0% found this document useful (0 votes)
14 views11 pages

Introduction to Modbus

Modbus is an industrial communication protocol developed in the late 1970s for connecting programmable logic controllers (PLCs), operating on a master/slave model. It supports various data types, including coils, discrete inputs, input registers, and holding registers, and can be implemented over serial (Modbus RTU) or Ethernet (Modbus TCP) connections. The protocol is widely used due to its open specification and royalty-free usage, allowing for flexible integration of industrial devices.

Uploaded by

nooruddinkhan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
14 views11 pages

Introduction to Modbus

Modbus is an industrial communication protocol developed in the late 1970s for connecting programmable logic controllers (PLCs), operating on a master/slave model. It supports various data types, including coils, discrete inputs, input registers, and holding registers, and can be implemented over serial (Modbus RTU) or Ethernet (Modbus TCP) connections. The protocol is widely used due to its open specification and royalty-free usage, allowing for flexible integration of industrial devices.

Uploaded by

nooruddinkhan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 11

Introduction to Modbus

What is Modbus?
Modbus is an industrial protocol standard that was created by Modicon, now Schneider
Electric, in the late 1970’s for communication among programmable logic controllers
(PLCs). Modbus remains the most widely available protocol for connecting industrial
devices. The Modbus protocol specification is openly published and use of the protocol
is royalty-free.
Modbus protocol is defined as a master/slave protocol, meaning a device operating as a
master will poll one or more devices operating as a slave. This means a slave device
cannot volunteer information; it must wait to be asked for it. The master will write data to
a slave device’s registers, and read data from a slave device’s registers. A register
address or register reference is always in the context of the slave’s registers.
The most commonly used form of Modbus protocol is RTU over RS-485. Modbus RTU
is a relatively simple serial protocol that can be transmitted via traditional UART
technology. Data is transmitted in 8-bit bytes, one bit at a time, at baud rates ranging
from 1200 bits per second (baud) to 115200 bits per second. The majority of Modbus
RTU devices only support speeds up to 38400 bits per second.

A Modbus RTU network has one Master and one or more Slaves. Each slave has a
unique 8-bit device address or unit number. Packets sent by the master include the

1|Page
address of the slave the message is intended for. The slave must respond only if its
address is recognized, and must respond within a certain time period or the master will
call it a "no response" error.
Each exchange of data consists of a request from the master, followed by a response
from the slave. Each data packet, whether request or response, begins with the device
address or slave address, followed by function code, followed by parameters defining
what is being asked for or provided. The exact formats of the request and response are
documented in detail in the Modbus protocol specification. The general outline of each
request and response is illustrated below.

Modbus data is most often read and written as "registers" which are 16-bit pieces of
data. Most often, the register is either a signed or unsigned 16-bit integer. If a 32-bit
integer or floating point is required, these values are actually read as a pair of registers.
The most commonly used register is called a Holding Register, and these can be read
or written. The other possible type is Input Register, which is read-only.
The exceptions to registers being 16 bits are the coil and the discrete input, which are
each 1 bit only. Coils can be read or written, while discrete inputs are read-only. Coils
are usually associated with relay outputs.
The type of register being addressed by a Modbus request is determined by the function
code. The most common codes include 3 for "read holding registers", and may read 1 or
more. Function code 6 is used to write a single holding register. Function code 16 is
used to write one or more holding registers.

Visualizing Data in the Modbus Device


Modbus slave devices can be visualized as having an internal spread sheet filled with
numbers. The Modbus master will ask a slave for its data value or number found in a
given row and column, and the slave will respond by sending that piece of data back to
the master. Of course, this process can be reversed with the Modbus master telling the
slave what number to put into its data table at a given row and column.

2|Page
The "columns" in a Modbus device's "spread sheet" are more formally known as register
types. Register type may be a coil, a discrete input (aka status input), an input register,
or a holding register.
The "rows" in a Modbus device's "spread sheet" are simply the register number. Most
often, these start at 1 and count up sequentially. Some devices might not have a
register 1, and their first register may be number 100 for example. If the register number
does not exist in the slave device, it will send back an "oops" message properly known
as an exception. The exception provides an error code that says "no such register"
(exception code 2, illegal data address).

What is Modbus TCP?


Modbus TCP encapsulates Modbus RTU request and response data packets in a TCP
packet transmitted over standard Ethernet networks. The unit number is still included
and its interpretation varies by application – the unit or slave address is not the primary
means of addressing in TCP. The address of most importance here is the IP address,
e.g. 192.168.1.100. The standard port for Modbus TCP is 502, but port number can
often be reassigned if desired.
The checksum field normally found at the end of an RTU packet is omitted from the
TCP packet. Checksum and error handling are handled by Ethernet in the case of
Modbus TCP.
The TCP version of Modbus follows the OSI Network Reference Model. Modbus TCP
defines the presentation and application layers in the OSI model.
Modbus TCP makes the definition of master and slave less obvious because Ethernet
allows peer to peer communication. The definition of client and server are better known

3|Page
entities in Ethernet based networking. In this context, the slave becomes the server and
the master becomes the client. There can be more than one client obtaining data from a
server. In Modbus terms, this means there can be multiple masters as well as multiple
slaves. Rather than defining master and slave on a physical device by device basis, it
now becomes the system designer’s responsibility to create logical associations
between master and slave functionality.

What is Modbus ASCII?


Modbus ASCII is an older implementation that contains all of the elements of an RTU
packet, but expressed entirely in printable ASCII characters. Modbus ASCII is
considered deprecated, is rarely used any more, and is not included in the formal
Modbus protocol specification.

Review of Modbus Register Types


The types of registers referenced in Modbus devices include the following:
• Coil (Discrete Output)
• Discrete Input (or Status Input)
• Input Register
• Holding Register
Whether a particular device includes all of these register types is up to the
manufacturer. It is very common to find all I/O mapped to holding registers only. Coils
are 1-bit registers, are used to control discrete outputs, and may be read or written.
Discrete Inputs are 1-bit registers used as inputs, and may only be read. Input registers
are 16-bit registers used for input, and may only be read. Holding registers are the most
universal 16-bit register, may be read or written, and may be used for a variety of things
including inputs, outputs, configuration data, or any requirement for "holding" data.
Control Solutions gateways will support all register types when the gateway is the
master, or when operating in direct mode (Babel Buster SP-GW). Control Solutions
gateways that connect a non-Modbus device to a Modbus network will in some cases
use only holding registers to represent the non-Modbus device data.
Most Control Solutions I/O devices use holding registers for all types of inputs and
outputs. In most cases, the same I/O is accessible as other register types as well, with
the I/O status or value being mirrored in multiple registers.

Review of Modbus Function Codes


Modbus protocol defines several function codes for accessing Modbus registers. There
are four different data blocks defined by Modbus, and the addresses or register
numbers in each of those overlap. Therefore, a complete definition of where to find a
piece of data requires both the address (or register number) and function code (or
register type).

4|Page
The function codes most commonly recognized by Modbus devices are indicated in the
table below. This is only a subset of the codes available - several of the codes have
special applications that most often do not apply.
Modbus Function Codes Recognized by CSI Gateways
Function Code Register Type
1 Read Coil
2 Read Discrete Input
3 Read Holding Registers
4 Read Input Registers
5 Write Single Coil
6 Write Single Holding Register
15 Write Multiple Coils
16 Write Multiple Holding Registers

Review of Modbus Exception (error) Codes


When a Modbus slave recognizes a packet, but determines that there is an error in the
request, it will return an exception code reply instead of a data reply. The exception
reply consists of the slave address or unit number, a copy of the function code with the
high bit set, and an exception code. If the function code was 3, for example, the function
code in the exception reply will be 0x83. The exception codes will be one of the
following:
The function code received in the query is not recognized by
1 Illegal Function
the slave or is not allowed by the slave.
The data address (register number) received in the query is
Illegal Data not an allowed address for the slave, i.e., the register does
2
Address not exist. If multiple registers were requested, at least one
was not permitted.
Illegal Data The value contained in the query's data field is not
3
Value acceptable to the slave.
Slave Device An unrecoverable error occurred while the slave was
4
Failure attempting to perform the requested action
Slave Device The slave is engaged in processing a long-duration
6
Busy command. The master should try again later.
Gateway Path Specialized use in conjunction with gateways, usually means
10
Unavailable the gateway is misconfigured or overloaded
Gateway Target
Specialized use in conjunction with gateways, indicates no
11 Device Failed
response was received from the target device.
to Respond

5|Page
Where do I Start for Communicating with My Modbus
Device?
Here are the first few things you need to find out:

(1) What is the physical connection?

Modbus RTU uses RS-485 or RS-232. Modbus TCP uses Ethernet. If you are looking
for a Control Solutions gateway, you will need to pick the model that matches the
electrical interface of the equipment you want to connect. If you are choosing a Control
Solutions I/O device, pick one that matches your network.

(2) How are the registers mapped?

When using a gateway to interface a Modbus device to a non-Modbus network, you


need to get documentation from the equipment manufacturer that describes the
available registers and how to address them. Modbus protocol does not provide a
means for registers to automatically identify themselves. Control Solutions cannot
determine this information for you. You must consult the equipment manufacturer.

When using Control Solutions I/O devices (such as AddMe III) you will find this
information in the online help files that came with the device, or on our web site.

(3) What are the communication parameters?

Modbus RTU requires that you know or define baud rate, character format (8 bits no
parity, etc), and slave ID (aka slave address, unit number, unit ID). A mis-match in any
of these will result in no communication.

Modbus TCP requires that you know or define IP addresses on the network. In some
cases, you also need unit ID's. Control Solutions Modbus TCP devices may use the unit
ID, or may ignore it, depending on the device and the application.

Modbus: When 40001 Really Means 1, or 0 Really Means


1
Documentation for Modbus is not well standardized. Actually there is a standard, but not
well followed when it comes to documentation. You will have to do one or more of the
following to decipher which register a manufacturer is really referring to:
a) Look for the register description, such as holding register, coil, etc. If the
documentation says #1, and tells you they are holding registers, then you have holding
register #1. You also have user friendly documentation.

6|Page
b) Look at the numbers themselves. If you see the first register on the list having a
number 40001, that really tells you register #1, and it is a holding register. This form of
notation is often referred to as the old Modicon convention.
c) Look for a definition of function codes to be used. If you see a register #1, along with
notation telling you to use function codes 3 and 16, that also tells you it is holding
register #1.
IMPORTANT: Register 1 is address 0. Read on…
d) Do the numbers in your documentation refer to the register number or address?
Register #1 is address zero. If it is not clear whether your documentation refers to
register or address, and you are not getting the expected result, try plus or minus one
for register number. All Control Solutions products refer to register numbers in
configuration software or web pages. However, some manufacturers document their
devices showing address, not register numbers. When you have addresses, you must
add one when entering that register into configuration software from Control Solutions.

40001: Modicon Convention Notation for Modbus


Registers
Modbus was originally developed by Gould-Modicon, which is presently Schneider
Electric. The notation originally used by Modicon is still often used today, even though
considered obsolete by present Modbus-IDA standards. The advantage in using the
Modicon notation is that two pieces of information are included in a single number: (a)
The register type; (b) The register number. A register number offset defines the type.
Note: Only the LonWorks versions of Babel Buster gateways use this notation as short
hand to conserve CP space. Many other equipment manufacturers still use this
convention in their products. Depending on which combination of products you are
using, you may have to translate between Modicon and current conventions.
The types of registers referenced in Modbus devices, and supported by Babel Buster
gateways, include the following:
• Coil (Discrete Output)
• Discrete Input (or Status Input)
• Input Register
• Holding Register
Valid address ranges as originally defined for Modbus were 0 to 9999 for each of the
above register types. Valid ranges allowed in the current specification are 0 to 65,535.
The address range originally supported by Babel Buster gateways was 0 to 9999. The
extended range addressing was later added to all new Babel Buster products.
The address range applies to each type of register, and one needs to look at the
function code in the Modbus message packet to determine what register type is being
referenced. The Modicon convention uses the first digit of a register reference to identify
the register type.

7|Page
Register types and reference ranges recognized with Modicon notation are as follows:
0x = Coil = 00001-09999
1x = Discrete Input = 10001-19999
3x = Input Register = 30001-39999
4x = Holding Register = 40001-49999
On occasion, it is necessary to access more than 10,000 of a register type. Based on
the original convention, there is another de facto standard that looks very similar.
Additional register types and reference ranges recognized with Modicon notation are as
follows:
0x = Coil = 000001-065535
1x = Discrete Input = 100001-165535
3x = Input Register = 300001-365535
4x = Holding Register = 400001-465535
When using the extended register referencing, it is mandatory that all register
references be exactly six digits. This is the only way Babel Buster will know the
difference between holding register 40001 and coil 40001. If coil 40001 is the target, it
must appear as 040001.

Registers Are 16-bits - How Do I Read Floating Point or


32-bit Data?
Modbus protocol defines a holding register as 16 bits wide; however, there is a widely
used de facto standard for reading and writing data wider than 16 bits. The most
common are IEEE 754 floating point, and 32-bit integer. The convention may also be
extended to double precision floating point and 64-bit integer data.

The wide data simply consists of two consecutive "registers" treated as a single wide
register. Floating point in 32-bit IEEE 754 standard, and 32-bit integer data, are widely
used. Although the convention of register pairs is widely recognized, agreement on
whether the high order or low order register should come first is not standardized. For
this reason, many devices, including all Control Solutions gateways, support a "swap"
option. This means you simply check the "swapped" option if the other device treats
wide data in the opposite order relative to Control Solutions default order. In some
cases, the “swap” option is more explicitly identified as “high order data is in first
register” or something to that effect.

Most Control Solutions Modbus products default to placing the high order register first,
or in the lower numbered register. This is known as "big endian", and is consistent with
Modbus protocol which is by definition big endian itself. The byte order for all 16-bit
values is most significant byte first.

What Does Notation Like 40001:7 Mean?

8|Page
This is a commonly used notation for referencing individual bits in a register. This
particular example references (Modicon notation) register 40001, bit 7. Bits are
generally numbered starting at bit 0, which is the least significant or right most bit in the
field of 16 bits found in a Modbus register. If this style notation is used, you may see
40001:0 through 40001:15.

How Do I Read Individual Bits in a Register?


Documentation tends to be slightly different for every Modbus device. But if your device
packs multiple bits into a single holding register, the documentation will note up to 16
different items found at the same register number or address. The bits may be identified
with “Bn” or “Dn” or just “bit n”. Most of the time, the least significant bit will be called bit
0 and the most significant will be bit 15. It is possible you could find reference to bit 1
through bit 16, in which case just subtract one from the number to reference the table
below.
You cannot read just one bit from a holding register. There is no way to do that -
Modbus protocol simply does not provide that function. You must read all 16 bits, and
then test the individual bit you are interested in for true or false (1 or 0). Babel Buster
gateways provide an automatic way of doing that by including a "mask" in each register
map or rule. Each time the register is read, the mask will be logically AND-ed with the
data from the register, and the result will be right justified to yield a 1 or 0 based on
whether the selected bit was 1 or 0. Babel Buster gateways provide optimization when
successive read maps or rules are selecting different bits from the same register. The
Modbus register will be read from the slave once, and the 16-bit data will be shared with
successive maps or rules, with each map or rule selecting its bit of interest.
The bit mask shown in the expanded form of the Babel Buster RTU read map is a 4 digit
hexadecimal (16 bit) value used to mask out one or more bits in a register. The selected
bits will be right justified, so a single bit regardless of where positioned in the source
register will be stored locally as 0 or 1. The hex bit mask values would be as follows:
B0/D0/bit 0 mask = 0001
B1/D1/bit 1 mask = 0002
B2/D2/bit 2 mask = 0004
B3/D3/bit 3 mask = 0008
B4/D4/bit 4 mask = 0010
B5/D5/bit 5 mask = 0020
B6/D6/bit 6 mask = 0040
B7/D7/bit 7 mask = 0080
B8/D8/bit 8 mask = 0100
B9/D9/bit 9 mask = 0200
B10/D10/bit 10 mask = 0400
B11/D11/bit 11 mask = 0800
B12/D12/bit 12 mask = 1000
B13/D13/bit 13 mask = 2000
B14/D14/bit 14 mask = 4000
B15/D15/bit 15 mask = 8000

9|Page
Some Modbus devices also back two 8-bit values into a single 16-bit register. The two
values will typically be documented as “high byte” and “low byte” or simply have “H” and
“L” indicated. If you run into this scenario, the masking for bytes is as follows:
High byte mask = FF00
Low byte mask = 00FF
When the mask value in a Babel Buster gateway is more than just one bit, the mask is
still logically AND-ed with the data from the Modbus slave, and the entire resulting value
is right justified to produce an integer value of less than the original bit width of the
original register.
There have been a few instances of documenting packed bits in a 32-bit register.
Although Modbus protocol is strictly 16-bit registers, some implementations force you to
read pairs of registers. If your device documents 32 packed bits, then you would insert
0000 in front of each mask above, and the remainder of the list would be as follows:
B16/D16/bit 16 mask = 00010000
B17/D17/bit 17 mask = 00020000
B18/D18/bit 18 mask = 00040000
B19/D19/bit 19 mask = 00080000
B20/D20/bit 20 mask = 00100000
B21/D21/bit 21 mask = 00200000
B22/D22/bit 22 mask = 00400000
B23/D23/bit 23 mask = 00800000
B24/D24/bit 24 mask = 01000000
B25/D25/bit 25 mask = 02000000
B26/D26/bit 26 mask = 04000000
B27/D27/bit 27 mask = 08000000
B28/D28/bit 28 mask = 10000000
B29/D29/bit 29 mask = 20000000
B30/D30/bit 30 mask = 40000000
B31/D31/bit 31 mask = 80000000

Can I Put 2 Gateways on the Same Modbus Network?


You can not have more than one Master on a Modbus RTU (RS-485) network.
Therefore, if the gateway is to be configured as the Master, you can only have 1
gateway. You cannot use multiple gateways to read more points from the same Modbus
slave device.
Multiple gateways configured as slaves can reside on the same Modbus RS-485
network.
If you are using RS-232 devices, you can have only two devices total, regardless of how
they are configured. RS-232 is not multi-drop.

How Many Devices Can I Have on a Modbus Network?

10 | P a g e
Logically you can address over 250 devices; however, the RS-485 transceivers are not
capable of physically driving that many devices. Modbus protocol states that the limit is
32 devices, and most RS-485 transceivers will agree with this. Only if all devices on the
network have low load transceivers can you have more than 32 devices.

Where Can I Get a Copy of the Modbus Protocol


Specification?
You can get a copy of the Modbus protocol specification by visiting www.modbus.org.
There are three documents of primary interest: (1) The application layer protocol which
defines the function codes and addressing; (2) The definition of use over a serial line
(RTU); (3) The definition of use over Ethernet (TCP). You will be asked to accept terms
of use, but there is no cost for these specifications.

11 | P a g e

You might also like