PROG
PROG
Automation Portal
Program blocks
Analog scale [FC1]
Analog scale Properties
General
Name Analog scale Number 1 Type FC Language LAD
Numbering Automatic
Information
Title Author Comment Family
Version 0.1 User-defined ID
Network 1:
NORM_X SCALE_X
Int to Real Real to Real
EN ENO EN ENO
0 MIN OUT #"NORM_X OUT" #"AI-SCAL_X MIN" MIN OUT #"AI-SCAL_X OUT"
#"AI-NORM_X #"NORM_X OUT" VALUE
VALUE" VALUE #"AI-SCAL_X MAX" MAX
27648 MAX
Totally Integrated
Automation Portal
Program blocks
TIME FONCTION [FC5]
TIME FONCTION Properties
General
Name TIME FONCTION Number 5 Type FC Language LAD
Numbering Automatic
Information
Title Author Comment Family
Version 0.1 User-defined ID
Program blocks
Transfer Fonction [FC2]
Transfer Fonction Properties
General
Name Transfer Fonction Number 2 Type FC Language LAD
Numbering Automatic
Information
Title Author Comment Family
Version 0.1 User-defined ID
Network 1:
MOVE
EN ENO
%IW116 %DB1.DBW0
"AI-01ST Outlet "DATA SYSTEM".
Conductivity" IN ANALOG[1]."AI-
OUT1 NORM_X"
MOVE
EN ENO
%IW118 %DB1.DBW14
"AI-02ND Outlet "DATA SYSTEM".
Conductivity" IN ANALOG[2]."AI-
OUT1 NORM_X"
MOVE
EN ENO
%IW114 %DB1.DBW28
"AI-Inlet "DATA SYSTEM".
Conductivity" IN ANALOG[3]."AI-
OUT1 NORM_X"
MOVE
EN ENO
%IW112
%DB1.DBW42
"AI-PH" IN
"DATA SYSTEM".
ANALOG[4]."AI-
OUT1 NORM_X"
Totally Integrated
Automation Portal
Program blocks
SYSTEM [FC3]
SYSTEM Properties
General
Name SYSTEM Number 3 Type FC Language LAD
Numbering Automatic
Information
Title Author Comment Family
Version 0.1 User-defined ID
Network 1:
%I0.0
"DI -Raw Water %I0.1
Tank Level "DI -Raw Water %M10.0
Middle" Tank Level Low" "row water pump"
%M10.0
"row water pump"
Network 2:
%I0.3
"DI -Middel Water %I0.2 %M10.1
%M10.0 Tank Level "DI -Middel Water "inhebitor pump
"row water pump" Middle" Tank Level High" control"
%M10.1 P#DB1.DBX56.0
"inhebitor pump "DATA SYSTEM".
control" TIME[1]
TON
Time
IN Q
ET T#0ms
%DB1.DBD60
"DATA SYSTEM".
TIME[1].PT PT
P#DB1.DBX72.0
"DATA SYSTEM".
TIME[2]
TON
Time
IN Q
ET T#0ms
%DB1.DBD76
"DATA SYSTEM".
TIME[2].PT PT
Network 3:
%I0.3
"DI -Middel Water %I0.4 %M10.2
Tank Level "DI -Middel Water "ro inlet valve
Middle" Tank Level Low" control"
%M10.2
"ro inlet valve
control"
%DB1.DBX414.2
"DATA SYSTEM".
"3"
Totally Integrated
Automation Portal
Network 4:
%I0.6 %I0.5
"DI -Pure Water "DI -Pure Water %M10.3
Tank 01 Level Tank 01 Level "1st hp pump
Middle" High" relay 01 tank"
%M10.3
"1st hp pump
relay 01 tank"
%DB1.DBX414.0
"DATA SYSTEM".
"1"
%I2.2 %I2.1
"DI -Pure Water "DI -Pure Water %M100.0
Tank 02 Level Tank 02 Level "1 st hp pump
Middle" High" relay 02 tank"
%M100.0
"1 st hp pump
relay 02 tank"
%DB1.DBX414.1
"DATA SYSTEM".
"2"
Network 5:
%I0.6 %I0.7
"DI -Pure Water "DI -Pure Water %M10.4
Tank 01 Level Tank 01 Level "ph adjusting
Middle" Low" control 01"
%M10.4
"ph adjusting
control 01"
%I2.2 %I2.3
"DI -Pure Water "DI -Pure Water %M100.1
Tank 02 Level Tank 02 Level "ph adjausting
Middle" Low" control 02"
%M100.1
"ph adjausting
control 02"
Network 6:
%I1.0 %I1.1
"DI-Washing "DI-Washing %M10.5
Water Tank Level Water Tank Level "second hp
Middle" Low" pump"
%M10.5
"second hp
pump"
Network 7:
Totally Integrated
Automation Portal
P#DB1.DBX136.0
%I1.2
"DATA SYSTEM".
"DI-Raw watr TIME[6]
Pump Outlet %M10.6
Pressure TON "Tag_1"
Controle" Time RS
IN Q R Q
ET T#0ms
%DB1.DBD140
"DATA SYSTEM".
TIME[6].PT PT
P#DB1.DBX120.0
%I1.2
"DATA SYSTEM".
"DI-Raw watr TIME[5]
Pump Outlet
Pressure TON
Controle" Time
IN Q S1
ET T#0ms
%DB1.DBD124
"DATA SYSTEM".
TIME[5].PT PT
Network 8:
P#DB1.DBX168.0
"DATA SYSTEM".
%I1.3 TIME[8]
"DI-High Pressure %M10.7
Pump Inlet Inlet %M20.0 TON "Tag_2"
Pressure Control" "S %Q2.3" Time RS
IN Q R Q
ET T#0ms
%DB1.DBD172
"DATA SYSTEM".
TIME[8].PT PT
P#DB1.DBX152.0
"DATA SYSTEM".
%I1.3 TIME[7]
"DI-High Pressure
Pump Inlet Inlet TON
Pressure Control" Time
IN Q S1
ET T#0ms
%DB1.DBD156
"DATA SYSTEM".
TIME[7].PT PT
Network 9:
%DB1.DBX68.2 %Q0.0
"DATA SYSTEM". %M10.0 "DO-Raw Water
TIME[1].Q "row water pump" Pump relay"
%I1.4
"DI-Backwash
Level"
Network 10:
Network 11:
Network 12:
Network 13:
Totally Integrated
Automation Portal
%Q0.5 %Q0.4
"DO-02ND HP "DO-PH Adjusting
Pump relay" Controle"
Network 14:
CALCULATE
Int
EN ENO
OUT := IN1*IN2
%DB1.DBW402 %DB1.DBW404
"DATA SYSTEM". "DATA SYSTEM".
"TIME FONCTION". "TIME FONCTION".
M IN1 OUT S
60 IN2
Network 15:
%DB1.DBX412.0 %DB1.DBX412.2
%M10.2 %M10.3 "DATA SYSTEM". %I2.5 "DATA SYSTEM". %DB1.DBX212.2 %Q0.5
"ro inlet valve "1st hp pump "TIME FONCTION". "DI-Electrical valv "TIME FONCTION". "DATA SYSTEM". "DO-02ND HP
control" relay 01 tank" Cuve01 feedbak" MCuve01 TIME[10].Q Pump relay"
%DB1.DBX412.1 %DB1.DBX412.3
%M10.2 %M100.0 "DATA SYSTEM". %I2.5 "DATA SYSTEM".
"ro inlet valve "1 st hp pump "TIME FONCTION". "DI-Electrical valv "TIME FONCTION".
control" relay 02 tank" Cuve02 feedbak" MCuve02
P#DB1.DBX200.0
"DATA SYSTEM".
TIME[10]
%Q0.5 %Q0.5
"DO-02ND HP "DO-02ND HP TOF
Pump relay" Pump relay" Time
N IN Q
%M100.2 ET T#0ms
%DB1.DBD204
"Tag_3"
"DATA SYSTEM".
TIME[10].PT PT
P#DB1.DBX406.0
"DATA SYSTEM".
"TIME FONCTION".
conteur
%M10.3 %M100.0
%M0.5 "1st hp pump "1 st hp pump CTU
"Clock_1Hz" relay 01 tank" relay 02 tank" Int
CU Q
CV 0
%DB1.DBX412.2
"DATA SYSTEM".
"TIME FONCTION".
MCuve01
N R
%M75.0
"N MCuve01" %DB1.DBW404
"DATA SYSTEM".
"TIME FONCTION".
S PV
%M10.3
"1st hp pump
relay 01 tank"
%M100.0
"1 st hp pump
relay 02 tank"
%DB1.DBX412.3
"DATA SYSTEM".
"TIME FONCTION".
MCuve02
N
%M75.1
"N MCuve02"
%DB1.DBX412.3 %DB1.DBX412.5
"DATA SYSTEM". "DATA SYSTEM".
"TIME FONCTION". "TIME FONCTION".
MCuve02 RCuve02
Network 16:
Totally Integrated
Automation Portal
%M10.4 %Q2.0
"ph adjusting "DO-Spply Pump
control 01" relay 01"
%Q2.1
"DO-UV Lamp
Controle 01"
%M100.1 %Q1.1
"ph adjausting "DO-Spply Pump
control 02" relay 02"
%Q1.2
"DO - Raw Water
Tank Low Level"
CALCULATE
UDInt
EN ENO
OUT := IN1*IN2
%DB1.DBD386
"DATA SYSTEM".
CTDPV01 IN2
%DB2
"IEC_Counter_0_
DB"
%Q2.0
"DO-Spply Pump %M0.5 %M1.0 CTD
relay 01" "Clock_1Hz" "P%Q2.0" UDInt
P CD Q
%M1.2 false LD CV #CTDCV01
"MP%Q2.0" #CTDPV01 PV
CALCULATE
UDInt
EN ENO
OUT := IN1/IN2
#CTDCV01 IN1
%DB1.DBD390
3600 IN2 "DATA SYSTEM".
OUT CTDCV01
CALCULATE
UDInt
EN ENO
OUT := IN1*IN2
%DB1.DBD394
"DATA SYSTEM".
CTDPV02 IN2
%DB3
"IEC_Counter_0_
DB_1"
%Q1.1
"DO-Spply Pump %M0.5 %M1.1 CTU
relay 02" "Clock_1Hz" "P%Q1.1" UDInt
P CU Q
%M1.3 false R CV #CTDCV02
"MP%Q1.0" #CTDPV02 PV
CALCULATE
UDInt
EN ENO
OUT := IN1/IN2
#CTDCV02 IN1
%DB1.DBD398
3600 IN2 "DATA SYSTEM".
OUT CTDCV02
Network 17:
%M10.5 %Q2.2
"second hp "DO-Washing
pump" Pump relay"
Network 18:
%I0.4 %Q2.4
"DI -Middel Water "DO-Middle water
Tank Level Low" Tank Low Level"
Network 19:
Totally Integrated
Automation Portal
%I0.7 %Q2.5
"DI -Pure Water "DO-Pure Water
Tank 01 Level Tank 01ST Low
Low" Level"
Network 20:
P#DB1.DBX88.0
"DATA SYSTEM".
TIME[3]
TON
Time
IN Q
ET T#0ms
%DB1.DBD92
"DATA SYSTEM".
TIME[3].PT PT
Network 21:
%Q2.3
"DO-Washing %M20.0
Valve Controle" "S %Q2.3"
P S
%M20.2
"P %Q1.3"
Network 22:
%Q2.3 %DB1.DBX116.2
"DO-Washing "DATA SYSTEM". %M20.1
Valve Controle" TIME[4].Q "Tag_6"
N
%M20.3
"N %Q1.3"
P#DB1.DBX104.0
"DATA SYSTEM".
%M20.1 TIME[4]
"Tag_6" TON
Time
IN Q
ET T#0ms
%DB1.DBD108
"DATA SYSTEM".
TIME[4].PT PT
Network 23:
%M20.1 %M20.0
"Tag_6" "S %Q2.3"
N R
%M20.4
"N %M20.1"
Network 24:
%DB1.DBX412.5 %I2.1
%M100.0 %M10.3 "DATA SYSTEM". "DI -Pure Water %Q1.0
"1 st hp pump "1st hp pump "TIME FONCTION". Tank 02 Level "DO-ELECTRICAL
relay 02 tank" relay 01 tank" RCuve02 High" VALV"
%DB1.DBX412.4
"DATA SYSTEM".
"TIME FONCTION".
RCuve01
%Q1.0
"DO-ELECTRICAL
VALV"
Network 25:
Totally Integrated
Automation Portal
%I0.1 %Q1.2
"DI -Raw Water "DO - Raw Water
Tank Level Low" Tank Low Level"
%Q1.3
%I0.2 "DO - Intermediat
"DI -Middel Water Water Tank High-
Tank Level High" Level"
%I0.5
"DI -Pure Water %Q1.4
Tank 01 Level "DO - Pur Water
High" Tank High-Level"
%I1.3
"DI-High Pressure %Q1.5
Pump Inlet Inlet "DO - RO inlet
Pressure Control" Pressure Low"
%I1.4 %Q1.6
"DI-Backwash "DO - Bakwash
Level" Level"
Totally Integrated
Automation Portal
Program blocks
ALARME [FC4]
ALARME Properties
General
Name ALARME Number 4 Type FC Language LAD
Numbering Automatic
Information
Title Author Comment Family
Version 0.1 User-defined ID
Network 1:
%Q0.0
"DO-Raw Water %DB1.DBX376.0
Pump relay" %DB1.DBX376.0
%DB1.DBX376.1
%DB1.DBX376.1
%I1.7
"DI-01ST HP Pump %DB1.DBX376.2
Working" %DB1.DBX376.2
%DB1.DBX376.3
%DB1.DBX376.3
%I2.0
"DI-02ND HP %DB1.DBX376.4
Pump Working" %DB1.DBX376.4
%DB1.DBX376.5
%DB1.DBX376.5
%Q2.0
"DO-Spply Pump %DB1.DBX376.6
relay 01" %DB1.DBX376.6
%DB1.DBX376.7
%DB1.DBX376.7
Network 2:
Totally Integrated
Automation Portal
%Q1.1
"DO-Spply Pump %DB1.DBX377.0
relay 02" %DB1.DBX377.0
%DB1.DBX377.1
%DB1.DBX377.1
%Q1.0
"DO-ELECTRICAL %DB1.DBX377.2
VALV" %DB1.DBX377.2
%DB1.DBX377.3
%DB1.DBX377.3
%I1.6
"DI-Inlet Valve %DB1.DBX377.4
Working" %DB1.DBX377.4
%DB1.DBX377.5
%DB1.DBX377.5
%Q2.3
"DO-Washing %DB1.DBX377.6
Valve Controle" %DB1.DBX377.6
%DB1.DBX377.7
%DB1.DBX377.7
Network 3:
%Q2.2
"DO-Washing %DB1.DBX378.0
Pump relay" %DB1.DBX378.0
%DB1.DBX378.1
%DB1.DBX378.1
%I0.1
"DI -Raw Water %DB1.DBX378.2
Tank Level Low" %DB1.DBX378.2
%I0.4
"DI -Middel Water %DB1.DBX378.3
Tank Level Low" %DB1.DBX378.3
%I0.2
"DI -Middel Water %DB1.DBX378.4
Tank Level High" %DB1.DBX378.4
%I0.7 %DB1.DBX382.5
"DI -Pure Water "DATA SYSTEM".
Tank 01 Level "DI-DO"."MDO-
Low" Waching Pump"
%I0.5
"DI -Pure Water
Tank 01 Level %DB1.DBX378.6
High" %DB1.DBX378.6
%I2.3
"DI -Pure Water
Tank 02 Level %DB1.DBX378.7
Low" %DB1.DBX378.7
%I2.1
"DI -Pure Water
Tank 02 Level %DB1.DBX379.0
High" %DB1.DBX379.0
Totally Integrated
Automation Portal
Program blocks
Main [OB1]
Main Properties
General
Name Main Number 1 Type OB Language LAD
Numbering Automatic
Information
Title "Main Program Sweep (Cy‐ Author Comment ANALOG INPUT Family
cle)"
Version 0.1 User-defined ID
Network 1:
Analog input
0001 FOR #i := 1 TO 4 DO
0002 // Statement section FOR
0003 ;
0004 "Analog scale"("AI-NORM_X VALUE" := "DATA SYSTEM".ANALOG[#i]."AI-NORM_X",
0005 "AI-SCAL_X MIN" := "DATA SYSTEM".ANALOG[#i]."AI-SCALE_X MIN",
0006 "AI-SCAL_X MAX" := "DATA SYSTEM".ANALOG[#i]."AI-SCALE_X MAX",
0007 "AI-SCAL_X OUT" => "DATA SYSTEM".ANALOG[#i]."AI-SCALE_X");
0008 END_FOR;
Network 2:
Transfert Data
0001 "Transfer Fonction"();
Network 3:
%FC3
"SYSTEM"
EN ENO
Network 4:
%FC4
"ALARME"
EN ENO
Network 5:
%FC6
"Block_1"
EN ENO
Network 6:
%M110.5 %M110.1
"pushbutton on" "st ct"
S
%M110.6 %M110.1
"pushbutton off" "st ct"
R
%M110.4 %Q2.7
"Tag_9" "Heater"
R
Network 7:
Totally Integrated
Automation Portal
"Data_block_1".
%M110.1 %Q2.6
temph
"st ct" "COLD"
<=
R
Real
60.0
Network 8:
%M110.1 %FC8
"st ct" "Block_3"
EN ENO
Totally Integrated
Automation Portal
Program blocks
DATA SYSTEM [DB1]
DATA SYSTEM Properties
General
Name DATA SYSTEM Number 1 Type DB Language DB
Numbering Automatic
Information
Title Author Comment Family
Version 0.1 User-defined ID
Name Data type Offset Start value Retain Accessi‐ Writ‐ Visible in Setpoint Supervi‐ Comment
ble from able HMI engi‐ sion
HMI/OPC from neering
UA/Web HMI/
API OPC
UA/
Web
API
Static
ANALOG Array[1..4] of 0.0 False True True True False
"Analog Input"
ANALOG[1] "Analog Input" 0.0 False True True True False
AI-NORM_X Int 0.0 0 False True True True False
AI-SCALE_X Real 2.0 0.0 False True True True False
AI-SCALE_X MAX Real 6.0 200.0 False True True True False
AI-SCALE_X MIN Real 10.0 0.0 False True True True False
ANALOG[2] "Analog Input" 14.0 False True True True False
AI-NORM_X Int 14.0 0 False True True True False
AI-SCALE_X Real 16.0 0.0 False True True True False
AI-SCALE_X MAX Real 20.0 20.0 False True True True False
AI-SCALE_X MIN Real 24.0 0.0 False True True True False
ANALOG[3] "Analog Input" 28.0 False True True True False
AI-NORM_X Int 28.0 0 False True True True False
AI-SCALE_X Real 30.0 0.0 False True True True False
AI-SCALE_X MAX Real 34.0 2000.0 False True True True False
AI-SCALE_X MIN Real 38.0 0.0 False True True True False
ANALOG[4] "Analog Input" 42.0 False True True True False
AI-NORM_X Int 42.0 0 False True True True False
AI-SCALE_X Real 44.0 0.0 False True True True False
AI-SCALE_X MAX Real 48.0 0.0 False True True True False
AI-SCALE_X MIN Real 52.0 0.0 False True True True False
TIME Array[1..20] of 56.0 False True True True True
IEC_TIMER
TIME[1] IEC_TIMER 56.0 False True True True True
PT Time 60.0 T#2s False True True True False
ET Time 64.0 T#0ms False True False True False
IN Bool 68.1 false False True True True False
Q Bool 68.2 false False True False True False
TIME[2] IEC_TIMER 72.0 False True True True True
PT Time 76.0 T#4s False True True True False
ET Time 80.0 T#0ms False True False True False
IN Bool 84.1 false False True True True False
Q Bool 84.2 false False True False True False
TIME[3] IEC_TIMER 88.0 False True True True True
PT Time 92.0 T#30s False True True True False
ET Time 96.0 T#0ms False True False True False
IN Bool 100.1 false False True True True False
Q Bool 100.2 false False True False True False
TIME[4] IEC_TIMER 104.0 False True True True True
PT Time 108.0 T#3s False True True True False
ET Time 112.0 T#0ms False True False True False
IN Bool 116.1 false False True True True False
Q Bool 116.2 false False True False True False
TIME[5] IEC_TIMER 120.0 False True True True True
PT Time 124.0 T#10s False True True True False
ET Time 128.0 T#0ms False True False True False
IN Bool 132.1 false False True True True False
Q Bool 132.2 false False True False True False
TIME[6] IEC_TIMER 136.0 False True True True True
PT Time 140.0 T#5s False True True True False
ET Time 144.0 T#0ms False True False True False
IN Bool 148.1 false False True True True False
Q Bool 148.2 false False True False True False
TIME[7] IEC_TIMER 152.0 False True True True True
PT Time 156.0 T#15s False True True True False
ET Time 160.0 T#0ms False True False True False
Totally Integrated
Automation Portal
Name Data type Offset Start value Retain Accessi‐ Writ‐ Visible in Setpoint Supervi‐ Comment
ble from able HMI engi‐ sion
HMI/OPC from neering
UA/Web HMI/
API OPC
UA/
Web
API
IN Bool 164.1 false False True True True False
Q Bool 164.2 false False True False True False
TIME[8] IEC_TIMER 168.0 False True True True True
PT Time 172.0 T#5s False True True True False
ET Time 176.0 T#0ms False True False True False
IN Bool 180.1 false False True True True False
Q Bool 180.2 false False True False True False
TIME[9] IEC_TIMER 184.0 False True True True True
PT Time 188.0 T#10s False True True True False
ET Time 192.0 T#0ms False True False True False
IN Bool 196.1 false False True True True False
Q Bool 196.2 false False True False True False
TIME[10] IEC_TIMER 200.0 False True True True True
PT Time 204.0 T#10s False True True True False
ET Time 208.0 T#0ms False True False True False
IN Bool 212.1 false False True True True False
Q Bool 212.2 false False True False True False
TIME[11] IEC_TIMER 216.0 False True True True True
PT Time 220.0 T#6000m False True True True False
ET Time 224.0 T#0ms False True False True False
IN Bool 228.1 false False True True True False
Q Bool 228.2 false False True False True False
TIME[12] IEC_TIMER 232.0 False True True True True
PT Time 236.0 T#10s False True True True False
ET Time 240.0 T#0ms False True False True False
IN Bool 244.1 false False True True True False
Q Bool 244.2 false False True False True False
TIME[13] IEC_TIMER 248.0 False True True True True
PT Time 252.0 T#0ms False True True True False
ET Time 256.0 T#0ms False True False True False
IN Bool 260.1 false False True True True False
Q Bool 260.2 false False True False True False
TIME[14] IEC_TIMER 264.0 False True True True True
PT Time 268.0 T#0ms False True True True False
ET Time 272.0 T#0ms False True False True False
IN Bool 276.1 false False True True True False
Q Bool 276.2 false False True False True False
TIME[15] IEC_TIMER 280.0 False True True True True
PT Time 284.0 T#0ms False True True True False
ET Time 288.0 T#0ms False True False True False
IN Bool 292.1 false False True True True False
Q Bool 292.2 false False True False True False
TIME[16] IEC_TIMER 296.0 False True True True True
PT Time 300.0 T#0ms False True True True False
ET Time 304.0 T#0ms False True False True False
IN Bool 308.1 false False True True True False
Q Bool 308.2 false False True False True False
TIME[17] IEC_TIMER 312.0 False True True True True
PT Time 316.0 T#0ms False True True True False
ET Time 320.0 T#0ms False True False True False
IN Bool 324.1 false False True True True False
Q Bool 324.2 false False True False True False
TIME[18] IEC_TIMER 328.0 False True True True True
PT Time 332.0 T#0ms False True True True False
ET Time 336.0 T#0ms False True False True False
IN Bool 340.1 false False True True True False
Q Bool 340.2 false False True False True False
TIME[19] IEC_TIMER 344.0 False True True True True
PT Time 348.0 T#0ms False True True True False
ET Time 352.0 T#0ms False True False True False
IN Bool 356.1 false False True True True False
Q Bool 356.2 false False True False True False
TIME[20] IEC_TIMER 360.0 False True True True True
PT Time 364.0 T#0ms False True True True False
ET Time 368.0 T#0ms False True False True False
IN Bool 372.1 false False True True True False
Q Bool 372.2 false False True False True False
ALARME Array[1..3] of 376.0 False True True True True
Word
ALARME[1] Word 376.0 16#0 False True True True True
Totally Integrated
Automation Portal
Name Data type Offset Start value Retain Accessi‐ Writ‐ Visible in Setpoint Supervi‐ Comment
ble from able HMI engi‐ sion
HMI/OPC from neering
UA/Web HMI/
API OPC
UA/
Web
API
ALARME[2] Word 378.0 16#0 False True True True True
ALARME[3] Word 380.0 16#0 False True True True True
DI-DO "DI_DO" 382.0 False True True True False
MDO- Raw Water Pump Bool 382.0 false False True True True False
MDO- 01ST HP Water Bool 382.1 false False True True True False
Pump
MDO- 02ND HP Water Bool 382.2 false False True True True False
Pump
MDO- 01ST Spply Water Bool 382.3 false False True True True False
Pump
MDO- 02ND Spply Water Bool 382.4 false False True True True False
Pump
MDO- Waching Pump Bool 382.5 false False True True True False
MDO- Inlet Valve Bool 382.6 false False True True True False
MDO- Waching Valve Bool 382.7 false False True True True False
MDO- Three Wave Valve Bool 383.0 false False True True True False
MDI - Raw Water Tank LM Bool 383.1 false False True True True False
MDI - Raw Water Tank LL Bool 383.2 false False True True True False
MDI - Middel Water Tank Bool 383.3 false False True True True False
LH
MDI - Middel Water Tank Bool 383.4 false False True True True False
LM
MDI - Middel Water Tank Bool 383.5 false False True True True False
LL
MDI - 01ST Pure Water Bool 383.6 false False True True True False
Tank LH
MDI - 01ST Pure Water Bool 383.7 false False True True True False
Tank LM
MDI - 01ST Pure Water Bool 384.0 false False True True True False
Tank LL
MDI - 02ND Pure Water Bool 384.1 false False True True True False
Tank LH
MDI - 02ND Pure Water Bool 384.2 false False True True True False
Tank LM
MDI - 02ND Pure Water Bool 384.3 false False True True True False
Tank LL
CTDPV01 UDInt 386.0 0 False True True True True
CTDCV01 UDInt 390.0 0 False True True True False
CTDPV02 UDInt 394.0 0 False True True True False
CTDCV02 UDInt 398.0 0 False True True True False
TIME FONCTION Struct 402.0 False True True True False
M Int 402.0 45 False True True True False
S Int 404.0 0 False True True True False
conteur IEC_COUNTER 406.0 False True True True False
CU Bool 406.0 false False True True True False
CD Bool 406.1 false False True True True False
R Bool 406.2 false False True True True False
LD Bool 406.3 false False True True True False
QU Bool 406.4 false False True True True False
QD Bool 406.5 false False True True True False
PV Int 408.0 0 False True True True False
CV Int 410.0 0 False True True True False
Cuve01 Bool 412.0 false False True True True True
Cuve02 Bool 412.1 false False True True True False
MCuve01 Bool 412.2 false False True True True False
MCuve02 Bool 412.3 false False True True True False
RCuve01 Bool 412.4 false False True True True False
RCuve02 Bool 412.5 false False True True True False
1 Bool 414.0 false False True True True False
2 Bool 414.1 false False True True True False
3 Bool 414.2 false False True True True False
Totally Integrated
Automation Portal
Program blocks
Block_1 [FC6]
Block_1 Properties
General
Name Block_1 Number 6 Type FC Language LAD
Numbering Automatic
Information
Title Author Comment Family
Version 0.1 User-defined ID
Network 1:
NORM_X SCALE_X
MOVE Int to Real Real to Real
EN ENO EN ENO EN ENO
%IW64 "Data_block_1". 0 MIN "Data_block_1". 0.0 MIN "Data_block_1".
"Tag_5" IN OUT1 tempin "Data_block_1". OUT ana "Data_block_1". OUT temph
tempin VALUE ana VALUE
27648 MAX 100.0 MAX
Totally Integrated
Automation Portal
Program blocks
Data_block_1 [DB4]
Data_block_1 Properties
General
Name Data_block_1 Number 4 Type DB Language DB
Numbering Automatic
Information
Title Author Comment Family
Version 0.1 User-defined ID
Name Data type Start value Retain Accessible Writ‐ Visible in Setpoint Supervi‐ Comment
from able HMI engi‐ sion
HMI/OPC from neering
UA/Web HMI/
API OPC
UA/
Web
API
Static
tempin Int 0 False True True True False
ana Real 0.0 False True True True False
temph Real 0.0 False True True True False
Cycn Int 0 False True True True False
countv Int 0 False True True True False
Totally Integrated
Automation Portal
Program blocks
HEATER CT [FC7]
HEATER CT Properties
General
Name HEATER CT Number 7 Type FC Language LAD
Numbering Automatic
Information
Title Author Comment Family
Version 0.1 User-defined ID
Network 1:
%Q2.7
"Data_block_1". "Heater"
temph
SR
<
S Q
Real
80.0
"Data_block_1".
temph
>
Real R1
82.0
Totally Integrated
Automation Portal
Program blocks
Block_3 [FC8]
Block_3 Properties
General
Name Block_3 Number 8 Type FC Language LAD
Numbering Automatic
Information
Title Author Comment Family
Version 0.1 User-defined ID
Network 1:
"Data_block_1". %M110.2
temph
"setcyc"
<=
S
Real
35.0
Network 2:
%M110.2 %FC7
"setcyc" "HEATER CT"
EN ENO
%Q2.6
"COLD"
S
Network 3:
%DB5
"ster T"
"Data_block_1". TON %M110.2
temph Time "setcyc"
>=
IN Q R
Real
T#30m PT ET T#0ms
80.0
Network 4:
Network 5:
%DB6
"IEC_Counter_0_
DB_2"
"IEC_Counter_0_
DB_2".CV
>=
Int R
3 3 PV
Totally Integrated
Automation Portal
Name Data type Start value Retain Accessible Writ‐ Visible in Setpoint Supervi‐ Comment
from able HMI engi‐ sion
HMI/OPC from neering
UA/Web HMI/
API OPC
UA/
Web
API
Static
CU Bool false True True True True False
CD Bool false True True True True False
R Bool false True True True True False
LD Bool false True True True True False
QU Bool false True True True True False
QD Bool false True True True True False
PV UDInt 0 True True True True False
CV UDInt 0 True True True True False
Totally Integrated
Automation Portal
Name Data type Start value Retain Accessible Writ‐ Visible in Setpoint Supervi‐ Comment
from able HMI engi‐ sion
HMI/OPC from neering
UA/Web HMI/
API OPC
UA/
Web
API
Static
CU Bool false True True True True False
CD Bool false True True True True False
R Bool false True True True True False
LD Bool false True True True True False
QU Bool false True True True True False
QD Bool false True True True True False
PV UDInt 0 True True True True False
CV UDInt 0 True True True True False
Totally Integrated
Automation Portal
Name Data type Start value Retain Accessible Writ‐ Visible in Setpoint Supervi‐ Comment
from able HMI engi‐ sion
HMI/OPC from neering
UA/Web HMI/
API OPC
UA/
Web
API
Static
PT Time T#0ms False True True True False
ET Time T#0ms False True False True False
IN Bool false False True True True False
Q Bool false False True False True False
Totally Integrated
Automation Portal
Name Data type Start value Retain Accessible Writ‐ Visible in Setpoint Supervi‐ Comment
from able HMI engi‐ sion
HMI/OPC from neering
UA/Web HMI/
API OPC
UA/
Web
API
Static
CU Bool false True True True True False
CD Bool false True True True True False
R Bool false True True True True False
LD Bool false True True True True False
QU Bool false True True True True False
QD Bool false True True True True False
PV Int 0 True True True True False
CV Int 0 True True True True False