Data sheet for three-phase Squirrel-Cage-Motors
MLFB-Ordering data : 1LG4206-2AA60
Client order no. : Item no. :
Order no. : Consignment no. :
Offer no. : Project :
Remarks :
Electrical data : General data :
Rated voltage : Frame size :
(6) 400 VD/690 VY, 50 Hz, 460 VD, 60 Hz 200 L
Frequency : Design of electrical machine : (0) IM B3 / B6 / B7 / B8 / V5
50 Hz 60 Hz without canopy
Rated power : Weight in kg, without optional accessories :
30.00 kW 33.50 kW / 205.00 kg
Frame material :
Rated speed : Cast iron
2950 1/min 3550 1/min
Degree of protection :
Rated torque : IP 55
97.1 Nm 90.1 Nm
Method of cooling, TEFC :
Rated current (IE) : VD VY VD VY IC 411
54.0 A 31.3 A 52.0 A Vibration class :
A
Starting / rated current : Insulation :
6.5 6.5 155(F) to 130(B)
Breakdown / rated torque : Duty type :
3.0 3.0 S1 - continuous duty
Starting / rated torque : Direction of rotation :
2.3 2.3 Bi-directional
4/4 3/4 2/4 4/4 3/4 2/4
Efficiency % Terminal box :
90.7 % 90.8 % 90.1 % 91.5 % 91.3 % 89.7 %
Power factor : Material of terminal box :
0.88 0.85 0.77 0.88 0.88 0.78 Aluminum
Efficiency class : Type of terminal box :
IE1 IE1 gk 430
no value Contact screw thread :
M6
No Max. cross-sectional area :
25.00 mm²
Cable diameter from ... to ... :
27.0mm - 35.0mm
Mechanical data :
Cable entry :
Sound pressure level 50Hz/60Hz (load) : 2xM50x1,5
73.0(A) 77.0(A)
Cable gland
Moment of inertia : null 2 plugs
0.13 kg m²
Bearing DE :
6212 ZC3 Special design :
Bearing NDE :
6212 ZC3
Type of bearing :
Locating bearing NDE (standard)
Condensate drainage holes :
Yes
Regreasing device :
No
Lubricants :
Esso Unirex N3
Grease lifetime/Relubrication interval :
40000 h
Quantity of grease for relubrication :
null g
External earthing terminal :
Yes
Coating :
Explosion protection :
Type of protection :
without (standard)
Environmental conditions :
Ambient temperature :
-20.0 °C - +40 °C
Altitude above sea level :
1000 m
Standards and specifications :
IEC, DIN, ISO, VDE, EN
Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Generated: 25.07.2024 11:44:45