MPO System Datasheet

Schneider Electric's MPO/MTP Solution is a pre-terminated optical fiber cabling system designed for high bandwidth and density in data centers and enterprise applications, utilizing MTP connectors for robust connectivity. The solution offers benefits such as space, time, and cost savings, with factory-terminated components ensuring compatibility and quality. It includes various products like trunk cables, cassettes, fan-out patch cords, and enclosures, all compliant with industry standards.

Uploaded by

Francisco Viltes
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
8 views7 pages

MPO System Datasheet

Schneider Electric's MPO/MTP Solution is a pre-terminated optical fiber cabling system designed for high bandwidth and density in data centers and enterprise applications, utilizing MTP connectors for robust connectivity. The solution offers benefits such as space, time, and cost savings, with factory-terminated components ensuring compatibility and quality. It includes various products like trunk cables, cassettes, fan-out patch cords, and enclosures, all compliant with industry standards.

Uploaded by

Francisco Viltes
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

MPO (Multi-Fiber Push On)/MTP Solution

Schneider Electric MPO/MTP Solution is a pre-terminated optical fiber cabling system specifically
designed to satisfy the increasing demand for high bandwidth and high density in data center network,
enterprise building applications. Schneider Electric adopts MTP branded MPO connectors manufactured by
US Conec Ltd. to provide high precision and robust connectivity in all components.

Factory-terminated solutions provide improved system performance; ensure component compatibility and
consistent quality. The MPO system significantly reduces installation time and cost by simplifying the process
of deploying an optical network in the limited space environment, particularly in data center applications.

Typical Application A

Typical Application B

Customer Benefits:

Space Saving Time Saving Money Saving Reliability


- Smaller - Installation and MAC - No field termination - Enable moves, adds and
components time reduction  No scrap changes without polarity
- Improved cable - Reduce training needs concerns
management - Termination & testing
done in factory

Compliance Standards:
1) EIA/TIA-568-C, ISO/IEC 11801
2) IEC 61754-7, EIA/TIA-604-5, EIA/TIA-604-10
3) GR-1435-Core
4) TIA/EIA-455-B
5) RoSH

Page 1 of 7
I. MPO Trunk Cables

Schneider Electric MPO trunk cables are available in fiber counts from 12 to 144 fibers. The trunk cables are
terminated with the male MTP connector (with guiding pins) or LC connectors for high-density applications to
provide space savings and rapid installation.

The 12-fiber MTP connector, which has similar size to a LC Duplex connector, enables reducing load in the
cable tray and enhancing the airflow for cooling.

All major TIA/EIA polarity management methods are provided. The default connector fiber path (Pair Flipped) is
shown as below:

MPO-MPO (A-side to B-side)


MPO Fiber 1 2 3 4 5 6 7 8 9 10 11 12
A Color Blue Orange Green Brown Slate White Red Black Yellow Violet Rose Aqua

MPO Fiber 1 2 3 4 5 6 7 8 9 10 11 12
B Color Orange Blue Brown Green White Slate Black Red Violet Yellow Aqua Rose

MPO-LC (A-side to B-side)


Fiber 1 2 3 4 5 6 7 8 9 10 11 12
MPO
Color Blue Orange Green Brown Slate White Red Black Yellow Violet Rose Aqua
LC 1A 1B 2A 2B 3A 3B 4A 4B 5A 5B 6A 6B

The design of pulling socks, which will be installed after factory testing on both ends of the trunk cable, makes
the installation much quick and easy. The connector protective tube provides ideal resistance against crush,
torsions, water and dust. The default fiber cable short term tensile strength is 400N.

Fiber types are available in OS2, OM3 and OM4, with cable outer sheath in both OFNP & LSZH material
options. And the default cable (12-core) outer dimension is 4.5mm while 24-core is 5.6mm.

The cable length measurement is from connector ends (without dust cap & pin length) at both sides of the
cable. The leg length (distance between heat shrinking tube to connector end) is 0.9m for MPO connector end
and 0.9m-1.0m for LC connector end.

Technical Specifications

A) Optical Performance
B)
MTP Connector LC Connector Trunk Cable
Multi-Mode
Insertion Loss (dB) Return Loss (dB) Insertion Loss (dB) Return Loss (dB) Attenuation
@850nm ≤0.5 ≥ 20 ≤0.2 ≥ 20 3.5dB/Km
@1300nm ≤0.5 ≥ 20 ≤0.2 ≥ 30 1.5dB/Km

Single-Mode MTP Connector LC/APC Connector Trunk Cable

Page 2 of 7
Insertion Loss (dB) Return Loss (dB) Insertion Loss (dB) Return Loss (dB) Attenuation
@1310nm ≤0.5 ≥ 60 ≤0.30 ≥ 50 0.4dB/Km
@1550nm ≤0.2 ≥ 60 ≤0.25 ≥ 50 0.3dB/Km

C) Minimum Bending Radius during installation: 90mm (12-core) / 112mm (24-core)


D) Minimum Bending Radius after installation: 45mm (12-core) / 56mm (24-core)
E) Nominal Mass: 24 kg/km (LSZH) or 26Kg/Km (OFNP)
F) Temperature Range:
Installation: -5ºC to +60ºC
Operation: -20ºC to +60ºC

Packing Information (based on the standard cable of Diameter 4.5 and with pulling sock protection)

Cable Length Packing Information


<50m Plastic bag (381*508*140mm) and shipping box (500*500*200mm)
≥50m Corrugated carton reel (D419 mm x H164 mm) and shipping box (610*335*594 mm)

Compliance Standards
 ISO/IEC 61754-7, ISO/IEC 61280-4-1
 GR-1435 4.6.4
 TIA/EIA 604-5, TIA /EIA 604-10

Ordering Information

Trunk Connector Type Fiber Type Fiber Core Fiber Cable Length Fiber Path
Cable Sheath
12=12
S= Single Mode,
MM = MTP–MTP 24=24 FP=OFNP
OS2 XXX F= Pair Flipped,
36=36
(5M-60M, 5m S= Straight Through,
ACTMT T= Multi-Mode 48=48
separator) e.g. R= Reversed
ML=MTP-LC OM3, 72=72
LS=LSZH 25m= 025
Duplex G=Multi-Mode
T4=144
OM4

For Example:
Part Number Description
ACTMTMMS12LS060F Single Mode MTP-MTP 12 Core LSZH 60M (Pair Flipped)
ACTMTMMT24FP100R Multi Mode MTP-MTP 24 Core OFNP 100M (Reversed)
ACTMTMLS12LS090F Single Mode MTP-LC 12 Core LSZH 90M (Pair Flipped)
ACTMTMLT24FP120S Multi Mode MTP-LC 24 Core OFNP 120M (Straight Through)

Page 3 of 7
II. MPO Cassette

Schneider Electric’s MPO Cassette is used to break out the MPO connectors terminated on trunk cables into
LC duplex connectors to facilitate patching into system equipment, patch panels or work area outlets. It
provides greater manageability and flexibility with a modular infrastructure in data center application. Both
Multi-mode OM3/OM4 and Single-mode OS2 types are available. MPO connector equipped on the cassette is
female type (without guiding pins).

The outer sheath is made of high quality metal sheet with high intensity, which provides superior protection for
inner fiber cable harness and accessories. It can be installed in a horizontal 1U optical fiber enclosure that can
hold up to three such cassettes. Alternatively, it can also be mounted in a 4U enclosure vertically up to 12 such
cassettes.
The connectivity capacity can be either 12 or 24 fibers with LC interfaces via below fiber path arrangement
(Straight Through). Other polarity management methods are able to be provided as options.

12 Core
Fiber 1 2 3 4 5 6 7 8 9 10 11 12
MTP
Color Blue Orange Green Brown Slate White Red Black Yellow Violet Rose Aqua

LC 1B 1A 2B 2A 3B 3A 4B 4A 5B 5A 6B 6A

24 Core (with 12F MTP Connector x2 units)


MTP Fiber 1 2 3 4 5 6 7 8 9 10 11 12
T1 Color Blue Orange Green Brown Slate White Red Black Yellow Violet Rose Aqua

LC 1B 1A 2B 2A 3B 3A 4B 4A 5B 5A 6B 6A

MTP Fiber 1 2 3 4 5 6 7 8 9 10 11 12
T2 Color Blue Orange Green Brown Slate White Red Black Yellow Violet Rose Aqua
LC 7B 7A 8B 8A 9B 9A 10B 10A 11B 11A 12B 12A

Mechanical:
Material: Steel
Colour Finish: Black
Dimension: 100mm (D)* 136mm (W)* 35mm (H)

Optical Performance:
Multi-mode Insertion Loss @ 850 nm: ≤ 0.65dB per MPO cassette
Single- mode Insertion Loss @ 1310 nm: ≤ 0.7 dB per MPO cassette
Temperature Range:
Installation: -5ºC to +60ºC
Operation: -20ºC to +60ºC

Compliance Standards:
 EIA-310-D
 TIA/EIA-568-C, ISO/IEC 11801

Page 4 of 7
Ordering Information:

Part Number Description


ACTMMOS12x MTP-LC CASSETTE 12F OS2
ACTMMOT12x MTP-LC CASSETTE 12F OM3
ACTMMOG12x MTP-LC CASSETTE 12F OM4
ACTMMOS24x MTP-LC CASSETTE 24F OS2
ACTMMOT24x MTP-LC CASSETTE 24F OM3
ACTMMOG24x MTP-LC CASSETTE 24F OM4
Where x denotes S= STRAIGHT THROUGH, R= REVERSED, F=PAIR FLIPPED, RF= REVERSED, PAIR FLIPPED

Page 5 of 7
III. Harness/Fan-Out Patch Cord

Schneider Electric MPO 12/24-Core Fan-Out Patch Cords are used to break out the 12-fiber MTP connector
terminated on trunk cables into LC duplex connectors. The solution helps dramatically reduce the space
occupied by traditional solution. The MTP connector equipped with is female type (without guiding pins). The
length measurement is from connector ends (without dust cap & pin length) at both sides of the patch cord.

Every harness patch cord is 100% factory tested with low attenuation loss according to international standards
and data center requirements. Each split of the fiber harness is numbered for easy application and
maintenance.

Default Fiber Path is Pair Flipped


Fiber 1 2 3 4 5 6 7 8 9 10 11 12
MTP
Color Blue Orange Green Brown Slate White Red Black Yellow Violet Rose Aqua

LC 1B 1A 2B 2A 3B 3A 4B 4A 5B 5A 6B 6A

The default cable (12 core) outer dimension is 4.5mm


Outer sheath options: OFNP/LSZH
Fan-out length: 900 +/- 50mm
MPO Maximum Insertion Loss: 0.5dB (MM); 0.7dB (SM)
Minimum bending radius: 90mm during installation; 45mm after installation

Compliance standards:
 ANSI/TIA-568-C.3, ISO/IEC 11801
 TIA-942

Packing Information (based on the standard cable of Diameter 4.5 and with pulling sock protection)

Cable Length Packing Info


<50m Plastic bag (310*380mm) and shipping box (350*300*146mm)
>=50m Corrugated carton reel (D419mm x H164mm) and shipping box (610*335*594mm)

Ordering Information (MTP 24-core will be 12-core MTP connector x2 units)


Harness Connector Type Fiber Type Fiber Sheath Cable Length Fiber Path
ML=MTP-LC S= Single Mode, XXXX
FP=OFNP S= Straight through, R =
Duplex 12 core OS2 (5M-10M; 0.5m
ACTMH Reversed, F= Pair Flipped,
MT=MTP-LC T= Multi-Mode OM3 separator)
LS=LSZH RF= Reversed, Pair Flipped
Duplex 24 core G= Multi-Mode OM4 e.g. 13.5m = 0135

Page 6 of 7
IV. MPO Enclosure

Schneider Electric MPO Enclosure is specifically designed for the LAN and data center environment. The
enclosures are mountable in 19’ equipment racks or cabinets. It provides the cross connect function for whole
data center equipments.

The 1U height enclosure accepts maximum 3 MPO cassettes (max fiber counts=72), and maximum 12 MPO
cassettes (max fiber counts=288) can be installed on the 4U unit.

Transparent front cover (available on 4U unit) provides instant visibility of the connection status, in the
meantime provides perfect protection against dust and humidity.

Enclosure Dimensions (L x W x H)
1U Unit 400mm x 482mm x 44cm
4U Unit 400mm x 482mm x 177mm

Compliance standards:
 EIA-310-D
 IEC 60297

Ordering Information:

Part Number Description


ACTMP1U 1U MPO Panel, unloaded (Max. 3 cassettes)
ACTMP4U 4U MPO Panel, unloaded (Max. 12 cassettes)
ACTMPBP Snap-in Blank Module Plate
ACTMANFNC MTP ADAPTER, W/O FLANGE, W/O CLIP

Page 7 of 7