TECHNICAL SPECIFICATION
Technical & Price Offer of 1250 kVA(11/0.415KV) Sub-Station
Project - Doctors Lab, Bakal, Satkhira
Prospect : Technical & Price Offer of 1250 kVA(11/0.415KV) Substation Equipments.
TECHNICAL SPECIFICATION
S.L. Description Price in Taka
QTY
NO. Unit Unit Price Total Price
01 DROPOUT FUSE Set 1
Technical Specification :
Rated Voltage (Nominal) : 11 kV
Rated Maximum Voltage : 15 kV
Rated Frequency : 50 Hz
BIL : 75 kV
Rated Current RMS : 80 A
Interrupting Current RMS : 10 kA
Withstand Test Voltage
-Dry , 1 Min. : 35 kV
-Wet , 10 sec. : 30 kV
02 LIGHTNING ARRESTOR Set 1
Technical Specification :
Rated Voltage (RMS) : 9 kV
Rated System voltage : 12 kV
Frecuency : 50 Hz
Minimum Spark Over (RMS) : 14 kV
Maximum Spark Over (RMS) : 40 kV
Maximum Impulse Spark (Crest) : 45 kV
Withstand Voltage
-Wet , 10 sec. : 24 kV
-Dry , 1 min. : 28 kV
Discharge 33 kV (Crest) : 5 kA
Impulse Current Withstand : 55 kA
S.L. Description Price in Taka
QTY
NO. Unit Unit Price Total Price
03 11 KV H.T. SWITCHGEAR (VCB) Set 1
Supply, installation, testing and commissioning of 14 SWG sheet steel clad, dust and vermin proof, POWDER
COATED, free standing, floor mounting indoor HT Switchgear 11KV, 50Hz, three phase, 800 A hard drawn
electrolytic copper busbars equipped with:
1 No.630 A, 11 KV, 25KA rated short time current, 50 Hz,
Electrical motor operated & spring charged stored energy
mechanism with draw type VCB, manual closing/ tripping
device for emergency operation, maximum service voltage
12KV, short circuit breaking capacity 25KA, 110V DC/
110VAC from PT for operating shunt tripping coil,
mechanically ON/OFF/TRIP indicator.
2 Nos. Cast resin insulated, single pole, Potential Transformer,
ratio: 11/√3/0.110/√3 KV, Class 0.5, 50 VA.
1 No. MCB of adequate rating for PT Scondary protection.
3 Nos. Cast resin insulated, 11 KV dry type double core CT
with Ratio: 100/5/5A, 1st core for metering, 2nd for protection
Core 1 : 10 VA, Class 0.5M5
Core 2 : 15 VA, Class 10P10
3 Nos. Ammeter, 0 - 200 A.
1 No. Voltmeter, 0 - 15 KV, with selector switch
1 No. Triple pole solid state micro-processor operated IDMT
relay for over current, earthfault and short circuit protection
with standard setting.
3 Nos. ON/OFF/RESET Push Button
3 Nos. Indicating Lamps/ON/OFF/TRIP
1 No. Panel Heater with Thermostate switch
S.L. Description Price in Taka
QTY
NO. Unit Unit Price Total Price
04 SUPPLY OF 1250KVA(11/0.415KV) TRANSFORMER Set 1
3 Phase oil immersed, naturally air cooled Transformer acc. to VDE/IEC/DIN/BSS standard with 3 HT Bushing and 4
LT Bushings arranged on tank top, conservator, oil level indicator, drain and filling valves, lifting lugs, with first filling
of oil in Transformer
TECHNICAL DATA
Rated Capacity : 1250 KVA
Rated Frequency : 50 Hz
Rated Voltage,
- Primary : 11000 V
-Secondary : 415 V
Vector Group : Dyn 11
Off-load tap changer : -2.5%, 0, 2,5%, 5%, 7.5% (4 Step, 5 Possition)
Ambient Temperature : 40°C
Temperature rise
- in Oil : 60°C (Max)
- in Coil : 65°C (Max)
Star point brought out & loadable upto : 100%
Max. service altitude : 1000 Meters
Installation : Indoor/outdoor
No load losses : 1620 W
Full load losses : 17100 W
Cooling system : ONAN
Impedence : 6 % (approx)
Accessories:
- Silicagel breather
- Thermometer
- Oil drain vulve
S.L. Description Price in Taka
QTY
NO. Unit Unit Price Total Price
05 LT SWITCHGEAR - 2000A Set 1
Sheet steel clad, dust and vermin proof, POWDER COATED, free standing, floor mounting type, 415V, 50 Hz, indoor
type Low Tension Switchgear with 2560A hard drawn copper busbars, TPN & E(50%) equipped with:
INCOMING
1 No. 2000A,415V,66KA, 3 Phase, 3Pole, Fixed type, Air circuit breaker,
motor operated stored energy mechanism,auxilary NO+NC contacts with built
in microprocessor/ solid state controll device for adjustable overload &
adjustable short circuit protection with U/V protection with ATS system
3 Nos. Current Transformer, Ratio : 2000/5A With Suitable Accuracy & Burden
1 No. Digital Multi Function Meter
3 Nos. Phase Indication Lamp
1 Set Contol Fuse
OUTGOING
1 No. 1250A, 50KA, TP MCCB with Adjustable thermal Overload & adjustable
magnetic short circuit releases. For PFI
1 No. 1250A, 50KA, TP MCCB with Adjustable thermal Overload & adjustable
magnetic short circuit releases.
1 No. 630A, 36KA, TP MCCB with Adjustable thermal Overload & adjustable
magnetic short circuit releases.
1 No. 125A, 25KA, TP MCCB with Adjustable thermal Overload & adjustable
magnetic short circuit releases.
S.L. Description Price in Taka
QTY
NO. Unit Unit Price Total Price
06 SUPPLY OF 750KVAR PFI PANEL Set 1
Sheet steel clad 14/16 SWG, dust and vermin proof, POWDER COATED, free standing, floor mounting, 415V, 50 Hz,
750 KVAR Indoor type Automatic Power Factor Improvement Plant with 1400A TP+E-50% Hard Drawn Copper
busbar & auto relay of 12 switching step, comprising:
2 Nos. (6*25) 150 KVAR Bank of TP dry type Power Capacitors with built-in
discharge resister
3 Nos. (4*25) 100 KVAR Bank of TP dry type Power Capacitors with
built-in discharge resister
1 No. (2*25) 50 KVAR Bank of TP dry type Power Capacitors with
built-in discharge resister
2 Nos. 25 KVAR Bank of TP dry type Power Capacitors with built-in
discharge resister
3 Nos. 10 KVAR Bank of TP dry type Power Capacitors with built-in
discharge resister
1 No. 7.5 KVAR Bank of TP dry type Power Capacitors with built-in
discharge resister
1 No. 12.5 KVAR Bank of TP dry type Power Capacitors with built-in
discharge resister fixed directly connected with busbar
1 No. Automatic Power Factor Correction Relay with interlocking
auxiliary relay
18 Nos. TP Magnetic Contactors of adequate rating
19 Nos. TP MCCB/MCB of adequate ratings
12 Nos. Indicating Lamps
1 Set of Control fuses
07 EARTHING FOR SUBSTATION Set 5
Earth Electrode
1.5" dia GI pipe Top and Bottom (10 feet in Both Side) = 20ft
Boring will be: 110ft.
Earthing Copper 0 SWG : 120 ft
Earthing Bar: 2 nos .
S.L. Description
QTY
NO. Unit
08 INSTALLATION OF SUBSTATION EQUIPMENT Job 1
11KV HT Switchgear(VCB)
- Installation, Testing & Commissioning of 11KV
HT Panel including supply of consumables
1250kVA Transformer
- Installation, Testing & Commissioning of 1250kVA
Transformer including supply of consumables
LT Switchgear
- Installation, Testing & Commissioning of LT Panel
including supply of consumables like
PFI Plants
- Installation, Testing & Commissioning of PFI Plants
including supply of consumables like
S.L. Description
QTY
NO. Unit
EQUIPMENT'S LIST
Sl
Description
No
1 DROPOUT FUSE Set 1
2 LIGHTNING ARRESTOR Set 1
3 11 KV H.T.SWITCHGEAR (VCB) Set 1
4 TRANSFORMER (1250kVA) Set 1
5 LT SWITCHGEAR (2000A) Set 1
6 750 KVAR AUTOMATIC PFI PLANT Set 1
7 EARTHING FOR SUB-STATION Set 5
8 11KV HEAT SHRINK KIT Set 6
9 INSTALLATION OF SUB-STATION Job 1
10 TRANSPORTATION, LOADING & UNLOADING Job 1
11 ELECTRICAL LICENSING BOARD FORMALITIES (ELB) Job 1