ANJUMAN HAMI-E-MUSLIMEEN’S
ESTD. 1980 ANJUMAN INSTITUTE OF TECHNOLOGY ANDMANAGEMENT
(FORMERLY ANJUMAN ENGINEERING COLLEGE FOR MEN)
S.T.D. Code :08385
ANJUMANABAD, P.O.BOX NO.24, BHATKAL – 581320, KARNATAKA STATE, INDIA. Office : 226554
(Affiliated to Visvesvaraya Technological University, Belgaum, Approved by A.I.C.T.E., New Delhi,& Accredited by N.B.A. Resi : 226307
New Delhi)AICTE Reg.No.F2-15/B-111/RC-MB/93/21734 dated 31.03.1994 Fax : 227175
Web: www.aitmb.ac.in Email:
[email protected] Head Office : 226214
Hostel Off. :226954
Ref. No. AITM/CC/6714/2024-25 Date: 02/01/2025
To,
Executive Engineer (Civil)
Karnataka power corporation Ltd.
Jyothinagar colony
GERUSOPPA
Sir,
Subject : Report of Test Conducted on treated STP water collected from residential
and non residential buildings pertaining to Jyothinagar Colony Gerusoppa
reg…
Reference: Letter. No.EE(C)GP/W/S &UGD/652
Dated : 07.12.2024
Please find enclosed herewith report of test conducted on treated STP water sample supplied by
you, which was collected from residential and non-residential building pertaining to Jyothinagar
Colony, KPCL Gerusoppa. Bill for the same is enclosed.
Thanking you,
Yours faithfully.
Principal
ANJUMAN HAMI-E-MUSLIMEEN’S
ANJUMAN INSTITUTE OF TECHNOLOGY AND MANAGEMENT
BHATKAL
Department of Civil Engineering
Ref. No. AITM/CC/6714/2024-25 Date: 02/01/2025
INVOICE
To,
Executive Engineer (Civil)
Karnataka power corporation Ltd.
Jyothinagar colony
GERUSOPPA
Sl.No. Particulars No of sets Rate Amount
1. Test on treated STP effluent 2 1000.00 2000.00
GST @18% 360.00
Our GSTIN : 29AABTA1339F1ZO
Grand Total 2360.00
(Rupees Two Thousand Three hundred sixty only )
Consultancy incharge Principal
(Dr. Chidanand Naik)
ANJUMAN HAMI-E-MUSLIMEEN’S
ANJUMAN INSTITUTE OF TECHNOLOGY AND MANAGEMENT
BHATKAL
Department of Civil Engineering
Ref. No AITM/CC/6714/2024-25 Date: 02/01/2025
TEST REPORT
Report of test conducted on treated STP water sample supplied by you which was collected from
residential and non-residential building pertaining to Jyothinagar Colony, KPC Ltd Gerusoppa.
TEST ON TREATED STP WATER
I) SAMPLE NO. 01 ( STP1)
Sl. No. Standard values as per CPCB
Parameters Tested. Test values Remarks
(for Public Sewer –Part A)
1 pH Value 7.9 5.5 to 9.0 Permissible
2 Suspended solids 550 mg/L Less than 600 mg/L Permissible
3 Iron 2.2 mg/L Less than 3.0.mg/L Permissible
4 Fluoride 4.0 mg/L Less than 15 mg/L Permissible
Less than 350 mg/L Permissible
5 BOD 290 mg/L
(COD is not required)
6 Nitrate Nitrogen 45 mg/L Nil Permissible
II) SAMPLE NO. 02 ( STP 2)
Sl. No. Standard values as per CPCB
Parameters Tested. Test values Remarks
(for Public Sewer –Part A)
1 pH Value 7.8 5.5 to 9.0 Permissible
2 Suspended solids 500 mg/L Less than 600 mg/L Permissible
3 Iron 2.7 mg/L Less than 3.0.mg/L Permissible
4 Fluoride 4.08mg/L Less than 15 mg/L Permissible
Less than 350 mg/L Permissible
5 BOD 300 mg/L
(COD is not required)
6 Nitrate Nitrogen 50 mg/L Nil Permissible
Remarks: As per Physical and Chemical analysis, for the STP samples supplied by you, it has
been observed that, all the parameters are well within the permissible limit as prescribed by the
“The Environment Protection and Pollution Control Manual” Karnataka Law Journal Publication
-2000 specification. Hence it is safe for the disposal by dilution method in Public Sewer.
Test Conducted by Principal
(Prof. Pratibha Gaonkar)