker type : WA111250M 1.3 Serial No. :0E/230208500150 1.4 Rated voltage : 690V 1.5 Rated current : 1250A 1.6 No. of Pole :3 1.7 Breaking Current : 66kA 1.8 Short Time Current : 66kA 1s
2.0 Insulation Resistance Test :
Insulation Resistance Close Condition Open Condition Test @ 500 V RY YB BR RE YE BE RR’ YY’ BB’ Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G
3.0 Coil Resistance Measurement :
Coil resistance of Motor Closing Coil Tripping Coil Values in Ω 8.96 10.3 9.98
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Values in μΩ 13.2 12.9 13.7
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 49 36 09 Y 49 36 09 B 49 36 09
6.0 Operation Counter Reading :
Before After 99946 99946 7.0 Control circuit and operational checks : Sr. No Description Remarks 7.1 Manual charging of spring OK 7.2 Mechanical Closing and Tripping OK 7.3 Electrical Closing and Tripping OK 7.4 Mechanical interlocks of breaker OK 7.5 Charging of spring through motor OK 7.6 Electrical interlocks of breaker OK 7.7 Abnormality, if any NONE
8.0 Maintenance and general check – up :
Sr. No Description Remarks 8.1 Inspection for physical damage OK 8.2 Breaker aux. switch contact healthiness OK 8.3 Spring charging mechanism operation OK 8.4 Cleaning and tightness of breaker bolts OK 8.5 Breaker rack – in and rack – out OK 8.6 Alignment of breaker OK 8.7 Earthing connection OK 8.8 Greasing of moving parts OK 8.9 Abnormality, if any NONE
9.0 Remarks : TESTED AS ABOVE
9.1 COUNTER NOT WORKING
TEST CERTIFICATE OF LT CIRCUIT BREAKER Client GUJARAT FLUOROCHEMICAL LIMITED, DAHEJ Tested on 08.03.2025 Plant PVDF EV LINE – 02 SUB – STATION Tested by ABZ Location P – 06 PELLETIZER – B1, 415 V LT PANEL
1.0 Name Plate details :
1.1 Make : SIEMENS 1.2 Breaker type : WA111250M 1.3 Serial No. :0E/230208600015 1.4 Rated voltage : 690V 1.5 Rated current : 1250A 1.6 No. of Pole :3 1.7 Breaking Current : 66kA 1.8 Short Time Current : 66kA 1s
2.0 Insulation Resistance Test :
Insulation Resistance Close Condition Open Condition Test @ 500 V RY YB BR RE YE BE RR’ YY’ BB’ Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G
3.0 Coil Resistance Measurement :
Coil resistance of Motor Closing Coil Tripping Coil Values in Ω 8.09 10.11 9.99
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Values in μΩ 12.1 11.9 11.7
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 49 34 07 Y 49 34 07 B 49 34 07
6.0 Operation Counter Reading :
Before After 00121 00124 7.0 Control circuit and operational checks : Sr. No Description Remarks 7.1 Manual charging of spring OK 7.2 Mechanical Closing and Tripping OK 7.3 Electrical Closing and Tripping OK 7.4 Mechanical interlocks of breaker OK 7.5 Charging of spring through motor OK 7.6 Electrical interlocks of breaker OK 7.7 Abnormality, if any NONE
8.0 Maintenance and general check – up :
Sr. No Description Remarks 8.1 Inspection for physical damage OK 8.2 Breaker aux. switch contact healthiness OK 8.3 Spring charging mechanism operation OK 8.4 Cleaning and tightness of breaker bolts OK 8.5 Breaker rack – in and rack – out OK 8.6 Alignment of breaker OK 8.7 Earthing connection OK 8.8 Greasing of moving parts OK 8.9 Abnormality, if any NONE
9.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF LT CIRCUIT BREAKER Client GUJARAT FLUOROCHEMICAL LIMITED, DAHEJ Tested on 08.03.2025 Plant PVDF EV LINE – 02 SUB – STATION Tested by ABZ Location P – 07 FILM CAST UNIT 415 V LT PANEL
1.0 Name Plate details :
1.1 Make : SIEMENS 1.2 Breaker type : WA111250M 1.3 Serial No. :0E/23020860016 1.4 Rated voltage : 690V 1.5 Rated current : 1250A 1.6 No. of Pole :3 1.7 Breaking Current : 66kA 1.8 Short Time Current : 66kA 1s
2.0 Insulation Resistance Test :
Insulation Resistance Close Condition Open Condition Test @ 500 V RY YB BR RE YE BE RR’ YY’ BB’ Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G
3.0 Coil Resistance Measurement :
Coil resistance of Motor Closing Coil Tripping Coil Values in Ω 7.83 9.48 9.85
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Values in μΩ 13.6 13.2 12.7
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 47 33 05 Y 47 33 05 B 47 33 05
6.0 Operation Counter Reading :
Before After 00087 00090 7.0 Control circuit and operational checks : Sr. No Description Remarks 7.1 Manual charging of spring OK 7.2 Mechanical Closing and Tripping OK 7.3 Electrical Closing and Tripping OK 7.4 Mechanical interlocks of breaker OK 7.5 Charging of spring through motor OK 7.6 Electrical interlocks of breaker OK 7.7 Abnormality, if any NONE
8.0 Maintenance and general check – up :
Sr. No Description Remarks 8.1 Inspection for physical damage OK 8.2 Breaker aux. switch contact healthiness OK 8.3 Spring charging mechanism operation OK 8.4 Cleaning and tightness of breaker bolts OK 8.5 Breaker rack – in and rack – out OK 8.6 Alignment of breaker OK 8.7 Earthing connection OK 8.8 Greasing of moving parts OK 8.9 Abnormality, if any NONE
9.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF LT CIRCUIT BREAKER Client GUJARAT FLUOROCHEMICAL LIMITED, DAHEJ Tested on 08.03.2025 Plant PVDF EV LINE – 02 SUB – STATION Tested by ABZ Location P – 08 APFC – 2 415 V LT PANEL
1.0 Name Plate details :
1.1 Make : SIEMENS 1.2 Breaker type : WA111250M 1.3 Serial No. :0E/230208500191 1.4 Rated voltage : 690V 1.5 Rated current : 1250A 1.6 No. of Pole :3 1.7 Breaking Current : 66kA 1.8 Short Time Current : 66kA 1s
2.0 Insulation Resistance Test :
Insulation Resistance Close Condition Open Condition Test @ 500 V RY YB BR RE YE BE RR’ YY’ BB’ Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G
3.0 Coil Resistance Measurement :
Coil resistance of Motor Closing Coil Tripping Coil Values in Ω 9.88 9.92 9.41
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Values in μΩ 11.3 11.8 11.5
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 49 37 09 Y 49 37 09 B 49 37 09
6.0 Operation Counter Reading :
Before After 00052 00055 7.0 Control circuit and operational checks : Sr. No Description Remarks 7.1 Manual charging of spring OK 7.2 Mechanical Closing and Tripping OK 7.3 Electrical Closing and Tripping OK 7.4 Mechanical interlocks of breaker OK 7.5 Charging of spring through motor OK 7.6 Electrical interlocks of breaker OK 7.7 Abnormality, if any NONE
8.0 Maintenance and general check – up :
Sr. No Description Remarks 8.1 Inspection for physical damage OK 8.2 Breaker aux. switch contact healthiness OK 8.3 Spring charging mechanism operation OK 8.4 Cleaning and tightness of breaker bolts OK 8.5 Breaker rack – in and rack – out OK 8.6 Alignment of breaker OK 8.7 Earthing connection OK 8.8 Greasing of moving parts OK 8.9 Abnormality, if any NONE
9.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF LT CIRCUIT BREAKER Client GUJARAT FLUOROCHEMICAL LIMITED, DAHEJ Tested on 07.03.2025 Plant PVDF EV LINE – 02 SUB – STATION Tested by ABZ Location P – 12 SFD – 2 (HEATER – 1) 415 V LT PANEL
1.0 Name Plate details :
1.1 Make : SIEMENS 1.2 Breaker type : WA111250M 1.3 Serial No. :0E/230208600011 1.4 Rated voltage : 690V 1.5 Rated current : 1250A 1.6 No. of Pole :3 1.7 Breaking Current : 66kA 1.8 Short Time Current : 66kA 1s
2.0 Insulation Resistance Test :
Insulation Resistance Close Condition Open Condition Test @ 500 V RY YB BR RE YE BE RR’ YY’ BB’ Values in Ω >1G >1G >1G >1G >1G >1G >1G >1G >1G
3.0 Coil Resistance Measurement :
Coil resistance of Motor Closing Coil Tripping Coil Values in Ω 8.33 8.80 9.26
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Values in μΩ 11.4 11.3 12.1
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 46 35 09 Y 46 35 09 B 46 35 09
6.0 Operation Counter Reading :
Before After 00102 00106 7.0 Control circuit and operational checks : Sr. No Description Remarks 7.1 Manual charging of spring OK 7.2 Mechanical Closing and Tripping OK 7.3 Electrical Closing and Tripping OK 7.4 Mechanical interlocks of breaker OK 7.5 Charging of spring through motor OK 7.6 Electrical interlocks of breaker OK 7.7 Abnormality, if any NONE
8.0 Maintenance and general check – up :
Sr. No Description Remarks 8.1 Inspection for physical damage OK 8.2 Breaker aux. switch contact healthiness OK 8.3 Spring charging mechanism operation OK 8.4 Cleaning and tightness of breaker bolts OK 8.5 Breaker rack – in and rack – out OK 8.6 Alignment of breaker OK 8.7 Earthing connection OK 8.8 Greasing of moving parts OK 8.9 Abnormality, if any NONE
9.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF HT CIRCUIT BREAKER Client GUJARAT FLUOROCHEMICAL LIMITED, DAHEJ Tested on 08.03.2025 Plant PVDF LINE – 2 11 KV HT SWBD Tested by ABZ Location P – 09 EV TRAFO FEEDER – 01, 11KV HTP
1.0 Name Plate Details :
1.1 Make : SIEMENS 1.2 Breaker Type : 3AK6532-A 1.3 Serial No. : N818419 1.4 Rated Voltage : 12kV 1.5 Rated Current : 1250A 1.6 Breaking Current : 40kA 1.7 Short Time Current : 40kA1.s
2.0 Insulation Resistance Test :
Insulation Resistance Close Condition Open Condition Test @ 5 kV RY YB BR RE YE BE RR’ YY’ BB’ Values in Ω >1T >1T >1T >1T >1T >1T >1T >1T >1T
3.0 Coil Resistance Measurement :
Coil resistance of Closing Coil TC – 1 TC – 2 Motor Winding Values in Ω 61.5 61.6 249 8.8
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Values in µΩ 24.4 25.5 23.6
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 70 51 66 Y 70 51 66 B 70 51 65
6.0 Vacuum Interrupter Test :
Test Voltage : 15 kV Phase Result R – R’ OK Y – Y’ OK B – B’ OK
7.0 Operation Counter reading :
Before After 00328 00332 8.0 Control Circuit and Operational Checks : Sr. No. Description Remark 8.1 Manual charging of spring OK 8.2 Mechanical closing and tripping REMARK 8.3 Mechanical interlocks of breaker OK 8.4 Charging of spring through Motor OK 8.5 Electrical interlocks of breaker OK 8.6 Electrical closing and tripping OK 8.7 Abnormality, if any REMARK
9.0 Maintenance and General Check – Up :
Sr. No. Description Remark 9.1 Inspection for physical damage OK 9.2 Lubrication of all Moving Parts of Mechanism OK 9.3 Oiling of Closing & Tripping Coil OK 9.4 Checking of Gear Box Operation OK 9.5 Checking of Test/Service Aux. Switch Operation OK 9.6 Checking of Tripping Mechanism Operation OK 9.7 Breaker aux. switch contact healthiness OK 9.8 Spring charging mechanism operation OK 9.9 Spring Charging Limit Switch Operation OK 9.10 Checking of contact arm assembly and complete Cleaning of contact surface OK 9.11 Checking of circlips & lock washers of VCB OK 9.12 Checking of Breaker ON/OFF Operation manually & electrically OK 9.13 Cleaning and tightness of breaker bolts & wiring OK 9.14 Breaker rack–in and rack–out OK 9.15 Earth Bus Continuity OK 9.16 Alignment of breaker OK 9.17 Abnormality, if any NONE
10.0 Remarks : TESTED AS ABOVE
10.1 TRIPPING PLUNGER FOUND OPEN AND SAME HAS BEEN NOTIFIED TEST CERTIFICATE OF HT CIRCUIT BREAKER Client GUJARAT FLUOROCHEMICAL LIMITED, DAHEJ Tested on 08.03.2025 Plant PVDF LINE – 02 11 KV HT SWBD Tested by ABZ Location P – 12 INCOMER FEEDER 11 KV HTP
1.0 Name Plate Details :
1.1 Make : SIEMENS 1.2 Breaker Type : 3AK6532-A 1.3 Serial No. : N818747 1.4 Rated Voltage : 12kV 1.5 Rated Current : 1250A 1.6 Breaking Current : 40kA 1.7 Short Time Current : 40KA3.s
2.0 Insulation Resistance Test :
Insulation Resistance Close Condition Open Condition Test @ 5 kV RY YB BR RE YE BE RR’ YY’ BB’ Values in Ω >1T >1T >1T >1T >1T >1T >1T >1T >1T
3.0 Coil Resistance Measurement :
Coil resistance of Closing Coil TC – 1 TC – 2 Motor Winding Values in Ω 61.7 60.1 267.8 7.6
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Values in µΩ 23.9 22.9 22.6
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 49 42 44 Y 49 42 44 B 49 42 44
6.0 Vacuum Interrupter Test :
Test Voltage : 15 kV Phase Result R – R’ OK Y – Y’ OK B – B’ OK
7.0 Operation Counter reading :
Before After 00568 00571 8.0 Control Circuit and Operational Checks : Sr. No. Description Remark 8.1 Manual charging of spring OK 8.2 Mechanical closing and tripping OK 8.3 Mechanical interlocks of breaker OK 8.4 Charging of spring through Motor OK 8.5 Electrical interlocks of breaker OK 8.6 Electrical closing and tripping OK 8.7 Abnormality, if any NONE
9.0 Maintenance and General Check – Up :
Sr. No. Description Remark 9.1 Inspection for physical damage OK 9.2 Lubrication of all Moving Parts of Mechanism OK 9.3 Oiling of Closing & Tripping Coil OK 9.4 Checking of Gear Box Operation OK 9.5 Checking of Test/Service Aux. Switch Operation OK 9.6 Checking of Tripping Mechanism Operation OK 9.7 Breaker aux. switch contact healthiness OK 9.8 Spring charging mechanism operation OK 9.9 Spring Charging Limit Switch Operation OK 9.10 Checking of contact arm assembly and complete Cleaning of contact surface OK 9.11 Checking of circlips & lock washers of VCB OK 9.12 Checking of Breaker ON/OFF Operation manually & electrically OK 9.13 Cleaning and tightness of breaker bolts & wiring OK 9.14 Breaker rack–in and rack–out OK 9.15 Earth Bus Continuity OK 9.16 Alignment of breaker OK 9.17 Abnormality, if any NONE
10.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF HT CIRCUIT BREAKER Client GUJARAT FLUOROCHEMICAL LIMITED, DAHEJ Tested on 08.03.2025 Plant PVDF LINE – 2 11 KV HT SWBD Tested by ABZ Location P – 10 FILM TRAFO FEEDER – 2 , 11KV HT PANEL
1.0 Name Plate Details :
1.1 Make : SIEMENS 1.2 Breaker Type : 3AK6532-A 1.3 Serial No. : N818679 1.4 Rated Voltage : 12kV 1.5 Rated Current : 1250A 1.6 Breaking Current : 40kA 1.7 Short Time Current : 40Ka3.s
2.0 Insulation Resistance Test :
Insulation Resistance Close Condition Open Condition Test @ 5 kV RY YB BR RE YE BE RR’ YY’ BB’ Values in Ω >1T >1T >1T >1T >1T >1T >1T >1T >1T
3.0 Coil Resistance Measurement :
Coil resistance of Closing Coil TC – 1 TC – 2 Motor Winding Values in Ω 60.7 61.7 252.7 6.3
4.0 Contact Resistance Measurement :
Contact resistance of R – Phase Y – Phase B – Phase Values in µΩ 24.9 25.7 26.7
5.0 Time Interval Test :
Phase Closing time (ms) Open time (ms) C/O time (ms) R 54 50 64 Y 54 50 64 B 54 50 64
6.0 Vacuum Interrupter Test :
Test Voltage : 15 kV Phase Result R – R’ OK Y – Y’ OK B – B’ OK
7.0 Operation Counter reading :
Before After 319 324 8.0 Control Circuit and Operational Checks : Sr. No. Description Remark 8.1 Manual charging of spring OK 8.2 Mechanical closing and tripping REMARK 8.3 Mechanical interlocks of breaker OK 8.4 Charging of spring through Motor OK 8.5 Electrical interlocks of breaker OK 8.6 Electrical closing and tripping OK 8.7 Abnormality, if any REMARK
9.0 Maintenance and General Check – Up :
Sr. No. Description Remark 9.1 Inspection for physical damage OK 9.2 Lubrication of all Moving Parts of Mechanism OK 9.3 Oiling of Closing & Tripping Coil OK 9.4 Checking of Gear Box Operation OK 9.5 Checking of Test/Service Aux. Switch Operation OK 9.6 Checking of Tripping Mechanism Operation OK 9.7 Breaker aux. switch contact healthiness OK 9.8 Spring charging mechanism operation OK 9.9 Spring Charging Limit Switch Operation OK 9.10 Checking of contact arm assembly and complete Cleaning of contact surface OK 9.11 Checking of circlips & lock washers of VCB OK 9.12 Checking of Breaker ON/OFF Operation manually & electrically OK 9.13 Cleaning and tightness of breaker bolts & wiring OK 9.14 Breaker rack–in and rack–out OK 9.15 Earth Bus Continuity OK 9.16 Alignment of breaker OK 9.17 Abnormality, if any NONE