DFU5010020 CAST XFP 1 or 2 Loop 32 Zone Engineering Manual Rev 5
DFU5010020 CAST XFP 1 or 2 Loop 32 Zone Engineering Manual Rev 5
Networkable
Analogue Addressable
Fire Alarm Control Panel
Engineering
Manual
Approved Document No. DFU5010020 Rev 5 01/10/21
CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
AL2
ENTER ACCESS LEVEL 3
Total Alarms = nn
DISPLAY FIRE EVENTS *
Alarms Since nn/nn/nn = nn Clear to todays date?
DISPLAY FAULT EVENTS *
Alarms Since nn/nn/nn = nn
DISPLAY DISABLEMENTS *
DISPLAY ZONES IN TEST *
PRINT EVENT HISTORY
LAMP TEST
DISPLAY EVENT HISTORY
DISPLAY ALARM COUNTER
RESET EVENT HISTORY
SET TIME/DATE
EVENT LOG FUNCTIONS
SET/CLEAR DISABLEMENTS ENABLE/DISABLE ZONES
CHANGE ACCESS LEVEL 2 CODE ENABLE/DISABLE SOUNDERS
ENABLE/DISABLE OUTPUTS
ENABLE/DISABLE RELAYS
AL3 CODE ENABLE/DISABLE DEVICES
ENTRY ENABLE/DISABLE FAULT RELAY
ENABLE/DISABLE OUTPUT DELAYS
AL3
DISPLAY FIRE EVENTS * CHANGE ACCESS LEVEL 2 CODE
DISPLAY FAULT EVENTS * CHANGE ACCESS LEVEL 3 CODE
DISPLAY DISABLEMENTS *
DISPLAY ZONES IN TEST * SET COMMS FUNCTION
SETUP PASSWORDS SET PANEL NUMBER
CONNECT TO PC SET PANEL FITTED
NETWORK FUNCTIONS
COMMISSIONING FUNCTIONS LOOP LEARN
ENGINEER FUNCTIONS ADDRESS FUNCTIONS AUTO ADDRESS
SHOW FITTED DEVICES REPLACE/ADD DEVICE
ASSIGN ZONE/GROUP CHANGE ADDRESS
SET DAY/NIGHT TIMES SHOW DUPLICATE ADDRESSES
ENABLE/DISABLE DST ADJUSTMENT FIX DUPLICATE ADDRESSES
CONFIGURE SOUNDER DISABLEMENTS IDENTIFY LOOP CHANGES
SWAPPED DEVICE DETECTION
CONFIGURE POLLING LED
MAKE A CLEAN START
CONTENTS
Important notes.................................................................................................................................... 4
Key features.......................................................................................................................................... 5
Maintenance....................................................................................................................................... 47
Manufacturer: Computionics Limited (C-TEC), Challenge Way, Martland Park, Wigan, Lancashire WN5 0LD. www.c-tec.com
IMPORTANT NOTES
This equipment MUST only be installed and maintained by a suitably skilled and
technically competent person. Ensure you have attended C-TEC’s Authorised Training
Course before handling the panel.
This equipment is a piece of Class 1 permanently connected equipment and MUST BE EARTHED.
CAUTION: DO NOT connect or disconnect the panel’s internal wiring / looms, or terminate
field wiring at the PCBs, with the panel’s power applied (either mains or battery). Failure to
observe this WILL destroy the panel’s electronic components and the warranty will be void.
System design
Fire alarm system design is beyond the scope of this document. A basic understanding of general fire
alarm system components and their use is assumed. Contact the Fire Officer concerned with the property
at an early stage in case there are any special requirements. We strongly recommend that a suitably
qualified and competent person is consulted regarding the design of the fire alarm system and that
the system is commissioned and serviced in accordance with the laid down specification and national
standards. In the UK we recommend you read BS 5839: “Fire Detection and Alarm Systems for Buildings
(Code of Practice for System Design, Installation, Commissioning and Maintenance)”. Other national, or
local standards of installation should be referenced where applicable.
Equipment guarantee
This equipment is NOT guaranteed unless the complete installation is installed and commissioned in
accordance with the laid down national standards (in the UK this is BS 5839 Part 1) by an approved
and competent person or organisation.
Anti-static handling guidelines
Always observe appropriate electro-static handling guidelines before handling the panel’s
PCBs, or any other static-sensitive components.
KEY FEATURES
The CAST XFP 1 loop, 32 zone (Part No. XFP501/CA) and CAST XFP 2 loop, 32 zone (Part No. XFP502/CA)
analogue addressable fire alarm panels are designed for use with fire and security systems and offer
the following features:
• Certification by the LPCB to EN54 parts 2 and 4.
• Full compatibility with C-TEC’s CAST® (C-TEC Addressable System Technology) - a powerful,
proprietary communication protocol.
• Short-circuit protected loop drivers (rated at 450mA max, 40V), each capable of supporting up to
255 addressable CAST devices per loop, giving 510 devices for a 2 loop panel. Each CAST Loop
device is fitted with a short-circuit isolator.
• Two CAST device addressing options - automatically by the panel (AUTO ADDRESS & LOOP LEARN
functions), or manually using the CAST Handheld Programmer (Part No. CAPROG).
• Ability to change a device’s address.
• Ability to detect and fix duplicate addresses.
• Ability to detect swapped loop devices.
• Ability to turn all device polling LEDs on/off.
• Fast response time from fire detection to multiple output groups.
• Two independently programmable conventional sounder circuits.
• Two programmable auxiliary inputs (non-monitored).
• A fault relay output and three programmable relay outputs with volt-free changeover contacts.
• A selection of zone dependency functions (EN54-2 Clause 7.12, type A, B or C) as detailed below:
Type A - If there is an alarm from a detector, the panel will look for a confirmatory alarm from
the same, or another, detector in the same zone before a full alarm is established. If there is no
confirmatory alarm, the first alarm will automatically reset.
Type B - As type A except the confirmatory signal must be from another detector in the same zone.
Type C - As type A except the confirmatory signal may also be from another zone and the first
alarm will not automatically reset.
• A day (building occupied) and night (building unoccupied) timing function.
• An investigation delay period function (programmable for length of time, which zones it applies
to and whether or not it operates in day/night mode).
• Individual sensitivity settings for each device.
• EN54-2 Clause 7.8 re-sounding fire alarm devices.
• EN54-2 Clause 7.11 delays to outputs and a phased evacuation facility.
• EN54-2 Clause 7.13 alarm counter to record the number of alarm states (maximum of 999 counts).
• EN54-2 Clause 8.3 reporting of faults from heat detectors, optical detectors & multi-detectors.
• EN54-2 Clause 9.5 disablements of addressable points individually.
• An integral 2.5A EN54-4 switched mode PSU.
• Earth fault monitoring.
• Keypad code to enter access levels 2 & 3. Keyswitch entry to access level 2.
• 40 characters of custom text per device.
• Comprehensive EN54-2 Clause 10 test with maintenance and commissioning functions.
• Windows based PC programming tools (Part No. XFP507) that MUST be used to configure the system.
• Certified with the following options with requirements from EN 54-2: 1997:
Clause 7.8 output to fire alarm devices.
-
Clause 7.11 delays to outputs and a phased evacuation facility.
-
- Clause 7.12.1 Dependencies on more than one alarm signal – Type A
- Clause 7.12.2 Dependencies on more than one alarm signal – Type B
- Clause 7.12.3 Dependencies on more than one alarm signal – Type C
Clause 7.13 alarm counter to record the number of alarm states (maximum of 999 counts).
-
- Clause 8.3 reporting of faults from points (heat detectors, optical detectors & multi-detectors).
- Clause 9.5 disablements of addressable points individually.
Clause 10 test condition.
-
Note: The CAST XFP network and XFP repeaters
Networking (Optional) have not been assessed to EN54-2.
If required, the panel can be configured to sit on a non-redundant network of up to eight connected
CAST XFP main panels (any variant), OR you can have up to eight XFP repeaters connected to one
non-networked CAST XFP main panel. FOR NETWORK WIRING 2-CORE SCREENED, ENHANCED FIRE-
RESISTANT CABLE IS RECOMMENDED. If you want to utilise either of these options, the panel will
require a separately available network driver card (Part No. AFP711). See pages 13-14 for details.
TELECOMS-STYLE LID/BASE
CONNECTOR CABLE
LCD PCB
MAIN POWER
CONTROL SUPPLY
PCB PCB
SWITCH & INDICATOR PCB
PCB RETAINING
SCREWS
FERRITE CLAMP
TWO-WAY LID/BASE
CONNECTOR CABLE
Fig.2 : Location of mounting holes and knockouts / side view of panel for flush mounting
60mm
These two knockouts are
BASE TOP
reserved for incoming
mains cable only
BASE
WALL
Mains wiring
All wiring should be installed in accordance with the current edition of the IEE Wiring Regs. (BS 7671), or
relevant national standards. The minimum requirement for the mains supply to the panel is fixed wiring
(no less than 1mm2 and no greater than 2.5mm2), either using 3-core cable, or a suitable three conductor
system fed from an isolating switched fused spur at 3A, or a 6A Type B circuit breaker to IEC/EN60898-1.
The mains supply MUST be exclusive to the panel and be reliably earthed at the indicated earthing post.
As an alternative to a switched fused spur, a double-pole isolating switch (S), with 3mm air gaps on the
contacts & switching L & N only, may be used in the mains feed from the Main Distribution Board (A) to
the Panel (C), providing it meets the appropriate wiring regulations (see drawing below).
CAUTION: DO NOT CONNECT MAINS TO THE POWER SUPPLY PCB UNTIL THE INSTALLATION
IS COMPLETE AND ALL RELEVANT PCBs ARE CORRECTLY FITTED IN THE PANEL.
Fig.3 : Power Supply PCB layout and mains connection details (Full Protective Cover & Cable Cover
shown fitted)
Incoming Mains Cable
This cable MUST be segregated
from other cables. Good quality
cable glands MUST always be fitted.
THIS L N
Base Earth Distribution Post
WAY UP
spring
CONN1
nut washer
Fig.4 : Typical analogue addressable loop Hint! Refer to www.c-tec.com for C-TEC’s
CAST range of compatible devices.
Polling
Monitored Input
Polling
Polling
Loop 1
(Loop 2 not
LOOP 1 A (OUT) LOOP 1 B (RETURN)
shown)
Hint! An XFP Loop & Battery Calculator Tool is available for download on C-TEC’s website in
the Support Hub to assist with system designs (available @ www.c-tec.com).
Each loop should be connected to the Main Control PCB terminals marked: A+, A- (LOOP A OUT) and
B+, B- (LOOP B RETURN), as shown in Fig.5 below. The loop’s earth screens should be connected to the
Main Control PCB terminals marked: Eth.
Analogue Loop 1
THIS
LOOP 1A (OUT) LOOP 1B (RETURN) WAY UP
LOOP 1
LOOP 2
PCB
CONN
CO
CONN1
ONNN1
N1
N 1
BAT
FUSE F
3.15 A H
+ _
BAT1
Two conventional sounder circuits are provided. See technical specification (page 48) for circuit
limitations. If a full complement of sounders are to be used, split them equally across both circuits.
A 6k8 end of line (EOL) resistor (provided) MUST be connected at the end of each sounder circuit to
allow the wiring to be monitored. If the sounder circuit is unused, the 6k8 resistor MUST still be fitted
at the panel terminals.
Each sounder circuit should be connected to the Main Control PCB terminals marked: S1+, S1- and S2+,
S2-, as shown in Fig.6 (page 11). Terminate earth screens at the panel’s base earth distribution post, as
shown in Fig.6, page 11.
+
DO NOT SPUR
(Wiring not monitored)
✗
screens
LOOP 1
LOOP 2
Base Earth Distribution Post
spring
washer
Additional Conventional Main Control nut 3 x plain
Sounder Circuit S2 washer
(if required)
PCB
screens
PSU Earth
crimped
Note about earthing of screens connection Distribution
Strap
All screens should be adequately insulated and connected between
the nut and washers on the base earth distribution post using Do not untighten lower nut
crimp connectors. The base earth distribution post is provided
+ –
for terminating earth screens or drains and is NOT the main earthing point.BAT1 The installer must review the
external earth bonding (if required) with respect to the national wiring rules. If the installation requires
protective earth bonding, then this must be applied externally and in conjunction with the type of earthing
system employed on site.
PC/Laptop
The ONLY way to program this panel
SAF7070000
is to use the panel’s PC programming (Molex-to-RS232 Lead)
RS232 Connections
Two new, good quality and fully charged 12V valve regulated lead acid (VRLA) batteries are required
as the emergency stand-by power supply for the panel. The batteries should be connected in series and
located in the panel’s enclosure, as shown in Fig.10 below. Battery leads and link wire are provided in
the panel’s accessory pack. Run the battery leads through the slits in the panel’s lower plastic ribs and
secure the batteries into position using cable ties if required.
The panel’s sophisticated battery monitoring unit protects the batteries against deep discharge by
activating a cut off circuit when the stand-by supply voltage reaches 21V approx. If batteries are not
fitted, are discharged or in poor condition, a PSU fault will show at the panel.
The capacity of the batteries used will depend upon the required stand-by time. To calculate the
batteries required for any given stand-by period, refer to the battery calculation guide on page 47.
battery battery
Black wire to Red wire to
Power Supply PCB Power Supply PCB
(BAT1- terminal) (BAT1+ terminal) Leave adequate clearance for
keyswitch when fitting batteies
Key features of the non-redundant network protocol when used for connecting CAST XFP main panels:
• Allows the connection of up to eight CAST XFP main panels (any mix of 1 loop 16 zone CAST XFPs
and 2 loop 32 zone CAST XFPs)
• Up to 1km of cable may be fitted to a CAST XFP main panel network.
• Each networked CAST XFP main panel can be programmed to:
Accept Fires from other main panels.
Accept Faults from other main panels.
Accept Control actions from other main panels, e.g. Silence Alarm Sounders and Control Panel Reset.
Accept Disablement commands from other main panels for zones, sounders and output sets.
(Each of these four functions may be individually selected via the panel’s PC programming tools.)
• All panels monitor all other panels for network wiring faults.
• Fires on remote panels are displayed on local panels including the point description of the alarm’s origin.
• Faults on remote panels are displayed on local panels.
• Cause and effects can be programmed into local panels dependent on which remote panel is in alarm.
• The network supports the programming of site information into remote panels from a PC
connected at a local panel.
• Time and date is common to all panels throughout the network.
Key features of the non-redundant network protocol when used for connecting XFP repeaters
• Allows the connection of up to eight XFP repeaters (any mix of 1 loop 16 zone repeaters and
2 loop 32 zone repeaters) to any non-networked main panel.
• Up to 500m of cable may be fitted to an XFP repeater network.
• Each XFP repeater offers all the functions and controls of a CAST XFP main panel.
Any CAST XFP main panel connected to the non-redundant network requires the installation of a
network driver card (Part No. AFP711), as shown in Fig.11 below. Repeaters come with a network
driver card already fitted. Typical network wiring details are shown in Fig.12, page 14.
Fig.11: Installing the Network Driver Card
CAUTION: BEFORE INSTALLING THE NETWORK DRIVER CARD, ISOLATE THE MAINS SUPPLY
AND DISCONNECT THE PANEL’S BATTERY BACK-UP SUPPLY.
With reference to the diagram below: I/O RLY1 RLY2 RLY3
• Refit the Main Control PCB and all relevant connection MAIN CONTROL PCB
cables previously removed. Ensure that the PCB retaining Washer
Note: DIP switch (SW1) on the network driver card has no function when used with this panel.
However, all networked CAST XFP main panels require a unique ID number (1 to 8) assigning.
To assign this number and set up network comms, see NETWORK FUNCTIONS page 22 for details.
XFP repeaters DO NOT require an ID number.
The network wiring should be installed to meet BS 5839: Part 1 and BS 7671 (Wiring Regulations) and/or
other national standards of installation where pertinent - see ‘cable types & limitations’, page 4.
IT IS RECOMMENDED THAT 2-CORE SCREENED, ENHANCED FIRE-RESISTANT CABLE ≥1 MM2 IS USED FOR
NETWORK WIRING.
At each network driver card, connect A to A, B to B and terminate incoming and outgoing screens to
terminal C only as shown below.
At ONE network driver card only, connect A to A, B to B and terminate screens to the panel’s base
earth distribution post as shown below.
RS485
A C
B A
RS485
C B
A CONN1
B
CONN1 Panel N
Panel 1
Network
Base Driver
Earth Card
Distribution Network (AFP711)
Post Driver
Card
(AFP711)
FOR OTHER NETWORKED PANELS
DO NOT CONNECT SCREENS TO THE
BASE EARTH DISTRIBUTION POST
AT ONE PANEL ONLY CONNECT SCREEN
TO THE BASE EARTH DISTRIBUTION POST
(PANEL 1 SHOWN ABOVE)
To Next Networked
Panel (If Required)
To Next Networked
Panel (If Required)
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Fire Alarm Control Panel Instructions To view more events use the scroll buttons
General fault
I To silence the internal sounder: press
flashing light - call engineer To silence/resound the alarm sounders: Turn key to l and press
176b OR press and . Enter code and press
O To reset the panel: Ensure all alarm conditions are silenced
and investigations are complete and press
To exit access mode: Remove key
XFP
OR press and hold
EN54-2 & 4 The system must be tested regularly.
Manufactured in England
If in doubt, refer to the user manual.
LED Indicators
Liquid Crystal Display Provides detailed information on the status of the system (the type of messages
displayed and what they mean is covered in greater detail in the panel’s
separate user manual).
(General) Fire Flashes red when there is a fire condition on any zone and goes steady red
when the alarm is silenced. Subsequent fire conditions will restart the (General)
Fire indicator flashing until it is silenced again.
Fire Zones (1-32) One or more of these indicators will flash red in a zone alarm condition and
will go steady when silenced.
Supply Present Normally lit green to show that all of the panel’s power supplies are
functioning correctly.
Test Lit yellow when the panel is in walk test mode. This LED does NOT illuminate
for any other test condition.
General Disablement Lit yellow when one or more zones, sounders, outputs, relays, devices, output
delays are disabled.
General Fault Flashes yellow when there is a fault condition on the panel. Will always
be lit in conjunction with at least one other fault LED.
Power Supply Fault Lit yellow when the panel’s power supply or mains has failed or the panel’s
standby battery is in poor condition.
System Fault Lit amber when a system error, such as a microprocessor fault, occurs AND REMAINS
LIT EVEN IF THE SYSTEM FAULT CLEARS. THIS SYSTEM FAULT LED CAN ONLY BE
CLEARED BY PRESSING THE CONTROL PANEL RESET BUTTON AT AL2 OR AL3.
Sounder Status Flashes yellow when a fault is detected on either of the panel’s two
conventional sounder circuits or if there is a sounder disablement anywhere on
the system.
Delays Running Lit yellow when one or more output delays have been programmed by an
engineer. Flashes yellow when one or more output delays are running.
Button controls
More Information Displays additional information on any fire or fault conditions that appear on
the panel’s display. Will also display additional context dependent information
where appropriate.
(Scroll Up) 51 Dependent on the status of the panel, these two buttons:
(Scroll Down) 63 • scroll vertically through any fire/fault/disablements/test conditions that
appear on the panel’s display
• scroll vertically through the panel’s user menus
• select Yes/No in the panel’s menu options
• manipulate date, time and disablement settings, etc
• serve as code input buttons to access levels 2 or 3.
Silence Internal Sounder Silences the panel’s internal sounder (also serves as a code input button when
performing a clean start, see page 34)
Control Panel Reset Resets the panel when the sounders are silenced (access levels 2 & 3 only)
Silence / Resound Sounders Silences or resounds the system’s sounders (access levels 2 & 3 only)
Investigate Starts the panel’s investigate timer function (access levels 2 & 3 only)
Keyswitch control
I
Turning the keyswitch to the armed position ‘I’ gives the user instant access to
O access level 2 (authorised user level). The key is non-removable in position ‘I’.
AL2
ENTER ACCESS LEVEL 3
Total Alarms = nn
DISPLAY FIRE EVENTS *
Alarms Since nn/nn/nn = nn Clear to todays date?
DISPLAY FAULT EVENTS *
Alarms Since nn/nn/nn = nn
DISPLAY DISABLEMENTS *
DISPLAY ZONES IN TEST *
PRINT EVENT HISTORY
LAMP TEST
DISPLAY EVENT HISTORY
DISPLAY ALARM COUNTER
RESET EVENT HISTORY
SET TIME/DATE
EVENT LOG FUNCTIONS
SET/CLEAR DISABLEMENTS ENABLE/DISABLE ZONES
CHANGE ACCESS LEVEL 2 CODE ENABLE/DISABLE SOUNDERS
ENABLE/DISABLE OUTPUTS
ENABLE/DISABLE RELAYS
AL3 CODE ENABLE/DISABLE DEVICES
ENTRY ENABLE/DISABLE FAULT RELAY
ENABLE/DISABLE OUTPUT DELAYS
AL3
DISPLAY FIRE EVENTS * CHANGE ACCESS LEVEL 2 CODE
DISPLAY FAULT EVENTS * CHANGE ACCESS LEVEL 3 CODE
DISPLAY DISABLEMENTS *
DISPLAY ZONES IN TEST * SET COMMS FUNCTION
SETUP PASSWORDS SET PANEL NUMBER
CONNECT TO PC SET PANEL FITTED
NETWORK FUNCTIONS
COMMISSIONING FUNCTIONS LOOP LEARN
ENGINEER FUNCTIONS ADDRESS FUNCTIONS AUTO ADDRESS
SHOW FITTED DEVICES REPLACE/ADD DEVICE
ASSIGN ZONE/GROUP CHANGE ADDRESS
SET DAY/NIGHT TIMES SHOW DUPLICATE ADDRESSES
ENABLE/DISABLE DST ADJUSTMENT FIX DUPLICATE ADDRESSES
CONFIGURE SOUNDER DISABLEMENTS IDENTIFY LOOP CHANGES
SWAPPED DEVICE DETECTION
CONFIGURE POLLING LED
MAKE A CLEAN START
Enter the four-digit code using the 5(1) 4(2) 6(3)3(4) buttons.
The default code is: 4 4 4 4 (four presses of the Escape3button).
Option 2: By entering access level 2, selecting ENTER ACCESS LEVEL 3 menu and repeating the
procedure above.
In access level 3, the panel’s Silence/Resound Sounders, Control Panel Reset and Investigate buttons
become active and you can:
• Scroll through any fire or fault conditions, disablements or zones in test
• Change the entry codes to access levels 2 and 3 from their factory default settings
• Connect the panel to a compatible PC for system programming
• Set the panel up to belong to a non-redundant network of eight CAST XFP main panels, or
allow it to have up to eight XFP repeaters connected to it
• Gain access to a wide range of commissioning functions including AUTO ADDRESS & LOOP LEARN
• Gain access to a wide range of engineering, test and fault finding functions
• Display firmware version numbers and PSU statistics
• Set the time the panel enters/exits day (building occupied) and night (building unoccupied) mode
• Access the panel’s access level 2 menu options as detailed in the panel’s separate user manual
(Document No. DFU5020000)
To disable the panel’s internal sounder (active in fire & fault conditions), remove PLK5
PLK5 link at the Main Control PCB.
A detailed description of the functions available at access level 3 can be found below.
Pressing the 5and6buttons will scroll the display through all active fire conditions. More detailed
information can be viewed by pressing the panel’s More Information button.
Pressing the 5and6buttons will scroll the display through all active faults. More detailed information
can be viewed by pressing the panel’s More Information button.
DISPLAY DISABLEMENTS
This function is only available when there are active disablements on the system.
Enter AL3 (4444) > Display Disablements.
If available, press the Accept4button and a window similar to the one below will appear:
Pressing the 5and6buttons will scroll the display through all active disablements.
Pressing the 5and6buttons will scroll the display through all zones currently in test.
SETUP PASSWORDS
This function allows you to change the access codes required to enter the panel’s access level 2 or 3
menu options.
When selected, press the Accept4button and the following window will appear:
Press the 5and6buttons to scroll to the desired option and press the Accept4button. The following
message will appear if the CHANGE ACCESS LEVEL 2 CODE prompt is selected:
Using the 5(1) 4(2) 6(3)3(4) buttons, enter the new four digit access level 2 code. After the fourth
digit has been entered, the panel will request you confirm the new code by re-entering it.
Enter the code again by pressing the 5(1) 4(2) 6(3)3(4) buttons in same sequence. If the two codes
match, the new code will be accepted. If you type an incorrect confirmation code, you will be prompted
to start the code entry sequence again. The same process can be used to change the access level 3 code.
CONNECT TO PC
This function allows you to activate the panel’s PC connection for system programming purposes. The
panel’s cause and effects programming, device and zone naming, zone dependency functions, etc.,
MUST be done using panel’s PC programming tools (Part No. XFP507).
When the CONNECT TO PC prompt appears, press the Accept4button. If all connections are correct,
the following message will appear:
PC connected...
Press ESC to disconnect from PC
This menu function allows you to configure the panel to be part of a non-redundant network of up to
eight CAST XFP main panels, OR allow it to have up to eight XFP repeaters connected to it. This option
is only available if you have a network driver card fitted at the panel (see pages 13 & 14 for an overview
of networking). The NETWORK FUNCTIONS menu has three options detailed below. Additional options
are set using the panel’s PC programming tools.
Enter AL3 (4444) > Network Functions > Set Comms Function.
When selected, press the Accept4button and a message similar to the one below will appear:
Press the 5and 6buttons to scroll between Repeater and Network and press the Accept4button.
Fit the NVM link when requested by the panel. The flash database is updated.
Press the Escape 3button x 3 and remove the NVM link when requested by the panel.
Enter AL3 (4444) > Network Functions > Set Panel Number.
When selected, press the Accept4button and a message similar to the one below will appear:
Press the 5and 6buttons to scroll to the desired network number (1 to 8, or No Network).
Fit the NVM link when requested by the panel and the flash database is updated.
Press the Escape 3button x 3 and remove the NVM link when requested by the panel.
Enter AL3 (4444) > Network Functions > Set Panel Fitted.
When selected, press the Accept4button and fit the NVM link when requested by the panel.
Use the and scroll 5 button to select a panel number (1 to 8) and press the Accept 4 button. A
message similar to the one below will appear:
COMMISSIONING FUNCTIONS
Selecting this menu option takes you to the COMMISSIONING FUNCTIONS menu. As a rule, pressing
the Escape3button when in a submenu will return you to the COMMISSIONING FUNCTIONS menu.
Note: The majority of system commissioning - cause and effects programming, device and zone
naming, etc. MUST be done using the panel’s PC programming tools (Part No. XFP507).
LOOP LEARN
NB! LOOP LEARN WILL NOT AUTO ADDRESS DEVICES. LOOP LEARN IS ONLY FOR
PRE-ADDRESSED DEVICES, E.G. USING THE CAPROG HANDHELD PROGRAMMER.
An alternative function to LOOP LEARN is the AUTO ADDRESS menu option. See page 25 for details.
During a loop learn, the panel interrogates every pre-addressed device on the loop to see if an
addressable unit is present and, if so, find out what type of device it is.
Select which loop(s) to learn: ALL or 1 or 2 using the scroll 5 button then press the Accept4button.
When requested by the panel fit the NVM link shown below:
As the panel may already have loop device data stored in its memory from a previous loop learn or PC
upload, you will be asked if you want to erase this information before the loop learn begins.
The panel will start a loop learn. Wait for the process to complete and a summary window will appear,
similar to the one shown below:
Press the Accept4button then press the Escape 3button x 3 to return the panel to a normal condition.
When requested by the panel remove the NVM link shown below:
6: 50 16 Jan : Normal
Remove the NVM Un-Lock link
Press the scroll 5 button to select ‘Yes’ then press the Accept 4button shown below:
Are you sure you want to erase Are you sure you want to erase
the Database? No the Database? Yes
To select ‘No’, press the Accept 4button, the panel will start a loop learn without erasing the database.
Only if you are confident to proceed, press the scroll 5 button to select ‘Yes’, then press the
Accept4button. The panel will erase its database, update its flash memory and start a loop learn.
Wait for the process to complete and a summary window will appear, similar to the one shown below:
Press the Accept4button then press the Escape 3button x 3 to return the panel to a normal condition.
When requested by the panel remove the NVM link shown below:
6: 50 16 Jan : Normal
Remove the NVM Un-Lock link
AFTER A SUCCESSFUL LOOP LEARN, YOU WILL HAVE A ‘ONE OUT, ALL OUT’ FIRE ALARM SYSTEM.
See Table 1 below for the default device assignment following a loop learn.
Assignment Terms:
Input devices such as detectors, manual call points and the input channels of I/O units are programmed
to be members of a Zone.
Output devices such as loop powered sounders, sounder control units and the panel’s conventional
sounder circuits are programmed to be members of a Group.
The output channels of I/O units and the panel’s relays are programmed to be members of a Set.
Default Cause & Effects (C&E): Zone 1 triggers Group 1 and Set 1.
Classifying input and output devices in this manner greatly simplifies cause & effects programming.
ADDRESS FUNCTIONS
Selecting this menu option takes you to the ADDRESS FUNCTIONS menu which allows you to perform an
auto address, replace/add a loop device, change an address, show/fix duplicate addresses and identify
changes to the loop.
AUTO ADDRESS
An alternative function to AUTO ADDRESS is the LOOP LEARN menu option. See page 23 for details.
During an auto address the panel automatically assigns an address to each loop device in sequentially
wired order.
Enter AL3 (4444) > Commissioning Functions > Address Functions > Auto Address.
When the AUTO ADDRESS prompt appears, press the Accept4button to continue.
Press the scroll 5 button to select ‘Yes’ then press the Accept4button shown below:
Continue with Loop Learn? No Continue with Loop Learn? Yes
The Database will be erased The Database will be erased
Select which loop(s) to auto address: ALL or 1 or 2 using the scroll 5 button then press the
Accept4button, shown below:
When requested by the panel fit the NVM link shown below:
You now have two options: ‘Continue from last address? No’, or ‘Continue from last address? Yes’, as
detailed below:
CAUTION: USING THIS OPTION WILL COMPLETELY ERASE THE PANEL’S DATABASE
OF STORED LOOP DEVICE INFORMATION INCLUDING ERASING ALL EXISTING DEVICE
ADDRESSES AND DEVICE ADDRESSES ASSIGNED BY A CAPROG PROGRAMMER. THIS IS
DIFFERENT TO THE LOOP LEARN FUNCTION. USE THIS OPTION WITH EXTREME CARE.
Use this option if the panel has not previously been programmed, or if you want to program an existing
system as if it were a new system, and you are confident to proceed.
Press the scroll 5 button to select ‘No’ then press the Accept4button shown below:
The panel will perform an auto address. Wait for the process to complete and a brief summary window
will appear, similar to the one shown below:
Press the Accept4button then press the Escape 3button x 4 to return the panel to a normal condition.
When requested by the panel remove the NVM link shown below:
6: 50 16 Jan : Normal
Remove the NVM Un-Lock link
AFTER A SUCCESSFUL AUTO ADDRESS, YOU WILL HAVE A ‘ONE OUT, ALL OUT’ FIRE ALARM SYSTEM.
See Table 1, page 24 for the default device assignment following an auto address.
Use this option if you do not want to erase the stored loop device data. The panel will start to learn the
loop from the last known address in its memory. Existing data will not be overwritten, e.g. zone and
group allocation, device names, etc., will remain unchanged. The only data that will be overwritten is
device type and whether or not it is fitted.
Press the scroll 5 button to select ‘Yes’ then press the Accept 4button shown below:
The panel will perform an auto address. Wait for the process to complete and a brief summary window
will appear, similar to the one shown below:
Press the Accept4button then press the Escape 3button x 4 to return the panel to a normal condition.
When requested by the panel remove the NVM link shown below:
6: 50 16 Jan : Normal
Remove the NVM Un-Lock link
REPLACE/ADD DEVICE
This function may be used, for example, to replace a faulty loop device, or add a new loop device.
Enter AL3 (4444) > Commissioning Functions > Address Functions > Replace/Add Device.
When the REPLACE/ADD DEVICE prompt is displayed press the Accept 4 button.
Select which loop (1 or 2) to replace or add a device using the using the scroll 5 button then press
the Accept4button.
Note: Loop 1 has been selected in the following example.
Loop : 1
Select the device address using the 5and6scroll buttons, as shown below:
Loop : 1 Device : 10
Loop : 1 Device : 10 Note: If you do not want to proceed at this point, you
Waiting for device may exit this function by pressing the Escape 3button.
Note: If the panel requests the NVM link to be fitted continue onto the following steps.
When requested by the panel fit the NVM link shown below:
The panel perform a loop learn and the following summary is displayed:
Press the Accept 4button and the Escape 3button. Remove the NVM link when requested by the panel.
CHANGE ADDRESS
This function is used to change device addresses at the panel, therefore saving the use of ladders to
access a device on site.
Note: The CAPROG Handheld Programmer can be used to manually change the address of a device, but
this will also require a loop learn to be carried out.
Enter AL3 (4444) > Commissioning Functions > Address Functions > Change Address.
When the CHANGE ADDRESS prompt is displayed press the Accept 4button.
Select which loop (1 or 2) to change an address using the scroll 5 button then press the Accept4button.
Note: Loop 1 has been selected in the following example and the following is displayed:
Enter the address you want to change using the 5and6scroll buttons then press the Accept 4button.
The device’s LED will light and the following is displayed, for example ‘Device 8’.
Loop : 1 Device : 8
New Address : 8
Enter the new address of the device using the 5and6scroll buttons, for example ‘Device 9’, then press
the Accept 4button.
Loop : 1 Device : 8
New Address : 9
When requested by the panel fit the NVM link shown below:
Press the Escape 3button x 4. The panel will re-learn the loop. Wait for the process to complete and
a brief summary window will appear, similar to the one shown below:
Press the Accept4button then press the Escape 3button to return the panel to a normal condition.
When requested by the panel remove the NVM link shown below:
6: 50 16 Jan : Normal
Remove the NVM Un-Lock link
If there is a duplicate address a fault may have been displayed at the panel stating, ‘Loop configuration
has changed on Loop 1’, ‘There are faults on this zone’.
Press More Information button, then press the 5and6scroll buttons to view additional information
on the fault.
When the SHOW DUPLICATE DEVICES prompt is displayed press the Accept 4button and details of the
double address will appear, for example:
Press the Accept4button and the LEDs of the devices with duplicate addresses will be lit steady red.
To fix the duplicate address at the panel, press the Escape 3button and enter FIX DUPLICATE
ADDRESS function (see page 30).
To switch off the device LEDs, press the Accept4button again as shown below.
Enter AL3 (4444) > Commissioning Functions > Address Functions > Fix Duplicate Addresses.
When FIX DUPLICATE ADDRESS prompt is accepted, select Loop 1 or 2 and press the Accept4button.
The panel will re-initialise and check the loop. Wait for the re-initialisation process to finish.
Press the Menu button and the LED of the first duplicate address will be lit steady red, also details of
the first duplicate address found will appear, for example:
Loop: 1 Device: 8
New Address: 3 [DUPLICATE?]
The panel will suggest a new address for the duplicate device. Press the Accept4button to change
to the new address, or press scroll 5and6 buttons and Accept 4button to select the new address.
The LED of the second duplicate address will now be lit steady red, also details of the second duplicate
address found will appear. The panel will display the following, for example:
Loop: 1 Device: 10
New Address: 8 [ORIGINAL]
The panel will suggest a new address for the original device. Press the Accept4button to change to
the new address, or press scroll 5and6 buttons and Accept 4button to select a new address.
The panel will confirm there are no duplicate addresses on the loop shown below:
Press the Escape 3button x 3 and the panel will force a loop learn on exiting access level 3. Wait for
the loop learn to finish.
When requested by the panel fit the NVM link shown below:
9 Devices Found
Auto learn complete, Press Accept
Enter AL3 (4444) > Commissioning Functions > Address Functions > Identify Loop Changes.
When the IDENTIFY LOOP CHANGES prompt is displayed, press the scroll 5,6 buttons and Accept4
button to select the loop (1 or 2) and the panel will re-initialise and check the loop.
In this example, the panel will light the LED of the 1st swapped device, for example:
Press the scroll 56buttons and the panel will light the LED of the 2nd swapped device (the LED on
the 1st device will turn off), for example:
Continue to press the scroll 56buttons and the panel will light the LED of further swapped devices.
Once all swapped devices have been identified, changeover the devices to their correct loop position.
Enter AL3 (4444) > Engineer Functions > Restart the Loop.
When selected, chose the loop to restart (1 or 2 or ALL) using the 5 and 6 scroll buttons and press
the Accept4button. A window similar to the one below will appear:
Restarting loop...
The panel will power down the loop, re-initialize the loop devices and automatically return to the
ENGINEER FUNCTIONS menu.
Enter AL3 (4444) > Commissioning Functions > Show Fitted Devices.
When the SHOW FITTED DEVICES prompt appears, press the Accept4button.
Select either Loop 1 or 2 using the using the scroll 5 button then press the Accept4button.
Note: Loop 1 has been selected in the following example and the following is typically displayed:
L:1 D: 1 SMCCOODCSD 10
L:1 D: 11 ZCSHHDDMMC 20
Devices are displayed in groups of 10. In the example above, the top line shows the type of devices fitted
at addresses 1 to 10 on loop 1 and the second line shows the type of devices fitted at addresses 11 to 20.
The following letters displayed are dependent on the type of device at that address location:
To view the remaining devices on the loop, press the 5and 6buttons to scroll. To exit press the
Escape 3button.
ASSIGN ZONE/GROUP
This function allows you to assign devices to be members of detector zones or sounder groups. This
would normally be done using the panel’s PC programming tools but is provided at the panel to get it
working in a basic manner before it is properly configured at a later date.
Press the 5& 6 buttons to scroll to the desired zone or group and press the Accept4button.
The assignment will be made and you will be prompted to select another loop/device to assign using
the same procedure. To exit press the Escape 3button x 4 and remove the NVM link when prompted.
Note: Although I/O units can be assigned to be members of zones using this menu, this only applies to
their input function. The panel’s PC programming tools MUST be used to assign them to output sets.
Enter AL3 (4444) > Commissioning Functions > Set Day/Night Times.
When the SET/DAY NIGHT TIMES prompt appears, press the Accept4button and the following window
(or similar) will appear:
Press the scroll 5and6 buttons and Accept 4button to set the time in hours and minutes that you
want the panel to enter day mode (the panel has a 24 hour clock).
When the desired time is displayed, press the Accept4button to access the night mode entry field.
Press the scroll 56buttons and Accept 4button to set the time in hours and minutes that you want
the panel to enter night mode. When the desired time is displayed, press the Accept4button to select.
Enter AL3 (4444) > Commissioning Functions > Enable/Disable DST Adjustment.
When the ENABLE/DISABLE DST ADJUSTMENT prompt appears, press the Accept4button and the
following window will appear:
Press the 5and6 buttons to scroll between ‘Enabled’ and ‘Disabled’ and Accept4to button select
the option.
When requested by the panel fit the NVM link.
Press the Escape 3button x 3 and when requested by the panel remove the NVM link.
Note: Changes to this menu option will affect the ENABLE/DISABLE SOUNDERS menu option, see page 36.
This function configures the sounder groups (1 to 16) to be ‘Globally’ or ‘Individually’ disabled or
enabled.
Enter AL3 (4444) > Commissioning Functions > Configure Sounder Disablements.
When accepted, two windows ‘Globally’ and ‘Individually’ are available by pressing the 5 and 6
scroll buttons:
Press the Accept4button to make a selection. When requested by the panel fit the NVM link.
Press the Escape 3button x 3 and when requested by the panel remove the NVM link.
SWAPPED DEVICE DETECTION
Note: This function is only used to enable ‘SWAPPED DEVICE DETECTION’ mode. Once this mode is
enabled enter ‘IDENTIFY LOOP CHANGES’ function to identify the swapped devices. See page 31 for
details.
This function allows you to detect swapped loop devices. A fault may have been displayed at the panel
stating ‘Loop Configuration Changed on Loop 1’ or ‘There are Faults on this Zone’.
First ensure the ‘SWAPPED DEVICE DETECTION’ function is enabled by performing the following
procedure.
Enter AL3 (4444) > Commissioning Functions > Swapped Device Detection.
When the SWAPPED DEVICE DETECTION prompt is displayed, press the Accept 4 button. The panel
will display the following window:
When requested by the panel fit the NVM link shown below:
The panel will update its flash database. Press the Escape 3button x 3.
Remove the NVM link when requested by the panel.
To identify the swapped devices, enter IDENTIFY LOOP CHANGES function, see page 31 for details.
Enter AL3 (4444) > Commissioning Functions > Configure Polling LED.
When accepted, the following window will appear:
Press the 5and6 buttons to scroll between ‘Enabled’ and ‘Disabled’, then press the Accept4button
to select.
When requested by the panel fit the NVM link. The panel will update the flash database and configure
the loop devices.
Press the Escape 3button x 3. When requested by the panel remove the NVM link.
MAKE A CLEAN START
CAUTION: USING THIS FUNCTION WILL COMPLETELY ERASE THE PANEL’S DATABASE OF
STORED INFORMATION. THEREFORE, USE THIS FUNCTION WITH EXTREME CARE.
This function allows you to clear the panel’s memory back to its factory default settings. Only if you are
confident to proceed, enter the five-digit confirmation code.
Note: The button sequence has to be entered VERY QUICKLY to avoid accidentally erasing panel data.
Enter AL3 (4444) > Commissioning Functions > Make a Clean Start.
The button sequence is: 5(1), 4(2), 6(3), 3(4), Silence Internal Sounder button.
When requested by the panel fit the NVM link. The panel will erase its record and update the flash database.
Press the Escape 3button x 3 and remove the NVM link when requested by the panel.
ENGINEER FUNCTIONS
Selecting this menu option takes you to the ENGINEER FUNCTIONS menu. As a rule, pressing the
Escape3button when in a submenu will return you to the ENGINEER FUNCTIONS menu.
Enter AL3 (4444) > Engineer Functions > Restart the Loop.
When selected, chose the loop to restart (1 or 2 or ALL) using the 5 and 6 scroll buttons and press
the Accept4button. A window similar to the one below will appear:
Restarting loop...
The panel will power down the loop, re-initialize the loop devices and automatically return to the
ENGINEER FUNCTIONS menu.
SET/CLEAR DISABLEMENTS
Selecting this menu option takes you to the disablements submenu which allows you to enable/disable
zones, sounders, outputs, relays, loop devices, the panel’s fault relay and output delays.
Any disablement(s) will be indicated at all access levels via the DISPLAY DISABLEMENTS menu option
and the General Disablement LED on the front of the panel.
ENABLE/DISABLE ZONES
This function allows you to disable zones from reporting faults, fires, etc., and may be used to
temporarily disable a zone of devices in areas such as loading bays that are prone to nuisance triggering
from vehicle fumes.
Enter AL3 (4444) > Engineer Functions > Set/Clear Disablements > Enable/Disable Zones.
When selected, press the Accept4button and a window similar to below will appear:
Select the zone (1 to 32 or ALL) to be disabled/enabled using the 5 and 6 scroll buttons, then press
the Accept4button and the zone’s status (Enabled or Disabled) will flash. Next, press the 5 and 6
scroll buttons to toggle between enabled and disabled and press the Accept4button to select. The
window will now move to the next available zone allowing further enablements or disablements to be
made. Alternatively, to return to the previous menu press the Escape 3button.
Note: If all input devices on a zone have been disabled using the ENABLE/DISABLE DEVICES function
detailed on page 37, the zone they belong to will also be disabled. If you try to re-enable a zone which
has no enabled devices on it, a prompt appears saying this cannot be done. Instead you MUST enable
at least one device on the zone using the ENABLE/DISABLE DEVICES function before re-enabling the
zone itself.
ENABLE/DISABLE SOUNDERS
Note: Changes made to the CONFIGURE SOUNDER DISABLEMENTS function, see page 33, will have an
affect on the options available at this menu.
This function allows you to disable one or more sounder groups from sounding in a fire condition.
Enter AL3 (4444) > Engineer Functions > Set/Clear Disablements > Enable/Disable Sounders.
When selected, press the Accept4button and windows similar to the ones below will appear:
Select the sounder group (1 to 16 or ALL) to be disabled/enabled using the 5and6 scroll buttons.
When the desired sounder group has been selected, press the Accept4button and the sounder
group’s status (Enabled or Disabled) will flash. Next, press the 5and6 scroll buttons to toggle
between enabled and disabled and press the Accept4button to select. The window will now move to
the next sounder group allowing further enablements or disablements to be made. Alternatively, to
return to the previous menu press the Escape3button.
ENABLE/DISABLE OUTPUTS
This function allows you to disable one or more output sets from activating in a fire condition. It is
typically used to disable, for example, auto-diallers to monitoring stations, roller shutter doors, etc.
from activating during routine maintenance.
Enter AL3 (4444) > Engineer Functions > Set/Clear Disablements > Enable/Disable Outputs.
When selected, press the Accept4button and windows similar to the ones below will appear:
Select the output set (1 to 16 or ALL) to be disabled/enabled using the 5and6 scroll buttons.
When the desired output set has been selected, press the Accept4button and the output set’s status
(Enabled or Disabled) will flash. Next, press the 5and6 scroll buttons to toggle between enabled
and disabled and press the Accept4button to select. The window will now move to the next output
set allowing further enablements or disablements to be made. Alternatively, to return to the previous
menu press the Escape3button.
ENABLE/DISABLE RELAYS
This function allows the disablement of one or more of the panel’s 3 auxiliary relays from activating as
programmed.
Enter AL3 (4444) > Engineer Functions > Set/Clear Disablements > Enable/Disable Relays.
When selected, press the Accept4button and windows similar to the ones below will appear:
Select the relay (1, 2 or 3) to be disabled/enabled using the 5and 6 scroll buttons.
When the desired output set has been selected, press the Accept4button and the relay’s status
(Enabled or Disabled) will flash. Next, press the 5and6 scroll buttons to toggle between enabled
and disabled and press the Accept4button to select. The window will now move to the next relay
allowing further enablements or disablements to be made. Alternatively, to return to the previous
menu press the Escape3button.
ENABLE/DISABLE DEVICES
This function allows loop devices to be disabled from reporting faults, fires, etc., and is normally used
to temporarily disable detectors/call points that are nuisance tripping.
Enter AL3 (4444) > Engineer Functions > Set/Clear Disablements > Enable/Disable Devices.
When selected, press the Accept4button and a window similar to the one below will appear:
Loop : 1
Press the 5and6 scroll buttons and Accept4buttons to select the loop (1 or 2) and range of devices.
When selected, the following display will appear, for example:
Loop : 1 From : 1 to 5
Enabled
Press the 5and6 scroll buttons to toggle between enabled and disabled, then press the Accept4button
to select.
Note: If all input devices on a zone have been disabled, the zone they belong to will also be disabled.
If you try to re-enable a zone which has no enabled devices on it using the ENABLE/DISABLE ZONES
function described on page 35, a prompt appears saying this cannot be done. Instead you MUST enable
at least one device on the zone using the ENABLE/DISABLE ZONES function before re-enabling the
zone itself.
Enter AL3 (4444) > Engineer Functions > Set/Clear Disablements > Enable/Disable Fault Relay.
When selected, press the Accept4button and the following window will appear:
Press the 5and6 scroll buttons to toggle between enabled and disabled and press the Accept4button
to select the desired option. Alternatively, to return to the previous menu press the Escape3button.
Enter AL3 (4444) > Engineer Functions > Set/Clear Disablements > Enable/Disable Output Delays.
When selected, press the Accept4button and the following will appear:
Press the 5and6 scroll buttons to toggle between enabled and disabled and press the Accept4button
to select the desired option. Alternatively, to return to the previous menu press the Escape3button.
MONITOR A POINT
This function allows you to view the current analogue status of any point (any addressable device on
the system).
When selected, choose the loop number (1 or 2), press the Accept4 button to continue then press the
5,6 and Accept4 buttons to select the device’s address.
The panel will temporarily disable the point in question and return back its analogue values, for
example:
The device's
The loop being The device's current analogue value The device's gain
monitored address (nominally ‘0’) value
The fault code for any fault The devices's type code
condition that device may be in
Note 1: The analogue values returned will differ dependent on whether the device is a detector,
manual call point, I/O unit or sounder.
Note 2: The information displayed will assist C-TEC Technical Support to identify the cause of any
problems.
Enter AL3 (4444) > Engineer Functions > Test Device Outputs.
When selected, you will be prompted to enter the loop (1 or 2), device’s address and the relevant output:
Loop : 1 Device : 1
Output Bit Value: NONE
Press the 5,6 scroll buttons and Accept4 button to select the device address and output bit value.
(as detailed in the table below).
When you have accepted the required output bit option, the panel will confirm your selection and the
device’s output channels will be asserted. If desired, you can now select alternative output channel
using the 5and 6 scroll buttons.
To exit this function press the Escape 3button x 2. The panel will ask for confirmation to reset the
outputs to their normal settings as shown below:
Press the Accept4 button to reset the outputs, or the Escape3button maintain the settings.
Enter AL3 (4444) > Engineer Functions > Test Output Sets.
When the TEST OUTPUT SETS prompt appears, press the Accept4 button and the output set selection
window will appear.
Output Set : 1
Press the 5and6 buttons to select the output set you would like to test (1 to 16 or ALL). Press the
Accept4button and the following window will appear:
Press the Accept4button and the selected output set will change state from normal to triggered.
To test additional output sets, press the 5and6 and Accept4button to change the output set’s
number and state.
Finally, press the Escape3button.
When exiting this function the panel will ask for confirmation to reset the outputs to their normal
settings. Press the Accept4 button to reset the outputs, or the Escape3button maintain the settings.
Enter AL3 (4444) > Engineer Functions > Test Sounders in Groups.
When the TEST SOUNDERS IN GROUPS prompt appears, press the Accept4button and the group
selection window will appear:
Sounder Group : 1
Press the 5and6 scroll buttons to select the sounder group you would like to test (1 to 16 or ALL).
Press the Accept4button and the following window will appear:
Press the Accept4button to change the state of the selected sounder group between Silenced,
Intermittent and Continuous. Should you want to test additional sounder groups, press the 5and6
buttons to change the sounder group’s number.
When exiting this function the panel will ask for confirmation to silence the sounders to their normal
settings. Press the Accept4 button to reset the sounders, or the Escape3button maintain the settings.
Enter AL3 (4444) > Engineer Functions > Test VADS in Groups.
When the TEST VADS IN GROUPS prompt appears, press the Accept4button and the group selection
window will appear:
VAD Group : 1
Press the 5and6 scroll buttons to select the sounder group you would like to test (1 to 16). Press the
Accept4button and the following window will appear:
Press the Accept4button to change the state of the selected VAD group between Normal and
Triggered, shown below:
Should you want to test additional VAD groups, press the 5and6 and Accept4buttons to change
the VAD group’s number and state. Press the Escape 3button to exit the function.
Enter AL3 (4444) > Engineer Functions > Test Panel Relays.
When the TEST PANEL RELAYS prompt appears, press the Accept4button and the panel relay selection
window will appear:
Panel Relay : 1
Press the 5 and6 scroll buttons to select the relay you would like to test (1 to 3). Press the
Accept4button and the following window will appear.
Press the Accept4button and the panel relay you have selected will trigger. To change the state back
to Normal press the Accept4button again. Press the Escape 3button to exit the function.
WALK TEST
This function puts one or more of the system’s detection zones into walk test mode. When a zone is in
walk test mode, any detector/manual call point triggered on that zone will turn on all of the sounders
(if enabled) that are mapped to that zone for a brief period (note that output sets will not operate).
When the WALK TEST prompt appears, press the Accept4button. To select either a walk test with
sounders either Disabled or Enabled, press the 5and6 scroll buttons shown:
Zone : All
Press the 5and6 scroll buttons to select the zone (1 to 32 or ALL) you want to put into walk test mode,
then press the Accept4 button and the following window will appear:
Zone : 1 Zone : 1
Normal operation Walk Test Mode
Press the 5and6 scroll buttons to change the zone’s state from Normal Operation to Walk Test Mode and
press the Accept4button. You now have the option to put additional zones into test at the same time.
To take zones out of test, reverse the procedure. Any zones in test will be indicated at all access levels
via the DISPLAY ZONES IN TEST menu option and the Test LED on the front panel.
Press the Escape 3button to exit the function.
Enter AL3 (4444) > Engineer Functions > Identify Loop Break.
When the IDENTIFY LOOP BREAK prompt appears, select the loop (1 or 2), press the Accept4button
and the panel will initialize both ends of the loop and the following is displayed:
Restarting Loop...
Please Wait
Wait for the process to finish. The following is displayed for example:
The LEDs on the devices either side of the loop break will light steady red.
S/C Detected
Loop 1
Enter AL3 (4444) > Engineer Functions > Identify Loop Break.
When the IDENTIFY LOOP BREAK prompt appears, select the loop (1 or 2), press the Accept4button
and the panel will initialize both ends of the loop and the following is displayed:
Restarting Loop...
Please Wait
The LEDs on the devices either side of the short circuit will light steady red.
LOOP TEST
This function helps pinpoint loop wiring/communication faults by continually polling all loop devices
for a specified number of times and reporting back both good and bad polls.
When selected, press the Accept4button, enter the loop (1 or 2) you want to monitor and enter how
many times you want the panel to poll each loop device, for example 5 times, as shown below:
Press the Accept4button, the test will begin and a test status window will appear, showing the address
currently being polled together with a running total of the number of good and bad polls.
The test will continuously scroll through the loop devices.
To halt this function press the Escape3button.
The test results will appear in a window similar to the one below.
Loop:1 Device:1
Good Polls:128 Bad Polls:3
Use the 5and6 buttons to scroll through the polling results for the loop devices.
A high number of bad polls in a particular section of the system indicates a problem area for
investigation, e.g. voltage drop, poor connection, etc.
To assert the LED output of the device being viewed, press the More Information button. You will be
presented with a window similar to the one below:
Loop:1 Device: 1
Turn ON device LED?
Press the Accept4button to activate the LED of the selected device. Once activated, you will be given
the option to turn off the device LED by pressing the Accept4button again.
Press the Escape 3button to exit the function.
DISPLAY DATABASE
This function allows you to view the panel’s database of loop devices. Available on a loop by loop
basis, the information displayed includes the device’s type, address and description (zone and device
text).
When the DISPLAY DATABASE prompt is accepted, select the loop number (1 or 2) and press the
Accept 4 button and you will be prompted to enter the device number.
Press the 5and6 scroll buttons to select the device address, then press the Accept 4 button.
Loop : 1 Device : 22
The information that is stored on the database that relates to that address will appear, for example:
In the above example, ‘Dev: 22/0’ denotes device address ‘22’ and sub-address ‘0’. Sub-addresses only
apply to I/O units which may have multiple channels and can be configured as both an input and an
output.
You can now press the 5and6 buttons to scroll through the rest of the loop device database.
Press the Escape 3button to exit the function.
VERSION NUMBERS
This function allows you to view the current version number of the panel’s firmware and to check when
the site’s data was last changed.
When accepted, the following two windows (with details specific to the panel) will scroll in quick
succession. Press the Escape 3button to exit the function.
Enter AL3 (4444) > Engineer Functions > Show PSU Stats.
Note: ‘Batt R’ shown above denotes the battery impedance. The information displayed will assist
C-TEC Technical Support to identify the cause of any problems.
Enter AL3 (4444) > Engineer Functions > Enable/Disable Earth Fault.
Press the 5and6 scroll buttons to toggle between ‘Enabled’ and ‘Disabled’, then press the
Accept4button. Fit the NVM link when requested by the panel.
Press the Escape 3button x 3 and remove the NVM link when requested by the panel.
SHOW DEVICE EEPROM
This function allows the panel to interrogate and view information held by CAST devices.
Enter AL3 (4444) > Engineer Functions > Show Device EEPROM.
When accepted, enter the loop (1 or 2) and address of the device, example shown below:
When accepted, a list of device parameters, flags, data, Loop ID, Version, etc. is shown on the display.
Press the 5and6 buttons to scroll through the data.
The information displayed will assist C-TEC Technical Support to identify the cause of any problems.
Enter AL3 (4444) > Engineer Functions > Turn LEDS ON/OFF.
When accepted, select the loop (1 or 2 or ALL) and panel displays (similar to the following) will appear.
At each display, press the 5and6 scroll buttons to toggle, then press the Accept4button to proceed.
Options are available to turn the device (polling) LEDS either ON or OFF, at Both Ends/End A Only/End B
Only and the Poll Group (see tables below for device numbers).
Press the Escape 3button to exit the function.
DIAGNOSTICS FUNCTIONS
These functions are for trained engineers only and are not detailed in this manual. Contact C-TEC
Technical for further assistance.
MAINTENANCE
Periodic system maintenance should be carried out on the system as prescribed in the local design,
maintenance and installation regulations.
The Fire Alarm panel’s standby batteries should be checked for integrity of the connections and deposits
indicating venting. A periodic load test with the mains supply disconnected should also be performed
to ensure adequate battery capacity. Both batteries should be renewed if there is any doubt about
their integrity.
The panel’s event log should be checked for any faults that have automatically cleared, and these dealt
with accordingly.
TECHNICAL SPECIFICATION CAST XFP 1 Loop 32 Zone Panel (Part No. XFP501/CA)
CAST XFP 2 Loop 32 Zone Panel (Part No. XFP502/CA)
POWER SUPPLY
Mains supply (a.c.) 230V ∿ 50/60Hz. Rated current 0.68A r.m.s.
Internal power supply 18.7Vd.c. to 29.0Vd.c. (Ripple voltage 500mV p-p)
Maximum rated current 2.5A @ 230Va.c. (2.5A battery only with mains off)
I max. a = 300mA (XFP501/CA), I max. a = 406mA (XFP502/CA)
Current specification
I max. b = 1.9A; I min. = 106mA
Maximum internal battery resistance Ri max. = 1.1Ω
Earth fault monitoring Yes (any conductor)
Mains supply & battery charger monitored for failure Yes
Batteries monitored for disconnection & failure Yes
Batteries protected against deep discharge Yes
Maximum battery size and type 2 x 12V, 1.2Ah to 7Ah VRLA batteries. Use YUASA NP7-12/12S for LPCB approved systems.
Quiescent current <50mA (1 loop unloaded - XFP501/CA); <56mA (2 loops unloaded - XFP502/CA) - with mains failed
LOOP DRIVER (PROGRAMMABLE & MONITORED)
Number of loop drivers 1 (XFP501/CA) or 2 (XFP502/CA)
Communication protocol CAST® (C-TEC Addressable System Technology)
Loop monitored for open and short circuit faults Yes
On-board loop isolators Yes
Auto-polling from each loop end & both ends (A & B) Yes
Maximum output current & voltage per loop 450mA (Voltage: 40V)
Max. number of addressable devices (detectors, MCPs) 255 CAST devices for 1 loop panel (XFP501/CA), 510 CAST devices for 2 loop panel (XFP502/CA)
Device addressing options Devices automatically addressed by the panel, or manually addressed using CAPROG
Short-circuit isolator in every loop device Yes
Maximum loop cable length 1km
Number of programmable sounder groups 16
Number of programmable output sets 16
CONVENTIONAL SOUNDER CIRCUIT (PROGRAMMABLE & MONITORED)
Number of sounder circuits 2 (programmable, independent conventional circuits)
End of line (EOL) resistor value 6800 ohm, 5% tolerance, 0.25W
Line monitored for open and short circuit faults Yes
Each output fused at (maximum sounder output current) 400mA. Protected by resettable overload circuit.
Output voltage 19.5V minimum; 28V maximum
Maximum length per circuit 500m
AUXILIARY OUTPUTS (PROGRAMMABLE)
Relay type / Output Volt-free, single pole changeover / 1A, 30Vd.c. (maximum)
3 x auxiliary relays (Relay1, Relay2, Relay3) Programmed from cause and effects
1 x failsafe fault relay Active when no faults are present
‘+24Vd.c.’ Aux. power output 19.5V minimum, 28V maximum. Maximum current 100mA.
AUXILIARY INPUTS (PROGRAMMABLE, NON-MONITORED)
2 x auxiliary inputs (I/P1, I/P2) Connect to 0V to trigger, maximum input voltage 27Vd.c. (non-latching).
FUSES (to EN60127-2)
Primary fuse (F1) T 1A H 250V 20mm ceramic (T=Time Delay, H=High Breaking Current)
Battery fuse (F3) 3.15A F 20mm ceramic (F=Fast Acting)
CONTROLS AND INDICATORS
Menu, More Information, Silence Internal Sounder, Control Panel Reset, Investigate,
Control buttons
Silence/Resound Sounders
Event scrolling and menu access buttons (scroll up) 5 (1), (scroll down) 6 (3), Accept 4 (2), Escape 3 (4)
Liquid crystal display Two lines x 40 characters, backlit
Number of zonal LED indicators 32
(General) Fire, Supply Present, Test, Accessed, General Disablement, Phased Evacuation,
Other LED indicators
General Fault, Power Supply Fault, System Fault, Sounder Status, Delays Running.
PHYSICAL
Dimensions 435mm(W) x 270mm(H) x 85mm(D)
Weight / Construction 4.5kg (without batteries) / hinged metal lid, metal back box
IP Rating (to EN60529) IP30 (indoor use only)
Paint finish Light grey texture (RAL7035) epoxy paint
CABLING REQUIREMENTS
Type of cable Fire resistant screened cable, minimum size 1mm2
Maximum loop cable length 1km
Connector blocks Fixed type, largest acceptable conductor size, 1.5mm2
Maximum allowable loop impedance (each conductor) 20 ohm
Maximum cable capacitance .27µF
NETWORK (OPTIONAL)
Network connection Via AFP711 network driver card, one card fitted at each networked main panel
Network type 2-wire, screened, enhanced fire-resistant cable ≥1 mm2, RS485 non-redundant network
Maximum number of main panels per network 8
Maximum no. of repeaters per non-networked main panel 8
Maximum cable length per network 1km (main panel network); 500m (repeater panel network)
PC/PRINTER INTERFACE
PC connection Via main PCB RS232 molex connector (lead supplied with XFP507 PC programming tools)
Printer connection Not available
OPERATING CONDITIONS
The enclosure is designed for indoor use only. The components are selected to operate within their specification when the environmental conditions
outside the enclosure comply with class 3k5 of IEC 721-3-3. Temperature range: -10oC to +40oC. Maximum humidity: 95% non condensing.
CERTIFICATES (Certificates and DOPs are available for download on C-TEC’s website)
LPCB Certificate Number: 176b LPCB Reference Numbers: 176b/27 (XFP501/CA) & 176b/28 (XFP502/CA)
Declaration of Performance: DOP0000072 CPR Certificate Numbers: 2831-CPR-F2523 (XFP501/CA) & 2831-CPR-F2524 (XFP502/CA)
UKCA Certificate Numbers: 0832-UKCA-CPR-F1052 (XFP501/CA) & 0832-UKCA-CPR-F1053 (XFP502/CA)
Tested to: EN54-2:1997 + A1:2006 and EN54-4:1997 + A1:2002 + A2:2006