General Notes:: Bureau of Design

The document outlines the specifications for an overhead service entrance for a one-storey school building, including electrical work compliance with the Philippine Electrical Code. It details the required service power supply, materials, installation guidelines, and load schedules for various electrical fixtures. Additionally, it emphasizes the need for supervision by a registered electrical engineer and proper grounding of all electrical components.

Uploaded by

Selina Marra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
19 views1 page

General Notes:: Bureau of Design

The document outlines the specifications for an overhead service entrance for a one-storey school building, including electrical work compliance with the Philippine Electrical Code. It details the required service power supply, materials, installation guidelines, and load schedules for various electrical fixtures. Additionally, it emphasizes the need for supervision by a registered electrical engineer and proper grounding of all electrical components.

Uploaded by

Selina Marra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

OVERHEAD SERVICE ENTRANCE:

230 V, 1Ø, 2W, 60Hz., A.C. WITH


25mmØ TYPE "F" CONDULET,
WEATHERHEAD

PROPOSED REINFORCED
GENERAL NOTES: CONCRETE PEDESTAL
POLE: SIZE AS REQUIRED

3100 mm (MIN.) - 5500 mm (MAX)


1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE LATEST EDITION OF THE PHILIPPINE
ELECTRICAL CODE, EXISTING APPLICABLE ORDINANCES, RULES AND REGULATIONS OF THE LOCAL GOVERNMENT AND WITH 2 - 14mm² THHN + 1 - 8.0mm²
THE REQUIREMENTS OF THE LOCAL POWER COMPANY. THHN (G) in 25mmØ RSC

2. THE TYPE OF SERVICE POWER SUPPLY TO BE USED SHALL BE SINGLE-PHASE, 2-WIRE, 230V, 60 HERTZ, A.C

3. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF SERVICE ENTRANCE FOR CONNECTION TO THE "DP"
POWER COMPANY SERVICE POINT.

4. UNLESS OTHERWISE SPECIFIED, THE MINIMUM SIZES OF WIRE AND GALVANIZED RIGID STEEL CONDUIT TO BE USED SHALL BE
3.5mm²,THHN AND 15mm NOMINAL DIAMETER, RESPECTIVELY. LIKEWISE ALL ELECTRICAL WIRES SHALL BE COLOR-CODED. M
5. ALL LIGHTING CIRCUIT HOME RUNS AND CONVENIENCE OUTLETS SHALL BE WIRED WITH NOT LESS THAN 3.5 mm² IN SIZE. 8.0mm² THHN GROUND WIRE in
15mmØ C - CLAMPED TO
SCHEDULE OF LIGHTING FIXTURES AND LAMPS
6. WHEREVER REQUIRED AND NECESSARY, PULL OR JUNCTION BOXES SHALL BE INSTALLED AT CONVENIENT AND
COPPER-CLAD GROUNDING ROD

1800 mm

1800 mm
INCONSPICUOUS LOCATION, ALTHOUGH SUCH BOXES ARE NOT SHOWN ON THE PLAN NOR MENTIONED IN THE SPECIFICATIONS.
INSTALLATION/
SYMBOLS DESCRIPTION
7. ALL NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT SHALL BE PROPERLY GROUNDED IN ACCORDANCE MOUNTING
WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE. SURFACED CEILING
1 ONE (1) - 28W, 230V, 60Hz AC, FLUORESCENT LIGHTING FIXTURE , BOX TYPE
MOUNTED
8. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND OF THE APPROVED TYPE FOR LOCATION AND PURPOSE. GROUND FLOOR LEVEL
SURFACED CEILING
2 TWO (2) - 28W, 230V, 60Hz AC, FLUORESCENT LIGHTING FIXTURE , BOX TYPE
9. STANDARD TYPE OF ACCESSORIES, SPLICING DEVICES, TERMINATIONS AND OTHER APPURTENANCES FOR THE ENTIRE MOUNTED
ELECTRICAL INSTALLATION SHALL BE USED.
FINISHED GRADE LEVEL ONE (1) - 18W, 230V, 60Hz AC,COMPACT FLUORESCENT LIGHTING FIXTURE SURFACED CEILING
10. ALL WALL OUTLETS SHALL BE INSTALLED AT THE FOLLOWING HEIGHTS ABOVE THE FINISHED FLOOR LEVEL, UNLESS NOTED IN WITH MEDIUM BASE KEYLESS TYPE PORCELAIN RECEPTACLE MOUNTED
GROUNDING SYSTEM
THE PLAN. 16mm Ø X 2400mm LENGTH
ALL FLUORESCENT LIGHTING FIXTURES SHALL BE EQUIPPED WITH A HIGH POWER FACTOR, PRE-HEAT
COPPERCLAD GROUNDING NOTE: WITH STARTER AND THERMALLY PROTECTED BALLAST, COMPLETE WITH ALL NECESSARY ACCESSORIES,
a) WALL SWITCHES @ 1300mm
b) WALL CONVENIENCE OUTLETS @ 300 mm
ROD WIRED AND READY FOR USE.

11. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT AND IMMEDIATE SUPERVISION OF A DULY REGISTERED
ELECTRICAL ENGINEER. ELECTRICAL RISER DIAGRAM
NOT TO SCALE

SCHEDULE OF LOADS AND COMPUTATIONS:


ELECTRICAL SYMBOLS:
DISTRIBUTION PANELBOARD " DP "
BRANCH
CKT. VA PER CKT. BREAKER SIZE OF HOMERUN
CEILING LIGHT OUTLET LOAD DESCRIPTION VOLTS
NO. CKT. ( WIRES IN CONDUIT )
REFER TO SCHEDULE OF AF P AT
CEILING LIGHT OUTLET LIGHTING FIXTURES AND LAMPS
1 LIGHTING OUTLETS 1260 230 50 2 20 2 - 3.5mm² THHN IN 15mm Ø C

CF CEILING FAN, 60 WATTS, 230V, 60Hz


2 LIGHTING OUTLETS 840 230 50 2 20 2 - 3.5mm² THHN IN 15mm Ø C

SCF CEILING FAN CONTROL SWITCH 3 LIGHTING OUTLETS 815 230 50 2 20 2 - 3.5mm² THHN IN 15mm Ø C

S SINGLE POLE WALL SWITCH IN ONE SWITCH PLATE 4 CEILING FAN OUTLETS 900 230 50 2 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
(10 AMP., 230 VOLTS)
S² 2 SINGLE POLE WALL SWITCHES IN ONE SWITCH PLATE 5 CEILING FAN OUTLETS 600 230 50 2 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
(10 AMP., 230 VOLTS)

6 CONVENIENCE OUTLETS 2160 230 50 2 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
S3W THREE WAY SWITCH

DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE, 20A, 250VOLTS 7 SPARE 1500 230 50 2 20
"WP" DENOTES WEATHERPROOF OUTLET
8 SPARE 1500 230 50 2 20
SINGLE CONVENIENCE OUTLET, GROUNDING TYPE
EF "EF" DENOTES EXHAUST FAN (15 AMP., 230 VOLTS)
TOTAL 9575 MACB : 100AF, 2P, 250V, 70AT, 18KAIC
CONCEALED OR EMBEDDED CONDUIT RUN

UNDERGROUND OR UNDERFLOOR CONDUIT RUN


9575 (0.80) = 33.30 AMPERES
I L @ 80% D.F. =
CIRCUIT HOMERUN 230

USE : 2 - 14.0mm² THHN + 1 - 8.0mm² THHN (G) IN 25mm Ø RSC


DISTRIBUTION PANELBOARD

M ELECTRIC SERVICE METER

PUSH BUTTON, 10 A, 230V


PB 1500mm ABOVE FINISHED GRADE LINE

B VIBRATING BELL OUTLET, 230mm DIAMETER, 230V, 60HZ


TO BE INSTALLED @ 300mm BELOW CEILING LINE

ELECTRIC SERVICE ENTRANCE

GROUNDING SYSTEM

REPUBLIC OF THE PHILIPPINES PROJECT AND LOCATION: SHEET CONTENTS: DESIGNED: SIGNED SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SET NO.: SHEET NO.:
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS MARU BRYAN T. ZAPLAN
ENGINEER II
PROPOSED: - GENERAL NOTES
- ELECTRICAL SYMBOLS DRAWN/CAD: SIGNED
BUREAU OF DESIGN STANDARD DEP-ED
ONE (1) STOREY, FIVE (5) CLASSROOM
-
-
ELECTRICAL RISER DIAGRAM
SCHEDULE OF LOADS AND
CARLO BRYANN J. PENETRANTE
ENGINEER II
APPROVED WITH SIGNATURE
BOD
E-2
BUILDINGS DIVISION
SCHOOL BUILDING COMPUTATIONS