LV Power Cables
This catalogue contains technical information on Riyadh Cables' low voltage cables including
PVC and XLPE insulations of Copper/Aluminium, armoured and un-armoured designs, single
and multicore constructions along with a different range of sheathing options. Cables are
categorized by insulation and armouring. Each section contains technical details and
contructional data.
Product Specifications
Low Voltage Cable designs use constructions covered by IEC 60502-1, BS 6346 and BS 5467.
Please note, however, that RCGC can also supply a range of alternative designs to meet more
specialized customers' needs including enhanced fire performance and added environmental
protection. Cables can also be supplied with alternative sheathing materials and colours, or
can be made to individual customer specification or other recognized standards, both National
and International. In particular, cables can be manufactures to meet specific requirements for
the elimination of smoke and toxic gases using low smoke and non halogen materials.
Cable Selection
It is essential that the type of cable ordered is suitable for its intended use. Cable choice will
be based on a whole range of factors including installation specifications, relevant local
regulations and the performance of appropriate cable types. It is therefore impossible to
provide a conclusive guide to cable selection and we would advise you to contact us for our
specialist advice on suitable designs to meet your specific cable needs.
Conductors
Conductors shall be of Copper or Aluminium, circular standed (Non-compacted or
Compacted) or Shaped, Class 2 to IEC 60228, BS EN 60228. For smaller sizes, a solid circular
conductor, Class 1 as per IEC 60228, BS EN 60228 can also be supplied upon request.
Insulation
XLPE material and thickness shall be as per IEC 60502 or BS 5467 rated for 90°C continuous
operation.
PVC material and thickness shall be as per IEC 60502 or BS 6346. PVC insulation Material-
Type A as per IEC 60502 or TI1 as per BS EN 50363.
Assembly
Two, Three or Four insulated conductors are laid-up together with non-hygroscopic fillers
compatible with the insulation material and the assembly is bedded with an extruded layer of
PVC. In case of non-armoured cables, this layer may be omitted if the outer shape of the cable
remains practically circular.
LV Power Cables Catalogue
Intruduction
LV Power Cables
Colour Code
Colour code (1) is followed by most utilities in the Middle East and colour of insulation is as
mentioned below. However, cables as per colour code (2) mentioned below are also provided
based on customer's request.
Colour code ( 1 ) Colour code ( 2 )
1 Core : Red or Black 1 Core : Brown or Blue
2 Cores : Red, Black 2 Cores : Brown, Blue
3 Cores : Red, Yellow, Blue 3 Cores : Brown, Black, Grey
4 Cores : Red, Yellow, Blue, Black 4 Cores : Blue, Brown, Black, Grey
5 Cores : Red, Yellow, Blue, Black, Green 5 Cores : Green/Yellow, Blue, Brown, Black, Grey
Metallic Screen
Metallic screen of bare copper tape with 0.075 mm nominal thickness is applied helically with
suitable overlap. Also, copper wire screen can be applied upon request.
Metallic Sheath
When required, lead sheath shall be as per BS EN 12548 and thickness shall be as per IEC
60502-1; it shall be applied over the inner sheath.
Armour
When required, Galvanized Steel Wires shall be applied helically over the bedding as per IEC
60502-1, or BS 5467 or BS 6346; or Double Steel Tapes shall be applied helically over the
bedding of multi-core cables as per IEC 60502-1. Single core cables shall have Aluminium
wire armour.
Outer Sheath
Outer sheath will be extruded PVC type ST2 as per IEC 60502-1, Type 9 as per BS 7655.
Special type of PVC sheathing material such as fire retardant PVC, anti-termite and anti-
rodent PVC, ultraviolet PVC, Oil resistant PVC, etc. are available on request, also other
special sheathing materials such as LLDPE, MDPE, HDPE, LSHF, etc are available.
Fire Performance of Cable Sheaths
Cables can be supplied with special flame retardant PVC outer sheath to comply with the
flame test requirements of IEC 60332-3-22, IEC 60332-3-23 and IEC 60332-3-24, can also
supply cables with Low Smoke Halogen Free (LSHF) material according to IEC 60502-1 and
BS 6724 or other equivalent standards.
Quality Assurance
Effective Quality Assurance procedures are essential to ensure Riyadh Cables of the
consistency and long term reliability and perfomance of all products. RCGC has always
recognized the importance of Quality Assurance and this commitment is reflected in the
company's accreditation. At RCGC, Quality Assurance is an integral part of production and
supply process and maintained at all stages from order entry and manufacture through testing,
packaging and shipping. All Quality Assurance procedures, and systems are regularly audited
against International Standards.
LV Power Cables Catalogue
Intruduction
LV Power Cables
LSHF Cables
Fire is a complex and emotive subject, the consequences of fire can be catastrophic.
The nature of organic material used in the manufacturing of cables and possible installation
conditions in areas of the fire risk can lead to a situation where cables may contribute to the
spread of fire, emission of smoke and release of combustion products injurious to equipment
and human health.
In power stations, hospitals, theatres, hotels and other large public buildings, the loss of
visibility caused by smoke evolved from burning cable materials can cause panic and create
serious problems when evacuating personnel. Location of the fire source and fire fighting are
also greatly hampered by smoke. Additionally the presence of corrosive gases in the smoke
result in damage and failure of sensitive electrical equipment and may initiate long term
deterioration of structures, as well as being injurious to the health of personnel even after
short exposure.
Awareness of this situation has lead to the development of new cable technologies and
introduction by major cable users of cable types with low emission of smoke, corrosive and
toxic fumes and reduced flame propagation properties.
In considering cable systems with improved fire performance characteristics it is useful to first
consider the various aspects of the effect of fire on a cable:
- Propagation of fire along cable runs.
- Evolution of smoke leading to obstruction of exits.
- Evolution of acid gas leading to corrosion of equipment.
- Evolution of toxic fumes leading to personal injury.
LSHF cables use special formulation based on non-halogenated polymers in order to restrict
the generation of smoke as much as possible. Materials are carefully selected and the
compounds carefully designed in order to ensure the best performance of the external sheaths,
which are directly exposed to fire.
LSHF Cables manufactured by Riyadh Cables group have been designed to offer improved
performance in areas where smoke and fume emission in the event of a fire would cause
particular problems. Compounds used in LSHF cables do not contain halogen hence, do not
emit halogenated acids when burnt which help in minimizing the total cost of the damage
caused by fire and generate little smoke when burned. Furthermore, the rate at which this low
level of smoke is released, is very much slower than that of PVC or similar halogenated
polymers.
LSHF Cables manufactured by Riyadh Cables Group have controlled limits on smoke
evolution, when assessed by burning samples of cables in a 3 meter cube smoke chamber as
per IEC 61034. Generally these cables combine the properties of low corrosive gas emission
and low toxic gas emission as they are essentially halogen free when assessed by IEC 60754-1
and IEC 60754-2.
LV Power Cables Catalogue
Intruduction
LV Power Cables
Vertical Flame Test for Single Cables (IEC 60332-1-2)
PURPOSE
The purpose of the test is to determine the resistance to flame propagation for single vertical
cables.
This test is not suitable for small wires with solid conductor having a diameter less than 0.8
mm or stranded conductors less than 0.5 mm² because the conductor melts before the test is
completed. (See IEC 60332)
EQUIPMENT
- Enclosure
- Burner
- Wedge (45°)
- A verticle adjustable jig
- Matches
- Ruler
- Stop-watch
This test is to be conducted in a 3-sided enclosure
(300mm wide, 450 mm deep and 1200 mm high)
with open front and closed top and bottom.
A 1 kW flame produced by a propane burner with adjustable air and gas flow is used.
CALIBRATION
The burner is calibrated by adjusting the flame to abou 180 mm and the inner blue cone to 55
mm. The temperature increase is measured 95 mm above the top of the burner by using a
thermocouple in a copper slug. The time for the temperature from 100°C should be 45 s.
LV Power Cables Catalogue
Intruduction
LV Power Cables
Bunch Burning Test (IEC 60332-3 SERIES)
PURPOSE
This standard describes a method of type approval testing to define the ability of bunched
cables to restrain flame propagation in defined conditions regardless of their application, i.e.
power, telecommunications (including data transmission and optical fibre cables), etc.
Three categories (A, B and C) are defined and distinguished by test duration and the volume
of non-metallic material of the sample under test. Two methods of mounting (designations F/R
and F) are application to category A. Only designation F applies to categories B and C.
EQUIPMENT
- Fire test rig
- Ladder
- Ignition source
LV Power Cables Catalogue
Intruduction
LV Power Cables
Smoke Density 3M Test Cube (IEC 61034)
PURPOSE
The measurement of smoke density is an important aspect in the evaluation of the burning
performance of electric cables as it is related to the evacuation of persons and accessibility for
fire-fighting. The standard describe measurements of smoke emission when electric cables are
burned horizontally. The light transmittance for flaming and smouldering conditions can be
used when comparing different cables.
EQUIPMENT
- Cube enclosure
- Photometric system
- Fire source
- Smoke mixer
LV Power Cables Catalogue
Intruduction
LV Power Cables
Acidity (pH) and Conductivity (IEC 60754-2)
TEST ON GASES EVOLVED DURING COMBUSTION OF ELECTRICAL CABLES
PURPOSE
The purpose of this test is to determine the pH and conductivity of gases evolved during the
combustion of materials taken from electric cables as a function of temperature.
PRINCIPLE OF OPERATION
A predetermined quantity of the test material is burned in a tube furnace. The evolved gases
are trapped by bubbling through bottles filled with distilled or demineralized water. The
acidity is measured by determination of pH value. The conductivity of the solution is also
measured.
EQUIPMENT
- Test apparatus
- pH meter
- Conductivity meter
- Analytical balance
- Computer containing a measuring program
- Deionized water
Cable mounted for fire test Fire test in progress Completion of fire test
(The charred portion is less than the specified requirement)
LV Power Cables Catalogue
Intruduction
LV Power Cables
FIRE RESISTANCE CABLES
Fire Resistance (as applicable)
Mica tape(s) shall be provided over copper conductor in order to satisfy the requirements of
IEC 60331, BS 6387 or BS 7846.
To determine the performance of a specimen of a cable when it is subjected to the conditions
of tests specified in the specifications for performance requirements for cables required to
maintain circuit integrity under fire conditions.
IEC 60331-1
Test Method: Fire ≥ 830⁰C & with shock on the support for a flame application time of either
30 minutes, 60 minutes, 90 minutes or 120 minutes as chosen.
Acceptance: voltage is maintained and conductor does not rupture.
IEC 60331-21
Procedure & Requirements: Fire ≥ 750⁰C alone, 90 minutes flame application time is
recommended where IEC 60331-11 is considered [Apparatus: Fire ≥ 750⁰C alone]]
Acceptance: voltage is maintained and conductor does not rupture.
BS 6387 : CWZ tests as per the following categories:
(1) Resistance to fire alone “C”: 950°C for 3 hours
(2) Resistance to fire with water “W”: 650°C for 15 minutes
(3) Resistance to fire with mechanical shock “ Z”: 950°C for 15 minutes (on the support
“specified vertical board”)
BS 7846 : F2 tests as per the following categories:
(1) Resistance to fire
(2) Resistance to fire with water.
(3) Resistance to fire with mechanical shock
These tests are assessed separately when tested in accordance with the standard.
BS 8491 : F30, F60 and F120 tests as per the following categories:
(1) F30: 842±40 °C with direct application of mechanical shock and water jet for 30 min.
(2) F60: 842±40 °C with direct application of mechanical shock and water jet for 60 min.
(3) F120: 842±40 °C with direct application of mechanical shock and water jet for 120 min.
LV Power Cables Catalogue
Intruduction
LV Power Cables
GUIDELENES FOR LOAD CAPACITY
The loading of the cable must be so limited that, at any point of the cable installation, all the
heat produced in the conductors under set conditions can be safety dissipated to the ambient
medium. Experience has shown that cables may be loaded as indicated in the tables The
values stated in Table no. 1 for cables laid in ground are based on standard service conditions
mostly used in power systems of electricity boards.
Load Factor : 1.0
Thermal resistivity of soil : 2.0 Km/W (dry area)
Ground temperature : 40oC
Air temperature : 55oC
No. of Cables/System :1
Laying depth : 0.7 meters
The current values apply to cables laid direct in the ground, bedded in sand if necessary and
covered with table tiles. It is also assumed that any pole mounted distribution points will be
shielded from direct sunlight.
The values given apply to cables laid in free air and shaded areas at 55⁰C. It is assumed here
that heat dissipation by convection and radiation will not be impeded, that the ambient
temperature will not rise and that there are no external heat sources. These conditions can be
taken as met if:
• The cable is laid at least "one cable diameter" from the nearest wall, floor or ceiling.
• The spacing between adjacent cable is at least twice the cable diameter.
• Cables being laid above each other have a vertical separation of at least twice the cable
diameter, the cable systems are at least four cable diameters or 30 cm.
• The rise in ambient temperature due to the dissipating heat is taken into consideration or
adequate space and ventilation is provided.
The leading ampacities determined according to IEC 60287 or CENELEC 64 will be identical.
They are based on the following figures for the thermal resistivity of the insulating materials.
PVC : 6.0 Km/W
XLPE : 3.5 Km/W
We also hold computerized calculations for the most varied working conditions and can
determine the maximum permissible load currents for almost any practical service condition.
LV Power Cables Catalogue
Intruduction
PARTICULARS & GUARANTEES RELATING TO PVC INSULATING COMPOUND (TYPE
A)
Sl. Guaranteed
Description Unit
No. Particulars
1 Tensile Strength and Elongation at break:
Min Tensile strength N/mm² 12.5
Min elongation at break % 150
2 Low temperature bend test:
Temperature at which specimen shall not crack °C -15±2
3 Low temperature elongation test:
Test temperature °C -15±2
Min. Elongation % 20
4 Low temperature Impact test:
Test temperature °C -
Min. Elongation
5 Accelerated ageing for specified at specified temperature
followed by loss of mass test:
Max. loss of mass after ageing 7 days at 80 ± 2 °C mg/cm² -
6 Accelerated ageing for specified period specified
temperature followed by tensile strength & elongation at
break
Number of Days ageing Days 7
Ageing Temperature °C 100 ± 2
Tensile Strength after ageing:
Min. value N/mm² 12.5
Max. variation % 25
Elongation at break after ageing:
Min. value % 150
Max. variation from unaged value % 25
7 Pressure test at high temperature:
Test temperature °C 80 ± 2
Max. indentation % 50
8 Resistance to cracking
Temperature at which specimen shall not crack °C 150 ± 2
9 Insulation resistance constant:
Min. K. value at 70°C M.Ohm.km
LV Power Cables Catalogue
Insulation/Sheath Materials
PARTICULARS & GUARANTEES RELATING TO PVC INSULATING COMPOUND (TYPE
TI1)
Sl. Guaranteed
Description Unit
No. Particulars
1 Tensile Strength and Elongation at break:
Min Tensile strength N/mm² 12.5
Min elongation at break % 125
2 Low temperature bend test:
Temperature at which specimen shall not crack °C -15 ± 2
3 Low temperature elongation test:
Test temperature °C -15 ± 2
Min. Elongation % 30
4 Accelerated ageing for specified period at specified
temperature followed by loss of mass test :
Max.loss of mass, after ageing for 7 days at 80 ± 2 °C mg/cm² 2.0
5 Accelerated ageing for specified period specified
temperature followed by tensile strength & elongation at
break
Number of Days ageing Days 7
Ageing Temperature °C 80 ± 2
Tensile Strength after ageing:
Min. value N/mm² 12.5
Max. variation % ± 20
Elongation at break after ageing:
Min. value % 125
Max. variation from unaged value % ± 20
6 Pressure test at high temperature:
Test temperature °C 80 ± 2
Max. indentation % 50
7 Resistance to cracking
Temperature at which specimen shall not crack °C 150 ± 2
8 Insulation resistance constant:
Min. K. value at 70°C M.Ohm.km 0.037
LV Power Cables Catalogue
Insulation/Sheath Materials
PARTICULARS & GUARANTEES RELATING TO XLPE INSULATION
Sl. Guaranteed
Description Unit
No. Particulars
1 Tensile Strength and Elongation at break:
Min Tensile strength N/mm² 12.5
Min elongation at break % 200
2 Accelerated ageing for specified period specified
temperature followed by tensile strength & elongation at
break
Number of Days ageing Days 7
Ageing Temperature °C 135 ± 2
Max. variation of tensile strength from unaged specimen % ± 25
Max. variation of elongation from unaged specimen % ± 25
3 Hot Set Test:
Treatment
- Temperature °C 200 ± 3
- Time under load Minutes 15
- Mechanical stress N/cm² 20
Max. elongation under load % 175
Max. permanent elongation after cooling % 15
4 Water Absorption:
Treatment
- Temperature °C 85 ± 2
- Duration Days 14
Max. variation of mass mg/cm² 1.0
5 Maximum permissible shrinkage:
Treatment
- Temperature °C 130 ± 3
- Duration Hours 1
Maximum permissible shrinkage: % 4
6 Insulation Resistance constant
(Ki) at maximum rated temperature (90°C) M.Ohm.km 3.67
7 Volume Resistivity at maximum rated temperature (90°C) Ohm.cm 1012
9 Acidic (corrosive) gases evolved :
Level of HCL % < 0.5
pH (minimum) BSEN 50267 4.3
Conductivity (maximum) (S/mm) BSEN 50267 10
LV Power Cables Catalogue
Insulation/Sheath Materials
PARTICULARS & GUARANTEES RELATING TO PVC OUTER SHEATH
TYPE ST2 (IEC 60502), TYPE 9 (BS 7655)
Sl. Guaranteed
Description Unit
No. Particulars
1 Tensile Strength and Elongation at break:
Min Tensile strength N/mm² 12.5
Min elongation at break % 150
2 Low temperature bend test:
Temperature at which specimen shall not crack °C -15 ± 2
3 Low temperature elongation test:
Test temperature °C -15 ± 2
Min. Elongation % 20
4 Low temperature Impact test:
Temperature at which specimen shall not crack °C -15 ± 2
5 Loss of mass:
After ageing for 7 days at 100 ± 2 °C
Max. loss of mass mg/cm² 1.5
6 Accelerated ageing for specified period at specified
temperature followed by tensile strength & elongation at
break test
Number of Days ageing 7
Ageing Temperature °C 100 ± 2
Tensile Strength after ageing:
Min. value N/mm² 12.5
Max. variation % 25
Elongation at break after ageing:
Min. value % 150
Max. variation from unaged value % 25
7 Pressure test at high temperature:
Test temperature °C 90 ± 2
Max. indentation % 50
8 Heat Shock Test:
Temperature at which specimen shall not crack % 150 ± 2
9 Insulation resistance constant:
Min. K. value at 20°C M.Ohm.km 0.0035
10 Flame Retardancy test (if required) As per IEC 60332-
1-2 (upon request)
LV Power Cables Catalogue
Insulation/Sheath Materials
Particulars & Guarantees Relating to LSHF Outer Sheath Type ST8 (IEC 60502-1)
Sl. Guaranteed
Description Unit
No. Particulars
1 Tensile Strength and Elongation at break :
Minimum Tensile strength N/mm² 9
Minimum Elongation at break % 125
2 Properties after ageing for specified period at specified
temperature followed by tensile strength and elongation at
break test
Number of days ageing 7
Ageing temperature °C 100 ± 2
Tensile Strength after ageing :
Minimum value N/mm² 9
Maximum variation % 40
Elongation at break after ageing :
Minimum Value % 100
Maximum variation from unaged value % 40
3 Low temperature bend test :
Temperature at which specimen shall not crack °C -15 ± 2
4 Low temperature elongation test :
Test temperature °C -15 ± 2
Minimum Elongation % 20
5 Low temperature impact test :
Temperature at which specimen shall not crack °C -15 ± 2
6 Pressure test at high temperature :
Test temperature °C 80 ± 2
Maximum indentation % 50
7 Water Absorption
Ageing : Number of hours 24
Ageing temperature °C 70 ± 2
Maximum increase in Mass mg/cm² 10
8 Acidic emission and corrosive gases evolved
Level of HCI % < 0.5
Fluorine Content % < 0.1
pH Minimum 4.3
Conductivity S/mm 10
LV Power Cables Catalogue
Insulation/Sheath Materials
Particulars & Guarantees Relating to LSHF Outer Sheath Type LTS 1 (BS 7655)
Sl. Guaranteed
Description Unit
No. Particulars
1 Tensile Strength and Elongation at break :
Minimum Tensile strength N/mm² 10
Minimum Elongation at break % 100
2 Properties after ageing for specified period at specified
temperature followed by tensile strength and elongation at
break test
Number of days ageing 7
Ageing temperature °C 100 ± 2
Tensile Strength after ageing :
Minimum value N/mm² 10
Maximum variation % 40
Elongation at break after ageing :
Minimum Value % 100
Maximum variation from unaged value % 40
3 Low temperature bend test :
Temperature at which specimen shall not crack °C -15 ± 2
4 Low temperature elongation test :
Test temperature °C -15 ± 2
Minimum Elongation % 30
5 Low temperature impact test :
Temperature at which specimen shall not crack °C -15 ± 2
6 Pressure test at high temperature :
Test temperature °C 80 ± 2
Maximum indentation % 50
7 Tear Resistance Test as per BS 6469 (sec. 99.1)
Minimum Value N/mm 5
8 Water Immersion Test as per BS 6469 (sec. 99.1)
Number of days ageing 7
Ageing temperature °C 70 ± 2
Maximum variation in tensile strength % 30
Maximum variation in elongation at break % 30
9 Acidic emission and corrosive gases evolved
Level of HCI % < 0.5
LV Power Cables Catalogue
Insulation/Sheath Materials
Single Core - Copper Conductor, XLPE Insulated Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
1- Core CU/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
1 x 1.5 7 1.6 0.7 1.4 6 50
1 x 2.5 7 2.0 0.7 1.4 7 70
1x4 7 2.6 0.7 1.4 7 80
1x6 7 3.1 0.7 1.4 8 110
1 x 10 7 4.0 0.7 1.4 9 150
1 x 16 7 5.0 0.7 1.4 10 210
1 x 25 7 6.3 0.9 1.4 11 310
1 x 35 7 7.4 0.9 1.4 13 410
1 x 50 19 8.8 1.0 1.4 14 530
1 x 70 19 10.6 1.1 1.4 16 740
1 x 95 19 12.4 1.1 1.5 18 1000
1 x 120 37 14.0 1.2 1.5 20 1240
1 x 150 37 15.5 1.4 1.6 22 1520
1 x 185 37 17.4 1.6 1.6 24 1890
1 x 240 61 20.3 1.7 1.7 28 2460
1 x 300 61 22.7 1.8 1.8 30 3060
1 x 400 61 25.4 2.0 1.9 34 3910
1 x 500 61 28.8 2.2 2.0 38 4980
1 x 630 61 30.4 2.4 2.2 40 6260
1 x 800 61 33.7 2.6 2.3 44 7950
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced Flat
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced
Trefoil [Gd] Touching in Three Trefoil [Air] Touching
Area Duct [Gd] Ducts [Gd] [Gd] [Air]
[Gd] Ducts [Gd] [Air]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps
1 x 1.5 22 21 21 22 24 21 18 25 19
1 x 2.5 29 27 29 29 31 27 25 34 26
1x4 38 34 37 37 39 35 32 44 33
1x6 47 43 45 47 49 44 42 56 43
1 x 10 62 57 59 61 65 57 58 77 59
1 x 16 80 73 77 79 83 75 76 101 79
1 x 25 102 94 98 100 106 95 100 133 103
1 x 35 122 113 119 120 128 115 127 166 131
1 x 50 144 134 139 142 150 135 153 200 157
1 x 70 176 164 172 173 184 167 195 254 201
1 x 95 211 197 204 206 220 199 241 313 248
1 x 120 240 225 234 234 251 228 282 365 291
1 x 150 268 253 261 262 281 256 325 418 335
1 x 185 302 286 297 295 318 291 375 482 387
1 x 240 351 333 347 341 371 341 455 583 470
1 x 300 392 373 393 381 417 385 517 667 535
1 x 400 443 423 448 430 476 441 605 781 625
1 x 500 496 475 515 481 541 505 697 909 721
1 x 630 547 525 574 530 606 566 777 1025 804
1 x 800 599 576 639 580 676 633 873 1167 903
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (Two & Three Cores) - Copper Conductor, XLPE Insulated Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
2-Cores CU/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
2 x 1.5 7 1.6 0.7 1.8 13 190 22 21 21
2 x 2.5 7 2.0 0.7 1.8 13 240 29 27 29
2x4 7 2.6 0.7 1.8 14 290 38 34 37
2x6 7 3.1 0.7 1.8 16 350 47 43 45
2 x 10 7 4.0 0.7 1.8 17 480 62 57 59
2 x 16 7 5.0 0.7 1.8 19 650 80 73 77
2 x 25 7 6.3 0.9 1.8 23 930 102 94 98
2 x 35 7 7.4 0.9 1.8 25 1190 122 113 119
2 x 50 19 8.8 1.0 1.8 28 1540 144 134 139
2 x 70 19 10.6 1.1 1.8 32 2100 176 164 172
2 x 95 19 12.4 1.1 2.0 37 2830 211 197 204
2 x 120 37 14.0 1.2 2.1 40 3500 240 225 234
2 x 150 37 15.5 1.4 2.2 44 4260 268 253 261
2 x 185 37 17.4 1.6 2.3 50 5340 302 286 297
2 x 240 61 20.3 1.7 2.5 56 6900 351 333 347
2 x 300 61 22.7 1.8 2.7 62 8600 392 373 393
2 x 400 61 25.4 2.0 2.9 69 10830 443 423 448
2 x 500 61 28.8 2.2 3.1 77 13710 496 475 515
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
3-Cores CU/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
3 x 1.5 7 1.6 0.7 1.8 13 210 21 17 18
3 x 2.5 7 2.0 0.7 1.8 14 260 27 23 24
3x4 7 2.6 0.7 1.8 15 330 35 29 31
3x6 7 3.1 0.7 1.8 16 410 44 37 39
3 x 10 7 4.0 0.7 1.8 18 570 58 49 54
3 x 16 7 5.0 0.7 1.8 20 790 75 63 71
3 x 25 7 6.3 0.9 1.8 24 1160 98 82 96
3 x 35 7 7.4 0.9 1.8 27 1380 115 99 115
3 x 50 19 8.8 1.0 1.8 30 1790 137 118 140
3 x 70 19 10.6 1.1 1.9 35 2510 167 146 176
3 x 95 19 12.4 1.1 2.0 39 3350 200 176 216
3 x 120 37 14.0 1.2 2.1 43 4150 227 201 251
3 x 150 37 15.5 1.4 2.3 48 5120 254 227 285
3 x 185 37 17.4 1.6 2.4 53 6360 286 257 327
3 x 240 61 20.3 1.7 2.6 60 8280 330 299 386
3 x 300 61 22.7 1.8 2.8 67 10270 370 339 441
3 x 400 61 25.4 2.0 3.1 74 13040 414 383 502
3 x 500 61 28.8 2.2 3.3 83 16610 462 431 569
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (Three and half & Four Cores) - Copper Conductor, XLPE Insulated Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
3½ -Cores CU/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Outer Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
Sheath Overall
Area* [Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne] Weight Amps Amps Amps
Thickness Diameter**
mm² No. mm mm mm mm kg/km
3x16+10 7/7 5/4 0.7 / 0.7 1.8 22 900 76 64 73
3x25+16 7/7 6.3 / 5 0.9 / 0.7 1.8 25 1320 98 83 97
3x35+16 7/7 6.6 / 5 0.9 / 0.7 1.8 25 1470 114 97 112
3x50+25 19 / 7 7.5 / 6.3 1.0 / 0.9 1.8 29 1950 135 117 137
3x70+35 19 / 7 9.1 / 7.4 1.1 / 0.9 1.9 33 2740 165 143 172
3x95+50 19 / 19 11 / 8.8 1.1 / 1.0 2.1 37 3670 198 173 211
3x120+70 37 / 19 12.2 / 10.6 1.2 / 1.1 2.2 41 4620 225 197 244
3x150+70 37 / 19 13.8 / 10.6 1.4 / 1.1 2.3 45 5580 251 224 278
3x185+95 37 / 19 15.1 / 12.4 1.6 / 1.1 2.5 50 7000 283 253 318
3x240+120 61 / 37 17.6 / 14 1.7 / 1.2 2.7 55 9040 326 294 373
3x300+150 61 / 37 19.8 / 15.5 1.8 / 1.4 2.9 61 11180 366 333 426
3x400+185 61 / 37 22.2 / 17.4 2.0 / 1.6 3.1 68 14160 412 379 490
3x500+240 61 / 61 26.3 / 20.3 2.2 / 1.7 3.4 76 18070 462 428 558
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
4-Cores CU/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Sheath Diameter** Weight
mm² No. mm mm mm mm kg/km
4 x 1.5 7 1.6 0.7 1.8 14 240 21 18 18
4 x 2.5 7 2.0 0.7 1.8 15 310 28 23 24
4x4 7 2.6 0.7 1.8 16 390 36 30 32
4x6 7 3.1 0.7 1.8 18 500 45 37 41
4 x 10 7 4.0 0.7 1.8 20 700 59 50 56
4 x 16 7 5.0 0.7 1.8 22 980 77 64 74
4 x 25 7 6.3 0.9 1.8 26 1450 99 84 99
4 x 35 7 6.6 0.9 1.8 26 1650 115 98 114
4 x 50 19 7.5 1.0 1.9 30 2160 136 117 139
4 x 70 19 9.1 1.1 2.0 34 3060 166 144 173
4 x 95 19 11.0 1.1 2.1 38 4100 199 175 213
4 x 120 37 12.2 1.2 2.3 43 5130 225 199 247
4 x 150 37 13.8 1.4 2.4 47 6320 253 225 281
4 x 185 37 15.1 1.6 2.6 52 7830 284 256 322
4 x 240 61 17.6 1.7 2.8 58 10180 328 298 378
4 x 300 61 19.8 1.8 3.0 64 12610 368 337 433
4 x 400 61 22.2 2.0 3.3 73 16120 415 384 497
4 x 500 61 26.3 2.2 3.5 80 20380 465 433 566
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (Five Cores) - Copper Conductor, XLPE Insulated Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
5-Cores CU/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
5 x 1.5 7 1.6 0.7 1.8 15 280 21 18 19
5 x 2.5 7 2.0 0.7 1.8 16 360 28 23 25
5x4 7 2.6 0.7 1.8 17 460 36 30 33
5x6 7 3.1 0.7 1.8 19 590 45 38 42
5 x 10 7 4.0 0.7 1.8 21 840 60 50 57
5 x 16 7 5.0 0.7 1.8 24 1190 78 66 76
5 x 25 7 6.3 0.9 1.8 28 1770 100 85 102
5 x 35 7 7.4 0.9 1.8 32 2180 120 104 126
5 x 50 19 8.8 1.0 2.0 37 2920 142 124 154
5 x 70 19 10.6 1.1 2.1 42 4050 174 153 194
5 x 95 19 12.4 1.1 2.3 48 5510 208 186 238
5 x 120 37 14.0 1.2 2.4 53 6850 237 212 277
5 x 150 37 15.5 1.4 2.6 58 8380 265 239 315
5 x 185 37 17.4 1.6 2.8 65 10520 299 272 362
5 x 240 61 20.3 1.7 3.0 74 13620 346 318 431
5 x 300 61 22.7 1.8 3.2 82 16990 387 359 491
5 x 400 61 25.4 2.0 3.6 91 21640 434 406 560
5 x 500 61 28.8 2.2 3.8 102 27450 486 459 639
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Aluminium Conductor, XLPE Insulated Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
1- Core AL/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
1 x 10 7 3.9 0.7 1.4 9 90
1 x 16 7 4.7 0.7 1.4 9 110
1 x 25 7 6.3 0.9 1.4 11 160
1 x 35 7 7.4 0.9 1.4 13 200
1 x 50 19 8.8 1.0 1.4 14 250
1 x 70 19 10.6 1.1 1.4 16 330
1 x 95 19 12.4 1.1 1.5 18 430
1 x 120 37 14.0 1.2 1.5 20 530
1 x 150 37 15.5 1.4 1.6 22 640
1 x 185 37 17.4 1.6 1.6 24 780
1 x 240 61 19.9 1.7 1.7 27 990
1 x 300 61 22.2 1.8 1.8 30 1210
1 x 400 61 25.2 2.0 1.9 33 1530
1 x 500 61 28.6 2.2 2.0 38 1910
1 x 630 91 32.6 2.4 2.2 42 2470
1 x 800 91 36.7 2.6 2.3 47 3090
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced Flat
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced
Trefoil [Gd] Touching in Three Trefoil [Air] Touching
Area Duct [Gd] Ducts [Gd] [Gd] [Air]
[Gd] Ducts [Gd] [Air]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps
1 x 10 48 44 45 47 50 44 44 59 45
1 x 16 61 56 58 60 64 56 57 76 58
1 x 25 79 73 76 78 82 74 78 103 80
1 x 35 95 88 92 93 99 89 98 129 101
1 x 50 112 104 108 110 117 105 118 155 122
1 x 70 137 128 133 134 143 129 151 197 156
1 x 95 164 153 158 160 171 154 187 242 193
1 x 120 186 175 182 182 195 177 220 284 227
1 x 150 209 197 202 204 218 199 253 324 261
1 x 185 237 223 231 230 247 226 293 375 303
1 x 240 274 260 270 267 288 264 352 448 363
1 x 300 310 295 307 301 326 301 409 520 423
1 x 400 354 338 353 344 373 346 479 609 496
1 x 500 406 388 410 393 430 402 570 723 589
1 x 630 460 441 468 445 492 461 663 844 686
1 x 800 517 497 531 499 559 525 767 982 794
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (Two & Three Cores) - Aluminium Conductor, XLPE Insulated Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
2-Cores AL/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
2 x 10 7 3.9 0.7 1.8 17 340 53 45 48
2 x 16 7 4.7 0.7 1.8 18 420 69 58 63
2 x 25 7 6.3 0.9 1.8 22 610 90 76 86
2 x 35 7 7.4 0.9 1.8 25 750 108 92 106
2 x 50 19 8.8 1.0 1.8 28 950 128 110 129
2 x 70 19 10.6 1.1 1.8 32 1260 157 137 164
2 x 95 19 12.4 1.1 2.0 36 1670 188 164 200
2 x 120 37 14.0 1.2 2.1 40 2040 214 188 233
2 x 150 37 15.5 1.4 2.2 44 2460 240 212 266
2 x 185 37 17.4 1.6 2.3 49 3080 272 243 306
2 x 240 61 19.9 1.7 2.5 55 3870 316 285 364
2 x 300 61 22.2 1.8 2.7 61 4770 356 325 418
2 x 400 61 25.2 2.0 2.9 68 5980 408 374 488
2 x 500 61 28.6 2.2 3.1 76 7450 466 432 568
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
3-Cores AL/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
3 x 10 7 3.9 0.7 1.8 18 380 45 37 41
3 x 16 7 4.7 0.7 1.8 19 470 58 49 54
3 x 25 7 6.3 0.9 1.8 24 690 76 64 74
3 x 35 7 7.4 0.9 1.8 26 750 89 76 88
3 x 50 19 8.8 1.0 1.8 30 940 106 91 108
3 x 70 19 10.6 1.1 1.9 35 1290 130 113 137
3 x 95 19 12.4 1.1 2.0 39 1640 155 136 168
3 x 120 37 14.0 1.2 2.1 43 1990 177 156 195
3 x 150 37 15.5 1.4 2.3 48 2460 198 177 222
3 x 185 37 17.4 1.6 2.4 53 3020 224 201 256
3 x 240 61 19.9 1.7 2.6 60 3850 260 236 304
3 x 300 61 22.2 1.8 2.8 66 4670 293 268 349
3 x 400 61 25.2 2.0 3.1 73 5870 335 310 405
3 x 500 61 28.6 2.2 3.3 83 7350 382 356 470
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (Three and half & Four Cores) - Aluminium Conductor, XLPE Insulated Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
3½ -Cores AL/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Outer Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
Sheath Overall
Area* [Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne] Weight Amps Amps Amps
Thickness Diameter**
mm² No. mm mm mm mm kg/km
3x16+10 7/7 4.7 / 3.9 0.7 / 0.7 1.8 20 530 58 49 55
3x25+16 7/7 6.3 / 4.7 0.9 / 0.7 1.8 24 760 76 64 75
3x35+16 7/7 6.5 / 4.7 0.9 / 0.7 1.8 25 740 88 75 87
3x50+25 7/7 7.5 / 6.3 1.0 / 0.9 1.8 29 950 105 91 106
3x70+35 14 / 7 9.1 / 7.4 1.1 / 0.9 1.9 33 1280 128 111 133
3x95+50 19 / 19 10.8 / 8.8 1.1 / 1.0 2.1 37 1650 153 134 163
3x120+70 19 / 19 12.2 / 10.6 1.2 / 1.1 2.2 41 2020 175 154 190
3x150+70 37 / 19 13.5 / 10.6 1.4 / 1.1 2.3 45 2450 195 174 216
3x185+95 37 / 19 15.2 / 12.4 1.6 / 1.1 2.5 50 3030 221 198 249
3x240+120 37 / 37 17.5 / 14 1.7 / 1.2 2.7 55 3870 256 231 293
3x300+150 37 / 37 19.6 / 15.5 1.8 / 1.4 2.9 61 4680 289 264 337
3x400+185 61 / 37 22.5 / 17.4 2.0 / 1.6 3.1 68 5890 331 304 394
3x500+240 61 / 61 25.6 / 19.9 2.2 / 1.7 3.4 76 7440 377 350 456
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
4-Cores AL/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Sheath Diameter** Weight
mm² No. mm mm mm mm kg/km
4 x 10 7 3.9 0.7 1.8 19 440 45 38 42
4 x 16 7 4.7 0.7 1.8 21 560 59 49 56
4 x 25 7 6.3 0.9 1.8 26 840 77 65 77
4 x 35 7 6.5 0.9 1.8 26 800 89 76 88
4 x 50 7 7.5 1.0 1.9 30 1020 105 91 108
4 x 70 14 9.1 1.1 2.0 34 1390 129 112 135
4 x 95 19 10.8 1.1 2.1 38 1780 154 136 165
4 x 120 19 12.2 1.2 2.3 43 2220 175 155 192
4 x 150 37 13.5 1.4 2.4 47 2690 196 175 219
4 x 185 37 15.2 1.6 2.6 52 3310 223 200 252
4 x 240 37 17.5 1.7 2.8 58 4240 258 234 298
4 x 300 37 19.6 1.8 3.0 64 5130 291 267 342
4 x 400 61 22.5 2.0 3.3 73 6580 334 309 400
4 x 500 61 25.6 2.2 3.5 80 8160 380 354 463
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (Five Cores) - Aluminium Conductor, XLPE Insulated Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
5-Cores AL/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
5 x 10 7 3.9 0.7 1.8 20 520 46 38 43
5 x 16 7 4.7 0.7 1.8 23 670 60 50 58
5 x 25 7 6.3 0.9 1.8 28 1010 78 66 79
5 x 35 7 7.4 0.9 1.8 31 1130 93 80 97
5 x 50 19 8.8 1.0 2.0 36 1500 110 96 118
5 x 70 19 10.6 1.1 2.1 42 2020 135 119 151
5 x 95 19 12.4 1.1 2.3 48 2670 162 144 185
5 x 120 37 14.0 1.2 2.4 53 3250 184 165 216
5 x 150 37 15.5 1.4 2.6 58 3950 206 187 246
5 x 185 37 17.4 1.6 2.8 65 4950 234 213 284
5 x 240 61 19.9 1.7 3.0 73 6230 272 251 338
5 x 300 61 22.2 1.8 3.2 81 7660 307 285 388
5 x 400 61 25.2 2.0 3.6 91 9690 352 329 453
5 x 500 61 28.6 2.2 3.8 101 12010 401 378 526
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Copper Conductor, PVC Insulated Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
1-Core CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
1 x 1.5 7 1.6 0.8 1.4 6 60
1 x 2.5 7 2.0 0.8 1.4 7 70
1x4 7 2.6 1.0 1.4 8 100
1x6 7 3.1 1.0 1.4 8 120
1 x 10 7 4.0 1.0 1.4 9 170
1 x 16 7 5.0 1.0 1.4 10 230
1 x 25 7 6.3 1.2 1.4 12 340
1 x 35 7 7.4 1.2 1.4 13 440
1 x 50 19 8.8 1.4 1.4 15 580
1 x 70 19 10.6 1.4 1.4 17 790
1 x 95 19 12.4 1.6 1.5 19 1080
1 x 120 37 14.0 1.6 1.5 21 1320
1 x 150 37 15.5 1.8 1.6 23 1610
1 x 185 37 17.4 2.0 1.7 25 2010
1 x 240 61 20.3 2.2 1.8 29 2620
1 x 300 61 22.7 2.4 1.9 32 3260
1 x 400 61 25.4 2.6 2.0 35 4140
1 x 500 61 28.8 2.8 2.1 39 5260
1 x 630 61 30.4 2.8 2.2 41 6470
1 x 800 61 33.7 2.8 2.3 44 8160
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced Flat
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced
Trefoil [Gd] Touching in Three Trefoil [Air] Touching
Area Duct [Gd] Ducts [Gd] [Gd] [Air]
[Gd] Ducts [Gd] [Air]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps
1 x 1.5 18 16 17 18 19 16 11 15 12
1 x 2.5 23 21 23 23 24 22 15 21 16
1x4 30 28 29 30 31 28 21 27 21
1x6 37 34 36 37 39 34 25 34 26
1 x 10 49 45 47 49 51 46 35 47 36
1 x 16 63 58 61 62 66 59 46 62 48
1 x 25 81 75 78 80 85 76 63 83 65
1 x 35 97 90 94 95 101 91 77 101 79
1 x 50 115 107 111 113 120 108 95 123 98
1 x 70 141 132 137 138 147 133 121 156 124
1 x 95 168 158 164 164 175 160 149 191 153
1 x 120 191 180 186 187 200 182 174 224 180
1 x 150 214 202 210 209 224 205 200 256 206
1 x 185 241 228 236 235 253 232 230 294 237
1 x 240 279 265 279 271 295 273 277 354 286
1 x 300 313 298 316 304 333 309 319 408 330
1 x 400 351 336 359 341 378 352 367 472 379
1 x 500 392 376 407 380 428 401 422 548 436
1 x 630 433 416 453 420 480 449 472 621 488
1 x 800 471 453 504 456 533 500 524 703 542
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (Two & Three Cores) - Copper Conductor, PVC Insulated Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
2-Cores CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
2 x 1.5 7 1.6 0.8 1.8 13 210 19 16 13
2 x 2.5 7 2.0 0.8 1.8 14 250 25 21 17
2x4 7 2.6 1.0 1.8 16 340 33 28 23
2x6 7 3.1 1.0 1.8 17 410 41 35 29
2 x 10 7 4.0 1.0 1.8 19 540 55 47 39
2 x 16 7 5.0 1.0 1.8 21 720 71 60 52
2 x 25 7 6.3 1.2 1.8 24 1030 91 78 69
2 x 35 7 7.4 1.2 1.8 26 1300 109 94 84
2 x 50 19 8.8 1.4 1.8 30 1700 130 113 103
2 x 70 19 10.6 1.4 1.9 33 2260 159 139 129
2 x 95 19 12.4 1.6 2.0 39 3080 191 169 160
2 x 120 37 14.0 1.6 2.1 42 3740 217 193 185
2 x 150 37 15.5 1.8 2.2 46 4540 243 217 211
2 x 185 37 17.4 2.0 2.4 51 5690 273 247 241
2 x 240 61 20.3 2.2 2.6 58 7370 316 288 286
2 x 300 61 22.7 2.4 2.7 65 9160 355 326 327
2 x 400 61 25.4 2.6 3.0 71 11510 398 368 373
2 x 500 61 28.8 2.8 3.2 80 14580 445 415 425
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
3-Cores CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
3 x 1.5 7 1.6 0.8 1.8 13 240 16 14 11
3 x 2.5 7 2.0 0.8 1.8 14 290 21 18 15
3x4 7 2.6 1.0 1.8 16 390 28 24 19
3x6 7 3.1 1.0 1.8 18 480 35 29 25
3 x 10 7 4.0 1.0 1.8 20 650 46 39 34
3 x 16 7 5.0 1.0 1.8 22 880 60 50 45
3 x 25 7 6.3 1.2 1.8 25 1280 77 65 59
3 x 35 7 7.4 1.2 1.8 28 1500 91 78 72
3 x 50 19 8.8 1.4 1.8 32 1950 108 94 87
3 x 70 19 10.6 1.4 2.0 36 2700 132 116 109
3 x 95 19 12.4 1.6 2.1 41 3630 158 139 134
3 x 120 37 14.0 1.6 2.2 45 4440 180 160 156
3 x 150 37 15.5 1.8 2.3 50 5440 201 180 178
3 x 185 37 17.4 2.0 2.5 55 6760 226 205 203
3 x 240 61 20.3 2.2 2.7 63 8800 261 238 240
3 x 300 61 22.7 2.4 2.9 69 10920 291 268 273
3 x 400 61 25.4 2.6 3.1 76 13770 327 304 311
3 x 500 61 28.8 2.8 3.4 86 17520 364 341 353
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (Three and half & Four Cores) - Copper Conductor, PVC Insulated Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
3½ -Cores CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Outer Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
Sheath Overall
Area* [Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne] Weight Amps Amps Amps
Thickness Diameter**
mm² No. mm mm mm mm kg/km
3x16+10 7/7 5/4 1.0 / 1.0 1.8 23 1010 60 51 46
3x25+16 7/7 6.3 / 5 1.2 / 1.0 1.8 27 1460 78 67 61
3x35+16 7/7 6.6 / 5 1.2 / 1.0 1.8 27 1600 90 78 70
3x50+25 19 / 7 7.5 / 6.3 1.4 / 1.2 1.9 31 2150 107 93 86
3x70+35 19 / 7 9.1 / 7.4 1.4 / 1.2 2.0 35 2950 131 115 107
3x95+50 19 / 19 11 / 8.8 1.6 / 1.4 2.2 39 3980 156 138 131
3x120+70 37 / 19 12.2 / 10.6 1.6 / 1.4 2.3 43 4980 177 157 152
3x150+70 37 / 19 13.8 / 10.6 1.8 / 1.4 2.4 47 5950 198 177 173
3x185+95 37 / 19 15.1 / 12.4 2.0 / 1.6 2.6 52 7440 223 202 198
3x240+120 61 / 37 17.6 / 14 2.2 / 1.6 2.8 58 9600 257 234 232
3x300+150 61 / 37 19.8 / 15.5 2.4 / 1.8 3.0 64 11880 288 265 265
3x400+185 61 / 37 22.2 / 17.4 2.6 / 2.0 3.2 72 15060 325 300 304
3x500+240 61 / 61 26.3 / 20.3 2.8 / 2.2 3.5 79 19050 363 337 346
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
4-Cores CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Sheath Diameter** Weight
mm² No. mm mm mm mm kg/km
4 x 1.5 7 1.6 0.8 1.8 14 270 17 14 11
4 x 2.5 7 2.0 0.8 1.8 15 340 22 18 15
4x4 7 2.6 1.0 1.8 18 470 28 24 20
4x6 7 3.1 1.0 1.8 19 580 35 30 25
4 x 10 7 4.0 1.0 1.8 21 800 47 40 35
4 x 16 7 5.0 1.0 1.8 24 1090 61 52 46
4 x 25 7 6.3 1.2 1.8 28 1600 78 67 62
4 x 35 7 6.6 1.2 1.8 28 1790 91 78 71
4 x 50 19 7.5 1.4 1.9 32 2390 107 94 86
4 x 70 19 9.1 1.4 2.1 36 3280 131 115 108
4 x 95 19 11.0 1.6 2.2 41 4430 157 139 133
4 x 120 37 12.2 1.6 2.4 45 5470 178 159 154
4 x 150 37 13.8 1.8 2.5 49 6720 199 179 175
4 x 185 37 15.1 2.0 2.7 55 8360 224 204 201
4 x 240 61 17.6 2.2 2.9 61 10790 259 237 236
4 x 300 61 19.8 2.4 3.1 67 13370 290 267 269
4 x 400 61 22.2 2.6 3.4 76 17030 327 304 309
4 x 500 61 26.3 2.8 3.6 83 21440 365 342 351
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (Five Cores) - Copper Conductor, PVC Insulated Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
5-Cores CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
5 x 1.5 7 1.6 0.8 1.8 15 310 17 14 12
5 x 2.5 7 2.0 0.8 1.8 16 400 22 19 15
5x4 7 2.6 1.0 1.8 19 550 29 24 21
5x6 7 3.1 1.0 1.8 20 690 36 30 26
5 x 10 7 4.0 1.0 1.8 23 960 47 40 36
5 x 16 7 5.0 1.0 1.8 26 1330 61 53 48
5 x 25 7 6.3 1.2 1.8 30 1960 79 68 63
5 x 35 7 7.4 1.2 1.9 33 2390 95 82 78
5 x 50 19 8.8 1.4 2.1 39 3210 112 99 95
5 x 70 19 10.6 1.4 2.2 44 4360 138 122 120
5 x 95 19 12.4 1.6 2.4 51 5980 165 148 148
5 x 120 37 14.0 1.6 2.5 55 7320 187 169 171
5 x 150 37 15.5 1.8 2.7 61 8990 209 191 195
5 x 185 37 17.4 2.0 2.9 68 11180 236 217 224
5 x 240 61 20.3 2.2 3.1 77 14480 273 253 266
5 x 300 61 22.7 2.4 3.3 85 18080 305 284 302
5 x 400 61 25.4 2.6 3.7 95 22910 343 323 345
5 x 500 61 28.8 2.8 4.0 106 29110 382 362 391
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Aluminium Conductor, PVC Insulated Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
1- Core AL/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
1 x 10 7 3.9 1.0 1.4 9 110
1 x 16 7 4.7 1.0 1.4 10 130
1 x 25 7 6.3 1.2 1.4 12 190
1 x 35 7 7.4 1.2 1.4 13 230
1 x 50 19 8.8 1.4 1.4 15 300
1 x 70 19 10.6 1.4 1.4 17 380
1 x 95 19 12.4 1.6 1.5 19 510
1 x 120 37 14.0 1.6 1.5 21 600
1 x 150 37 15.5 1.8 1.6 23 730
1 x 185 37 17.4 2.0 1.7 25 910
1 x 240 61 19.9 2.2 1.8 28 1150
1 x 300 61 22.2 2.4 1.9 31 1410
1 x 400 61 25.2 2.6 2.0 35 1770
1 x 500 61 28.6 2.8 2.1 39 2180
1 x 630 91 32.6 2.8 2.2 43 2740
1 x 800 91 36.7 2.8 2.3 47 3360
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced Flat
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced
Trefoil [Gd] Touching in Three Trefoil [Air] Touching
Area Duct [Gd] Ducts [Gd] [Gd] [Air]
[Gd] Ducts [Gd] [Air]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps
1 x 10 38 35 36 37 39 35 27 36 28
1 x 16 49 45 47 48 51 46 36 47 37
1 x 25 63 59 60 62 66 59 49 64 50
1 x 35 75 70 73 74 78 71 60 78 61
1 x 50 89 83 86 88 93 84 74 96 76
1 x 70 109 102 106 107 114 103 94 122 97
1 x 95 131 122 128 128 136 124 115 149 119
1 x 120 149 140 145 145 155 142 136 174 140
1 x 150 167 157 163 163 174 160 156 199 161
1 x 185 188 178 184 184 197 181 180 229 186
1 x 240 219 208 214 213 229 211 215 273 222
1 x 300 247 235 244 240 259 240 250 315 258
1 x 400 283 270 283 274 298 278 295 372 305
1 x 500 322 309 325 312 342 319 346 437 358
1 x 630 365 351 372 354 391 366 404 513 418
1 x 800 409 393 420 395 443 416 463 594 479
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (Two & Three Cores) - Aluminium Conductor, PVC Insulated Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
2-Cores AL/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
2 x 10 7 3.9 1.0 1.8 18 400 42 35 30
2 x 16 7 4.7 1.0 1.8 19 490 54 46 39
2 x 25 7 6.3 1.2 1.8 23 710 71 60 53
2 x 35 7 7.4 1.2 1.8 26 860 85 73 65
2 x 50 19 8.8 1.4 1.8 29 1100 100 87 79
2 x 70 19 10.6 1.4 1.9 33 1430 124 108 100
2 x 95 19 12.4 1.6 2.0 38 1910 148 131 123
2 x 120 37 14.0 1.6 2.1 41 2270 168 149 143
2 x 150 37 15.5 1.8 2.2 45 2730 189 168 163
2 x 185 37 17.4 2.0 2.4 51 3420 214 193 189
2 x 240 61 19.9 2.2 2.6 57 4330 248 226 223
2 x 300 61 22.2 2.4 2.7 63 5320 280 256 256
2 x 400 61 25.2 2.6 3.0 70 6650 320 296 299
2 x 500 61 28.6 2.8 3.2 79 8310 365 339 348
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
3-Cores AL/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
3 x 10 7 3.9 1.0 1.8 19 450 35 30 26
3 x 16 7 4.7 1.0 1.8 21 560 46 39 34
3 x 25 7 6.3 1.2 1.8 25 810 60 51 46
3 x 35 7 7.4 1.2 1.8 28 870 71 61 56
3 x 50 19 8.8 1.4 1.8 32 1100 84 73 68
3 x 70 19 10.6 1.4 2.0 36 1470 103 90 85
3 x 95 19 12.4 1.6 2.1 41 1920 123 108 105
3 x 120 37 14.0 1.6 2.2 45 2280 140 125 122
3 x 150 37 15.5 1.8 2.3 50 2780 157 140 139
3 x 185 37 17.4 2.0 2.5 55 3420 177 161 160
3 x 240 61 19.9 2.2 2.7 62 4360 206 188 189
3 x 300 61 22.2 2.4 2.9 68 5310 232 213 216
3 x 400 61 25.2 2.6 3.1 76 6600 265 246 252
3 x 500 61 28.6 2.8 3.4 85 8250 301 281 292
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (Three and half & Four Cores) - Aluminium Conductor, PVC Insulated Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
3½ -Cores AL/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Outer Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
Sheath Overall
Area* [Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne] Weight Amps Amps Amps
Thickness Diameter**
mm² No. mm mm mm mm kg/km
3x16+10 7/7 4.7 / 3.9 1.0 / 1.0 1.8 22 640 46 39 35
3x25+16 7/7 6.3 / 4.7 1.2 / 1.0 1.8 26 900 60 52 47
3x35+16 7/7 6.5 / 4.7 1.2 / 1.0 1.8 27 870 70 60 55
3x50+25 7/7 7.5 / 6.3 1.4 / 1.2 1.9 31 1150 83 72 66
3x70+35 14 / 7 9.1 / 7.4 1.4 / 1.2 2.0 35 1490 102 89 83
3x95+50 19 / 19 10.8 / 8.8 1.6 / 1.4 2.2 39 1960 121 107 102
3x120+70 19 / 19 12.2 / 10.6 1.6 / 1.4 2.3 43 2380 138 123 118
3x150+70 37 / 19 13.5 / 10.6 1.8 / 1.4 2.4 47 2820 155 138 135
3x185+95 37 / 19 15.2 / 12.4 2.0 / 1.6 2.6 52 3480 175 158 155
3x240+120 37 / 37 17.5 / 14 2.2 / 1.6 2.8 58 4430 203 185 183
3x300+150 37 / 37 19.6 / 15.5 2.4 / 1.8 3.0 64 5380 229 210 210
3x400+185 61 / 37 22.5 / 17.4 2.6 / 2.0 3.2 72 6790 262 242 245
3x500+240 61 / 61 25.6 / 19.9 2.8 / 2.2 3.5 79 8410 298 277 284
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
4-Cores AL/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Sheath Diameter** Weight
mm² No. mm mm mm mm kg/km
4 x 10 7 3.9 1.0 1.8 20 540 36 30 26
4 x 16 7 4.7 1.0 1.8 22 670 46 39 35
4 x 25 7 6.3 1.2 1.8 27 990 61 52 48
4 x 35 7 6.5 1.2 1.8 28 940 70 61 55
4 x 50 7 7.5 1.4 1.9 32 1260 83 73 67
4 x 70 14 9.1 1.4 2.1 36 1610 102 90 84
4 x 95 19 10.8 1.6 2.2 41 2110 122 108 103
4 x 120 19 12.2 1.6 2.4 45 2550 139 124 120
4 x 150 37 13.5 1.8 2.5 49 3090 155 140 136
4 x 185 37 15.2 2.0 2.7 55 3830 176 160 157
4 x 240 37 17.5 2.2 2.9 61 4850 204 186 186
4 x 300 37 19.6 2.4 3.1 67 5890 230 212 213
4 x 400 61 22.5 2.6 3.4 76 7490 263 245 249
4 x 500 61 25.6 2.8 3.6 83 9210 300 280 288
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (Five Cores) - Aluminium Conductor, PVC Insulated Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
5-Cores AL/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
5 x 10 7 3.9 1.0 1.8 22 640 36 31 27
5 x 16 7 4.7 1.0 1.8 24 810 47 40 36
5 x 25 7 6.3 1.2 1.8 30 1200 61 53 49
5 x 35 7 7.4 1.2 1.9 33 1340 73 64 60
5 x 50 19 8.8 1.4 2.1 39 1790 87 77 74
5 x 70 19 10.6 1.4 2.2 44 2330 107 95 93
5 x 95 19 12.4 1.6 2.4 51 3130 128 115 115
5 x 120 37 14 1.6 2.5 55 3720 146 132 133
5 x 150 37 15.5 1.8 2.7 61 4560 163 149 152
5 x 185 37 17.4 2.0 2.9 68 5610 185 170 176
5 x 240 61 19.9 2.2 3.1 76 7080 215 199 209
5 x 300 61 22.2 2.4 3.3 84 8720 243 226 239
5 x 400 61 25.2 2.6 3.7 94 10940 277 261 279
5 x 500 61 28.6 2.8 4.0 105 13650 316 300 323
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Copper Conductor, XLPE Insulated CU Shielded Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC, LSF or PE)
1-Core CU/XLPE/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
1 x 1.5 7 1.6 0.7 1.4 9 100
1 x 2.5 7 2.0 0.7 1.4 9 120
1x4 7 2.6 0.7 1.4 10 140
1x6 7 3.1 0.7 1.4 10 170
1 x 10 7 4.0 0.7 1.4 11 220
1 x 16 7 5.0 0.7 1.4 12 290
1 x 25 7 6.3 0.9 1.4 14 400
1 x 35 7 7.4 0.9 1.4 15 510
1 x 50 19 8.8 1.0 1.4 16 640
1 x 70 19 10.6 1.1 1.5 19 870
1 x 95 19 12.4 1.1 1.5 20 1140
1 x 120 37 14.0 1.2 1.6 22 1410
1 x 150 37 15.5 1.4 1.6 24 1690
1 x 185 37 17.4 1.6 1.7 27 2090
1 x 240 61 20.3 1.7 1.8 30 2680
1 x 300 61 22.7 1.8 1.9 33 3310
1 x 400 61 25.4 2.0 2.0 37 4220
1 x 500 61 28.8 2.2 2.1 41 5330
1 x 630 61 30.4 2.4 2.2 43 6610
1 x 800 61 33.7 2.6 2.3 47 8380
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced Flat
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced
Trefoil [Gd] Touching in Three Trefoil [Air] Touching
Area Duct [Gd] Ducts [Gd] [Gd] [Air]
[Gd] Ducts [Gd] [Air]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps
1 x 1.5 23 21 22 24 24 21 21 26 21
1 x 2.5 30 27 28 30 31 28 27 34 28
1x4 38 35 37 39 40 36 36 46 37
1x6 47 44 46 48 49 44 44 57 46
1 x 10 62 58 60 64 65 58 60 78 62
1 x 16 80 74 77 82 83 75 80 102 82
1 x 25 103 96 100 105 107 97 107 137 110
1 x 35 123 115 118 126 128 115 131 167 134
1 x 50 145 135 141 148 151 137 157 201 162
1 x 70 178 167 174 182 185 169 202 256 208
1 x 95 211 199 206 216 220 201 245 311 253
1 x 120 240 226 233 245 250 228 286 362 295
1 x 150 269 254 263 275 281 257 328 413 338
1 x 185 304 289 300 311 318 293 383 480 395
1 x 240 351 334 349 359 369 341 456 572 470
1 x 300 395 377 396 403 416 386 526 659 542
1 x 400 445 426 450 455 472 439 610 763 628
1 x 500 499 479 512 510 534 499 702 884 724
1 x 630 552 530 577 563 597 560 784 997 808
1 x 800 605 583 642 617 663 623 878 1124 904
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (2 & 3 Cores) - Copper Conductor, XLPE Insulated CU Shielded Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC, LSF or PE)
2-Cores CU/XLPE/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
2 x 1.5 7 1.6 0.7 1.8 13 220 25 21 21
2 x 2.5 7 2.0 0.7 1.8 14 260 32 27 28
2x4 7 2.6 0.7 1.8 15 320 42 35 36
2x6 7 3.1 0.7 1.8 16 390 52 44 46
2 x 10 7 4.0 0.7 1.8 18 520 70 58 63
2 x 16 7 5.0 0.7 1.8 20 690 90 76 84
2 x 25 7 6.3 0.9 1.8 23 990 116 99 111
2 x 35 7 7.4 0.9 1.8 25 1250 139 118 136
2 x 50 19 8.8 1.0 1.8 28 1610 164 141 165
2 x 70 19 10.6 1.1 1.9 33 2190 202 176 210
2 x 95 19 12.4 1.1 2.0 37 2920 241 211 257
2 x 120 37 14.0 1.2 2.1 41 3610 274 241 298
2 x 150 37 15.5 1.4 2.2 45 4380 308 274 340
2 x 185 37 17.4 1.6 2.3 50 5460 346 310 389
2 x 240 61 20.3 1.7 2.5 56 7050 401 362 461
2 x 300 61 22.7 1.8 2.7 62 8760 449 410 525
2 x 400 61 25.4 2.0 2.9 69 11010 506 465 603
2 x 500 61 28.8 2.2 3.1 77 13910 566 525 687
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC, LSF or PE)
3-Cores CU/XLPE/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
3 x 1.5 7 1.6 0.7 1.8 13 240 21 18 18
3 x 2.5 7 2.0 0.7 1.8 14 300 28 23 24
3x4 7 2.6 0.7 1.8 15 370 36 29 31
3x6 7 3.1 0.7 1.8 17 450 44 37 40
3 x 10 7 4.0 0.7 1.8 19 620 59 50 55
3 x 16 7 5.0 0.7 1.8 21 840 76 64 72
3 x 25 7 6.3 0.9 1.8 24 1220 98 83 96
3 x 35 7 7.4 0.9 1.8 27 1450 115 99 115
3 x 50 19 8.8 1.0 1.8 30 1860 137 118 140
3 x 70 19 10.6 1.1 1.9 35 2590 167 146 176
3 x 95 19 12.4 1.1 2.0 39 3450 200 176 216
3 x 120 37 14.0 1.2 2.2 44 4280 227 201 251
3 x 150 37 15.5 1.4 2.3 48 5250 254 227 285
3 x 185 37 17.4 1.6 2.4 53 6490 286 257 327
3 x 240 61 20.3 1.7 2.6 61 8440 330 301 387
3 x 300 61 22.7 1.8 2.8 67 10440 369 339 440
3 x 400 61 25.4 2.0 3.1 74 13240 414 382 501
3 x 500 61 28.8 2.2 3.3 83 16830 461 430 568
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (3½ & 4 Cores) - Copper Conductor, XLPE Insulated CU Shielded Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC, LSF or PE)
3½ Cores CU/XLPE/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Outer Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
Sheath Overall
Area* [Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne] Weight Amps Amps Amps
Thickness Diameter**
mm² No. mm mm mm mm kg/km
3x16+10 7/7 5/4 0.7 / 0.7 1.8 22 960 77 64 74
3x25+16 7/7 6.3 / 5 0.9 / 0.7 1.8 25 1380 98 83 98
3x35+16 7/7 6.6 / 5 0.9 / 0.7 1.8 26 1540 114 98 113
3x50+25 19 / 7 7.5 / 6.3 1.0 / 0.9 1.8 29 2020 135 117 137
3x70+35 19 / 7 9.1 / 7.4 1.1 / 0.9 2.0 33 2840 165 143 171
3x95+50 19 / 19 11 / 8.8 1.1 / 1.0 2.1 37 3760 198 173 211
3x120+70 37 / 19 12.2 / 10.6 1.2 / 1.1 2.2 41 4720 224 197 244
3x150+70 37 / 19 13.8 / 10.6 1.4 / 1.1 2.3 45 5690 251 224 278
3x185+95 37 / 19 15.1 / 12.4 1.6 / 1.1 2.5 50 7120 283 253 318
3x240+120 61 / 37 17.6 / 14 1.7 / 1.2 2.7 56 9190 326 295 374
3x300+150 61 / 37 19.8 / 15.5 1.8 / 1.4 2.9 61 11340 365 333 426
3x400+185 61 / 37 22.2 / 17.4 2.0 / 1.6 3.2 69 14370 412 378 490
3x500+240 61 / 61 26.3 / 20.3 2.2 / 1.7 3.4 76 18270 461 428 557
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC, LSF or PE)
4-Cores CU/XLPE/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Sheath Diameter** Weight
mm² No. mm mm mm mm kg/km
4 x 1.5 7 1.6 0.7 1.8 14 270 21 18 18
4 x 2.5 7 2 0.7 1.8 15 340 28 23 24
4x4 7 2.6 0.7 1.8 16 430 36 30 32
4x6 7 3.1 0.7 1.8 18 540 45 37 41
4 x 10 7 4 0.7 1.8 20 740 59 50 56
4 x 16 7 5 0.7 1.8 22 1030 77 64 74
4 x 25 7 6.3 0.9 1.8 26 1510 99 84 99
4 x 35 7 6.6 0.9 1.8 27 1720 115 98 115
4 x 50 19 7.5 1.0 1.9 30 2240 136 117 138
4 x 70 19 9.1 1.1 2.0 35 3150 166 145 174
4 x 95 19 11 1.1 2.2 39 4210 199 175 214
4 x 120 37 12.2 1.2 2.3 43 5240 225 199 246
4 x 150 37 13.8 1.4 2.5 48 6460 252 226 282
4 x 185 37 15.1 1.6 2.6 52 7960 284 256 321
4 x 240 61 17.6 1.7 2.8 59 10330 328 298 379
4 x 300 61 19.8 1.8 3.0 64 12780 367 336 431
4 x 400 61 22.2 2.0 3.3 73 16310 414 383 495
4 x 500 61 26.3 2.2 3.6 81 20630 464 432 565
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (5 Cores) - Copper Conductor, XLPE Insulated CU Shielded Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC, LSF or PE)
5-Cores CU/XLPE/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
5 x 1.5 7 1.6 0.7 1.8 15 310 21 18 19
5 x 2.5 7 2 0.7 1.8 16 390 28 23 25
5x4 7 2.6 0.7 1.8 18 500 36 30 33
5x6 7 3.1 0.7 1.8 19 630 45 38 42
5 x 10 7 4 0.7 1.8 22 890 60 50 58
5 x 16 7 5 0.7 1.8 24 1250 77 65 76
5 x 25 7 6.3 0.9 1.8 29 1840 100 86 102
5 x 35 7 7.4 0.9 1.9 32 2270 120 104 125
5 x 50 19 8.8 1.0 2.0 37 3010 142 124 153
5 x 70 19 10.6 1.1 2.1 42 4160 173 153 193
5 x 95 19 12.4 1.1 2.3 48 5630 207 185 237
5 x 120 37 14 1.2 2.4 53 6990 236 211 275
5 x 150 37 15.5 1.4 2.6 59 8530 264 239 315
5 x 185 37 17.4 1.6 2.8 66 10690 298 272 361
5 x 240 61 20.3 1.7 3.0 74 13810 344 317 427
5 x 300 61 22.7 1.8 3.3 82 17250 385 357 486
5 x 400 61 25.4 2.0 3.6 91 21880 432 404 555
5 x 500 61 28.8 2.2 3.9 102 27770 483 457 632
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Aluminium Conductor, XLPE Insulated CU Shielded Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC, LSF or PE)
1- Core AL/XLPE/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
1 x 10 7 3.9 0.7 1.4 11 160
1 x 16 7 4.7 0.7 1.4 12 190
1 x 25 7 6.3 0.9 1.4 14 250
1 x 35 7 7.4 0.9 1.4 15 300
1 x 50 19 8.8 1.0 1.4 16 360
1 x 70 19 10.6 1.1 1.5 19 470
1 x 95 19 12.4 1.1 1.5 20 570
1 x 120 37 14 1.2 1.6 22 690
1 x 150 37 15.5 1.4 1.6 24 810
1 x 185 37 17.4 1.6 1.7 27 980
1 x 240 61 19.9 1.7 1.8 30 1220
1 x 300 61 22.2 1.8 1.9 32 1460
1 x 400 61 25.2 2.0 2.0 36 1840
1 x 500 61 28.6 2.2 2.1 40 2250
1 x 630 91 32.6 2.4 2.2 45 2840
1 x 800 91 36.7 2.6 2.3 50 3550
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced Flat
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced
Trefoil [Gd] Touching in Three Trefoil [Air] Touching
Area Duct [Gd] Ducts [Gd] [Gd] [Air]
[Gd] Ducts [Gd] [Air]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps
1 x 10 48 44 46 49 50 45 46 60 48
1 x 16 62 57 59 63 64 58 61 79 63
1 x 25 80 75 77 82 83 75 83 106 86
1 x 35 95 89 92 97 99 89 101 129 104
1 x 50 112 105 109 115 117 106 122 156 125
1 x 70 138 130 135 141 144 131 157 199 162
1 x 95 164 154 160 168 171 156 190 242 196
1 x 120 187 176 181 191 195 177 223 281 229
1 x 150 209 198 204 214 218 200 255 321 263
1 x 185 238 226 233 243 248 228 299 374 309
1 x 240 276 263 272 282 288 266 358 446 369
1 x 300 310 296 309 317 324 301 410 511 423
1 x 400 355 340 355 363 372 346 483 598 498
1 x 500 405 389 407 414 425 397 567 701 584
1 x 630 462 444 470 471 487 458 665 824 686
1 x 800 518 500 532 529 551 519 766 951 790
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (2 & 3 Cores) - Aluminium Conductor, XLPE Insulated CU Shielded Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC, LSF or PE)
2-Cores AL/XLPE/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
2 x 10 7 3.9 0.7 1.8 17 380 53 45 48
2 x 16 7 4.7 0.7 1.8 19 460 69 58 63
2 x 25 7 6.3 0.9 1.8 23 670 90 77 86
2 x 35 7 7.4 0.9 1.8 25 810 107 91 105
2 x 50 19 8.8 1.0 1.8 28 1020 127 109 128
2 x 70 19 10.6 1.1 1.9 32 1360 156 136 162
2 x 95 19 12.4 1.1 2.0 36 1760 187 163 198
2 x 120 37 14 1.2 2.1 40 2140 213 188 231
2 x 150 37 15.5 1.4 2.2 44 2570 239 211 263
2 x 185 37 17.4 1.6 2.3 49 3200 270 242 303
2 x 240 61 19.9 1.7 2.5 55 4020 314 284 360
2 x 300 61 22.2 1.8 2.7 61 4930 354 323 412
2 x 400 61 25.2 2.0 2.9 68 6160 405 372 481
2 x 500 61 28.6 2.2 3.1 76 7650 463 430 561
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC, LSF or PE)
3-Cores AL/XLPE/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
3 x 10 7 3.9 0.7 1.8 18 420 45 38 41
3 x 16 7 4.7 0.7 1.8 20 520 58 49 55
3 x 25 7 6.3 0.9 1.8 24 750 76 64 75
3 x 35 7 7.4 0.9 1.8 27 810 90 77 89
3 x 50 19 8.8 1.0 1.8 30 1010 106 91 109
3 x 70 19 10.6 1.1 1.9 35 1370 130 113 137
3 x 95 19 12.4 1.1 2.0 39 1740 155 136 168
3 x 120 37 14 1.2 2.2 44 2120 177 156 196
3 x 150 37 15.5 1.4 2.3 48 2590 198 177 222
3 x 185 37 17.4 1.6 2.4 53 3150 224 201 256
3 x 240 61 19.9 1.7 2.6 60 4000 260 235 303
3 x 300 61 22.2 1.8 2.8 66 4840 293 268 348
3 x 400 61 25.2 2.0 3.1 74 6070 335 310 405
3 x 500 61 28.6 2.2 3.3 83 7570 381 355 469
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (3½ & 4 Cores) - Aluminium Conductor, XLPE Insulated CU Shielded Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC, LSF or PE)
3½ -Cores AL/XLPE/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Outer Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
Sheath Overall
Area* [Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne] Weight Amps Amps Amps
Thickness Diameter**
mm² No. mm mm mm mm kg/km
3x16+10 7/7 4.7 / 3.9 0.7 / 0.7 1.8 21 580 59 49 56
3x25+16 7/7 6.3 / 4.7 0.9 / 0.7 1.8 25 820 76 64 76
3x35+16 7/7 6.5 / 4.7 0.9 / 0.7 1.8 26 810 89 76 88
3x50+25 7/7 7.5 / 6.3 1.0 / 0.9 1.8 29 1020 105 91 106
3x70+35 14 / 7 9.1 / 7.4 1.1 / 0.9 2.0 33 1380 128 111 133
3x95+50 19 / 19 10.8 / 8.8 1.1 / 1.0 2.1 37 1740 153 134 163
3x120+70 19 / 19 12.2 / 10.6 1.2 / 1.1 2.2 41 2120 175 154 190
3x150+70 37 / 19 13.5 / 10.6 1.4 / 1.1 2.3 45 2560 195 174 216
3x185+95 37 / 19 15.2 / 12.4 1.6 / 1.1 2.5 50 3160 221 198 249
3x240+120 37 / 37 17.5 / 14 1.7 / 1.2 2.7 56 4010 256 232 294
3x300+150 37 / 37 19.6 / 15.5 1.8 / 1.4 2.9 61 4840 289 264 337
3x400+185 61 / 37 22.5 / 17.4 2.0 / 1.6 3.2 69 6100 331 304 394
3x500+240 61 / 61 25.6 / 19.9 2.2 / 1.7 3.4 76 7630 377 350 455
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC, LSF or PE)
4-Cores AL/XLPE/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Sheath Diameter** Weight
mm² No. mm mm mm mm kg/km
4 x 10 7 3.9 0.7 1.8 19 490 45 38 42
4 x 16 7 4.7 0.7 1.8 21 610 59 49 56
4 x 25 7 6.3 0.9 1.8 26 900 77 65 77
4 x 35 7 6.5 0.9 1.8 27 870 89 76 89
4 x 50 7 7.5 1.0 1.9 30 1100 105 91 107
4 x 70 14 9.1 1.1 2.0 35 1470 129 113 135
4 x 95 19 10.8 1.1 2.2 39 1900 154 136 166
4 x 120 19 12.2 1.2 2.3 43 2320 175 155 192
4 x 150 37 13.5 1.4 2.5 48 2830 196 176 219
4 x 185 37 15.2 1.6 2.6 52 3440 222 200 252
4 x 240 37 17.5 1.7 2.8 59 4390 258 234 298
4 x 300 37 19.6 1.8 3.0 64 5300 291 266 341
4 x 400 61 22.5 2.0 3.3 73 6770 333 308 398
4 x 500 61 25.6 2.2 3.6 81 8410 379 353 462
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (Five Cores) - Aluminium Conductor, XLPE Insulated CU Shielded Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC, LSF or PE)
5-Cores AL/XLPE/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
5 x 10 7 3.9 0.7 1.8 21 570 46 39 44
5 x 16 7 4.7 0.7 1.8 23 730 59 50 58
5 x 25 7 6.3 0.9 1.8 28 1080 77 66 79
5 x 35 7 7.4 0.9 1.9 32 1220 93 80 97
5 x 50 19 8.8 1.0 2.0 37 1590 110 96 119
5 x 70 19 10.6 1.1 2.1 42 2130 135 119 150
5 x 95 19 12.4 1.1 2.3 48 2790 161 144 184
5 x 120 37 14 1.2 2.4 53 3390 184 165 214
5 x 150 37 15.5 1.4 2.6 59 4100 206 186 245
5 x 185 37 17.4 1.6 2.8 66 5120 234 213 283
5 x 240 61 19.9 1.7 3.0 73 6420 271 250 335
5 x 300 61 22.2 1.8 3.3 81 7910 306 284 384
5 x 400 61 25.2 2.0 3.6 91 9920 350 328 449
5 x 500 61 28.6 2.2 3.9 102 12330 399 378 522
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Copper Conductor, PVC Insulated CU Shielded Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC or PE)
1-Core CU/PVC/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
1 x 1.5 7 1.6 0.8 1.4 9 110
1 x 2.5 7 2.0 0.8 1.4 9 130
1x4 7 2.6 1.0 1.4 10 160
1x6 7 3.1 1.0 1.4 11 190
1 x 10 7 4.0 1.0 1.4 12 240
1 x 16 7 5.0 1.0 1.4 13 310
1 x 25 7 6.3 1.2 1.4 14 430
1 x 35 7 7.4 1.2 1.4 15 550
1 x 50 19 8.8 1.4 1.4 17 700
1 x 70 19 10.6 1.4 1.5 19 930
1 x 95 19 12.4 1.6 1.5 21 1220
1 x 120 37 14.0 1.6 1.6 23 1490
1 x 150 37 15.5 1.8 1.7 25 1800
1 x 185 37 17.4 2.0 1.7 28 2210
1 x 240 61 20.3 2.2 1.8 31 2840
1 x 300 61 22.7 2.4 1.9 34 3510
1 x 400 61 25.4 2.6 2.0 38 4450
1 x 500 61 28.8 2.8 2.1 42 5600
1 x 630 61 30.4 2.8 2.2 44 6830
1 x 800 61 33.7 2.8 2.4 48 8610
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced Flat
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced
Trefoil [Gd] Touching in Three Trefoil [Air] Touching
Area Duct [Gd] Ducts [Gd] [Gd] [Air]
[Gd] Ducts [Gd] [Air]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps
1 x 1.5 18 17 17 19 19 17 13 16 13
1 x 2.5 23 22 22 24 24 22 16 21 17
1x4 30 28 29 31 31 28 22 28 23
1x6 38 35 36 39 39 35 28 36 29
1 x 10 50 46 48 51 52 47 38 49 39
1 x 16 64 60 62 65 67 60 50 64 51
1 x 25 82 76 79 83 85 77 65 84 67
1 x 35 97 91 94 100 101 92 80 102 82
1 x 50 115 108 112 118 120 109 98 124 101
1 x 70 141 133 138 144 147 134 123 157 127
1 x 95 169 159 164 172 175 160 152 192 156
1 x 120 191 181 188 195 199 183 177 223 182
1 x 150 214 203 209 219 223 205 202 254 208
1 x 185 242 230 238 247 253 233 236 295 243
1 x 240 279 266 277 285 293 271 280 350 288
1 x 300 313 300 314 320 330 306 322 402 331
1 x 400 353 339 361 360 373 350 372 464 383
1 x 500 395 380 409 403 422 396 427 537 440
1 x 630 436 420 455 445 471 442 478 606 492
1 x 800 477 460 511 487 523 493 534 684 550
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (2 & 3 Cores) - Copper Conductor, PVC Insulated CU Shielded Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC or PE)
2-Cores CU/PVC/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
2 x 1.5 7 1.6 0.8 1.8 13 240 19 16 13
2 x 2.5 7 2.0 0.8 1.8 14 290 25 21 17
2x4 7 2.6 1.0 1.8 16 380 32 28 22
2x6 7 3.1 1.0 1.8 17 450 40 34 28
2 x 10 7 4.0 1.0 1.8 19 580 54 46 39
2 x 16 7 5.0 1.0 1.8 21 770 70 60 51
2 x 25 7 6.3 1.2 1.8 24 1080 90 77 68
2 x 35 7 7.4 1.2 1.8 27 1370 108 94 84
2 x 50 19 8.8 1.4 1.8 30 1770 128 112 101
2 x 70 19 10.6 1.4 1.9 34 2350 157 138 128
2 x 95 19 12.4 1.6 2.0 39 3180 188 167 156
2 x 120 37 14.0 1.6 2.1 42 3850 214 191 181
2 x 150 37 15.5 1.8 2.3 46 4680 239 214 206
2 x 185 37 17.4 2.0 2.4 52 5820 270 244 237
2 x 240 61 20.3 2.2 2.6 59 7520 313 285 281
2 x 300 61 22.7 2.4 2.8 65 9360 350 322 319
2 x 400 61 25.4 2.6 3.0 72 11700 394 364 365
2 x 500 61 28.8 2.8 3.2 80 14780 439 410 413
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC or PE)
3-Cores CU/PVC/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
3 x 1.5 7 1.6 0.8 1.8 14 270 16 14 11
3 x 2.5 7 2.0 0.8 1.8 15 320 21 18 15
3x4 7 2.6 1.0 1.8 17 430 28 24 20
3x6 7 3.1 1.0 1.8 18 520 35 29 25
3 x 10 7 4.0 1.0 1.8 20 700 46 39 34
3 x 16 7 5.0 1.0 1.8 22 940 60 50 45
3 x 25 7 6.3 1.2 1.8 26 1340 77 66 60
3 x 35 7 7.4 1.2 1.8 28 1570 91 78 71
3 x 50 19 8.8 1.4 1.9 32 2050 107 94 87
3 x 70 19 10.6 1.4 2.0 37 2790 131 115 109
3 x 95 19 12.4 1.6 2.1 42 3740 157 140 134
3 x 120 37 14.0 1.6 2.2 45 4550 178 159 155
3 x 150 37 15.5 1.8 2.4 50 5590 199 179 175
3 x 185 37 17.4 2.0 2.5 55 6900 225 204 201
3 x 240 61 20.3 2.2 2.7 63 8970 259 237 238
3 x 300 61 22.7 2.4 2.9 70 11110 290 268 271
3 x 400 61 25.4 2.6 3.2 77 14010 325 302 308
3 x 500 61 28.8 2.8 3.4 86 17740 361 339 349
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (3½ & 4 Cores) - Copper Conductor, PVC Insulated CU Shielded Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC or PE)
3½ Cores CU/PVC/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Outer Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
Sheath Overall
Area* [Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne] Weight Amps Amps Amps
Thickness Diameter**
mm² No. mm mm mm mm kg/km
3x16+10 7/7 5/4 1.0 / 1.0 1.8 23 1070 60 51 45
3x25+16 7/7 6.3 / 5 1.2 / 1.0 1.8 27 1530 77 66 60
3x35+16 7/7 6.6 / 5 1.2 / 1.0 1.8 27 1670 90 77 70
3x50+25 19 / 7 7.5 / 6.3 1.4 / 1.2 1.9 31 2230 106 92 85
3x70+35 19 / 7 9.1 / 7.4 1.4 / 1.2 2.0 35 3040 130 114 106
3x95+50 19 / 19 11 / 8.8 1.6 / 1.4 2.2 40 4080 155 138 131
3x120+70 37 / 19 12.2 / 10.6 1.6 / 1.4 2.3 43 5090 176 156 150
3x150+70 37 / 19 13.8 / 10.6 1.8 / 1.4 2.4 47 6070 197 176 171
3x185+95 37 / 19 15.1 / 12.4 2.0 / 1.6 2.6 52 7570 222 201 196
3x240+120 61 / 37 17.6 / 14 2.2 / 1.6 2.8 58 9750 256 233 230
3x300+150 61 / 37 19.8 / 15.5 2.4 / 1.8 3.0 64 12040 287 263 262
3x400+185 61 / 37 22.2 / 17.4 2.6 / 2.0 3.2 72 15240 322 298 300
3x500+240 61 / 61 26.3 / 20.3 2.8 / 2.2 3.5 80 19250 361 337 343
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC or PE)
4-Cores CU/PVC/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Sheath Diameter** Weight
mm² No. mm mm mm mm kg/km
4 x 1.5 7 1.6 0.8 1.8 15 300 17 14 11
4 x 2.5 7 2.0 0.8 1.8 16 370 22 18 15
4x4 7 2.6 1.0 1.8 18 510 28 24 20
4x6 7 3.1 1.0 1.8 19 620 35 30 25
4 x 10 7 4.0 1.0 1.8 21 850 47 39 34
4 x 16 7 5.0 1.0 1.8 24 1150 60 51 46
4 x 25 7 6.3 1.2 1.8 28 1670 78 67 61
4 x 35 7 6.6 1.2 1.8 28 1860 90 78 71
4 x 50 19 7.5 1.4 2.0 33 2490 106 93 86
4 x 70 19 9.1 1.4 2.1 36 3370 130 114 107
4 x 95 19 11.0 1.6 2.3 41 4550 156 138 131
4 x 120 37 12.2 1.6 2.4 45 5590 177 158 152
4 x 150 37 13.8 1.8 2.5 50 6840 198 178 174
4 x 185 37 15.1 2.0 2.7 55 8500 223 202 198
4 x 240 61 17.6 2.2 2.9 61 10950 257 235 233
4 x 300 61 19.8 2.4 3.1 67 13540 288 266 265
4 x 400 61 22.2 2.6 3.4 76 17220 324 302 304
4 x 500 61 26.3 2.8 3.7 84 21700 363 339 347
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (5 Cores) - Copper Conductor, PVC Insulated CU Shielded Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC or PE)
5-Cores CU/PVC/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
5 x 1.5 7 1.6 0.8 1.8 15 350 17 14 11
5 x 2.5 7 2.0 0.8 1.8 17 430 22 18 15
5x4 7 2.6 1.0 1.8 19 600 28 24 20
5x6 7 3.1 1.0 1.8 21 740 35 30 26
5 x 10 7 4.0 1.0 1.8 23 1010 47 40 35
5 x 16 7 5.0 1.0 1.8 26 1390 61 52 47
5 x 25 7 6.3 1.2 1.8 30 2030 78 68 63
5 x 35 7 7.4 1.2 1.9 34 2470 94 82 77
5 x 50 19 8.8 1.4 2.1 39 3310 111 98 94
5 x 70 19 10.6 1.4 2.2 44 4470 136 121 118
5 x 95 19 12.4 1.6 2.4 51 6110 163 147 145
5 x 120 37 14.0 1.6 2.5 56 7460 185 168 169
5 x 150 37 15.5 1.8 2.7 61 9150 207 189 191
5 x 185 37 17.4 2.0 2.9 68 11350 234 215 220
5 x 240 61 20.3 2.2 3.1 77 14680 270 251 261
5 x 300 61 22.7 2.4 3.4 86 18340 302 283 296
5 x 400 61 25.4 2.6 3.7 95 23150 339 320 338
5 x 500 61 28.8 2.8 4.0 106 29380 378 359 383
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Aluminium Conductor, PVC Insulated CU Shielded Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC or PE)
1-Core AL/PVC/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
1 x 10 7 3.9 1.0 1.4 12 180
1 x 16 7 4.7 1.0 1.4 12 210
1 x 25 7 6.3 1.2 1.4 14 280
1 x 35 7 7.4 1.2 1.4 15 340
1 x 50 19 8.8 1.4 1.4 17 410
1 x 70 19 10.6 1.4 1.5 19 520
1 x 95 19 12.4 1.6 1.5 21 660
1 x 120 37 14 1.6 1.6 23 770
1 x 150 37 15.5 1.8 1.7 25 920
1 x 185 37 17.4 2.0 1.7 28 1100
1 x 240 61 19.9 2.2 1.8 31 1370
1 x 300 61 22.2 2.4 1.9 34 1650
1 x 400 61 25.2 2.6 2.0 38 2070
1 x 500 61 28.6 2.8 2.1 42 2520
1 x 630 91 32.6 2.8 2.2 46 3110
1 x 800 91 36.7 2.8 2.4 51 3850
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced Flat
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced
Trefoil [Gd] Touching in Three Trefoil [Air] Touching
Area Duct [Gd] Ducts [Gd] [Gd] [Air]
[Gd] Ducts [Gd] [Air]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps
1 x 10 38 36 37 39 40 36 29 37 30
1 x 16 49 46 47 50 51 46 38 48 39
1 x 25 63 59 61 65 66 60 51 65 52
1 x 35 76 71 73 77 79 71 62 79 64
1 x 50 90 84 87 91 93 85 76 96 78
1 x 70 110 103 107 112 114 104 96 122 99
1 x 95 131 123 127 134 136 124 118 149 121
1 x 120 149 141 146 152 155 142 138 173 142
1 x 150 167 158 162 170 174 159 157 197 162
1 x 185 190 180 186 194 197 182 185 230 190
1 x 240 220 209 216 224 229 212 220 273 227
1 x 300 248 237 246 253 259 241 254 315 262
1 x 400 283 272 285 289 296 277 298 368 308
1 x 500 323 311 327 330 339 318 349 430 360
1 x 630 366 353 373 374 386 363 407 503 419
1 x 800 411 397 426 420 437 413 468 581 482
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (2 & 3 Cores) - Aluminium Conductor, PVC Insulated CU Shielded Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC or PE)
2-Cores AL/PVC/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
2 x 10 7 3.9 1.0 1.8 18 440 41 35 29
2 x 16 7 4.7 1.0 1.8 20 540 53 46 39
2 x 25 7 6.3 1.2 1.8 24 760 70 60 53
2 x 35 7 7.4 1.2 1.8 26 920 84 72 64
2 x 50 19 8.8 1.4 1.8 29 1180 99 86 78
2 x 70 19 10.6 1.4 1.9 33 1510 122 107 99
2 x 95 19 12.4 1.6 2.0 38 2010 146 129 121
2 x 120 37 14 1.6 2.1 42 2380 167 148 141
2 x 150 37 15.5 1.8 2.3 46 2870 186 167 160
2 x 185 37 17.4 2.0 2.4 51 3560 211 191 184
2 x 240 61 19.9 2.2 2.6 57 4480 245 223 218
2 x 300 61 22.2 2.4 2.8 64 5510 276 254 251
2 x 400 61 25.2 2.6 3.0 71 6840 316 293 293
2 x 500 61 28.6 2.8 3.2 79 8520 360 335 339
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC or PE)
3-Cores AL/PVC/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
3 x 10 7 3.9 1.0 1.8 19 500 35 30 26
3 x 16 7 4.7 1.0 1.8 21 610 46 39 34
3 x 25 7 6.3 1.2 1.8 25 870 60 51 46
3 x 35 7 7.4 1.2 1.8 28 940 70 60 55
3 x 50 19 8.8 1.4 1.9 32 1190 83 73 67
3 x 70 19 10.6 1.4 2.0 37 1570 102 90 85
3 x 95 19 12.4 1.6 2.1 42 2030 122 109 104
3 x 120 37 14 1.6 2.2 45 2390 139 124 121
3 x 150 37 15.5 1.8 2.4 50 2930 156 140 137
3 x 185 37 17.4 2.0 2.5 55 3560 176 160 158
3 x 240 61 19.9 2.2 2.7 62 4520 204 187 187
3 x 300 61 22.2 2.4 2.9 69 5490 231 212 215
3 x 400 61 25.2 2.6 3.2 77 6830 263 245 250
3 x 500 61 28.6 2.8 3.4 86 8470 300 281 289
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (3½ & 4 Cores) - Aluminium Conductor, PVC Insulated CU Shielded Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC or PE)
3½ Cores AL/PVC/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Outer Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
Sheath Overall
Area* [Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne] Weight Amps Amps Amps
Thickness Diameter**
mm² No. mm mm mm mm kg/km
3x16+10 7/7 4.7 / 3.9 1.0 / 1.0 1.8 22 690 46 39 34
3x25+16 7/7 6.3 / 4.7 1.2 / 1.0 1.8 26 960 60 51 46
3x35+16 7/7 6.5 / 4.7 1.2 / 1.0 1.8 27 940 70 60 54
3x50+25 7/7 7.5 / 6.3 1.4 / 1.2 1.9 31 1230 82 72 66
3x70+35 14 / 7 9.1 / 7.4 1.4 / 1.2 2.0 35 1580 101 89 83
3x95+50 19 / 19 10.8 / 8.8 1.6 / 1.4 2.2 40 2060 121 107 101
3x120+70 19 / 19 12.2 / 10.6 1.6 / 1.4 2.3 43 2490 137 122 117
3x150+70 37 / 19 13.5 / 10.6 1.8 / 1.4 2.4 47 2940 153 137 133
3x185+95 37 / 19 15.2 / 12.4 2.0 / 1.6 2.6 52 3610 174 157 154
3x240+120 37 / 37 17.5 / 14 2.2 / 1.6 2.8 58 4580 201 184 181
3x300+150 37 / 37 19.6 / 15.5 2.4 / 1.8 3.0 64 5550 227 209 208
3x400+185 61 / 37 22.5 / 17.4 2.6 / 2.0 3.2 72 6980 260 240 242
3x500+240 61 / 61 25.6 / 19.9 2.8 / 2.2 3.5 80 8620 296 276 281
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC or PE)
4-Cores AL/PVC/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Sheath Diameter** Weight
mm² No. mm mm mm mm kg/km
4 x 10 7 3.9 1.0 1.8 21 590 36 30 26
4 x 16 7 4.7 1.0 1.8 23 730 46 39 35
4 x 25 7 6.3 1.2 1.8 27 1050 60 52 47
4 x 35 7 6.5 1.2 1.8 28 1010 70 60 55
4 x 50 7 7.5 1.4 2.0 33 1350 82 72 66
4 x 70 14 9.1 1.4 2.1 36 1700 101 89 83
4 x 95 19 10.8 1.6 2.3 41 2240 121 107 102
4 x 120 19 12.2 1.6 2.4 45 2670 138 123 118
4 x 150 37 13.5 1.8 2.5 50 3220 154 139 135
4 x 185 37 15.2 2.0 2.7 55 3970 175 159 155
4 x 240 37 17.5 2.2 2.9 61 5000 202 185 183
4 x 300 37 19.6 2.4 3.1 67 6070 228 211 210
4 x 400 61 22.5 2.6 3.4 76 7690 261 243 245
4 x 500 61 25.6 2.8 3.7 84 9470 298 279 284
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (5 Cores) - Aluminium Conductor, PVC Insulated CU Shielded Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Shield : Copper Tape Screen
Oversheath : Extruded Material (PVC or PE)
5-Cores AL/PVC/CUT/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
5 x 10 7 3.9 1.0 1.8 22 690 36 30 27
5 x 16 7 4.7 1.0 1.8 24 870 47 40 35
5 x 25 7 6.3 1.2 1.8 30 1270 61 53 49
5 x 35 7 7.4 1.2 1.9 34 1420 73 64 60
5 x 50 19 8.8 1.4 2.1 39 1890 86 76 73
5 x 70 19 10.6 1.4 2.2 44 2440 106 94 92
5 x 95 19 12.4 1.6 2.4 51 3260 127 114 113
5 x 120 37 14 1.6 2.5 56 3860 145 131 132
5 x 150 37 15.5 1.8 2.7 61 4720 162 147 149
5 x 185 37 17.4 2.0 2.9 68 5780 183 169 173
5 x 240 61 19.9 2.2 3.1 76 7280 213 198 205
5 x 300 61 22.2 2.4 3.4 85 8980 240 224 235
5 x 400 61 25.2 2.6 3.7 94 11190 275 258 273
5 x 500 61 28.6 2.8 4.0 106 13930 313 297 317
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Copper Conductor, XLPE Insulated Lead Sheathed Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC, LSF or PE)
1-Core CU/XLPE/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Lead Sheath Outer Sheath Overall Cable
Area Strands
Diameter Thickness Thickness Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
1 x 1.5 7 1.6 0.7 1.2 1.4 12 420
1 x 2.5 7 2.0 0.7 1.2 1.4 12 460
1x4 7 2.6 0.7 1.2 1.4 13 500
1x6 7 3.1 0.7 1.2 1.4 13 550
1 x 10 7 4.0 0.7 1.2 1.4 14 640
1 x 16 7 5.0 0.7 1.2 1.4 15 750
1 x 25 7 6.3 0.9 1.2 1.4 17 930
1 x 35 7 7.4 0.9 1.2 1.4 18 1080
1 x 50 19 8.8 1.0 1.2 1.5 20 1290
1 x 70 19 10.6 1.1 1.2 1.5 22 1590
1 x 95 19 12.4 1.1 1.2 1.6 24 1950
1 x 120 37 14.0 1.2 1.2 1.6 25 2280
1 x 150 37 15.5 1.4 1.2 1.7 28 2660
1 x 185 37 17.4 1.6 1.3 1.8 30 3250
1 x 240 61 20.3 1.7 1.4 1.9 34 4090
1 x 300 61 22.7 1.8 1.4 1.9 36 4830
1 x 400 61 25.4 2.0 1.5 2.1 40 6060
1 x 500 61 28.8 2.2 1.6 2.2 45 7510
1 x 630 61 30.4 2.4 1.7 2.3 47 9060
1 x 800 61 33.7 2.6 1.8 2.5 52 11270
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced Flat Touching
Trefoil [Gd] Touching in Three Trefoil [Air]
Area Duct [Gd] Ducts [Gd] [Gd] [Air] [Air]
[Gd] Ducts [Gd]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps
1 x 1.5 23 22 23 24 24 22 23 28 23
1 x 2.5 30 28 29 31 31 28 29 36 30
1x4 39 37 38 40 41 37 39 48 40
1x6 48 45 47 49 50 46 48 60 49
1 x 10 64 60 62 65 66 60 65 82 67
1 x 16 82 76 79 83 85 77 86 107 88
1 x 25 105 98 102 107 109 99 114 142 117
1 x 35 125 117 121 128 130 118 138 173 142
1 x 50 147 139 144 151 153 140 168 210 173
1 x 70 180 170 174 184 187 170 211 263 217
1 x 95 215 203 210 219 222 204 259 321 266
1 x 120 242 230 236 247 251 230 297 367 305
1 x 150 272 259 267 278 281 259 343 421 352
1 x 185 306 291 303 312 315 291 393 479 403
1 x 240 354 338 352 360 361 336 470 568 482
1 x 300 395 378 397 401 402 375 535 644 548
1 x 400 444 426 450 449 447 418 615 728 628
1 x 500 497 478 512 500 492 463 709 825 721
1 x 630 546 526 566 547 533 501 787 903 797
1 x 800 595 574 630 592 568 536 877 979 882
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (2 & 3 Cores) - Copper Conductor, XLPE Insulated Lead Sheathed Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC, LSF or PE)
2-Cores CU/XLPE/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Lead Sheath Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Thickness Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
2 x 1.5 7 1.6 0.7 1.2 1.8 16 690 25 21 22
2 x 2.5 7 2.0 0.7 1.2 1.8 17 770 33 28 29
2x4 7 2.6 0.7 1.2 1.8 18 870 42 36 38
2x6 7 3.1 0.7 1.2 1.8 19 980 53 45 48
2 x 10 7 4.0 0.7 1.2 1.8 21 1190 70 60 65
2 x 16 7 5.0 0.7 1.2 1.8 23 1440 91 78 86
2 x 25 7 6.3 0.9 1.2 1.8 26 1880 117 100 114
2 x 35 7 7.4 0.9 1.2 1.8 28 2240 140 120 139
2 x 50 19 8.8 1.0 1.3 1.8 32 2830 166 145 170
2 x 70 19 10.6 1.1 1.4 1.9 36 3700 203 178 214
2 x 95 19 12.4 1.1 1.5 2.1 41 4780 243 214 262
2 x 120 37 14.0 1.2 1.6 2.2 45 5800 276 246 303
2 x 150 37 15.5 1.4 1.7 2.3 49 6930 309 277 345
2 x 185 37 17.4 1.6 1.8 2.4 54 8500 347 314 394
2 x 240 61 20.3 1.7 2.0 2.6 61 10880 401 366 466
2 x 300 61 22.7 1.8 2.1 2.8 68 13210 450 413 532
2 x 400 61 25.4 2.0 2.3 3.1 75 16450 504 466 605
2 x 500 61 28.8 2.2 2.5 3.3 83 20530 560 522 686
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC, LSF or PE)
3-Cores CU/XLPE/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Lead Sheath Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Thickness Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
3 x 1.5 7 1.6 0.7 1.2 1.8 16 730 22 18 19
3 x 2.5 7 2.0 0.7 1.2 1.8 17 820 28 24 25
3x4 7 2.6 0.7 1.2 1.8 19 940 36 31 33
3x6 7 3.1 0.7 1.2 1.8 20 1080 45 38 42
3 x 10 7 4.0 0.7 1.2 1.8 22 1320 60 50 57
3 x 16 7 5.0 0.7 1.2 1.8 24 1640 77 65 75
3 x 25 7 6.3 0.9 1.2 1.8 27 2160 99 84 99
3 x 35 7 7.4 0.9 1.3 1.8 30 2590 116 101 119
3 x 50 19 8.8 1.0 1.4 1.9 34 3280 138 120 144
3 x 70 19 10.6 1.1 1.5 2.0 39 4360 168 148 181
3 x 95 19 12.4 1.1 1.6 2.1 43 5560 201 178 221
3 x 120 37 14.0 1.2 1.7 2.3 48 6770 228 204 256
3 x 150 37 15.5 1.4 1.8 2.4 53 8180 255 229 291
3 x 185 37 17.4 1.6 1.9 2.6 58 9950 287 260 332
3 x 240 61 20.3 1.7 2.1 2.8 66 12810 330 302 391
3 x 300 61 22.7 1.8 2.2 2.9 72 15450 369 340 444
3 x 400 61 25.4 2.0 2.5 3.2 80 19560 412 383 504
3 x 500 61 28.8 2.2 2.7 3.5 90 24550 456 428 569
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (3½ & 4 Cores) - Copper Conductor, XLPE Insulated Lead Sheathed Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC, LSF or PE)
3½ Cores CU/XLPE/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Nominal Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
[Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne]
Lead Sheath Outer Sheath Overall
Weight
Area* Diameter** Amps Amps Amps
Thickness Thickness
mm² No. mm mm mm mm mm kg/km
3x16+10 7/7 5/4 0.7 / 0.7 1.2 1.8 25 1790 77 66 76
3x25+16 7/7 6.3 / 5 0.9 / 0.7 1.2 1.8 29 2370 100 86 101
3x35+16 7/7 6.6 / 5 0.9 / 0.7 1.3 1.8 29 2620 115 100 116
3x50+25 19 / 7 7.5 / 6.3 1.0 / 0.9 1.4 1.9 33 3370 137 119 141
3x70+35 19 / 7 9.1 / 7.4 1.1 / 0.9 1.5 2.1 37 4510 166 146 176
3x95+50 19 / 19 11 / 8.8 1.1 / 1.0 1.6 2.2 41 5740 199 175 215
3x120+70 37 / 19 12.2 / 10.6 1.2 / 1.1 1.7 2.3 45 7050 226 201 249
3x150+70 37 / 19 13.8 / 10.6 1.4 / 1.1 1.8 2.5 50 8450 253 226 283
3x185+95 37 / 19 15.1 / 12.4 1.6 / 1.1 2.0 2.6 55 10500 284 257 324
3x240+120 61 / 37 17.6 / 14 1.7 / 1.2 2.1 2.8 61 13140 327 298 380
3x300+150 61 / 37 19.8 / 15.5 1.8 / 1.4 2.3 3.0 67 16100 366 336 432
3x400+185 61 / 37 22.2 / 17.4 2.0 / 1.6 2.5 3.3 75 20210 411 380 495
3x500+240 61 / 61 26.3 / 20.3 2.2 / 1.7 2.7 3.6 83 25330 457 427 560
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC, LSF or PE)
4-Cores CU/XLPE/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of Nominal Outer
Conductor Insulation Lead Sheath Sheath Thickness
Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Thickness Diameter** Weight
mm² No. mm mm mm mm mm kg/km
4 x 1.5 7 1.6 0.7 1.2 1.8 17 790 22 18 19
4 x 2.5 7 2.0 0.7 1.2 1.8 18 900 28 24 26
4x4 7 2.6 0.7 1.2 1.8 20 1050 37 31 34
4x6 7 3.1 0.7 1.2 1.8 21 1210 45 38 43
4 x 10 7 4.0 0.7 1.2 1.8 23 1510 60 51 58
4 x 16 7 5.0 0.7 1.2 1.8 26 1900 78 66 77
4 x 25 7 6.3 0.9 1.3 1.8 30 2640 100 86 103
4 x 35 7 6.6 0.9 1.3 1.8 30 2850 116 100 118
4 x 50 19 7.5 1.0 1.5 2.0 34 3760 137 119 142
4 x 70 19 9.1 1.1 1.6 2.1 39 5010 167 148 178
4 x 95 19 11.0 1.1 1.7 2.3 43 6420 200 177 218
4 x 120 37 12.2 1.2 1.8 2.4 47 7840 226 202 251
4 x 150 37 13.8 1.4 1.9 2.6 52 9510 254 228 286
4 x 185 37 15.1 1.6 2.1 2.8 58 11710 286 260 328
4 x 240 61 17.6 1.7 2.3 3.0 64 14930 328 301 384
4 x 300 61 19.8 1.8 2.4 3.2 70 18030 368 339 437
4 x 400 61 22.2 2.0 2.7 3.5 80 23060 413 385 500
4 x 500 61 26.3 2.2 2.9 3.8 88 28650 460 431 567
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (5 Cores) - Copper Conductor, XLPE Insulated Lead Sheathed Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC, LSF or PE)
5-Cores CU/XLPE/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Lead Sheath Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Thickness Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
5 x 1.5 7 1.6 0.7 1.2 1.8 18 870 22 18 20
5 x 2.5 7 2.0 0.7 1.2 1.8 19 1000 28 24 26
5x4 7 2.6 0.7 1.2 1.8 21 1170 37 31 34
5x6 7 3.1 0.7 1.2 1.8 22 1360 46 39 43
5 x 10 7 4.0 0.7 1.2 1.8 25 1710 61 52 59
5 x 16 7 5.0 0.7 1.2 1.8 27 2180 78 67 78
5 x 25 7 6.3 0.9 1.3 1.8 32 3070 101 87 105
5 x 35 7 7.4 0.9 1.4 1.9 36 3750 121 105 129
5 x 50 19 8.8 1.0 1.5 2.1 41 4870 143 125 156
5 x 70 19 10.6 1.1 1.7 2.2 47 6590 175 155 198
5 x 95 19 12.4 1.1 1.8 2.4 53 8560 209 187 242
5 x 120 37 14.0 1.2 1.9 2.6 58 10440 237 214 279
5 x 150 37 15.5 1.4 2.1 2.8 64 12740 265 242 318
5 x 185 37 17.4 1.6 2.2 2.9 71 15590 298 274 364
5 x 240 61 20.3 1.7 2.4 3.2 80 19940 343 318 430
5 x 300 61 22.7 1.8 2.6 3.4 89 24560 382 358 488
5 x 400 61 25.4 2.0 2.9 3.8 98 30990 425 399 551
5 x 500 61 28.8 2.2 3.1 4.1 110 38680 469 445 622
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Aluminium Conductor, XLPE Insulated Lead Sheathed Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC, LSF or PE)
1-Core AL/XLPE/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Lead Sheath Outer Sheath Overall Cable
Area Strands
Diameter Thickness Thickness Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
1 x 10 7 3.9 0.7 1.2 1.4 14 570
1 x 16 7 4.7 0.7 1.2 1.4 15 640
1 x 25 7 6.3 0.9 1.2 1.4 17 780
1 x 35 7 7.4 0.9 1.2 1.4 18 870
1 x 50 19 8.8 1.0 1.2 1.5 20 1010
1 x 70 19 10.6 1.1 1.2 1.5 22 1190
1 x 95 19 12.4 1.1 1.2 1.6 24 1380
1 x 120 37 14 1.2 1.2 1.6 25 1560
1 x 150 37 15.5 1.4 1.2 1.7 28 1770
1 x 185 37 17.4 1.6 1.3 1.8 30 2140
1 x 240 61 19.9 1.7 1.4 1.9 33 2600
1 x 300 61 22.2 1.8 1.4 1.9 36 2960
1 x 400 61 25.2 2.0 1.5 2.1 40 3670
1 x 500 61 28.6 2.2 1.6 2.2 45 4430
1 x 630 91 32.6 2.4 1.7 2.3 49 5420
1 x 800 91 36.7 2.6 1.8 2.5 55 6630
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced Flat Touching
Trefoil [Gd] Touching in Three Trefoil [Air]
Area Duct [Gd] Ducts [Gd] [Gd] [Air] [Air]
[Gd] Ducts [Gd]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps
1 x 10 49 46 47 50 51 46 50 63 51
1 x 16 63 59 61 64 66 59 66 83 68
1 x 25 81 76 79 83 85 77 88 110 91
1 x 35 97 91 94 99 101 91 107 134 110
1 x 50 114 108 112 117 119 109 131 163 134
1 x 70 140 132 135 143 145 133 164 204 169
1 x 95 167 158 163 170 173 159 201 249 207
1 x 120 189 179 184 193 196 179 231 287 238
1 x 150 212 201 207 216 219 202 267 328 274
1 x 185 239 228 236 244 247 229 307 376 316
1 x 240 277 264 275 282 285 265 365 444 375
1 x 300 313 299 311 318 320 298 422 510 434
1 x 400 356 342 356 362 361 338 493 587 505
1 x 500 405 390 410 410 406 382 578 677 591
1 x 630 457 441 466 461 450 425 668 770 680
1 x 800 510 493 526 511 491 465 765 858 774
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (2 & 3 Cores) - Aluminium Conductor, XLPE Insulated Lead Sheathed Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC, LSF or PE)
2-Cores AL/XLPE/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Lead Sheath Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Thickness Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
2 x 10 7 3.9 0.7 1.2 1.8 20 1020 54 46 50
2 x 16 7 4.7 0.7 1.2 1.8 22 1170 70 59 66
2 x 25 7 6.3 0.9 1.2 1.8 26 1540 91 78 88
2 x 35 7 7.4 0.9 1.2 1.8 28 1770 108 93 108
2 x 50 19 8.8 1.0 1.3 1.8 31 2210 128 111 131
2 x 70 19 10.6 1.1 1.4 1.9 36 2840 158 138 166
2 x 95 19 12.4 1.1 1.5 2.1 40 3580 188 166 202
2 x 120 37 14 1.2 1.6 2.2 44 4300 214 190 235
2 x 150 37 15.5 1.4 1.7 2.3 48 5100 240 215 267
2 x 185 37 17.4 1.6 1.8 2.4 54 6200 272 246 308
2 x 240 61 19.9 1.7 2.0 2.6 60 7760 315 286 365
2 x 300 61 22.2 1.8 2.1 2.8 66 9280 355 325 417
2 x 400 61 25.2 2.0 2.3 3.1 74 11530 405 375 485
2 x 500 61 28.6 2.2 2.5 3.3 82 14190 460 428 562
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC, LSF or PE)
3-Cores AL/XLPE/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Lead Sheath Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Thickness Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
3 x 10 7 3.9 0.7 1.2 1.8 21 1090 46 38 43
3 x 16 7 4.7 0.7 1.2 1.8 23 1270 59 50 57
3 x 25 7 6.3 0.9 1.2 1.8 27 1670 77 65 77
3 x 35 7 7.4 0.9 1.3 1.8 30 1950 90 78 92
3 x 50 19 8.8 1.0 1.4 1.9 34 2420 107 93 112
3 x 70 19 10.6 1.1 1.5 2.0 39 3140 131 115 140
3 x 95 19 12.4 1.1 1.6 2.1 43 3850 156 138 172
3 x 120 37 14 1.2 1.7 2.3 48 4620 178 159 200
3 x 150 37 15.5 1.4 1.8 2.4 53 5520 199 179 227
3 x 185 37 17.4 1.6 1.9 2.6 58 6610 225 204 261
3 x 240 61 19.9 1.7 2.1 2.8 65 8320 261 238 307
3 x 300 61 22.2 1.8 2.2 2.9 71 9770 294 271 352
3 x 400 61 25.2 2.0 2.5 3.2 80 12350 335 312 409
3 x 500 61 28.6 2.2 2.7 3.5 89 15250 379 355 471
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (3½ & 4 Cores) - Aluminium Conductor, XLPE Insulated Lead Sheathed Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC, LSF or PE)
3½ Cores AL/XLPE/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Nominal Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
[Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne]
Lead Sheath Outer Sheath Overall
Weight
Area* Diameter** Amps Amps Amps
Thickness Thickness
mm² No. mm mm mm mm mm kg/km
3x16+10 7/7 4.7 / 3.9 0.7 / 0.7 1.2 1.8 24 1370 59 50 58
3x25+16 7/7 6.3 / 4.7 0.9 / 0.7 1.2 1.8 28 1780 77 66 78
3x35+16 7/7 6.5 / 4.7 0.9 / 0.7 1.3 1.8 29 1890 89 77 90
3x50+25 7/7 7.5 / 6.3 1.0 / 0.9 1.4 1.9 33 2370 106 92 110
3x70+35 14 / 7 9.1 / 7.4 1.1 / 0.9 1.5 2.1 37 3050 129 113 137
3x95+50 19 / 19 10.8 / 8.8 1.1 / 1.0 1.6 2.2 41 3720 154 136 167
3x120+70 19 / 19 12.2 / 10.6 1.2 / 1.1 1.7 2.3 45 4460 176 157 194
3x150+70 37 / 19 13.5 / 10.6 1.4 / 1.1 1.8 2.5 50 5320 197 176 220
3x185+95 37 / 19 15.2 / 12.4 1.6 / 1.1 2.0 2.6 55 6540 223 202 254
3x240+120 37 / 37 17.5 / 14 1.7 / 1.2 2.1 2.8 61 7970 258 235 299
3x300+150 37 / 37 19.6 / 15.5 1.8 / 1.4 2.3 3.0 67 9600 291 267 343
3x400+185 61 / 37 22.5 / 17.4 2.0 / 1.6 2.5 3.3 75 11940 332 307 399
3x500+240 61 / 61 25.6 / 19.9 2.2 / 1.7 2.7 3.6 83 14700 376 351 459
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC, LSF or PE)
4-Cores AL/XLPE/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of Nominal Outer
Conductor Insulation Lead Sheath Sheath Thickness
Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Thickness Diameter** Weight
mm² No. mm mm mm mm mm kg/km
4 x 10 7 3.9 0.7 1.2 1.8 22 1220 46 39 44
4 x 16 7 4.7 0.7 1.2 1.8 24 1430 60 50 58
4 x 25 7 6.3 0.9 1.3 1.8 29 2000 77 67 79
4 x 35 7 6.5 0.9 1.3 1.8 30 2000 90 78 91
4 x 50 7 7.5 1.0 1.5 2.0 34 2620 106 92 110
4 x 70 14 9.1 1.1 1.6 2.1 39 3340 130 115 139
4 x 95 19 10.8 1.1 1.7 2.3 43 4110 155 138 169
4 x 120 19 12.2 1.2 1.8 2.4 47 4920 176 157 195
4 x 150 37 13.5 1.4 1.9 2.6 52 5880 197 178 222
4 x 185 37 15.2 1.6 2.1 2.8 58 7190 224 203 257
4 x 240 37 17.5 1.7 2.3 3.0 64 8990 259 237 302
4 x 300 37 19.6 1.8 2.4 3.2 70 10560 292 269 346
4 x 400 61 22.5 2.0 2.7 3.5 80 13520 334 311 403
4 x 500 61 25.6 2.2 2.9 3.8 88 16420 379 354 465
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (5 Cores) - Aluminium Conductor, XLPE Insulated Lead Sheathed Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC, LSF or PE)
5-Cores AL/XLPE/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Lead Sheath Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Thickness Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
5 x 10 7 3.9 0.7 1.2 1.8 24 1370 46 39 45
5 x 16 7 4.7 0.7 1.2 1.8 26 1610 60 51 60
5 x 25 7 6.3 0.9 1.3 1.8 32 2280 78 68 81
5 x 35 7 7.4 0.9 1.4 1.9 35 2690 93 82 99
5 x 50 19 8.8 1.0 1.5 2.1 41 3440 111 97 121
5 x 70 19 10.6 1.1 1.7 2.2 47 4560 136 121 154
5 x 95 19 12.4 1.1 1.8 2.4 53 5710 162 146 188
5 x 120 37 14 1.2 1.9 2.6 58 6840 185 167 218
5 x 150 37 15.5 1.4 2.1 2.8 64 8310 207 189 248
5 x 185 37 17.4 1.6 2.2 2.9 71 10020 234 215 286
5 x 240 61 19.9 1.7 2.4 3.2 79 12460 271 251 338
5 x 300 61 22.2 1.8 2.6 3.4 87 15110 305 285 387
5 x 400 61 25.2 2.0 2.9 3.8 98 18990 347 326 449
5 x 500 61 28.6 2.2 3.1 4.1 109 23180 392 372 518
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Copper Conductor, PVC Insulated Lead Sheathed Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC or PE)
1-Core CU/PVC/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Lead Sheath Outer Sheath Overall Cable
Area Strands
Diameter Thickness Thickness Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
1 x 1.5 7 1.6 0.8 1.2 1.4 12 440
1 x 2.5 7 2.0 0.8 1.2 1.4 12 470
1x4 7 2.6 1.0 1.2 1.4 13 550
1x6 7 3.1 1.0 1.2 1.4 14 600
1 x 10 7 4.0 1.0 1.2 1.4 15 690
1 x 16 7 5.0 1.0 1.2 1.4 16 800
1 x 25 7 6.3 1.2 1.2 1.4 17 990
1 x 35 7 7.4 1.2 1.2 1.4 19 1150
1 x 50 19 8.8 1.4 1.2 1.5 20 1380
1 x 70 19 10.6 1.4 1.2 1.5 22 1680
1 x 95 19 12.4 1.6 1.2 1.6 25 2080
1 x 120 37 14.0 1.6 1.2 1.7 26 2410
1 x 150 37 15.5 1.8 1.2 1.7 28 2790
1 x 185 37 17.4 2.0 1.3 1.8 31 3400
1 x 240 61 20.3 2.2 1.4 1.9 35 4290
1 x 300 61 22.7 2.4 1.5 2.0 38 5220
1 x 400 61 25.4 2.6 1.6 2.1 42 6480
1 x 500 61 28.8 2.8 1.6 2.2 46 7850
1 x 630 61 30.4 2.8 1.7 2.3 48 9320
1 x 800 61 33.7 2.8 1.8 2.5 52 11500
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced Flat Touching
Trefoil [Gd] Touching in Three Trefoil [Air]
Area Duct [Gd] Ducts [Gd] [Gd] [Air] [Air]
[Gd] Ducts [Gd]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps
1 x 1.5 19 17 18 19 19 17 14 17 14
1 x 2.5 24 22 23 24 25 23 18 23 19
1x4 31 29 30 32 32 29 24 30 24
1x6 38 36 37 39 40 36 30 38 31
1 x 10 51 48 49 52 53 48 41 51 42
1 x 16 65 61 63 66 68 62 54 67 55
1 x 25 83 78 81 85 86 79 70 87 71
1 x 35 100 94 97 102 103 95 86 107 88
1 x 50 117 110 114 119 121 111 103 128 106
1 x 70 143 135 138 146 148 135 129 161 133
1 x 95 171 162 166 174 177 162 160 197 164
1 x 120 193 183 190 197 199 184 183 226 188
1 x 150 216 205 212 220 222 205 209 256 215
1 x 185 243 232 240 248 250 231 242 294 248
1 x 240 281 269 282 285 286 267 288 347 295
1 x 300 314 301 317 318 316 296 329 392 337
1 x 400 352 338 358 355 350 328 378 442 385
1 x 500 392 378 404 394 385 362 431 499 438
1 x 630 430 415 450 430 416 392 479 546 484
1 x 800 466 450 495 463 440 416 529 589 531
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (2 & 3 Cores) - Copper Conductor, PVC Insulated Lead Sheathed Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC or PE)
2-Cores CU/PVC/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Lead Sheath Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Thickness Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
2 x 1.5 7 1.6 0.8 1.2 1.8 16 720 19 17 13
2 x 2.5 7 2.0 0.8 1.2 1.8 17 810 25 22 17
2x4 7 2.6 1.0 1.2 1.8 19 970 33 28 23
2x6 7 3.1 1.0 1.2 1.8 20 1090 41 35 29
2 x 10 7 4.0 1.0 1.2 1.8 22 1300 54 47 40
2 x 16 7 5.0 1.0 1.2 1.8 24 1570 70 61 53
2 x 25 7 6.3 1.2 1.2 1.8 27 2020 90 78 69
2 x 35 7 7.4 1.2 1.3 1.8 30 2490 109 95 85
2 x 50 19 8.8 1.4 1.4 1.9 34 3180 129 113 104
2 x 70 19 10.6 1.4 1.5 2.0 38 4050 158 141 130
2 x 95 19 12.4 1.6 1.6 2.1 43 5270 189 168 159
2 x 120 37 14.0 1.6 1.7 2.2 47 6280 215 193 185
2 x 150 37 15.5 1.8 1.8 2.4 51 7500 240 218 209
2 x 185 37 17.4 2.0 1.9 2.5 56 9140 270 246 239
2 x 240 61 20.3 2.2 2.1 2.7 64 11700 312 287 283
2 x 300 61 22.7 2.4 2.2 2.9 70 14220 349 323 320
2 x 400 61 25.4 2.6 2.4 3.2 78 17590 390 364 365
2 x 500 61 28.8 2.8 2.6 3.4 86 21940 432 406 412
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC or PE)
3-Cores CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Lead Sheath Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Thickness Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
3 x 1.5 7 1.6 0.8 1.2 1.8 17 770 17 14 12
3 x 2.5 7 2.0 0.8 1.2 1.8 18 870 22 18 15
3x4 7 2.6 1.0 1.2 1.8 20 1060 28 24 21
3x6 7 3.1 1.0 1.2 1.8 21 1200 35 30 26
3 x 10 7 4.0 1.0 1.2 1.8 23 1450 47 40 35
3 x 16 7 5.0 1.0 1.2 1.8 25 1780 60 51 46
3 x 25 7 6.3 1.2 1.2 1.8 29 2340 78 67 61
3 x 35 7 7.4 1.2 1.3 1.8 31 2770 91 79 73
3 x 50 19 8.8 1.4 1.4 1.9 36 3530 108 95 89
3 x 70 19 10.6 1.4 1.5 2.1 40 4620 132 117 111
3 x 95 19 12.4 1.6 1.6 2.2 46 5970 158 141 136
3 x 120 37 14.0 1.6 1.7 2.3 50 7150 179 161 158
3 x 150 37 15.5 1.8 1.9 2.5 55 8810 200 182 179
3 x 185 37 17.4 2.0 2.0 2.6 60 10650 225 205 204
3 x 240 61 20.3 2.2 2.2 2.9 69 13730 259 239 240
3 x 300 61 22.7 2.4 2.3 3.0 75 16560 289 268 272
3 x 400 61 25.4 2.6 2.5 3.3 83 20560 322 301 309
3 x 500 61 28.8 2.8 2.7 3.6 92 25720 356 336 347
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (3½ & 4 Cores) - Copper Conductor, PVC Insulated Lead Sheathed Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC or PE)
3½ Cores CU/PVC/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Nominal Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
[Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne]
Lead Sheath Outer Sheath Overall
Weight
Area* Diameter** Amps Amps Amps
Thickness Thickness
mm² No. mm mm mm mm mm kg/km
3x16+10 7/7 5/4 1.0 / 1.0 1.2 1.8 26 1970 60 52 47
3x25+16 7/7 6.3 / 5 1.2 / 1.0 1.3 1.8 30 2670 78 67 62
3x35+16 7/7 6.6 / 5 1.2 / 1.0 1.3 1.8 30 2820 90 79 71
3x50+25 19 / 7 7.5 / 6.3 1.4 / 1.2 1.5 2.0 35 3790 107 94 87
3x70+35 19 / 7 9.1 / 7.4 1.4 / 1.2 1.6 2.1 39 4910 130 116 109
3x95+50 19 / 19 11 / 8.8 1.6 / 1.4 1.7 2.3 44 6350 156 139 133
3x120+70 37 / 19 12.2 / 10.6 1.6 / 1.4 1.8 2.4 48 7720 177 159 153
3x150+70 37 / 19 13.8 / 10.6 1.8 / 1.4 1.9 2.5 52 9100 198 179 174
3x185+95 37 / 19 15.1 / 12.4 2.0 / 1.6 2.0 2.7 57 11090 223 203 199
3x240+120 61 / 37 17.6 / 14 2.2 / 1.6 2.2 2.9 64 14110 256 236 233
3x300+150 61 / 37 19.8 / 15.5 2.4 / 1.8 2.4 3.1 70 17280 286 265 265
3x400+185 61 / 37 22.2 / 17.4 2.6 / 2.0 2.6 3.4 79 21680 321 299 303
3x500+240 61 / 61 26.3 / 20.3 2.8 / 2.2 2.8 3.7 86 26890 356 334 342
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC or PE)
4-Cores CU/PVC/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of Nominal Outer
Conductor Insulation Lead Sheath Sheath Thickness
Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Thickness Diameter** Weight
mm² No. mm mm mm mm mm kg/km
4 x 1.5 7 1.6 0.8 1.2 1.8 18 840 17 14 12
4 x 2.5 7 2.0 0.8 1.2 1.8 19 960 22 19 16
4x4 7 2.6 1.0 1.2 1.8 21 1190 28 24 21
4x6 7 3.1 1.0 1.2 1.8 22 1360 35 30 26
4 x 10 7 4.0 1.0 1.2 1.8 25 1670 47 40 36
4 x 16 7 5.0 1.0 1.2 1.8 27 2070 61 52 47
4 x 25 7 6.3 1.2 1.3 1.8 31 2860 78 68 63
4 x 35 7 6.6 1.2 1.4 1.9 32 3170 91 80 73
4 x 50 19 7.5 1.4 1.5 2.0 37 4120 107 95 88
4 x 70 19 9.1 1.4 1.6 2.2 41 5330 131 116 110
4 x 95 19 11.0 1.6 1.8 2.4 46 7060 157 141 135
4 x 120 37 12.2 1.6 1.9 2.5 50 8480 178 160 155
4 x 150 37 13.8 1.8 2.0 2.7 55 10230 199 181 176
4 x 185 37 15.1 2.0 2.1 2.8 60 12400 223 204 201
4 x 240 61 17.6 2.2 2.3 3.1 67 15750 257 237 236
4 x 300 61 19.8 2.4 2.5 3.3 73 19300 288 267 268
4 x 400 61 22.2 2.6 2.8 3.6 83 24540 323 302 306
4 x 500 61 26.3 2.8 3.0 3.9 91 30320 358 337 347
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (5 Cores) - Copper Conductor, PVC Insulated Lead Sheathed Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC or PE)
5-Cores CU/PVC/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Lead Sheath Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Thickness Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
5 x 1.5 7 1.6 0.8 1.2 1.8 19 920 17 15 12
5 x 2.5 7 2.0 0.8 1.2 1.8 20 1060 22 19 16
5x4 7 2.6 1.0 1.2 1.8 22 1330 29 24 21
5x6 7 3.1 1.0 1.2 1.8 24 1530 36 31 27
5 x 10 7 4.0 1.0 1.2 1.8 26 1910 47 41 36
5 x 16 7 5.0 1.0 1.3 1.8 29 2490 61 53 48
5 x 25 7 6.3 1.2 1.4 1.9 34 3450 79 69 64
5 x 35 7 7.4 1.2 1.5 2.0 38 4170 95 84 79
5 x 50 19 8.8 1.4 1.6 2.2 43 5420 112 99 95
5 x 70 19 10.6 1.4 1.7 2.3 48 7000 137 123 120
5 x 95 19 12.4 1.6 1.9 2.5 56 9390 164 148 148
5 x 120 37 14.0 1.6 2.0 2.7 61 11260 186 170 171
5 x 150 37 15.5 1.8 2.1 2.8 66 13520 207 190 193
5 x 185 37 17.4 2.0 2.3 3.0 73 16670 233 216 221
5 x 240 61 20.3 2.2 2.5 3.3 83 21310 268 250 261
5 x 300 61 22.7 2.4 2.7 3.5 92 26260 298 281 295
5 x 400 61 25.4 2.6 3.0 3.9 102 32940 331 314 334
5 x 500 61 28.8 2.8 3.2 4.2 114 41080 364 348 375
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Aluminium Conductor, PVC Insulated Lead Sheathed Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC or PE)
1-Core AL/PVC/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Lead Sheath Outer Sheath Overall Cable
Area Strands
Diameter Thickness Thickness Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
1 x 10 7 3.9 1.0 1.2 1.4 15 620
1 x 16 7 4.7 1.0 1.2 1.4 15 690
1 x 25 7 6.3 1.2 1.2 1.4 17 840
1 x 35 7 7.4 1.2 1.2 1.4 19 940
1 x 50 19 8.8 1.4 1.2 1.5 20 1100
1 x 70 19 10.6 1.4 1.2 1.5 22 1270
1 x 95 19 12.4 1.6 1.2 1.6 25 1510
1 x 120 37 14 1.6 1.2 1.7 26 1700
1 x 150 37 15.5 1.8 1.2 1.7 28 1910
1 x 185 37 17.4 2.0 1.3 1.8 31 2290
1 x 240 61 19.9 2.2 1.4 1.9 34 2800
1 x 300 61 22.2 2.4 1.5 2.0 38 3340
1 x 400 61 25.2 2.6 1.6 2.1 42 4090
1 x 500 61 28.6 2.8 1.6 2.2 46 4760
1 x 630 91 32.6 2.8 1.7 2.3 50 5740
1 x 800 91 36.7 2.8 1.8 2.5 55 6930
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced Flat Touching
Trefoil [Gd] Touching in Three Trefoil [Air]
Area Duct [Gd] Ducts [Gd] [Gd] [Air] [Air]
[Gd] Ducts [Gd]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps
1 x 10 39 37 38 40 40 37 31 39 32
1 x 16 50 47 48 51 52 47 40 51 41
1 x 25 65 61 63 66 67 61 54 68 56
1 x 35 77 73 76 79 80 73 67 83 69
1 x 50 91 85 88 93 94 86 80 99 82
1 x 70 111 105 108 113 115 105 100 125 103
1 x 95 133 126 129 135 138 126 124 154 128
1 x 120 150 143 148 153 156 144 143 176 147
1 x 150 168 160 165 171 174 160 163 200 167
1 x 185 191 182 188 194 197 182 189 231 195
1 x 240 221 211 218 224 226 210 224 272 231
1 x 300 249 239 249 253 253 237 260 312 267
1 x 400 283 272 285 287 285 268 304 359 311
1 x 500 321 310 325 325 319 301 353 412 360
1 x 630 362 350 368 364 353 333 408 468 415
1 x 800 402 389 416 402 384 363 464 519 469
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (2 & 3 Cores) - Aluminium Conductor, PVC Insulated Lead Sheathed Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC or PE)
2-Cores AL/PVC/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Lead Sheath Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Thickness Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
2 x 10 7 3.9 1.0 1.2 1.8 21 1130 41 36 30
2 x 16 7 4.7 1.0 1.2 1.8 23 1290 54 47 40
2 x 25 7 6.3 1.2 1.2 1.8 27 1680 70 61 54
2 x 35 7 7.4 1.2 1.3 1.8 29 2020 84 73 66
2 x 50 19 8.8 1.4 1.4 1.9 33 2550 100 88 80
2 x 70 19 10.6 1.4 1.5 2.0 37 3180 123 108 101
2 x 95 19 12.4 1.6 1.6 2.1 42 4080 146 131 123
2 x 120 37 14 1.6 1.7 2.2 46 4780 167 150 143
2 x 150 37 15.5 1.8 1.8 2.4 50 5660 187 168 162
2 x 185 37 17.4 2.0 1.9 2.5 56 6840 212 192 187
2 x 240 61 19.9 2.2 2.1 2.7 62 8570 245 225 221
2 x 300 61 22.2 2.4 2.2 2.9 69 10270 276 255 253
2 x 400 61 25.2 2.6 2.4 3.2 77 12660 315 294 294
2 x 500 61 28.6 2.8 2.6 3.4 86 15600 358 336 340
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC or PE)
3-Cores AL/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Lead Sheath Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Thickness Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
3 x 10 7 3.9 1.0 1.2 1.8 22 1230 36 30 27
3 x 16 7 4.7 1.0 1.2 1.8 24 1410 46 40 35
3 x 25 7 6.3 1.2 1.2 1.8 28 1850 60 52 47
3 x 35 7 7.4 1.2 1.3 1.8 31 2130 71 61 56
3 x 50 19 8.8 1.4 1.4 1.9 36 2670 84 74 69
3 x 70 19 10.6 1.4 1.5 2.1 40 3400 103 91 86
3 x 95 19 12.4 1.6 1.6 2.2 46 4270 123 110 106
3 x 120 37 14 1.6 1.7 2.3 50 4990 140 126 123
3 x 150 37 15.5 1.8 1.9 2.5 55 6150 156 142 139
3 x 185 37 17.4 2.0 2.0 2.6 60 7300 177 161 161
3 x 240 61 19.9 2.2 2.2 2.9 68 9230 205 189 189
3 x 300 61 22.2 2.4 2.3 3.0 74 10860 231 214 217
3 x 400 61 25.2 2.6 2.5 3.3 82 13350 262 245 251
3 x 500 61 28.6 2.8 2.7 3.6 92 16410 297 280 289
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (3½ & 4 Cores) - Aluminium Conductor, PVC Insulated Lead Sheathed Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC or PE)
3½ Cores AL/PVC/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Nominal Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
[Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne]
Lead Sheath Outer Sheath Overall
Weight
Area* Diameter** Amps Amps Amps
Thickness Thickness
mm² No. mm mm mm mm mm kg/km
3x16+10 7/7 4.7 / 3.9 1.0 / 1.0 1.2 1.8 25 1540 46 40 36
3x25+16 7/7 6.3 / 4.7 1.2 / 1.0 1.3 1.8 30 2070 60 52 48
3x35+16 7/7 6.5 / 4.7 1.2 / 1.0 1.3 1.8 30 2090 70 61 55
3x50+25 7/7 7.5 / 6.3 1.4 / 1.2 1.5 2.0 35 2790 83 73 68
3x70+35 14 / 7 9.1 / 7.4 1.4 / 1.2 1.6 2.1 39 3450 101 90 84
3x95+50 19 / 19 10.8 / 8.8 1.6 / 1.4 1.7 2.3 44 4330 121 108 103
3x120+70 19 / 19 12.2 / 10.6 1.6 / 1.4 1.8 2.4 48 5120 138 124 119
3x150+70 37 / 19 13.5 / 10.6 1.8 / 1.4 1.9 2.5 52 5970 154 140 136
3x185+95 37 / 19 15.2 / 12.4 2.0 / 1.6 2.0 2.7 57 7130 175 160 156
3x240+120 37 / 37 17.5 / 14 2.2 / 1.6 2.2 2.9 64 8930 202 186 184
3x300+150 37 / 37 19.6 / 15.5 2.4 / 1.8 2.4 3.1 70 10780 228 211 211
3x400+185 61 / 37 22.5 / 17.4 2.6 / 2.0 2.6 3.4 79 13410 260 242 245
3x500+240 61 / 61 25.6 / 19.9 2.8 / 2.2 2.8 3.7 86 16260 294 276 282
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC or PE)
4-Cores AL/PVC/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of Nominal Outer
Conductor Insulation Lead Sheath Sheath Thickness
Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Thickness Diameter** Weight
mm² No. mm mm mm mm mm kg/km
4 x 10 7 3.9 1.0 1.2 1.8 24 1380 36 31 27
4 x 16 7 4.7 1.0 1.2 1.8 26 1600 47 40 36
4 x 25 7 6.3 1.2 1.3 1.8 31 2220 61 53 49
4 x 35 7 6.5 1.2 1.4 1.9 32 2320 70 62 56
4 x 50 7 7.5 1.4 1.5 2.0 37 2980 83 73 68
4 x 70 14 9.1 1.4 1.6 2.2 41 3650 102 90 85
4 x 95 19 10.8 1.6 1.8 2.4 46 4740 122 109 104
4 x 120 19 12.2 1.6 1.9 2.5 50 5560 138 125 121
4 x 150 37 13.5 1.8 2.0 2.7 55 6600 155 141 137
4 x 185 37 15.2 2.0 2.1 2.8 60 7870 175 160 157
4 x 240 37 17.5 2.2 2.3 3.1 67 9810 203 187 186
4 x 300 37 19.6 2.4 2.5 3.3 73 11820 229 213 213
4 x 400 61 22.5 2.6 2.8 3.6 83 15000 261 245 248
4 x 500 61 25.6 2.8 3.0 3.9 91 18100 296 279 285
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (5 Cores) - Aluminium Conductor, PVC Insulated Lead Sheathed Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Shield : Extruded Lead Alloy Sheath
Oversheath : Extruded Material (PVC or PE)
5-Cores AL/PVC/Lead/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Lead Sheath Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Thickness Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
5 x 10 7 3.9 1.0 1.2 1.8 26 1560 36 31 28
5 x 16 7 4.7 1.0 1.3 1.8 28 1900 47 41 37
5 x 25 7 6.3 1.2 1.4 1.9 34 2670 61 53 50
5 x 35 7 7.4 1.2 1.5 2.0 37 3110 73 64 61
5 x 50 19 8.8 1.4 1.6 2.2 43 3990 87 77 74
5 x 70 19 10.6 1.4 1.7 2.3 48 4970 106 95 93
5 x 95 19 12.4 1.6 1.9 2.5 56 6540 127 115 115
5 x 120 37 14 1.6 2.0 2.7 61 7660 145 132 133
5 x 150 37 15.5 1.8 2.1 2.8 66 9090 162 148 151
5 x 185 37 17.4 2.0 2.3 3.0 73 11100 184 170 174
5 x 240 61 19.9 2.2 2.5 3.3 82 13820 213 198 206
5 x 300 61 22.2 2.4 2.7 3.5 91 16780 239 224 236
5 x 400 61 25.2 2.6 3.0 3.9 101 20930 271 256 273
5 x 500 61 28.6 2.8 3.2 4.2 113 25570 306 291 313
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Copper Conductor, XLPE Insulated Armored Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Armor : Aluminium Wires
Oversheath : Extruded Material (PVC, LSF or PE)
1-Core CU/XLPE/AWA/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
1 x 120 37 14.0 1.2 1.6 1.7 25 1610
1 x 150 37 15.5 1.4 1.6 1.7 27 1910
1 x 185 37 17.4 1.6 1.6 1.8 30 2330
1 x 240 61 20.3 1.7 1.6 1.9 33 2950
1 x 300 61 22.7 1.8 1.6 1.9 36 3590
1 x 400 61 25.4 2.0 2.0 2.1 40 4650
1 x 500 61 28.8 2.2 2.0 2.2 44 5800
1 x 630 61 30.4 2.4 2.0 2.3 47 7110
1 x 800 61 33.7 2.6 2.5 2.5 52 9120
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced Flat Touching
Trefoil [Gd] Touching in Three Trefoil [Air]
Area Duct [Gd] Ducts [Gd] [Gd] [Air] [Air]
[Gd] Ducts [Gd]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps
1 x 120 239 227 233 242 237 217 295 352 301
1 x 150 267 253 262 269 260 240 336 395 341
1 x 185 298 284 295 299 286 264 386 444 391
1 x 240 340 325 339 339 318 295 453 508 456
1 x 300 376 360 378 372 343 319 514 561 514
1 x 400 410 393 415 399 356 333 574 596 566
1 x 500 447 430 458 431 379 354 644 650 629
1 x 630 482 464 500 460 398 374 705 694 682
1 x 800 497 480 527 468 404 382 745 719 711
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (2 & 3 Cores) - Copper Conductor, XLPE Insulated Armored Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC, LSF or PE)
2-Cores CU/XLPE/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
2 x 1.5 7 1.6 0.7 0.8 1.8 14 350 25 21 21
2 x 2.5 7 2.0 0.7 0.8 1.8 15 400 33 27 28
2x4 7 2.6 0.7 0.8 1.8 16 470 42 36 37
2x6 7 3.1 0.7 0.8 1.8 17 550 53 45 47
2 x 10 7 4.0 0.7 1.3 1.8 20 840 71 60 66
2 x 16 7 5.0 0.7 1.3 1.8 22 1060 91 77 87
2 x 25 7 6.3 0.9 1.6 1.8 26 1570 118 101 116
2 x 35 7 7.4 0.9 1.6 1.8 28 1900 141 121 142
2 x 50 19 8.8 1.0 1.6 1.8 31 2330 167 144 172
2 x 70 19 10.6 1.1 1.6 2.0 36 3040 204 179 217
2 x 95 19 12.4 1.1 2.0 2.1 41 4160 244 215 266
2 x 120 37 14.0 1.2 2.0 2.2 45 4970 277 246 308
2 x 150 37 15.5 1.4 2.0 2.3 49 5890 309 276 349
2 x 185 37 17.4 1.6 2.5 2.5 55 7630 347 313 399
2 x 240 61 20.3 1.7 2.5 2.7 61 9500 398 362 469
2 x 300 61 22.7 1.8 2.5 2.8 67 11420 444 407 532
2 x 400 61 25.4 2.0 2.5 3.1 74 13990 494 456 603
2 x 500 61 28.8 2.2 3.2 3.3 83 18210 546 508 682
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC, LSF or PE)
3-Cores CU/XLPE/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
3 x 1.5 7 1.6 0.7 0.8 1.8 15 370 21 18 18
3 x 2.5 7 2.0 0.7 0.8 1.8 16 440 28 23 24
3x4 7 2.6 0.7 0.8 1.8 17 520 36 30 32
3x6 7 3.1 0.7 0.8 1.8 18 620 45 37 41
3 x 10 7 4.0 0.7 1.3 1.8 21 960 60 50 56
3 x 16 7 5.0 0.7 1.3 1.8 23 1230 77 65 74
3 x 25 7 6.3 0.9 1.6 1.8 27 1830 99 84 99
3 x 35 7 7.4 0.9 1.6 1.8 30 2140 117 101 119
3 x 50 19 8.8 1.0 1.6 1.9 33 2650 138 120 144
3 x 70 19 10.6 1.1 2.0 2.0 39 3780 168 148 181
3 x 95 19 12.4 1.1 2.0 2.2 43 4800 200 177 221
3 x 120 37 14.0 1.2 2.0 2.3 47 5740 227 201 255
3 x 150 37 15.5 1.4 2.5 2.5 53 7340 252 227 289
3 x 185 37 17.4 1.6 2.5 2.6 58 8820 282 256 329
3 x 240 61 20.3 1.7 2.5 2.8 66 11090 322 294 385
3 x 300 61 22.7 1.8 2.5 3.0 72 13340 357 328 434
3 x 400 61 25.4 2.0 2.5 3.2 79 16420 394 364 488
3 x 500 61 28.8 2.2 3.2 3.5 90 21450 426 399 542
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (3½ & 4 Cores) - Copper Conductor, XLPE Insulated Armored Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC, LSF or PE)
3½ Cores CU/XLPE/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Nominal Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
[Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne]
Armor Wire Outer Sheath Overall
Weight
Area* Diameter** Amps Amps Amps
Diameter Thickness
mm² No. mm mm mm mm mm kg/km
3x16+10 7/7 5/4 0.7 / 0.7 1.3 1.8 24 1360 77 65 76
3x25+16 7/7 6.3 / 5 0.9 / 0.7 1.6 1.8 28 2030 99 85 101
3x35+16 7/7 6.6 / 5 0.9 / 0.7 1.6 1.8 28 2180 115 99 116
3x50+25 19 / 7 7.5 / 6.3 1.0 / 0.9 1.6 1.9 32 2770 137 119 141
3x70+35 19 / 7 9.1 / 7.4 1.1 / 0.9 2.0 2.1 37 3950 166 146 177
3x95+50 19 / 19 11 / 8.8 1.1 / 1.0 2.0 2.2 41 5000 199 175 216
3x120+70 37 / 19 12.2 / 10.6 1.2 / 1.1 2.0 2.4 45 6100 225 200 249
3x150+70 37 / 19 13.8 / 10.6 1.4 / 1.1 2.5 2.5 50 7660 251 224 283
3x185+95 37 / 19 15.1 / 12.4 1.6 / 1.1 2.5 2.7 55 9300 281 254 322
3x240+120 61 / 37 17.6 / 14 1.7 / 1.2 2.5 2.9 61 11600 321 293 375
3x300+150 61 / 37 19.8 / 15.5 1.8 / 1.4 2.5 3.0 66 13920 357 326 424
3x400+185 61 / 37 22.2 / 17.4 2.0 / 1.6 3.2 3.3 75 18120 395 365 482
3x500+240 61 / 61 26.3 / 20.3 2.2 / 1.7 3.2 3.6 83 22510 431 402 537
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC, LSF or PE)
4-Cores CU/XLPE/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of Nominal Outer
Conductor Insulation Armor Wire Sheath Thickness
Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Diameter Diameter** Weight
mm² No. mm mm mm mm mm kg/km
4 x 1.5 7 1.6 0.7 0.8 1.8 15 410 21 18 19
4 x 2.5 7 2.0 0.7 0.8 1.8 16 490 28 23 25
4x4 7 2.6 0.7 0.8 1.8 18 600 36 30 33
4x6 7 3.1 0.7 1.3 1.8 20 860 45 38 42
4 x 10 7 4.0 0.7 1.3 1.8 22 1110 60 50 58
4 x 16 7 5.0 0.7 1.6 1.8 25 1600 78 66 77
4 x 25 7 6.3 0.9 1.6 1.8 29 2190 100 86 102
4 x 35 7 6.6 0.9 1.6 1.9 30 2400 116 100 118
4 x 50 19 7.5 1.0 1.6 2.0 33 3020 137 119 142
4 x 70 19 9.1 1.1 2.0 2.2 39 4330 168 148 179
4 x 95 19 11.0 1.1 2.0 2.3 43 5500 200 177 219
4 x 120 37 12.2 1.2 2.5 2.5 48 7090 226 202 252
4 x 150 37 13.8 1.4 2.5 2.6 53 8490 253 227 288
4 x 185 37 15.1 1.6 2.5 2.8 57 10220 283 257 326
4 x 240 61 17.6 1.7 2.5 3.0 64 12870 323 296 381
4 x 300 61 19.8 1.8 2.5 3.2 69 15560 359 329 430
4 x 400 61 22.2 2.0 3.2 3.5 79 20360 398 369 488
4 x 500 61 26.3 2.2 3.2 3.8 87 25070 436 407 546
2
*Sectoral Shape for conductor size > 25 mm
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (5 Cores) - Copper Conductor, XLPE Insulated Armored Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC, LSF or PE)
5-Cores CU/XLPE/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
5 x 1.5 7 1.6 0.7 0.8 1.8 16 460 22 18 19
5 x 2.5 7 2.0 0.7 0.8 1.8 17 560 28 24 25
5x4 7 2.6 0.7 1.3 1.8 20 830 37 31 34
5x6 7 3.1 0.7 1.3 1.8 21 980 46 38 43
5 x 10 7 4.0 0.7 1.3 1.8 24 1290 61 52 59
5 x 16 7 5.0 0.7 1.6 1.8 27 1860 79 67 79
5 x 25 7 6.3 0.9 1.6 1.8 32 2580 101 88 106
5 x 35 7 7.4 0.9 1.6 1.9 35 3090 121 105 129
5 x 50 19 8.8 1.0 2.0 2.1 41 4250 143 125 158
5 x 70 19 10.6 1.1 2.0 2.3 46 5620 174 154 197
5 x 95 19 12.4 1.1 2.5 2.4 53 7700 208 186 243
5 x 120 37 14.0 1.2 2.5 2.6 58 9320 234 211 279
5 x 150 37 15.5 1.4 2.5 2.8 64 11060 260 237 316
5 x 185 37 17.4 1.6 2.5 3.0 71 13540 290 266 359
5 x 240 61 20.3 1.7 2.5 3.2 79 17030 329 304 418
5 x 300 61 22.7 1.8 3.2 3.4 89 21760 358 335 468
5 x 400 61 25.4 2.0 3.2 3.8 98 26950 391 367 521
5 x 500 61 28.8 2.2 3.2 4.1 109 33430 423 401 578
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Aluminium Conductor, XLPE Insulated Armored Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Armor : Aluminium Wires
Oversheath : Extruded Material (PVC, LSF or PE)
1-Core AL/XLPE/AWA/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
1 x 120 37 14 1.2 1.6 1.7 25 890
1 x 150 37 15.5 1.4 1.6 1.7 27 1030
1 x 185 37 17.4 1.6 1.6 1.8 30 1220
1 x 240 61 19.9 1.7 1.6 1.9 33 1480
1 x 300 61 22.2 1.8 1.6 1.9 35 1730
1 x 400 61 25.2 2.0 2.0 2.1 40 2270
1 x 500 61 28.6 2.2 2.0 2.2 44 2730
1 x 630 91 32.6 2.4 2.0 2.3 49 3360
1 x 800 91 36.7 2.6 2.5 2.5 55 4330
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced Flat Touching
Trefoil [Gd] Touching in Three Trefoil [Air]
Area Duct [Gd] Ducts [Gd] [Gd] [Air] [Air]
[Gd] Ducts [Gd]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps
1 x 120 187 178 183 190 189 173 231 281 237
1 x 150 209 198 205 212 209 193 263 317 269
1 x 185 236 225 233 238 233 215 305 361 311
1 x 240 271 259 269 273 262 244 360 417 366
1 x 300 303 289 302 303 288 268 410 466 415
1 x 400 338 324 338 334 308 288 472 513 472
1 x 500 377 363 379 370 334 313 542 571 537
1 x 630 418 403 426 405 360 339 618 633 607
1 x 800 444 430 458 425 377 356 676 677 656
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (2 & 3 Cores) - Aluminium Conductor, XLPE Insulated Armored Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC, LSF or PE)
2-Cores AL/XLPE/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
2 x 10 7 3.9 0.7 1.3 1.8 19 680 54 46 50
2 x 16 7 4.7 0.7 1.3 1.8 21 800 70 59 66
2 x 25 7 6.3 0.9 1.6 1.8 25 1230 91 78 89
2 x 35 7 7.4 0.9 1.6 1.8 28 1440 109 94 110
2 x 50 19 8.8 1.0 1.6 1.8 31 1720 130 112 133
2 x 70 19 10.6 1.1 1.6 2.0 35 2190 158 139 167
2 x 95 19 12.4 1.1 2.0 2.1 40 2990 190 167 206
2 x 120 37 14 1.2 2.0 2.2 44 3500 216 191 239
2 x 150 37 15.5 1.4 2.0 2.3 48 4060 241 215 271
2 x 185 37 17.4 1.6 2.5 2.5 54 5330 272 246 312
2 x 240 61 19.9 1.7 2.5 2.7 60 6430 315 285 368
2 x 300 61 22.2 1.8 2.5 2.8 66 7550 353 323 421
2 x 400 61 25.2 2.0 2.5 3.1 73 9090 401 370 487
2 x 500 61 28.6 2.2 3.2 3.3 83 11890 454 423 565
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC, LSF or PE)
3-Cores AL/XLPE/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
3 x 10 7 3.9 0.7 1.3 1.8 20 740 46 38 43
3 x 16 7 4.7 0.7 1.3 1.8 22 880 59 49 56
3 x 25 7 6.3 0.9 1.6 1.8 27 1350 77 65 77
3 x 35 7 7.4 0.9 1.6 1.8 30 1490 90 78 92
3 x 50 19 8.8 1.0 1.6 1.9 33 1790 107 93 111
3 x 70 19 10.6 1.1 2.0 2.0 39 2560 131 115 141
3 x 95 19 12.4 1.1 2.0 2.2 43 3090 156 138 172
3 x 120 37 14 1.2 2.0 2.3 47 3590 177 158 199
3 x 150 37 15.5 1.4 2.5 2.5 53 4680 198 178 226
3 x 185 37 17.4 1.6 2.5 2.6 58 5480 223 202 260
3 x 240 61 19.9 1.7 2.5 2.8 65 6620 257 235 305
3 x 300 61 22.2 1.8 2.5 3.0 71 7690 288 265 348
3 x 400 61 25.2 2.0 2.5 3.2 79 9210 325 301 401
3 x 500 61 28.6 2.2 3.2 3.5 89 12190 361 338 456
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (3½ & 4 Cores) - Aluminium Conductor, XLPE Insulated Armored Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC, LSF or PE)
3½ Cores AL/XLPE/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Nominal Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
[Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne]
Armor Wire Outer Sheath Overall
Weight
Area* Diameter** Amps Amps Amps
Diameter Thickness
mm² No. mm mm mm mm mm kg/km
3x16+10 7/7 4.7 / 3.9 0.7 / 0.7 1.3 1.8 23 970 59 50 58
3x25+16 7/7 6.3 / 4.7 0.9 / 0.7 1.6 1.8 28 1440 77 66 78
3x35+16 7/7 6.5 / 4.7 0.9 / 0.7 1.6 1.8 28 1450 89 77 90
3x50+25 7/7 7.5 / 6.3 1.0 / 0.9 1.6 1.9 32 1770 106 92 109
3x70+35 14 / 7 9.1 / 7.4 1.1 / 0.9 2.0 2.1 37 2490 129 113 137
3x95+50 19 / 19 10.8 / 8.8 1.1 / 1.0 2.0 2.2 41 2980 155 136 168
3x120+70 19 / 19 12.2 / 10.6 1.2 / 1.1 2.0 2.4 45 3510 176 156 194
3x150+70 37 / 19 13.5 / 10.6 1.4 / 1.1 2.5 2.5 50 4530 196 176 221
3x185+95 37 / 19 15.2 / 12.4 1.6 / 1.1 2.5 2.7 55 5340 221 200 253
3x240+120 37 / 37 17.5 / 14 1.7 / 1.2 2.5 2.9 61 6430 255 232 297
3x300+150 37 / 37 19.6 / 15.5 1.8 / 1.4 2.5 3.0 66 7430 286 262 339
3x400+185 61 / 37 22.5 / 17.4 2.0 / 1.6 3.2 3.3 75 9860 323 298 393
3x500+240 61 / 61 25.6 / 19.9 2.2 / 1.7 3.2 3.6 83 11880 362 338 448
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC, LSF or PE)
4-Cores AL/XLPE/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of Nominal Outer
Conductor Insulation Armor Wire Sheath Thickness
Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Diameter Diameter** Weight
mm² No. mm mm mm mm mm kg/km
4 x 10 7 3.9 0.7 1.3 1.8 21 850 46 39 44
4 x 16 7 4.7 0.7 1.6 1.8 24 1130 60 51 58
4 x 25 7 6.3 0.9 1.6 1.8 29 1560 78 67 79
4 x 35 7 6.5 0.9 1.6 1.9 30 1550 90 78 92
4 x 50 7 7.5 1.0 1.6 2.0 33 1880 106 92 110
4 x 70 14 9.1 1.1 2.0 2.2 39 2650 130 115 139
4 x 95 19 10.8 1.1 2.0 2.3 43 3190 156 138 170
4 x 120 19 12.2 1.2 2.5 2.5 48 4180 177 158 197
4 x 150 37 13.5 1.4 2.5 2.6 53 4860 198 178 225
4 x 185 37 15.2 1.6 2.5 2.8 57 5700 223 202 256
4 x 240 37 17.5 1.7 2.5 3.0 64 6930 257 235 302
4 x 300 37 19.6 1.8 2.5 3.2 69 8080 288 264 343
4 x 400 61 22.5 2.0 3.2 3.5 79 10820 325 301 397
4 x 500 61 25.6 2.2 3.2 3.8 87 12850 366 342 455
2
*Sectoral Shape for conductor size > 25 mm
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (5 Cores) - Aluminium Conductor, XLPE Insulated Armored Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC, LSF or PE)
5-Cores AL/XLPE/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
5 x 10 7 3.9 0.7 1.3 1.8 23 960 47 39 45
5 x 16 7 4.7 0.7 1.6 1.8 26 1290 60 52 60
5 x 25 7 6.3 0.9 1.6 1.8 31 1800 78 67 82
5 x 35 7 7.4 0.9 1.6 1.9 35 2030 94 82 100
5 x 50 19 8.8 1.0 2.0 2.1 41 2830 111 97 123
5 x 70 19 10.6 1.1 2.0 2.3 46 3580 136 120 154
5 x 95 19 12.4 1.1 2.5 2.4 53 4850 162 145 190
5 x 120 37 14 1.2 2.5 2.6 58 5720 184 166 219
5 x 150 37 15.5 1.4 2.5 2.8 64 6630 205 187 249
5 x 185 37 17.4 1.6 2.5 3.0 71 7970 231 212 285
5 x 240 61 19.9 1.7 2.5 3.2 78 9600 265 244 334
5 x 300 61 22.2 1.8 3.2 3.4 87 12360 293 273 379
5 x 400 61 25.2 2.0 3.2 3.8 97 14940 328 308 433
5 x 500 61 28.6 2.2 3.2 4.1 108 17990 364 345 492
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Copper Conductor, PVC Insulated Armored Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Armor : Aluminium Wires
Oversheath : Extruded Material (PVC or PE)
1-Core CU/PVC/AWA/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
1 x 120 37 14.0 1.6 1.6 1.7 26 1700
1 x 150 37 15.5 1.8 1.6 1.7 28 2010
1 x 185 37 17.4 2.0 1.6 1.8 31 2450
1 x 240 61 20.3 2.2 1.6 1.9 34 3110
1 x 300 61 22.7 2.4 2.0 2.0 38 3910
1 x 400 61 25.4 2.6 2.0 2.1 42 4880
1 x 500 61 28.8 2.8 2.0 2.2 46 6080
1 x 630 61 30.4 2.8 2.0 2.4 48 7360
1 x 800 61 33.7 2.8 2.5 2.5 53 9330
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced Flat Touching
Trefoil [Gd] Touching in Three Trefoil [Air]
Area Duct [Gd] Ducts [Gd] [Gd] [Air] [Air]
[Gd] Ducts [Gd]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps
1 x 120 190 180 187 192 187 172 181 215 185
1 x 150 211 201 207 213 205 189 206 241 209
1 x 185 236 225 233 236 224 208 236 270 239
1 x 240 269 257 267 267 248 230 276 306 277
1 x 300 293 280 296 287 259 242 310 330 307
1 x 400 322 309 327 312 277 260 349 361 343
1 x 500 350 337 360 336 294 276 390 393 380
1 x 630 375 362 393 357 308 290 423 416 409
1 x 800 385 372 408 363 314 297 447 436 427
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (2 & 3 Cores) - Copper Conductor, PVC Insulated Armored Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC or PE)
2-Cores CU/PVC/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
2 x 1.5 7 1.6 0.8 0.8 1.8 15 370 20 17 13
2 x 2.5 7 2.0 0.8 0.8 1.8 15 430 26 22 18
2x4 7 2.6 1.0 0.8 1.8 17 540 33 28 23
2x6 7 3.1 1.0 1.3 1.8 19 760 42 36 30
2 x 10 7 4.0 1.0 1.3 1.8 21 930 55 47 41
2 x 16 7 5.0 1.0 1.3 1.8 23 1150 72 61 54
2 x 25 7 6.3 1.2 1.6 1.8 27 1700 92 80 71
2 x 35 7 7.4 1.2 1.6 1.8 29 2040 111 96 87
2 x 50 19 8.8 1.4 1.6 1.9 33 2550 131 114 106
2 x 70 19 10.6 1.4 2.0 2.0 38 3480 161 142 134
2 x 95 19 12.4 1.6 2.0 2.2 43 4500 191 170 163
2 x 120 37 14.0 1.6 2.0 2.3 46 5310 217 194 188
2 x 150 37 15.5 1.8 2.5 2.4 51 6660 242 219 214
2 x 185 37 17.4 2.0 2.5 2.6 57 8070 272 248 245
2 x 240 61 20.3 2.2 2.5 2.8 64 10050 312 286 288
2 x 300 61 22.7 2.4 2.5 2.9 70 12140 347 320 325
2 x 400 61 25.4 2.6 2.5 3.2 77 14790 385 358 368
2 x 500 61 28.8 2.8 3.2 3.4 86 19210 424 398 414
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC or PE)
3-Cores CU/PVC/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
3 x 1.5 7 1.6 0.8 0.8 1.8 15 400 17 14 11
3 x 2.5 7 2.0 0.8 0.8 1.8 16 470 22 18 15
3x4 7 2.6 1.0 1.3 1.8 19 740 28 24 20
3x6 7 3.1 1.0 1.3 1.8 20 840 35 30 26
3 x 10 7 4.0 1.0 1.3 1.8 22 1060 47 40 35
3 x 16 7 5.0 1.0 1.3 1.8 24 1350 61 52 46
3 x 25 7 6.3 1.2 1.6 1.8 29 1980 78 68 62
3 x 35 7 7.4 1.2 1.6 1.8 31 2290 92 80 74
3 x 50 19 8.8 1.4 1.6 2.0 35 2890 109 95 89
3 x 70 19 10.6 1.4 2.0 2.1 40 4020 133 117 112
3 x 95 19 12.4 1.6 2.0 2.2 45 5150 158 141 137
3 x 120 37 14.0 1.6 2.0 2.3 49 6060 179 161 158
3 x 150 37 15.5 1.8 2.5 2.5 55 7730 199 180 180
3 x 185 37 17.4 2.0 2.5 2.7 60 9310 222 202 204
3 x 240 61 20.3 2.2 2.5 2.9 68 11700 253 233 238
3 x 300 61 22.7 2.4 2.5 3.1 75 14120 280 259 268
3 x 400 61 25.4 2.6 3.2 3.4 83 18250 305 285 299
3 x 500 61 28.8 2.8 3.2 3.6 92 22500 332 312 333
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (3½ & 4 Cores) - Copper Conductor, PVC Insulated Armored Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC or PE)
3½ Cores CU/PVC/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Nominal Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
[Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne]
Armor Wire Outer Sheath Overall
Weight
Area* Diameter** Amps Amps Amps
Diameter Thickness
mm² No. mm mm mm mm mm kg/km
3x16+10 7/7 5/4 1.0 / 1.0 1.6 1.8 26 1650 61 53 47
3x25+16 7/7 6.3 / 5 1.2 / 1.0 1.6 1.8 30 2220 79 68 63
3x35+16 7/7 6.6 / 5 1.2 / 1.0 1.6 1.9 30 2370 91 79 73
3x50+25 19 / 7 7.5 / 6.3 1.4 / 1.2 2.0 2.0 35 3260 108 95 89
3x70+35 19 / 7 9.1 / 7.4 1.4 / 1.2 2.0 2.1 39 4200 132 116 110
3x95+50 19 / 19 11 / 8.8 1.6 / 1.4 2.0 2.3 44 5420 157 140 135
3x120+70 37 / 19 12.2 / 10.6 1.6 / 1.4 2.5 2.5 49 6980 178 160 156
3x150+70 37 / 19 13.8 / 10.6 1.8 / 1.4 2.5 2.6 52 8120 198 178 175
3x185+95 37 / 19 15.1 / 12.4 2.0 / 1.6 2.5 2.7 57 9800 222 202 200
3x240+120 61 / 37 17.6 / 14 2.2 / 1.6 2.5 2.9 63 12260 252 230 232
3x300+150 61 / 37 19.8 / 15.5 2.4 / 1.8 2.5 3.1 69 14790 280 257 263
3x400+185 61 / 37 22.2 / 17.4 2.6 / 2.0 3.2 3.4 79 19230 309 287 297
3x500+240 61 / 61 26.3 / 20.3 2.8 / 2.2 3.2 3.7 86 23630 336 315 331
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC or PE)
4-Cores CU/PVC/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of Nominal Outer
Conductor Insulation Armor Wire Sheath Thickness
Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Diameter Diameter** Weight
mm² No. mm mm mm mm mm kg/km
4 x 1.5 7 1.6 0.8 0.8 1.8 16 450 17 14 12
4 x 2.5 7 2.0 0.8 0.8 1.8 17 540 22 19 16
4x4 7 2.6 1.0 1.3 1.8 20 830 29 24 21
4x6 7 3.1 1.0 1.3 1.8 21 980 36 30 26
4 x 10 7 4.0 1.0 1.3 1.8 24 1240 48 41 36
4 x 16 7 5.0 1.0 1.6 1.8 27 1750 61 53 48
4 x 25 7 6.3 1.2 1.6 1.8 31 2370 79 68 64
4 x 35 7 6.6 1.2 1.6 1.9 31 2590 92 79 73
4 x 50 19 7.5 1.4 2.0 2.1 37 3600 108 95 90
4 x 70 19 9.1 1.4 2.0 2.2 40 4590 132 117 111
4 x 95 19 11.0 1.6 2.5 2.4 46 6340 158 141 137
4 x 120 37 12.2 1.6 2.5 2.5 50 7540 178 160 157
4 x 150 37 13.8 1.8 2.5 2.7 55 8980 199 181 178
4 x 185 37 15.1 2.0 2.5 2.9 60 10870 223 203 202
4 x 240 61 17.6 2.2 2.5 3.1 66 13610 254 233 236
4 x 300 61 19.8 2.4 2.5 3.3 72 16450 282 260 266
4 x 400 61 22.2 2.6 3.2 3.6 83 21400 312 292 302
4 x 500 61 26.3 2.8 3.2 3.9 90 26330 340 319 336
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (5 Cores) - Copper Conductor, PVC Insulated Armored Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC or PE)
5-Cores CU/PVC/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
5 x 1.5 7 1.6 0.8 0.8 1.8 17 510 17 14 12
5 x 2.5 7 2.0 0.8 0.8 1.8 18 600 22 19 16
5x4 7 2.6 1.0 1.3 1.8 21 950 29 25 21
5x6 7 3.1 1.0 1.3 1.8 23 1120 36 31 27
5 x 10 7 4.0 1.0 1.6 1.8 26 1600 48 41 37
5 x 16 7 5.0 1.0 1.6 1.8 29 2050 62 54 49
5 x 25 7 6.3 1.2 1.6 1.9 33 2830 80 69 65
5 x 35 7 7.4 1.2 2.0 2.0 38 3610 96 84 81
5 x 50 19 8.8 1.4 2.0 2.2 43 4620 113 100 97
5 x 70 19 10.6 1.4 2.0 2.3 48 5960 138 123 122
5 x 95 19 12.4 1.6 2.5 2.5 56 8290 163 148 150
5 x 120 37 14.0 1.6 2.5 2.7 61 9870 185 168 173
5 x 150 37 15.5 1.8 2.5 2.9 66 11800 204 187 194
5 x 185 37 17.4 2.0 2.5 3.0 73 14260 228 210 221
5 x 240 61 20.3 2.2 3.2 3.3 84 18980 256 238 256
5 x 300 61 22.7 2.4 3.2 3.6 92 23100 279 262 285
5 x 400 61 25.4 2.6 3.2 3.9 101 28420 304 287 318
5 x 500 61 28.8 2.8 3.2 4.2 113 35240 329 313 352
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Aluminium Conductor, PVC Insulated Armored Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Armor : Aluminium Wires
Oversheath : Extruded Material (PVC or PE)
1-Core AL/PVC/AWA/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
1 x 120 37 14 1.6 1.6 1.7 26 980
1 x 150 37 15.5 1.8 1.6 1.7 28 1130
1 x 185 37 17.4 2 1.6 1.8 31 1350
1 x 240 61 19.9 2.2 1.6 1.9 34 1640
1 x 300 61 22.2 2.4 2.0 2.0 38 2050
1 x 400 61 25.2 2.6 2.0 2.1 41 2510
1 x 500 61 28.6 2.8 2.0 2.2 46 3010
1 x 630 91 32.6 2.8 2.0 2.4 50 3670
1 x 800 91 36.7 2.8 2.5 2.5 56 4620
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced Flat Touching
Trefoil [Gd] Touching in Three Trefoil [Air]
Area Duct [Gd] Ducts [Gd] [Gd] [Air] [Air]
[Gd] Ducts [Gd]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps
1 x 120 149 142 147 151 150 138 142 172 146
1 x 150 166 158 163 168 165 153 162 194 165
1 x 185 187 179 184 189 184 170 187 220 191
1 x 240 215 206 213 216 206 192 220 253 224
1 x 300 238 228 238 236 221 207 251 279 253
1 x 400 267 256 266 263 241 226 287 310 287
1 x 500 297 286 300 290 261 246 330 346 326
1 x 630 328 316 333 317 280 264 373 381 366
1 x 800 347 336 358 332 294 279 408 412 396
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (2 & 3 Cores) - Aluminium Conductor, PVC Insulated Armored Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC or PE)
2-Cores AL/PVC/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
2 x 10 7 3.9 1.0 1.3 1.8 20 770 42 36 31
2 x 16 7 4.7 1.0 1.3 1.8 22 900 55 47 41
2 x 25 7 6.3 1.2 1.6 1.8 27 1360 72 62 56
2 x 35 7 7.4 1.2 1.6 1.8 29 1580 86 75 68
2 x 50 19 8.8 1.4 1.6 1.9 33 1940 102 89 82
2 x 70 19 10.6 1.4 2.0 2.0 37 2620 125 110 104
2 x 95 19 12.4 1.6 2.0 2.2 42 3310 149 132 126
2 x 120 37 14 1.6 2.0 2.3 46 3810 169 151 147
2 x 150 37 15.5 1.8 2.5 2.4 51 4860 190 171 167
2 x 185 37 17.4 2.0 2.5 2.6 56 5770 214 194 192
2 x 240 61 19.9 2.2 2.5 2.8 62 6970 247 225 226
2 x 300 61 22.2 2.4 2.5 2.9 69 8260 277 255 258
2 x 400 61 25.2 2.6 2.5 3.2 76 9890 314 292 298
2 x 500 61 28.6 2.8 3.2 3.4 86 12880 355 333 345
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC or PE)
3-Cores AL/PVC/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
3 x 10 7 3.9 1.0 1.3 1.8 21 850 36 30 27
3 x 16 7 4.7 1.0 1.3 1.8 23 1000 47 40 35
3 x 25 7 6.3 1.2 1.6 1.8 28 1520 61 52 48
3 x 35 7 7.4 1.2 1.6 1.8 31 1660 72 62 57
3 x 50 19 8.8 1.4 1.6 2.0 35 2020 84 74 69
3 x 70 19 10.6 1.4 2.0 2.1 40 2800 103 91 87
3 x 95 19 12.4 1.6 2.0 2.2 45 3440 123 110 107
3 x 120 37 14 1.6 2.0 2.3 49 3900 140 126 124
3 x 150 37 15.5 1.8 2.5 2.5 55 5070 156 142 141
3 x 185 37 17.4 2.0 2.5 2.7 60 5970 176 160 161
3 x 240 61 19.9 2.2 2.5 2.9 67 7220 203 186 189
3 x 300 61 22.2 2.4 2.5 3.1 74 8460 227 210 216
3 x 400 61 25.2 2.6 3.2 3.4 83 11070 254 237 247
3 x 500 61 28.6 2.8 3.2 3.6 92 13230 283 267 282
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (3½ & 4 Cores) - Aluminium Conductor, PVC Insulated Armored Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC or PE)
3½ Cores AL/PVC/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Nominal Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
[Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne]
Armor Wire Outer Sheath Overall
Weight
Area* Diameter** Amps Amps Amps
Diameter Thickness
mm² No. mm mm mm mm mm kg/km
3x16+10 7/7 4.7 / 3.9 1.0 / 1.0 1.6 1.8 25 1240 47 40 36
3x25+16 7/7 6.3 / 4.7 1.2 / 1.0 1.6 1.8 29 1620 61 53 48
3x35+16 7/7 6.5 / 4.7 1.2 / 1.0 1.6 1.9 30 1640 71 61 56
3x50+25 7/7 7.5 / 6.3 1.4 / 1.2 2.0 2.0 35 2260 84 74 69
3x70+35 14 / 7 9.1 / 7.4 1.4 / 1.2 2.0 2.1 39 2730 103 91 86
3x95+50 19 / 19 10.8 / 8.8 1.6 / 1.4 2.0 2.3 44 3400 122 109 105
3x120+70 19 / 19 12.2 / 10.6 1.6 / 1.4 2.5 2.5 49 4380 139 125 122
3x150+70 37 / 19 13.5 / 10.6 1.8 / 1.4 2.5 2.6 52 4990 155 140 137
3x185+95 37 / 19 15.2 / 12.4 2.0 / 1.6 2.5 2.7 57 5840 175 159 158
3x240+120 37 / 37 17.5 / 14 2.2 / 1.6 2.5 2.9 63 7080 201 184 185
3x300+150 37 / 37 19.6 / 15.5 2.4 / 1.8 2.5 3.1 69 8290 225 207 211
3x400+185 61 / 37 22.5 / 17.4 2.6 / 2.0 3.2 3.4 79 10960 254 236 243
3x500+240 61 / 61 25.6 / 19.9 2.8 / 2.2 3.2 3.7 86 12990 284 266 277
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC or PE)
4-Cores AL/PVC/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of Nominal Outer
Conductor Insulation Armor Wire Sheath Thickness
Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Diameter Diameter** Weight
mm² No. mm mm mm mm mm kg/km
4 x 10 7 3.9 1.0 1.3 1.8 23 970 36 31 27
4 x 16 7 4.7 1.0 1.6 1.8 26 1290 47 41 37
4 x 25 7 6.3 1.2 1.6 1.8 30 1760 61 53 49
4 x 35 7 6.5 1.2 1.6 1.9 31 1750 71 62 57
4 x 50 7 7.5 1.4 2.0 2.1 37 2460 84 74 69
4 x 70 14 9.1 1.4 2.0 2.2 40 2910 103 91 87
4 x 95 19 10.8 1.6 2.5 2.4 46 4030 123 110 106
4 x 120 19 12.2 1.6 2.5 2.5 50 4620 140 125 123
4 x 150 37 13.5 1.8 2.5 2.7 55 5350 156 141 140
4 x 185 37 15.2 2.0 2.5 2.9 60 6350 176 160 159
4 x 240 37 17.5 2.2 2.5 3.1 66 7660 202 185 187
4 x 300 37 19.6 2.4 2.5 3.3 72 8970 227 209 213
4 x 400 61 22.5 2.6 3.2 3.6 83 11870 256 240 247
4 x 500 61 25.6 2.8 3.2 3.9 90 14110 287 269 281
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (5 Cores) - Aluminium Conductor, PVC Insulated Armored Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Armor : Galvanized Steel Wires
Oversheath : Extruded Material (PVC or PE)
5-Cores AL/PVC/SWA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
5 x 10 7 3.9 1.0 1.6 1.8 25 1260 37 31 28
5 x 16 7 4.7 1.0 1.6 1.8 27 1480 48 41 37
5 x 25 7 6.3 1.2 1.6 1.9 33 2050 62 54 51
5 x 35 7 7.4 1.2 2.0 2.0 37 2550 74 65 62
5 x 50 19 8.8 1.4 2.0 2.2 43 3200 88 78 76
5 x 70 19 10.6 1.4 2.0 2.3 48 3920 107 96 95
5 x 95 19 12.4 1.6 2.5 2.5 56 5450 128 116 117
5 x 120 37 14 1.6 2.5 2.7 61 6280 145 132 136
5 x 150 37 15.5 1.8 2.5 2.9 66 7370 161 147 153
5 x 185 37 17.4 2.0 2.5 3.0 73 8690 182 168 176
5 x 240 61 19.9 2.2 3.2 3.3 83 11510 207 193 206
5 x 300 61 22.2 2.4 3.2 3.6 91 13670 230 215 232
5 x 400 61 25.2 2.6 3.2 3.9 101 16400 257 242 266
5 x 500 61 28.6 2.8 3.2 4.2 112 19780 284 271 301
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (2 & 3 Cores) - Copper Conductor, XLPE Insulated Armored Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC, LSF or PE)
2-Cores CU/XLPE/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Tape Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Thickness Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
2 x 1.5 7 1.6 0.7 0.2 1.8 13 260 25 21 21
2 x 2.5 7 2.0 0.7 0.2 1.8 14 310 32 27 28
2x4 7 2.6 0.7 0.2 1.8 15 370 42 35 37
2x6 7 3.1 0.7 0.2 1.8 16 440 53 44 47
2 x 10 7 4.0 0.7 0.2 1.8 18 570 70 59 64
2 x 16 7 5.0 0.7 0.2 1.8 20 760 91 76 84
2 x 25 7 6.3 0.9 0.2 1.8 24 1060 117 99 113
2 x 35 7 7.4 0.9 0.2 1.8 26 1340 140 120 138
2 x 50 19 8.8 1.0 0.2 1.8 29 1710 166 143 168
2 x 70 19 10.6 1.1 0.2 1.9 33 2310 203 176 212
2 x 95 19 12.4 1.1 0.2 2.0 37 3050 242 211 259
2 x 120 37 14.0 1.2 0.5 2.1 42 4130 276 244 303
2 x 150 37 15.5 1.4 0.5 2.3 47 4970 309 275 346
2 x 185 37 17.4 1.6 0.5 2.4 52 6130 348 312 396
2 x 240 61 20.3 1.7 0.5 2.6 58 7800 401 364 467
2 x 300 61 22.7 1.8 0.5 2.7 64 9560 449 411 533
2 x 400 61 25.4 2.0 0.5 3.0 71 11930 504 464 608
2 x 500 61 28.8 2.2 0.5 3.2 79 14940 562 520 691
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC, LSF or PE)
3-Cores CU/XLPE/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
3 x 1.5 7 1.6 0.7 0.2 1.8 14 280 21 18 18
3 x 2.5 7 2.0 0.7 0.2 1.8 15 340 27 23 24
3x4 7 2.6 0.7 0.2 1.8 16 410 36 30 32
3x6 7 3.1 0.7 0.2 1.8 17 500 44 37 40
3 x 10 7 4.0 0.7 0.2 1.8 19 680 59 50 55
3 x 16 7 5.0 0.7 0.2 1.8 21 910 76 64 72
3 x 25 7 6.3 0.9 0.2 1.8 25 1300 98 83 97
3 x 35 7 7.4 0.9 0.2 1.8 27 1540 115 99 115
3 x 50 19 8.8 1.0 0.2 1.8 31 1970 137 118 141
3 x 70 19 10.6 1.1 0.2 1.9 36 2720 167 146 177
3 x 95 19 12.4 1.1 0.2 2.1 40 3600 199 175 217
3 x 120 37 14.0 1.2 0.5 2.2 45 4840 227 202 253
3 x 150 37 15.5 1.4 0.5 2.4 50 5890 254 227 287
3 x 185 37 17.4 1.6 0.5 2.5 55 7200 285 258 329
3 x 240 61 20.3 1.7 0.5 2.7 63 9250 329 299 388
3 x 300 61 22.7 1.8 0.5 2.9 69 11340 367 337 441
3 x 400 61 25.4 2.0 0.5 3.1 76 14190 411 381 501
3 x 500 61 28.8 2.2 0.5 3.3 85 17900 456 425 567
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (3½ & 4 Cores) - Copper Conductor, XLPE Insulated Armored Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC, LSF or PE)
3½ Cores CU/XLPE/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Nominal Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
[Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne]
Armor Wire Outer Sheath Overall
Weight
Area* Diameter** Amps Amps Amps
Diameter Thickness
mm² No. mm mm mm mm mm kg/km
3x16+10 7/7 5/4 0.7 / 0.7 0.2 1.8 22 1030 76 64 73
3x25+16 7/7 6.3 / 5 0.9 / 0.7 0.2 1.8 26 1470 99 84 98
3x35+16 7/7 6.6 / 5 0.9 / 0.7 0.2 1.8 26 1620 114 98 113
3x50+25 19 / 7 7.5 / 6.3 1.0 / 0.9 0.2 1.8 29 2120 135 117 137
3x70+35 19 / 7 9.1 / 7.4 1.1 / 0.9 0.2 2.0 34 2960 165 144 173
3x95+50 19 / 19 11 / 8.8 1.1 / 1.0 0.5 2.1 39 4230 198 175 214
3x120+70 37 / 19 12.2 / 10.6 1.2 / 1.1 0.5 2.3 43 5260 225 199 247
3x150+70 37 / 19 13.8 / 10.6 1.4 / 1.1 0.5 2.4 47 6290 251 224 280
3x185+95 37 / 19 15.1 / 12.4 1.6 / 1.1 0.5 2.6 52 7790 283 254 320
3x240+120 61 / 37 17.6 / 14 1.7 / 1.2 0.5 2.8 58 9930 325 295 375
3x300+150 61 / 37 19.8 / 15.5 1.8 / 1.4 0.5 2.9 63 12120 364 331 427
3x400+185 61 / 37 22.2 / 17.4 2.0 / 1.6 0.5 3.2 71 15250 409 377 491
3x500+240 61 / 61 26.3 / 20.3 2.2 / 1.7 0.5 3.4 78 19240 456 422 555
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC, LSF or PE)
4-Cores CU/XLPE/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of Nominal Outer
Conductor Insulation Armor Wire Sheath Thickness
Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Diameter Diameter** Weight
mm² No. mm mm mm mm mm kg/km
4 x 1.5 7 1.6 0.7 0.2 1.8 15 320 21 18 19
4 x 2.5 7 2.0 0.7 0.2 1.8 16 390 28 23 25
4x4 7 2.6 0.7 0.2 1.8 17 480 36 30 32
4x6 7 3.1 0.7 0.2 1.8 18 590 45 37 41
4 x 10 7 4.0 0.7 0.2 1.8 20 810 59 50 56
4 x 16 7 5.0 0.7 0.2 1.8 23 1110 77 65 75
4 x 25 7 6.3 0.9 0.2 1.8 27 1600 99 84 100
4 x 35 7 6.6 0.9 0.2 1.8 27 1810 115 98 115
4 x 50 19 7.5 1.0 0.2 1.9 31 2340 136 117 140
4 x 70 19 9.1 1.1 0.2 2.0 35 3270 166 145 175
4 x 95 19 11.0 1.1 0.5 2.2 40 4700 199 175 216
4 x 120 37 12.2 1.2 0.5 2.4 45 5810 226 201 249
4 x 150 37 13.8 1.4 0.5 2.5 49 7060 253 226 284
4 x 185 37 15.1 1.6 0.5 2.7 54 8660 284 257 324
4 x 240 61 17.6 1.7 0.5 2.9 60 11110 327 296 380
4 x 300 61 19.8 1.8 0.5 3.1 66 13630 366 335 433
4 x 400 61 22.2 2.0 0.5 3.4 75 17280 412 381 496
4 x 500 61 26.3 2.2 0.8 3.7 84 22470 461 430 566
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (5 Cores) - Copper Conductor, XLPE Insulated Armored Cables
Conductor : Round Stranded Copper
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC, LSF or PE)
5-Cores CU/XLPE/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
5 x 1.5 7 1.6 0.7 0.2 1.8 15 360 21 18 19
5 x 2.5 7 2.0 0.7 0.2 1.8 17 440 28 24 25
5x4 7 2.6 0.7 0.2 1.8 18 560 36 30 33
5x6 7 3.1 0.7 0.2 1.8 20 690 45 38 42
5 x 10 7 4.0 0.7 0.2 1.8 22 960 60 51 58
5 x 16 7 5.0 0.7 0.2 1.8 25 1330 78 66 77
5 x 25 7 6.3 0.9 0.2 1.8 29 1940 100 86 103
5 x 35 7 7.4 0.9 0.2 1.9 33 2380 120 104 127
5 x 50 19 8.8 1.0 0.2 2.0 37 3140 142 124 154
5 x 70 19 10.6 1.1 0.5 2.2 44 4720 175 154 196
5 x 95 19 12.4 1.1 0.5 2.3 50 6250 209 186 241
5 x 120 37 14.0 1.2 0.5 2.5 55 7700 237 213 279
5 x 150 37 15.5 1.4 0.5 2.7 61 9310 265 241 319
5 x 185 37 17.4 1.6 0.5 2.9 68 11560 299 273 365
5 x 240 61 20.3 1.7 0.5 3.1 76 14810 345 319 431
5 x 300 61 22.7 1.8 0.5 3.3 84 18310 385 358 491
5 x 400 61 25.4 2.0 0.8 3.7 95 23970 433 407 562
5 x 500 61 28.8 2.2 0.8 4.0 105 30110 482 457 637
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (2 & 3 Cores) - Aluminium Conductor, XLPE Insulated Armored Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC, LSF or PE)
2-Cores AL/XLPE/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Tape Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Thickness Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
2 x 10 7 3.9 0.7 0.2 1.8 18 430 54 45 49
2 x 16 7 4.7 0.7 0.2 1.8 19 520 69 59 64
2 x 25 7 6.3 0.9 0.2 1.8 23 740 90 77 87
2 x 35 7 7.4 0.9 0.2 1.8 25 890 108 92 106
2 x 50 19 8.8 1.0 0.2 1.8 28 1110 128 109 129
2 x 70 19 10.6 1.1 0.2 1.9 33 1470 158 137 164
2 x 95 19 12.4 1.1 0.2 2.0 37 1880 188 164 201
2 x 120 37 14 1.2 0.5 2.1 42 2650 215 190 236
2 x 150 37 15.5 1.4 0.5 2.3 46 3150 240 214 268
2 x 185 37 17.4 1.6 0.5 2.4 51 3850 272 244 308
2 x 240 61 19.9 1.7 0.5 2.6 57 4750 315 286 366
2 x 300 61 22.2 1.8 0.5 2.7 63 5710 355 323 420
2 x 400 61 25.2 2.0 0.5 3.0 70 7060 405 373 487
2 x 500 61 28.6 2.2 0.5 3.2 78 8670 462 428 566
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC, LSF or PE)
3-Cores AL/XLPE/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
3 x 10 7 3.9 0.7 0.2 1.8 18 470 45 37 41
3 x 16 7 4.7 0.7 0.2 1.8 20 580 58 49 55
3 x 25 7 6.3 0.9 0.2 1.8 24 830 76 64 74
3 x 35 7 7.4 0.9 0.2 1.8 27 900 89 76 89
3 x 50 19 8.8 1.0 0.2 1.8 31 1110 106 91 109
3 x 70 19 10.6 1.1 0.2 1.9 36 1490 130 114 138
3 x 95 19 12.4 1.1 0.2 2.1 40 1890 155 136 169
3 x 120 37 14 1.2 0.5 2.2 45 2680 177 158 197
3 x 150 37 15.5 1.4 0.5 2.4 50 3220 198 177 224
3 x 185 37 17.4 1.6 0.5 2.5 55 3860 224 202 258
3 x 240 61 19.9 1.7 0.5 2.7 62 4800 260 236 305
3 x 300 61 22.2 1.8 0.5 2.9 68 5710 292 268 350
3 x 400 61 25.2 2.0 0.5 3.1 75 7010 333 308 405
3 x 500 61 28.6 2.2 0.5 3.3 85 8630 379 353 470
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (3½ & 4 Cores) - Aluminium Conductor, XLPE Insulated Armored Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC, LSF or PE)
3½ Cores AL/XLPE/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Nominal Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
[Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne]
Armor Wire Outer Sheath Overall
Weight
Area* Diameter** Amps Amps Amps
Diameter Thickness
mm² No. mm mm mm mm mm kg/km
3x16+10 7/7 4.7 / 3.9 0.7 / 0.7 0.2 1.8 21 650 59 49 56
3x25+16 7/7 6.3 / 4.7 0.9 / 0.7 0.2 1.8 25 900 76 64 76
3x35+16 7/7 6.5 / 4.7 0.9 / 0.7 0.2 1.8 26 890 89 76 88
3x50+25 7/7 7.5 / 6.3 1.0 / 0.9 0.2 1.8 29 1120 105 91 107
3x70+35 14 / 7 9.1 / 7.4 1.1 / 0.9 0.2 2.0 34 1490 128 112 134
3x95+50 19 / 19 10.8 / 8.8 1.1 / 1.0 0.5 2.1 39 2210 154 136 166
3x120+70 19 / 19 12.2 / 10.6 1.2 / 1.1 0.5 2.3 43 2660 175 155 192
3x150+70 37 / 19 13.5 / 10.6 1.4 / 1.1 0.5 2.4 47 3160 196 174 218
3x185+95 37 / 19 15.2 / 12.4 1.6 / 1.1 0.5 2.6 52 3820 222 199 251
3x240+120 37 / 37 17.5 / 14 1.7 / 1.2 0.5 2.8 58 4740 256 233 296
3x300+150 37 / 37 19.6 / 15.5 1.8 / 1.4 0.5 2.9 63 5620 289 263 339
3x400+185 61 / 37 22.5 / 17.4 2.0 / 1.6 0.5 3.2 71 6980 330 304 396
3x500+240 61 / 61 25.6 / 19.9 2.2 / 1.7 0.5 3.4 78 8610 375 347 455
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC, LSF or PE)
4-Cores AL/XLPE/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of Nominal Outer
Conductor Insulation Armor Wire Sheath Thickness
Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Diameter Diameter** Weight
mm² No. mm mm mm mm mm kg/km
4 x 10 7 3.9 0.7 0.2 1.8 20 550 46 38 43
4 x 16 7 4.7 0.7 0.2 1.8 22 680 59 50 57
4 x 25 7 6.3 0.9 0.2 1.8 26 990 77 65 77
4 x 35 7 6.5 0.9 0.2 1.8 27 960 89 76 89
4 x 50 7 7.5 1.0 0.2 1.9 31 1200 106 91 109
4 x 70 14 9.1 1.1 0.2 2.0 35 1590 129 113 136
4 x 95 19 10.8 1.1 0.5 2.2 40 2390 155 136 167
4 x 120 19 12.2 1.2 0.5 2.4 45 2890 176 157 194
4 x 150 37 13.5 1.4 0.5 2.5 49 3440 197 176 221
4 x 185 37 15.2 1.6 0.5 2.7 54 4130 223 201 254
4 x 240 37 17.5 1.7 0.5 2.9 60 5160 258 234 299
4 x 300 37 19.6 1.8 0.5 3.1 66 6150 291 266 343
4 x 400 61 22.5 2.0 0.5 3.4 75 7740 332 307 400
4 x 500 61 25.6 2.2 0.8 3.7 84 10230 379 353 464
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (5 Cores) - Aluminium Conductor, XLPE Insulated Armored Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded XLPE Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC, LSF or PE)
5-Cores AL/XLPE/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
5 x 10 7 3.9 0.7 0.2 1.8 21 640 46 39 44
5 x 16 7 4.7 0.7 0.2 1.8 23 810 60 50 58
5 x 25 7 6.3 0.9 0.2 1.8 29 1180 78 67 80
5 x 35 7 7.4 0.9 0.2 1.9 32 1330 93 80 98
5 x 50 19 8.8 1.0 0.2 2.0 37 1720 110 96 119
5 x 70 19 10.6 1.1 0.5 2.2 44 2690 136 120 152
5 x 95 19 12.4 1.1 0.5 2.3 50 3400 162 145 188
5 x 120 37 14 1.2 0.5 2.5 55 4090 185 166 218
5 x 150 37 15.5 1.4 0.5 2.7 61 4870 207 188 249
5 x 185 37 17.4 1.6 0.5 2.9 68 5990 235 215 286
5 x 240 61 19.9 1.7 0.5 3.1 75 7400 272 250 339
5 x 300 61 22.2 1.8 0.5 3.3 83 8950 307 285 389
5 x 400 61 25.2 2.0 0.8 3.7 94 11990 351 329 455
5 x 500 61 28.6 2.2 0.8 4.0 105 14650 400 379 528
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (2 & 3 Cores) - Copper Conductor, PVC Insulated Armored Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC or PE)
2-Cores CU/PVC/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
2 x 1.5 7 1.6 0.8 0.2 1.8 14 280 19 17 13
2 x 2.5 7 2.0 0.8 0.2 1.8 15 330 25 22 17
2x4 7 2.6 1.0 0.2 1.8 16 430 33 28 23
2x6 7 3.1 1.0 0.2 1.8 18 500 41 35 29
2 x 10 7 4.0 1.0 0.2 1.8 19 650 55 47 39
2 x 16 7 5.0 1.0 0.2 1.8 21 840 71 60 52
2 x 25 7 6.3 1.2 0.2 1.8 25 1170 91 78 70
2 x 35 7 7.4 1.2 0.2 1.8 27 1460 110 95 85
2 x 50 19 8.8 1.4 0.2 1.8 31 1870 130 113 104
2 x 70 19 10.6 1.4 0.2 1.9 34 2470 159 139 130
2 x 95 19 12.4 1.6 0.2 2.1 40 3330 190 168 160
2 x 120 37 14.0 1.6 0.5 2.2 44 4410 217 193 187
2 x 150 37 15.5 1.8 0.5 2.3 48 5270 242 218 212
2 x 185 37 17.4 2.0 0.5 2.4 53 6480 272 246 242
2 x 240 61 20.3 2.2 0.5 2.6 60 8270 314 286 287
2 x 300 61 22.7 2.4 0.5 2.8 67 10190 352 324 326
2 x 400 61 25.4 2.6 0.5 3.1 74 12650 394 365 372
2 x 500 61 28.8 2.8 0.5 3.3 82 15860 438 408 421
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC or PE)
3-Cores CU/PVC/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
3 x 1.5 7 1.6 0.8 0.2 1.8 14 310 17 14 11
3 x 2.5 7 2.0 0.8 0.2 1.8 15 370 22 18 15
3x4 7 2.6 1.0 0.2 1.8 17 480 28 24 20
3x6 7 3.1 1.0 0.2 1.8 18 580 35 29 25
3 x 10 7 4.0 1.0 0.2 1.8 20 760 46 39 34
3 x 16 7 5.0 1.0 0.2 1.8 23 1010 60 51 45
3 x 25 7 6.3 1.2 0.2 1.8 26 1430 77 66 60
3 x 35 7 7.4 1.2 0.2 1.8 29 1660 91 79 72
3 x 50 19 8.8 1.4 0.2 1.9 33 2160 108 94 88
3 x 70 19 10.6 1.4 0.2 2.0 37 2910 132 116 110
3 x 95 19 12.4 1.6 0.5 2.2 43 4290 158 140 136
3 x 120 37 14.0 1.6 0.5 2.3 47 5150 180 160 157
3 x 150 37 15.5 1.8 0.5 2.4 52 6230 201 181 179
3 x 185 37 17.4 2.0 0.5 2.6 57 7640 225 205 204
3 x 240 61 20.3 2.2 0.5 2.8 65 9810 259 238 241
3 x 300 61 22.7 2.4 0.5 2.9 71 12000 290 267 273
3 x 400 61 25.4 2.6 0.5 3.2 79 15000 324 300 311
3 x 500 61 28.8 2.8 0.5 3.4 88 18850 359 336 351
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (3½ & 4 Cores) - Copper Conductor, PVC Insulated Armored Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC or PE)
3½ Cores CU/PVC/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Nominal Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
[Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne]
Armor Wire Outer Sheath Overall
Weight
Area* Diameter** Amps Amps Amps
Diameter Thickness
mm² No. mm mm mm mm mm kg/km
3x16+10 7/7 5/4 1.0 / 1.0 0.2 1.8 24 1150 61 52 46
3x25+16 7/7 6.3 / 5 1.2 / 1.0 0.2 1.8 27 1620 78 67 61
3x35+16 7/7 6.6 / 5 1.2 / 1.0 0.2 1.8 28 1760 91 78 71
3x50+25 19 / 7 7.5 / 6.3 1.4 / 1.2 0.2 1.9 32 2340 107 94 86
3x70+35 19 / 7 9.1 / 7.4 1.4 / 1.2 0.2 2.0 35 3160 130 115 107
3x95+50 19 / 19 11 / 8.8 1.6 / 1.4 0.5 2.2 41 4590 157 138 133
3x120+70 37 / 19 12.2 / 10.6 1.6 / 1.4 0.5 2.3 45 5640 178 159 153
3x150+70 37 / 19 13.8 / 10.6 1.8 / 1.4 0.5 2.5 49 6690 198 178 174
3x185+95 37 / 19 15.1 / 12.4 2.0 / 1.6 0.5 2.6 54 8240 223 202 199
3x240+120 61 / 37 17.6 / 14 2.2 / 1.6 0.5 2.8 60 10500 256 233 233
3x300+150 61 / 37 19.8 / 15.5 2.4 / 1.8 0.5 3.0 66 12860 287 263 266
3x400+185 61 / 37 22.2 / 17.4 2.6 / 2.0 0.5 3.3 74 16210 322 298 303
3x500+240 61 / 61 26.3 / 20.3 2.8 / 2.2 0.8 3.6 83 21070 359 336 346
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC or PE)
4-Cores CU/PVC/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of Nominal Outer
Conductor Insulation Armor Wire Sheath Thickness
Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Diameter Diameter** Weight
mm² No. mm mm mm mm mm kg/km
4 x 1.5 7 1.6 0.8 0.2 1.8 15 350 17 14 12
4 x 2.5 7 2.0 0.8 0.2 1.8 16 420 22 18 15
4x4 7 2.6 1.0 0.2 1.8 18 570 28 24 20
4x6 7 3.1 1.0 0.2 1.8 20 690 35 30 26
4 x 10 7 4.0 1.0 0.2 1.8 22 920 47 40 35
4 x 16 7 5.0 1.0 0.2 1.8 24 1230 61 52 46
4 x 25 7 6.3 1.2 0.2 1.8 28 1760 78 67 62
4 x 35 7 6.6 1.2 0.2 1.8 29 1960 91 79 72
4 x 50 19 7.5 1.4 0.2 2.0 33 2600 107 94 87
4 x 70 19 9.1 1.4 0.5 2.1 38 3840 132 116 110
4 x 95 19 11.0 1.6 0.5 2.3 43 5080 157 140 135
4 x 120 37 12.2 1.6 0.5 2.4 47 6160 178 159 155
4 x 150 37 13.8 1.8 0.5 2.6 52 7500 200 180 177
4 x 185 37 15.1 2.0 0.5 2.7 57 9200 224 204 202
4 x 240 61 17.6 2.2 0.5 3.0 63 11760 258 236 236
4 x 300 61 19.8 2.4 0.5 3.2 69 14440 288 265 269
4 x 400 61 22.2 2.6 0.5 3.5 78 18240 324 301 308
4 x 500 61 26.3 2.8 0.8 3.8 87 23610 362 339 351
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (5 Cores) - Copper Conductor, PVC Insulated Armored Cables
Conductor : Round Stranded Copper
Insulation : Extruded PVC Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC or PE)
5-Cores CU/PVC/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
5 x 1.5 7 1.6 0.8 0.2 1.8 16 400 17 14 12
5 x 2.5 7 2.0 0.8 0.2 1.8 17 490 22 19 16
5x4 7 2.6 1.0 0.2 1.8 20 660 29 24 21
5x6 7 3.1 1.0 0.2 1.8 21 810 36 30 26
5 x 10 7 4.0 1.0 0.2 1.8 24 1090 48 41 36
5 x 16 7 5.0 1.0 0.2 1.8 26 1480 61 53 48
5 x 25 7 6.3 1.2 0.2 1.8 31 2140 79 68 64
5 x 35 7 7.4 1.2 0.2 1.9 34 2590 95 82 78
5 x 50 19 8.8 1.4 0.2 2.1 40 3450 112 99 96
5 x 70 19 10.6 1.4 0.5 2.2 46 5040 138 123 122
5 x 95 19 12.4 1.6 0.5 2.4 53 6760 165 148 149
5 x 120 37 14.0 1.6 0.5 2.6 57 8200 187 170 172
5 x 150 37 15.5 1.8 0.5 2.8 63 9970 209 190 196
5 x 185 37 17.4 2.0 0.5 2.9 70 12230 236 217 225
5 x 240 61 20.3 2.2 0.5 3.2 79 15720 272 252 266
5 x 300 61 22.7 2.4 0.5 3.4 88 19450 304 284 303
5 x 400 61 25.4 2.6 0.8 3.8 98 25320 341 321 346
5 x 500 61 28.8 2.8 0.8 4.1 109 31820 379 360 391
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (2 & 3 Cores) - Aluminium Conductor, PVC Insulated Armored Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC or PE)
2-Cores AL/PVC/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
2 x 10 7 3.9 1.0 0.2 1.8 19 500 42 36 30
2 x 16 7 4.7 1.0 0.2 1.8 20 600 54 46 40
2 x 25 7 6.3 1.2 0.2 1.8 24 840 71 61 54
2 x 35 7 7.4 1.2 0.2 1.8 27 1010 85 73 66
2 x 50 19 8.8 1.4 0.2 1.8 30 1280 101 87 80
2 x 70 19 10.6 1.4 0.2 1.9 34 1620 124 108 101
2 x 95 19 12.4 1.6 0.2 2.1 39 2160 148 131 124
2 x 120 37 14 1.6 0.5 2.2 44 2930 169 150 146
2 x 150 37 15.5 1.8 0.5 2.3 48 3450 189 170 165
2 x 185 37 17.4 2.0 0.5 2.4 53 4210 214 193 190
2 x 240 61 19.9 2.2 0.5 2.6 59 5210 248 225 225
2 x 300 61 22.2 2.4 0.5 2.8 65 6320 279 256 257
2 x 400 61 25.2 2.6 0.5 3.1 73 7780 318 295 299
2 x 500 61 28.6 2.8 0.5 3.3 81 9570 362 337 346
*Overall Diameter Tolerence Range: [-2% , +6%]
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC or PE)
3-Cores AL/PVC/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
3 x 10 7 3.9 1.0 0.2 1.8 20 560 36 30 26
3 x 16 7 4.7 1.0 0.2 1.8 21 680 46 39 34
3 x 25 7 6.3 1.2 0.2 1.8 26 960 60 52 47
3 x 35 7 7.4 1.2 0.2 1.8 29 1030 71 61 56
3 x 50 19 8.8 1.4 0.2 1.9 33 1300 84 73 68
3 x 70 19 10.6 1.4 0.2 2.0 37 1690 103 90 86
3 x 95 19 12.4 1.6 0.5 2.2 43 2580 123 109 106
3 x 120 37 14 1.6 0.5 2.3 47 2990 140 125 123
3 x 150 37 15.5 1.8 0.5 2.4 52 3570 157 141 140
3 x 185 37 17.4 2.0 0.5 2.6 57 4290 177 161 161
3 x 240 61 19.9 2.2 0.5 2.8 64 5350 205 188 190
3 x 300 61 22.2 2.4 0.5 2.9 70 6370 231 213 217
3 x 400 61 25.2 2.6 0.5 3.2 78 7810 263 244 252
3 x 500 61 28.6 2.8 0.5 3.4 87 9570 299 280 291
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (3½ & 4 Cores) - Aluminium Conductor, PVC Insulated Armored Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC or PE)
3½ Cores AL/PVC/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Nominal Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
[Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne]
Armor Wire Outer Sheath Overall
Weight
Area* Diameter** Amps Amps Amps
Diameter Thickness
mm² No. mm mm mm mm mm kg/km
3x16+10 7/7 4.7 / 3.9 1.0 / 1.0 0.2 1.8 23 760 47 40 35
3x25+16 7/7 6.3 / 4.7 1.2 / 1.0 0.2 1.8 27 1050 60 52 47
3x35+16 7/7 6.5 / 4.7 1.2 / 1.0 0.2 1.8 28 1030 70 60 55
3x50+25 7/7 7.5 / 6.3 1.4 / 1.2 0.2 1.9 32 1330 83 73 67
3x70+35 14 / 7 9.1 / 7.4 1.4 / 1.2 0.2 2.0 35 1690 102 89 83
3x95+50 19 / 19 10.8 / 8.8 1.6 / 1.4 0.5 2.2 41 2560 122 108 103
3x120+70 19 / 19 12.2 / 10.6 1.6 / 1.4 0.5 2.3 45 3040 139 124 120
3x150+70 37 / 19 13.5 / 10.6 1.8 / 1.4 0.5 2.5 49 3560 155 139 136
3x185+95 37 / 19 15.2 / 12.4 2.0 / 1.6 0.5 2.6 54 4270 175 159 157
3x240+120 37 / 37 17.5 / 14 2.2 / 1.6 0.5 2.8 60 5320 203 184 184
3x300+150 37 / 37 19.6 / 15.5 2.4 / 1.8 0.5 3.0 66 6360 228 209 211
3x400+185 61 / 37 22.5 / 17.4 2.6 / 2.0 0.5 3.3 74 7940 260 241 245
3x500+240 61 / 61 25.6 / 19.9 2.8 / 2.2 0.8 3.6 83 10420 296 277 285
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC or PE)
4-Cores AL/PVC/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of Nominal Outer
Conductor Insulation Armor Wire Sheath Thickness
Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Diameter Diameter** Weight
mm² No. mm mm mm mm mm kg/km
4 x 10 7 3.9 1.0 0.2 1.8 21 650 36 30 27
4 x 16 7 4.7 1.0 0.2 1.8 23 800 47 40 35
4 x 25 7 6.3 1.2 0.2 1.8 28 1150 61 52 48
4 x 35 7 6.5 1.2 0.2 1.8 29 1110 71 61 56
4 x 50 7 7.5 1.4 0.2 2.0 33 1470 83 73 67
4 x 70 14 9.1 1.4 0.5 2.1 38 2160 102 91 86
4 x 95 19 10.8 1.6 0.5 2.3 43 2760 122 109 105
4 x 120 19 12.2 1.6 0.5 2.4 47 3240 139 124 121
4 x 150 37 13.5 1.8 0.5 2.6 52 3870 156 141 138
4 x 185 37 15.2 2.0 0.5 2.7 57 4670 176 160 158
4 x 240 37 17.5 2.2 0.5 3.0 63 5810 204 186 187
4 x 300 37 19.6 2.4 0.5 3.2 69 6960 230 211 214
4 x 400 61 22.5 2.6 0.5 3.5 78 8700 262 244 249
4 x 500 61 25.6 2.8 0.8 3.8 87 11370 298 280 289
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore (5 Cores) - Aluminium Conductor, PVC Insulated Armored Cables
Conductor : Round Stranded Aluminium
Insulation : Extruded PVC Material
Armor : Galvanized Steel Tapes
Oversheath : Extruded Material (PVC or PE)
5-Cores AL/PVC/STA/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Armor Wire Outer Sheath Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Diameter Thickness Diameter* Weight
mm² No. mm mm mm mm mm kg/km
5 x 10 7 3.9 1.0 0.2 1.8 23 770 36 31 28
5 x 16 7 4.7 1.0 0.2 1.8 25 950 47 40 36
5 x 25 7 6.3 1.2 0.2 1.8 30 1370 61 53 49
5 x 35 7 7.4 1.2 0.2 1.9 34 1540 74 64 61
5 x 50 19 8.8 1.4 0.2 2.1 40 2020 87 77 74
5 x 70 19 10.6 1.4 0.5 2.2 46 3000 107 96 95
5 x 95 19 12.4 1.6 0.5 2.4 53 3910 128 115 116
5 x 120 37 14 1.6 0.5 2.6 57 4600 146 133 135
5 x 150 37 15.5 1.8 0.5 2.8 63 5530 163 149 153
5 x 185 37 17.4 2.0 0.5 2.9 70 6650 185 171 177
5 x 240 61 19.9 2.2 0.5 3.2 78 8290 215 199 210
5 x 300 61 22.2 2.4 0.5 3.4 86 10060 242 227 240
5 x 400 61 25.2 2.6 0.8 3.8 97 13340 277 261 280
5 x 500 61 28.6 2.8 0.8 4.1 109 16340 315 300 325
*Overall Diameter Tolerence Range: [-2% , +6%]
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Copper Conductor, XLPE Insulated Cables [90 oC]
Electrical Parameters [TOUCHED Cables in Trefoil & Flat Formation ]
DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance Capacitance Current
Area [60 Hz] [90 oC] 3-φ 1-φ Resistance [20oC]
[20 oC] [90 oC] [90 oC] [Conductor]
mm² /km /km /km mH/km /km /km V/A/km V/A/km F/km M.km kA
1 x 1.5 12.10 15.43 15.43 0.597 0.225 15.43 21.61 24.96 0.103 1045 0.21
1 x 2.5 7.41 9.45 9.45 0.546 0.206 9.45 13.31 15.37 0.114 840 0.36
1x4 4.61 5.88 5.88 0.514 0.194 5.88 8.35 9.64 0.121 720 0.57
1x6 3.08 3.93 3.93 0.474 0.179 3.93 5.63 6.50 0.131 585 0.86
1 x 10 1.83 2.33 2.33 0.439 0.165 2.34 3.41 3.93 0.140 475 1.43
1 x 16 1.15 1.47 1.47 0.407 0.153 1.48 2.19 2.53 0.149 385 2.29
1 x 25 0.727 0.927 0.927 0.387 0.146 0.939 1.44 1.66 0.147 400 3.58
1 x 35 0.524 0.668 0.668 0.365 0.138 0.683 1.07 1.24 0.153 340 5.01
1 x 50 0.387 0.494 0.494 0.353 0.133 0.511 0.823 0.950 0.155 330 7.15
1 x 70 0.268 0.342 0.342 0.336 0.127 0.365 0.606 0.700 0.157 310 10.02
1 x 95 0.193 0.246 0.247 0.321 0.121 0.275 0.468 0.541 0.162 260 13.59
1 x 120 0.153 0.195 0.197 0.305 0.115 0.228 0.392 0.452 0.163 255 17.17
1 x 150 0.124 0.158 0.160 0.307 0.116 0.198 0.342 0.395 0.161 270 21.46
1 x 185 0.0991 0.126 0.129 0.298 0.112 0.171 0.295 0.340 0.161 275 26.47
1 x 240 0.0754 0.0961 0.0992 0.292 0.110 0.148 0.252 0.291 0.163 255 34.34
1 x 300 0.0601 0.0766 0.0807 0.281 0.106 0.133 0.222 0.256 0.165 240 42.93
1 x 400 0.0470 0.0599 0.0650 0.280 0.105 0.123 0.199 0.230 0.165 235 57.23
1 x 500 0.0366 0.0467 0.0529 0.278 0.105 0.118 0.182 0.211 0.166 230 71.54
1 x 630 0.0283 0.0361 0.0436 0.276 0.104 0.113 0.168 0.195 0.166 235 90.14
1 x 800 0.0221 0.0282 0.0368 0.275 0.104 0.110 0.159 0.184 0.166 230 114.47
Electrical Parameters [SPACED Cables in Trefoil & Flat Formation ]
DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance Capacitance Current
Area [60 Hz] [90 oC] 3-φ 1-φ Resistance [20oC]
[20 oC] [90 oC] [90 oC] [Conductor]
mm² /km /km /km mH/km /km /km V/A/km V/A/km F/km M.km kA
1 x 1.5 12.10 15.43 15.43 0.782 0.295 15.43 21.69 24.96 0.103 1045 0.21
1 x 2.5 7.41 9.45 9.45 0.731 0.276 9.45 13.38 15.37 0.114 840 0.36
1x4 4.61 5.88 5.88 0.699 0.264 5.88 8.42 9.64 0.121 720 0.57
1x6 3.08 3.93 3.93 0.659 0.248 3.94 5.70 6.50 0.131 585 0.86
1 x 10 1.83 2.33 2.33 0.624 0.235 2.35 3.48 3.93 0.140 475 1.43
1 x 16 1.15 1.47 1.47 0.592 0.223 1.48 2.26 2.53 0.149 385 2.29
1 x 25 0.727 0.927 0.927 0.572 0.216 0.952 1.51 1.66 0.147 400 3.58
1 x 35 0.524 0.668 0.668 0.550 0.207 0.700 1.14 1.24 0.153 340 5.01
1 x 50 0.387 0.494 0.494 0.538 0.203 0.534 0.895 0.950 0.155 330 7.15
1 x 70 0.268 0.342 0.342 0.520 0.196 0.394 0.678 0.700 0.157 310 10.02
1 x 95 0.193 0.246 0.247 0.506 0.191 0.312 0.541 0.541 0.162 260 13.59
1 x 120 0.153 0.195 0.196 0.489 0.185 0.269 0.465 0.452 0.163 255 17.17
1 x 150 0.124 0.158 0.159 0.492 0.186 0.245 0.415 0.395 0.161 270 21.46
1 x 185 0.0991 0.126 0.128 0.483 0.182 0.222 0.367 0.340 0.161 275 26.47
1 x 240 0.0754 0.0961 0.0978 0.477 0.180 0.205 0.325 0.291 0.163 255 34.34
1 x 300 0.0601 0.0766 0.0788 0.466 0.176 0.193 0.295 0.256 0.165 240 42.93
1 x 400 0.0470 0.0599 0.0626 0.464 0.175 0.186 0.272 0.230 0.165 235 57.23
1 x 500 0.0366 0.0467 0.0500 0.463 0.174 0.181 0.254 0.211 0.166 230 71.54
1 x 630 0.0283 0.0361 0.0402 0.461 0.174 0.179 0.241 0.195 0.166 235 90.14
1 x 800 0.0221 0.0282 0.0331 0.460 0.173 0.176 0.231 0.184 0.166 230 114.47
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Copper Conductor, PVC Insulated Cables [70 oC]
Electrical Parameters [TOUCHED Cables in Trefoil & Flat Formation ]
DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance Capacitance Current
Area [60 Hz] [70 oC] 3-φ 1-φ Resistance [20oC]
[20 oC] [70 oC] [70 oC] [Conductor]
mm² /km /km /km mH/km /km /km V/A/km V/A/km F/km M.km kA
1 x 1.5 12.10 14.48 14.48 0.597 0.225 14.48 20.30 23.43 0.315 15.0 0.17
1 x 2.5 7.41 8.87 8.87 0.546 0.206 8.87 12.50 14.43 0.348 10.0 0.29
1x4 4.61 5.52 5.52 0.514 0.194 5.52 7.85 9.06 0.346 10.0 0.46
1x6 3.08 3.69 3.69 0.489 0.184 3.69 5.30 6.17 0.375 10.0 0.69
1 x 10 1.83 2.19 2.19 0.452 0.171 2.20 3.21 3.71 0.405 10.0 1.15
1 x 16 1.15 1.38 1.38 0.420 0.158 1.39 2.07 2.39 0.434 10.0 1.84
1 x 25 0.727 0.870 0.870 0.387 0.146 0.882 1.36 1.57 0.437 5.1 2.88
1 x 35 0.524 0.627 0.627 0.376 0.142 0.643 1.02 1.17 0.459 5.0 4.03
1 x 50 0.387 0.463 0.463 0.353 0.133 0.482 0.780 0.901 0.458 5.0 5.75
1 x 70 0.268 0.321 0.321 0.336 0.127 0.346 0.577 0.667 0.477 5.0 8.05
1 x 95 0.193 0.231 0.232 0.329 0.124 0.263 0.450 0.52 0.482 5.0 10.93
1 x 120 0.153 0.183 0.186 0.312 0.118 0.219 0.378 0.437 0.494 5.0 13.8
1 x 150 0.124 0.148 0.150 0.307 0.116 0.190 0.329 0.38 0.492 5.0 17.25
1 x 185 0.0991 0.119 0.121 0.305 0.115 0.167 0.287 0.331 0.493 5.0 21.28
1 x 240 0.0754 0.0902 0.0934 0.298 0.112 0.146 0.246 0.284 0.498 5.0 27.6
1 x 300 0.0601 0.0719 0.0759 0.292 0.110 0.134 0.219 0.253 0.502 5.0 34.5
1 x 400 0.047 0.0562 0.0612 0.289 0.109 0.125 0.198 0.229 0.505 5.0 41.12
1 x 500 0.0366 0.0438 0.0501 0.282 0.106 0.117 0.180 0.207 0.510 5.0 51.4
1 x 630 0.0283 0.0339 0.0414 0.280 0.106 0.114 0.168 0.193 0.515 5.0 64.77
1 x 800 0.0221 0.0264 0.0353 0.275 0.104 0.110 0.157 0.181 0.525 5.0 82.24
Electrical Parameters [SPACED Cables in Trefoil & Flat Formation ]
DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance Capacitance Current
Area [60 Hz] [70 oC] 3-φ 1-φ Resistance [20oC]
[20 oC] [70 oC] [70 oC] [Conductor]
mm² /km /km /km mH/km /km /km V/A/km V/A/km F/km M.km kA
1 x 1.5 12.10 14.48 14.48 0.782 0.295 14.48 20.37 23.43 0.315 15.0 0.17
1 x 2.5 7.41 8.87 8.87 0.731 0.276 8.87 12.57 14.43 0.348 10.0 0.29
1x4 4.61 5.52 5.52 0.699 0.264 5.52 7.92 9.06 0.346 10.0 0.46
1x6 3.08 3.69 3.69 0.674 0.254 3.69 5.37 6.17 0.375 10.0 0.69
1 x 10 1.83 2.19 2.19 0.637 0.240 2.20 3.28 3.71 0.405 10.0 1.15
1 x 16 1.15 1.38 1.38 0.605 0.228 1.40 2.14 2.39 0.434 10.0 1.84
1 x 25 0.727 0.870 0.870 0.572 0.216 0.900 1.43 1.57 0.437 5.1 2.88
1 x 35 0.524 0.627 0.627 0.561 0.211 0.662 1.09 1.17 0.459 5.0 4.03
1 x 50 0.387 0.463 0.463 0.538 0.203 0.506 0.853 0.901 0.458 5.0 5.75
1 x 70 0.268 0.321 0.321 0.520 0.196 0.376 0.649 0.667 0.477 5.0 8.05
1 x 95 0.193 0.231 0.232 0.514 0.194 0.302 0.523 0.52 0.482 5.0 10.93
1 x 120 0.153 0.183 0.184 0.497 0.187 0.262 0.450 0.437 0.494 5.0 13.8
1 x 150 0.124 0.148 0.149 0.492 0.186 0.239 0.401 0.38 0.492 5.0 17.25
1 x 185 0.0991 0.119 0.120 0.489 0.185 0.220 0.360 0.331 0.493 5.0 21.28
1 x 240 0.0754 0.0902 0.0920 0.483 0.182 0.204 0.319 0.284 0.498 5.0 27.6
1 x 300 0.0601 0.0719 0.0741 0.477 0.180 0.195 0.292 0.253 0.502 5.0 34.5
1 x 400 0.047 0.0562 0.0590 0.474 0.179 0.188 0.271 0.229 0.505 5.0 41.12
1 x 500 0.0366 0.0438 0.0473 0.467 0.176 0.182 0.252 0.207 0.510 5.0 51.4
1 x 630 0.0283 0.0339 0.0381 0.465 0.175 0.179 0.239 0.193 0.515 5.0 64.77
1 x 800 0.0221 0.0264 0.0316 0.460 0.173 0.176 0.229 0.181 0.525 5.0 82.24
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore - Copper Conductor, XLPE Insulated Cables [90 oC]
Electrical Parameters
DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance Capacitance Current
Area [60 Hz] [90 oC] 3-φ 1-φ Resistance [20oC]
[20 oC] [90 oC] [90 oC] [Conductor]
mm² /km /km /km mH/km /km /km V/A/km V/A/km F/km M.km kA
1.5 12.10 15.43 15.43 0.319 0.120 15.43 21.50 24.83 0.103 1045 0.21
2.5 7.41 9.45 9.45 0.294 0.111 9.45 13.21 15.25 0.114 840 0.36
4 4.61 5.88 5.88 0.279 0.105 5.88 8.25 9.53 0.121 720 0.57
6 3.08 3.93 3.93 0.262 0.099 3.93 5.55 6.40 0.131 585 0.86
10 1.83 2.33 2.33 0.248 0.094 2.33 3.33 3.85 0.140 475 1.43
16 1.15 1.47 1.47 0.237 0.089 1.47 2.13 2.45 0.149 385 2.29
25 0.727 0.927 0.928 0.239 0.090 0.932 1.38 1.59 0.147 400 3.58
35 0.524 0.668 0.669 0.231 0.087 0.675 1.02 1.18 0.153 340 5.01
50 0.387 0.494 0.495 0.230 0.087 0.502 0.775 0.895 0.155 330 7.15
70 0.268 0.342 0.343 0.227 0.086 0.354 0.565 0.652 0.157 310 10.02
95 0.193 0.246 0.248 0.221 0.083 0.262 0.430 0.497 0.162 260 13.59
120 0.153 0.195 0.198 0.220 0.083 0.214 0.360 0.416 0.163 255 17.17
150 0.124 0.158 0.161 0.222 0.084 0.182 0.311 0.359 0.161 270 21.46
185 0.0991 0.126 0.130 0.223 0.084 0.155 0.268 0.309 0.161 275 26.47
240 0.0754 0.0961 0.101 0.220 0.083 0.131 0.227 0.262 0.163 255 34.34
300 0.0601 0.0766 0.0830 0.218 0.082 0.117 0.200 0.231 0.165 240 42.93
400 0.0470 0.0599 0.0678 0.218 0.082 0.106 0.179 0.207 0.165 235 57.23
500 0.0366 0.0467 0.0562 0.217 0.082 0.099 0.163 0.188 0.166 230 71.54
Multicore - Copper Conductor, PVC Insulated Cables [70 oC]
Electrical Parameters
DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance Capacitance Current
Area [60 Hz] [70 oC] 3-φ 1-φ Resistance [20oC]
[20 oC] [70 oC] [70 oC] [Conductor]
mm² /km /km /km mH/km /km /km V/A/km V/A/km F/km M.km kA
1.5 12.10 14.48 14.4777 0.332 0.125 14.478 20.191 23.31 0.315 15.0 0.17
2.5 7.41 8.87 8.8661 0.305 0.115 8.867 12.405 14.32 0.348 10.0 0.29
4 4.61 5.52 5.5159 0.307 0.116 5.517 7.764 8.97 0.346 10.0 0.46
6 3.08 3.69 3.6853 0.287 0.108 3.687 5.219 6.03 0.375 10.0 0.69
10 1.83 2.19 2.1898 0.269 0.101 2.192 3.139 3.63 0.405 10.0 1.15
16 1.15 1.38 1.3763 0.255 0.096 1.38 2.007 2.32 0.434 10.0 1.84
25 0.727 0.870 0.8703 0.253 0.095 0.875 1.305 1.51 0.437 5.1 2.88
35 0.524 0.627 0.6276 0.244 0.092 0.634 0.965 1.12 0.459 5.0 4.03
50 0.387 0.463 0.464 0.244 0.092 0.473 0.739 0.853 0.458 5.0 5.75
70 0.268 0.321 0.3221 0.236 0.089 0.334 0.539 0.622 0.477 5.0 8.05
95 0.193 0.231 0.2329 0.235 0.088 0.249 0.414 0.478 0.482 5.0 10.93
120 0.153 0.183 0.1856 0.23 0.087 0.205 0.348 0.401 0.494 5.0 13.8
150 0.124 0.148 0.1515 0.231 0.087 0.175 0.3 0.347 0.492 5.0 17.25
185 0.0991 0.119 0.1225 0.23 0.087 0.15 0.26 0.300 0.493 5.0 21.28
240 0.0754 0.0902 0.0953 0.228 0.086 0.128 0.221 0.256 0.498 5.0 27.6
300 0.0601 0.0719 0.0782 0.227 0.086 0.116 0.198 0.228 0.502 5.0 34.5
400 0.047 0.0562 0.064 0.226 0.085 0.106 0.177 0.204 0.505 5.0 41.12
500 0.0366 0.0438 0.0532 0.224 0.085 0.1 0.162 0.187 0.510 5.0 51.4
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Aluminium Conductor, XLPE Insulated Cables [90 oC]
Electrical Parameters [TOUCHED Cables in Trefoil & Flat Formation ]
DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance Capacitance Current
Area [60 Hz] [90 oC] 3-φ 1-φ Resistance [20oC]
[20 oC] [90 oC] [90 oC] [Conductor]
mm² /km /km /km mH/km /km /km V/A/km V/A/km F/km M.km kA
1 x 10 3.08 3.95 3.95 0.443 0.167 3.95 5.65 6.52 0.140 480 0.94
1 x 16 1.91 2.45 2.45 0.421 0.159 2.45 3.56 4.11 0.146 415 1.51
1 x 25 1.20 1.54 1.54 0.387 0.146 1.55 2.28 2.64 0.147 400 2.36
1 x 35 0.868 1.11 1.11 0.366 0.138 1.12 1.69 1.95 0.153 345 3.31
1 x 50 0.641 0.822 0.822 0.354 0.133 0.833 1.28 1.48 0.154 340 4.72
1 x 70 0.443 0.568 0.568 0.336 0.127 0.582 0.919 1.06 0.157 310 6.61
1 x 95 0.320 0.410 0.411 0.321 0.121 0.428 0.695 0.802 0.162 260 8.98
1 x 120 0.253 0.324 0.325 0.305 0.115 0.345 0.570 0.658 0.163 255 11.34
1 x 150 0.206 0.264 0.265 0.307 0.116 0.289 0.488 0.563 0.161 270 14.17
1 x 185 0.164 0.210 0.211 0.298 0.112 0.239 0.409 0.473 0.161 275 17.48
1 x 240 0.125 0.160 0.162 0.290 0.109 0.195 0.337 0.390 0.163 255 22.68
1 x 300 0.100 0.128 0.130 0.285 0.107 0.168 0.291 0.337 0.165 240 28.35
1 x 400 0.0778 0.100 0.102 0.281 0.106 0.147 0.252 0.291 0.165 235 37.79
1 x 500 0.0605 0.078 0.0808 0.279 0.105 0.132 0.221 0.255 0.166 230 47.24
1 x 630 0.0469 0.060 0.0644 0.270 0.102 0.121 0.195 0.225 0.167 225 59.52
1 x 800 0.0367 0.047 0.0523 0.269 0.102 0.115 0.178 0.0206 0.168 210 75.59
Electrical Parameters [SPACED Cables in Trefoil & Flat Formation ]
DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance Capacitance Current
Area [60 Hz] [90 oC] 3-φ 1-φ Resistance [20oC]
[20 oC] [90 oC] [90 oC] [Conductor]
mm² /km /km /km mH/km /km /km V/A/km V/A/km F/km M.km kA
1 x 10 3.08 3.95 3.95 0.628 0.237 3.96 5.72 6.52 0.140 480 0.94
1 x 16 1.91 2.45 2.45 0.606 0.228 2.46 3.63 4.11 0.146 415 1.51
1 x 25 1.20 1.54 1.54 0.572 0.216 1.55 2.36 2.64 0.147 400 2.36
1 x 35 0.868 1.11 1.11 0.551 0.208 1.13 1.76 1.95 0.153 345 3.31
1 x 50 0.641 0.822 0.822 0.539 0.203 0.847 1.35 1.480 0.154 340 4.72
1 x 70 0.443 0.568 0.568 0.520 0.196 0.601 0.991 1.06 0.157 310 6.61
1 x 95 0.32 0.410 0.411 0.506 0.191 0.453 0.768 0.802 0.162 260 8.98
1 x 120 0.253 0.324 0.325 0.489 0.185 0.374 0.643 0.658 0.163 255 11.34
1 x 150 0.206 0.264 0.265 0.492 0.186 0.324 0.560 0.563 0.161 270 14.17
1 x 185 0.164 0.210 0.211 0.483 0.182 0.279 0.482 0.473 0.161 275 17.48
1 x 240 0.125 0.160 0.161 0.475 0.179 0.241 0.410 0.390 0.163 255 22.68
1 x 300 0.100 0.128 0.129 0.470 0.177 0.219 0.364 0.337 0.165 240 28.35
1 x 400 0.0778 0.100 0.101 0.466 0.176 0.203 0.325 0.291 0.165 235 37.79
1 x 500 0.0605 0.078 0.0795 0.464 0.175 0.192 0.294 0.255 0.166 230 47.24
1 x 630 0.0469 0.060 0.0626 0.455 0.172 0.183 0.268 0.225 0.167 225 59.52
1 x 800 0.0367 0.047 0.0502 0.454 0.171 0.178 0.250 0.0206 0.168 210 75.59
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Single Core - Aluminium Conductor, PVC Insulated Cables [70 oC]
Electrical Parameters [TOUCHED Cables in Trefoil & Flat Formation ]
DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance Capacitance Current
Area [60 Hz] [70 oC] 3-φ 1-φ Resistance [20oC]
[20 oC] [70 oC] [70 oC] [Conductor]
mm² /km /km /km mH/km /km /km V/A/km V/A/km F/km M.km kA
1 x 10 3.08 3.70 3.70 0.457 0.172 3.71 5.31 6.13 0.404 6.5 0.76
1 x 16 1.91 2.30 2.30 0.421 0.159 2.30 3.35 3.86 0.424 5.6 1.22
1 x 25 1.20 1.44 1.44 0.387 0.146 1.45 2.15 2.48 0.437 5.1 1.90
1 x 35 0.868 1.04 1.04 0.377 0.142 1.05 1.59 1.84 0.457 4.4 2.66
1 x 50 0.641 0.770 0.770 0.354 0.133 0.782 1.210 1.39 0.456 4.5 3.80
1 x 70 0.443 0.532 0.533 0.336 0.127 0.548 0.870 1.01 0.477 3.8 5.32
1 x 95 0.320 0.384 0.385 0.329 0.124 0.404 0.662 0.765 0.482 3.7 7.22
1 x 120 0.253 0.304 0.305 0.312 0.118 0.327 0.545 0.629 0.494 3.3 9.12
1 x 150 0.206 0.248 0.248 0.307 0.116 0.274 0.465 0.537 0.492 3.4 11.40
1 x 185 0.164 0.197 0.198 0.305 0.115 0.229 0.394 0.455 0.493 3.3 14.07
1 x 240 0.125 0.150 0.152 0.296 0.112 0.189 0.327 0.377 0.497 3.2 18.25
1 x 300 0.100 0.120 0.122 0.296 0.112 0.166 0.286 0.330 0.501 3.1 22.81
1 x 400 0.0778 0.093 0.096 0.291 0.11 0.146 0.247 0.286 0.505 3.0 27.19
1 x 500 0.0605 0.073 0.076 0.284 0.107 0.131 0.217 0.250 0.510 2.8 33.99
1 x 630 0.0469 0.056 0.0607 0.274 0.103 0.120 0.191 0.221 0.521 2.5 42.83
1 x 800 0.0367 0.044 0.0496 0.269 0.102 0.113 0.175 0.202 0.533 2.2 54.39
Electrical Parameters [SPACED Cables in Trefoil & Flat Formation ]
DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance Capacitance Current
Area [60 Hz] [70 oC] 3-φ 1-φ Resistance [20oC]
[20 oC] [70 oC] [70 oC] [Conductor]
mm² /km /km /km mH/km /km /km V/A/km V/A/km F/km M.km kA
1 x 10 3.08 3.70 3.70 0.641 0.242 3.71 5.38 6.13 0.404 6.5 0.76
1 x 16 1.91 2.30 2.29 0.606 0.228 2.31 3.42 3.86 0.424 5.6 1.22
1 x 25 1.20 1.44 1.44 0.572 0.216 1.46 2.22 2.48 0.437 5.1 1.90
1 x 35 0.868 1.04 1.04 0.562 0.212 1.06 1.67 1.84 0.457 4.4 2.66
1 x 50 0.641 0.770 0.770 0.539 0.203 0.797 1.28 1.39 0.456 4.5 3.80
1 x 70 0.443 0.532 0.533 0.520 0.196 0.567 0.942 1.01 0.477 3.8 5.32
1 x 95 0.320 0.384 0.385 0.514 0.194 0.431 0.735 0.765 0.482 3.7 7.22
1 x 120 0.253 0.304 0.304 0.497 0.187 0.357 0.617 0.629 0.494 3.3 9.12
1 x 150 0.206 0.248 0.248 0.492 0.186 0.310 0.537 0.537 0.492 3.4 11.40
1 x 185 0.164 0.197 0.198 0.489 0.185 0.271 0.467 0.455 0.493 3.3 14.07
1 x 240 0.125 0.150 0.151 0.481 0.181 0.236 0.398 0.377 0.497 3.2 18.25
1 x 300 0.100 0.120 0.121 0.481 0.181 0.218 0.357 0.330 0.501 3.1 22.81
1 x 400 0.0778 0.093 0.0950 0.476 0.179 0.203 0.319 0.286 0.505 3.0 27.19
1 x 500 0.0605 0.073 0.0747 0.468 0.177 0.192 0.289 0.250 0.510 2.8 33.99
1 x 630 0.0469 0.056 0.0590 0.459 0.173 0.183 0.264 0.221 0.521 2.5 42.83
1 x 800 0.0367 0.044 0.0474 0.454 0.171 0.177 0.246 0.202 0.533 2.2 54.39
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Multicore - Aluminium Conductor, XLPE Insulated Cables [90 oC]
Electrical Parameters
DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance Capacitance Current
Area [60 Hz] [90 oC] 3-φ 1-φ Resistance [20oC]
[20 oC] [90 oC] [90 oC] [Conductor]
mm² /km /km /km mH/km /km /km V/A/km V/A/km F/km M.km kA
10 3.08 3.95 3.95 0.248 0.094 3.95 5.57 6.43 0.140 480 0.94
16 1.91 2.45 2.45 0.241 0.091 2.45 3.49 4.03 0.146 415 1.51
25 1.20 1.54 1.54 0.239 0.090 1.54 2.23 2.57 0.147 400 2.36
35 0.868 1.11 1.11 0.232 0.087 1.12 1.63 1.89 0.153 345 3.31
50 0.641 0.82 0.822 0.231 0.087 0.827 1.23 1.42 0.154 340 4.72
70 0.443 0.568 0.569 0.227 0.086 0.575 0.877 1.01 0.157 310 6.61
95 0.320 0.410 0.411 0.221 0.083 0.419 0.656 0.757 0.162 260 8.98
120 0.253 0.324 0.326 0.220 0.083 0.336 0.537 0.620 0.163 255 11.34
150 0.206 0.264 0.266 0.222 0.084 0.278 0.455 0.525 0.161 270 14.17
185 0.164 0.210 0.212 0.223 0.084 0.228 0.381 0.439 0.161 275 17.48
240 0.125 0.160 0.163 0.220 0.083 0.183 0.312 0.359 0.163 255 22.68
300 0.100 0.128 0.131 0.218 0.082 0.155 0.267 0.307 0.165 240 28.35
400 0.0778 0.100 0.103 0.218 0.082 0.132 0.228 0.263 0.165 235 37.79
500 0.0605 0.0780 0.0823 0.217 0.082 0.116 0.199 0.228 0.166 230 47.24
Multicore - Aluminium Conductor, PVC Insulated Cables [70 oC]
Electrical Parameters
DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance Capacitance Current
Area [60 Hz] [70 oC] 3-φ 1-φ Resistance [20oC]
[20 oC] [70 oC] [70 oC] [Conductor]
mm² /km /km /km mH/km /km /km V/A/km V/A/km F/km M.km kA
10 3.08 3.70 3.70 0.270 0.102 3.70 5.23 6.04 0.404 6.5 0.76
16 1.91 2.30 2.30 0.260 0.098 2.30 3.28 3.79 0.424 5.6 1.22
25 1.20 1.440 1.44 0.253 0.095 1.45 2.10 2.42 0.437 5.1 1.90
35 0.868 1.04 1.04 0.245 0.092 1.05 1.54 1.78 0.457 4.4 2.66
50 0.641 0.770 0.770 0.245 0.092 0.776 1.16 1.34 0.456 4.5 3.80
70 0.443 0.532 0.533 0.236 0.089 0.540 0.831 0.959 0.477 3.8 5.32
95 0.320 0.384 0.385 0.235 0.088 0.395 0.625 0.722 0.482 3.7 7.22
120 0.253 0.304 0.305 0.230 0.087 0.317 0.513 0.592 0.494 3.3 9.12
150 0.206 0.248 0.249 0.231 0.087 0.264 0.435 0.502 0.492 3.4 11.40
185 0.164 0.197 0.199 0.230 0.087 0.217 0.366 0.422 0.493 3.3 14.07
240 0.125 0.150 0.153 0.229 0.086 0.175 0.301 0.346 0.497 3.2 18.25
300 0.100 0.120 0.123 0.228 0.086 0.150 0.260 0.299 0.501 3.1 22.81
400 0.0778 0.093 0.0972 0.226 0.085 0.129 0.223 0.256 0.505 3.0 27.19
500 0.0605 0.073 0.0774 0.224 0.085 0.115 0.196 0.224 0.510 2.8 33.99
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Typical Cables' Correction Factors for Variation in
Installation Conditions In Ground
Correction Factors For Soil Thermal Resistivity
T.R Single-Core Multi-Core Single-Core Multi-Core
o
[ C.m/W] Cable Cable (in Duct) (in Duct)
1.00 1.36 1.29 1.25 1.17
1.20 1.26 1.21 1.18 1.12
1.50 1.14 1.12 1.10 1.07
2.00 1.00 1.00 1.00 1.00
2.50 0.90 0.91 0.91 0.93
3.00 0.80 0.80 0.80 0.80
Grouping Factors For Number of Circuits
No. of Circuits Trefoil [Gd] Flat Spaced [Gd] Multicore [Gd]
1 1.00 1.00 1.00
2
125mm 0.80 0.78 0.82
250mm 0.84 0.83 0.86
500mm 0.89 0.88 0.89
3
125mm 0.69 0.67 0.71
250mm 0.75 0.73 0.76
500mm 0.82 0.80 0.81
4
125mm 0.63 0.61 0.65
250mm 0.70 0.68 0.72
500mm 0.78 0.77 0.77
5
125mm 0.59 0.56 0.61
250mm 0.66 0.64 0.68
500mm 0.76 0.74 0.74
6
125mm 0.56 0.54 0.58
250mm 0.64 0.62 0.66
500mm 0.74 0.73 0.72
Correction Factors For Ground Correction Factors For Cable
Temperature Depth
o
Temp.[ C] Factor Depth [mm] Factor
20 1.18 500 1.02
30 1.09 700 1.00
35 1.04 1000 0.95
40 1.00 1200 0.94
50 0.89 1500 0.92
55 0.83 2000 0.85
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Typical Cables' Correction Factors for Variation in
Installation Conditions In Air
Grouping Factors
Cables No. of Circuits or Multi-Core Cables
arrangement 1 2 3 4 5 6 7 8 9
Bunched in air, on a
surface, embedded or 1.00 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50
enclosed
Single layer on wall,
floor or unperforated 1.00 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70
cable tray systems
Single layer fixed
directly under a 0.95 0.81 0.72 0.68 0.66 0.64 0.63 0.62 0.61
wooden ceiling
Single layer on a
perforated horizontal or
1.00 0.88 0.82 0.77 0.75 0.73 0.73 0.72 0.72
vertical cable tray
systems
Single layer on cable
ladder systems or 1.00 0.87 0.82 0.80 0.80 0.79 0.79 0.78 0.78
cleats etc.,
Correction Factors For Air
Temperature
Temp.[oC] Factor
20 1.49
30 1.36
35 1.29
40 1.22
50 1.08
55 1.00
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Drum Handling Instructions
Cables and Conductors should be installed by trained personnel in accordance with good engineering practices,
recognized codes of practice, statutory local requirements, IEE wiring regulations and where relevant, in
accordance with any specific instructions issued by the company. Cables are often supplied in heavy cable reels and
handling these reels can constitute a safety hazard. In particulat, dangers may arise during the removal of steel
binding straps and during the removal of retaining battens and timbers which may expose projecting nails.
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES
Drum Storage Instructions
1. Cable is a high commodity value; it is very sensitive to damage and must be handled with necessary care.
2. Unloading the reel should be by forklift or crane, rolling should be avoided. In case of fortklift, cradle both reel
flanges carefully between forks. Never allow fork to touch cable surface or reel wrap.
3. If the above equipment is not available, rolling as per direction on special constructed ramps is allowed with
a slope of 1/4 (=14 degrees).
4. When the reels are lifted by an axle supported from above, a separator bar must be employed to prevent damage
to the conductor or reel, or both, by inward pressure on the reel flange. Alternatively reels can be hoisted with a
shaft extending through both flanges. Do not lift by top flange. Cables or reel will be damaged.
5. Reel should not be dropped on the ground under any circumstances even on soft material.
6. Be sure that the end tightener is still in place. Be sure that the end seal cap is still in place.
7. Reels should not be immersed in water; therefore drainage system should be arranged at storage site.
8. Reels should be stored and shipped upright, i.e., resting on both flanges. Do not store or ship reels on their side.
Storage or shipment of the reel while lying on its side greatly increases the likelihood of tangling and damage to
the cable.
9. Reels should be lagged all the time. If reels of cable will be stored for long times (> one month), they should be
protected from rain and direct exposure to sunlight to maximize service life.
RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES