Technical MCCB All-New
Technical MCCB All-New
Technical information
62D4-E-0058
CONTENTS
Chapter 1 Chapter 4
Environment and usage
Protecting low-voltage circuits
precautions
1-1 Description ...................................................................... 4 4-1 Standard conditions ...................................................... 90
1-2 Overcurrent protection .................................................... 5 4-2 Application to special environments ............................. 91
1-3 Phase-loss protection ..................................................... 6 4-3 Connection precautions ................................................ 93
4-4 Malfunction due to transient inrush current .................. 94
Chapter 2
Operating characteristics and
performance Chapter 5 Maintenance inspections
2-1 Overcurrent tripping characteristics ................................ 8 5-1 Faults and causes ......................................................... 96
2-2 Breaking performance .................................................. 11 5-2 Periodic inspections ...................................................... 98
2-3 Overload switching performance .................................. 26 5-3 Replacement recommendations ................................. 100
2-4 Performance with current at 100% ................................ 27
2-5 Durability ....................................................................... 29 Chapter 6 Short-circuit current calculation
2-6 Withstand voltage performance .................................... 31
2-7 Handle operating force and angle ................................. 32
6-1 Calculating short-circuit current .................................. 102
Chapter 3 Selection and application Glossary ....................................................................... 106
3-1 Selection check points .................................................. 34
3-2 Cascade trip applications ............................................. 40
3-3 Selective trip applications ............................................. 43
3-4 Wiring protection ........................................................... 52
3-5 Motor circuit applications .............................................. 57
3-6 Applications on the primary side of transformers ......... 63
3-7 Welder circuit applications ............................................ 66
3-8 Selecting an MCCB for capacitor circuit ....................... 69
3-9 MCCBs for semiconductor circuit ................................. 73
3-10 Protecting SSCs using MCCBs or MMSs .................... 77
3-11 Protecting inverter circuits using MCCBs .................... 79
3-12 MCCBs for high frequency circuits .............................. 80
3-13 MCCBs for DC circuit applications .............................. 81
3-14 MCCBs for UPS applications ....................................... 83
3-15 MCCBs for servo amplifier applications ....................... 84
3-16 Ground fault protection in system applications ............ 85
Introduction
FUJI has employed its comprehensive technical expertise to bring a complete
range of models and features to its line of molded case circuit breakers (MCCBs),
the mainstay for low-voltage overcurrent protection devices.
A more complete line of breakers is combined with better performance and
greater economy to yield a wider selection of products than ever before. Now
with superior applicability, operability and safety, MCCBs have firmly established
their place in the world of overcurrent protection devices for low-voltage circuits.
In response to customer needs, this product line represents some of the safest
and most economical protection systems available. This Technical Information
contains the data that is needed for selecting the most appropriate FUJI MCCB.
It is provided to help you design superior equipment that is safe and cost efficient.
Protecting low-voltage
Chapter 1 circuits
CONTENTS
3
Protecting low-voltage circuits
1 1-1 Description
1-1 Description
The most common faults occurring with low-voltage circuits
are overcurrent (resulting from overload or short-circuit),
ground faults, and phase-loss. A device that will protect
equipment from these faults is therefore needed for reliable
and economical operation. The following section describes
lowvoltage circuit faults along with measures to protect against
them.
4
Protecting low-voltage circuits
1-2 Overcurrent protection
1
5
Protecting low-voltage circuits
1 1-3 Phase-loss protection
6
Operating characteristics
Chapter 2 and performance
CONTENTS
2-5 Durability
2-5-1 Switching durability ......................................................................................................29
2-5-2 Trip switching durability ...............................................................................................29
2-5-3 Rated ultimate short-circuit breaking performance .....................................................29
2-5-4 Switching durability of accessories ..............................................................................30
7
Operating characteristics and performance
2 2-1 Overcurrent tripping characteristics
8
Operating characteristics and performance
2-1 Overcurrent tripping characteristics
2
Hot start
Current
Mounting angle Vertical * Horizontal Horizontal Slant 15° Slant 45° Slant 15° Slant 45°
(upside (backward) (backward) (forward) (forward)
down)
ON ON ON
P ON
ON
ON OFF
MCCB ELCB (Reference) OFF ON OFF OFF OFF OFF
BW32AAG, BW32SAG EW32AAG, EW32EAG 100% 85% 115% 95% 90% 105% 110%
EW32SAG
correction factor
ON
OFF
ON OFF OFF ON
OFF
ON
9
Operating characteristics and performance
2 2-1 Overcurrent tripping characteristics
(5) Frequencies
(a) Commercial frequencies (50Hz, 60Hz)
The characteristics of breakers are generally the same at 50
and 60Hz.
Trip device Inverse time-delay trip characteristic Instantaneous trip characteristics Operating characteristic curve
Thermal-magnetic None The instantaneous trip current is
higher than that for an AC circuit.
Operating time
The rate of variation depends DC
on the ampere-frame size, rated AC
current and model. The trip current
can be as high as 140% of the AC Current
value.
Operating time
DC
AC
Current
10
Operating characteristics and performance
2-2 Breaking performance
2
When a short-circuit fault occurs and a short-circuit current Non current-limiting type
flows, the instantaneous trip device is actuated to quickly open
the contacts. An arc is generated between the contacts the
moment the moving contact separates from the stationary
Supply voltage
contact.
The rapid movement of the moving contact away from the 2 2 460 V
stationary contact draws the arc rapidly across the arc horn
and into the arc quencher. The arc lengthens as the distance L1 phase voltage
between the contacts increases, until the electromotive force 14.9 kA
L1 phase current
generated between the grid and arc current drives the arc 39.5 kA
deeply into the V-notches in the magnetic sheets composing L2 phase voltage
the arc quencher’s grid. The grid thus splits the arc into a L2 phase current
series of shorter arcs. With the arc stretched and split up in
this way, the resistance and the arc voltage increase due to L3 phase voltage
the combined action of cooling by the grid, the rising pressure L3 phase current
in the arc quencher, and the cathode effect. The arc is
43.0 kA
extinguished (quenched) when the arc voltage becomes larger
than the supply voltage. At this time, a voltage equivalent
to the supply voltage (recovery voltage) appears across the Current-limiting type
contacts. This condition is called completion of breaking.
In general, a circuit in which a large short-circuit current
occurs has a low power factor. If the arc is quenched
at the zerocrossing point of the short-circuit current, a
circuit-constant, dependent oscillating transient voltage is
superimposed on the recovery voltage that appears across
the contacts. This voltage is called the restrike voltage and
can cause rearcing between the contacts if the isolation
between the contacts has not recovered sufficiently. To achieve
complete breaking without rearcing, powerful arc-quenching
action and sufficient contact spacing must be ensured quickly.
To achieve current-limiting breaking, current-limiting MCCBs
use the electromotive force generated across two parallel
conductors to quickly open the contacts without waiting for
instantaneous trip, while increasing the arc voltage in an
extremely short time. In DC circuits, the current does not fall
to zero as in AC circuits. The arc voltage must be increased
through a powerful arc quenching effect to suppress the
current: arc quenching is complete when the supply of energy
needed to maintain arcing is no longer available.
Fig. 2-5 shows the three-phase short-circuit current breaking
test oscillograms.
11
Operating characteristics and performance
2 2-2 Breaking performance
C
X
iS A'
Y
i B C'
t
0
P'
iS: Short-circuit current
C-C': Intermediate line between the envelopes A-A' and B-B'
P-P': 1/2 cycle after occurrence of short-circuit fault
X: AC component of short-circuit current
Y: DC component of short-circuit current
12
Operating characteristics and performance
2-2 Breaking performance
2
(4) Breaking characteristics flow until completion of breaking. The time interval between
the occurrence of a short-circuit fault and the opening of the
When the magnitude of an overcurrent exceeds a certain
contacts is called the contact opening time. The time interval
limit, the instantaneous trip device is actuated to open the
between completion of breaking and quenching of the arc
pole immediately. The minimum current that can actuate the
generated by contact opening is called the arcing time. The
instantaneous trip device is called the instantaneous trip
sum of the contact opening time and the arcing time, or the
current, which is expressed as a symmetrical effective value.
period of time from the occurrence of a short-circuit fault to
With thermal-magnetic MCCBs, the instantaneous trip current
completion of breaking, is called the total opening time. Table
setting is adjustable because their instantaneous trip device
2-7 lists the contact opening times, arcing times, and total
is installed separately from the inverse time-delay trip device.
opening times of MCCBs at breaking of the rated breaking
This eases coordination with other devices. Fig. 2-7 shows
current.
the progress of time after the start of short-circuit current
Time
Contact Zero-crossing point of
opening
Load current time Arcing time short-circuit current
Short-circuit current
Total opening time breaking point
Recovery voltage
Restrike voltage
(5) Maximum let-through current and maximum value, the smaller the thermal effects on the cable and load
breaking I2t equipment. Fig. 2-8 to 2-9 and Fig. 2-10 to 2-11 give the
maximum let-through I2t or maximum let-through current, and
The current that would flow through a short circuit without a
available short-circuit current of MCCBs.
circuit breaker is called the available short-circuit current. It is
the short-circuit current that is determined from the impedance
map at circuit breaker selection, not the current that is actually
interrupted by the circuit breaker. The current that actually
2-2-3 Arc space
flows through the circuit is smaller than the available short- When a short-circuit current is broken, an ionized gas is
circuit current. As the trip device in the circuit breaker is emitted from the breaker’s line side exhaust vent and, because
actuated to open the contact immediately on occurrence of a this gas is conductive, it could induce an interphase short
short circuit, the arc voltage is increased to inhibit current flow. circuit or ground fault if it bridges adjacent bare live parts or
This is equivalent in effect to having a variable resistor, called a bare live part and an adjacent grounded metallic surface.
an arc resistor, connected in series in the circuit. Because this is potentially hazardous, an arc space (insulation
Current-limiting circuit breakers that take advantage of the space) is required for safety.
magnetic repulsion force represent an application of this Table 2-7 lists the arc spaces required for specific conditions.
principle; current-limiting breaking is done before the short- When wiring is done, live parts should be either taped or
circuit current reaches its peak value. protected by insulating barriers in the ranges specified in
The maximum current that can flow through the circuit breaker Table 2-7 to allow for conditions that could be encountered
is called the maximum let-through current, which is expressed while the MCCB is in service. Improved insulation may be
as a peak value. The smaller the maximum let-through current, needed outside the arc space depending on the service
the less mechanical stress is imposed on the cable and load conditions of the MCCB.
equipment. With a high short-circuit current having a low
power factor, the transient peak value is more than twice the
symmetrical effective value. In mechanical stress studies,
therefore, a choice must be made between the current-
limiting type and the non-current-limiting type, along with full
allowance for electromotive force.
13
Operating characteristics and performance
2 2-2 Breaking performance
100
80
50
30
20
(16)* 35mm2
(12) 30mm2
10
(8.18) 25mm2 8 BW630EAG, RAG, HAG BW800EAG, RAG, HAG
R H
(6.8) 22mm2 EW630EAG, RAG, HAG EW800EAG, RAG, HAG
BW630RAGU, HAGU BW800RAGU, HAGU
E
EW630RAGU
5
BW400EAG, SAG, RAG, HAG
(3.35) 16mm2 S R H
Max. let-through current
(1.05) 8mm2 1
R H BW50HAG (40, 50A) BW125JAG, RAG, HAG (40 to 125A)
0.8 EW50HAG (40, 50A) EW125JAG, RAG, HAG (40 to 125A)
J BW125JAGU, RAGU (40 to 125A)
EW125JAGU, RAGU (40 to 125A)
(0.471) 6mm2 0.5 BW32SAG BW50, 63SAG
(0.4) 5.5mm2 BW50, 63EAG EW50, 63SAG
BW100AAG BW50, 63RAG BW50RAGU
0.3 EW32SAG BW100EAG BW100EAGU
EW50, 63EAG EW50, 63RAG EW50RAGU
(0.21) 4mm2 EW100AAG EW100, EAG, EAD EW100EAGU
0.2
(0.13) 3.5mm2 BW32, 50AAG BW50HAG (30A) BW125JAG, RAG, HAG (30A)
EW32, 50AAG EW50HAG (30A) EW125JAG, RAG, HAG (30A)
0.1 BW125JAGU, RAGU (30A)
(0.082) 2.5mm2 0.08 R H EW125JAGU, RAGU (30A)
J
R H BW50HAG (20A) BW125JAG, RAG, HAG (20A)
(0.05) 2mm2 0.05 J EW50HAG (20A) EW125JAG, RAG, HAG (20A)
R H BW125JAGU, RAGU (20A)
J EW125JAGU, RAGU (20A)
0.03
BW50, 63EBG BW50HAG (15A) BW125JAG, RAG, HAG (15A)
EW50, 63EBG EW50HAG (15A) EW125JAG, RAG, HAG (15A)
0.02 BW125JAGU, RAGU (15A)
EW125JAGU, RAGU (15A)
BW32, 50, 63SBG BW50RBGU
EW32, 50, 63SBG EW50RBGU
0.01
1 2 5 10 20 50 100 200 500 1000
Available short-circuit current (rms. sym.) (kA)
Note: * The parentheses ( ) indicate approximate tolerances I2t for each wire gauge. (See Table 3-11, Chapter 3.)
14
Operating characteristics and performance
2-2 Breaking performance
2
100
80
50
30
BW630EAG, RAG, HAG BW800EAG, RAG, HAG
EW630EAG, RAG, HAG EW800EAG, RAG, HAG
20
(16)* 35mm2 BW630RAGU, HAGU BW800RAGU, HAGU
EW630RAGU
H
(12) 30mm2
R BW400EAG, SAG, RAG, HAG
10 E H EW400EAG, SAG, RAG, HAG
(8.18) 25mm2 R BW400EAGU, SAGU, RAGU, HAGU
8
(6.8) 22mm2 S EW400SAGU, RAGU, HAGU
E
(1.31) 10mm2
Max. let-through current
(1.05) 8mm2 1
0.8 BW50, 63SAG
ò i2dt (x106A2s)
0.03
0.02
BW50, 63EBG
EW50, 63EBG
0.01
1 2 5 10 20 50 100 200 500 1000
Note: * The parentheses ( ) indicate approximate tolerances I2t for each wire gauge. (See Table 3-11, Chapter 3.)
15
Operating characteristics and performance
2 2-2 Breaking performance
1000
800
600
500
400
300 Unlimited
200
Peak let-through current (kA)
10 BW50HAG (30A)
H
S R BW125JAG, SAG, RAG, HAG (30A)
J H
S R EW125JAG, SAG, RAG (30A)
J
S R H
BW50HAG (20A)
5 J
BW125JAG, SAG, RAG, HAG (20A)
EW125JAG, SAG, RAG (20A)
BW50, 63RAG BW50HAG (15A)
BW100EAG BW125JAG, SAG, RAG, HAG (15A)
BW32SAG BW50, 63SAG EW50, 63RAG EW125JAG, SAG, RAG (15A)
2 BW50, 63EAG EW50, 63SAG EW100EAG
BW100AAG
EW32SAG
BW32, 50AAG EW50, 63EAG
EW32, 50AAG EW100AAG
1
1 2 5 10 20 50 100 200 500 1000
16
Operating characteristics and performance
2-2 Breaking performance
2
1000
800
600
500
400
300 Unlimited
200
BW630EAG, RAG, HAG
Peak let-through current (kA)
H BW50HAG (30A)
R BW125JAG, SAG, RAG, HAG (30A)
S
J R H
S EW125JAG, SAG, RAG (30A)
10 J
R H
J S
BW50HAG (20A)
BW125JAG, SAG, RAG, HAG (20A)
EW125JAG, SAG, RAG (20A)
5 BW50HAG (15A)
BW125JAG, SAG, RAG, HAG (15A)
BW50, 63RAG EW125JAG, SAG, RAG (15A)
BW100EAG
BW32SAG BW50, 63SAG EW50, 63RAG
BW50, 63EAG EW50, 63SAG EW100EAG
2 BW100AAG
EW32SAG
BW32, 50AAG EW50, 63EAG
EW32, 50AAG EW100AAG
17
Operating characteristics and performance
2 2-2 Breaking performance
18
Operating characteristics and performance
2-2 Breaking performance
2
5 5
3 3
2 2
1.41 1.41
8 8
10 10
5 5
3 3
2 2
7 7
10 10
2 2
As 5 As 5 BX630
R H BX630 H
3 BX400 3 BX400
2 2 R
6 6 BX250
10 R H BX250
10
R, H
BX100 BX100
5 BX160
5 BX160
3 3
2 2
5 5
10 10
5 5
3 3
2 2
2 3 4 6 10 20 30 40 50 70 100 150 200 300 2 3 4 6 10 20 30 40 50 70 100 150 200 300
kA rms kA rms
19
Operating characteristics and performance
2 2-2 Breaking performance
200 200
146 146
100 100
80 80
70 70
60 BX630
60
50 H 50
BX400
40 R 40 BX630
k kÂ
30 BX250 30 H BX400
H BX100
R
BX160
20 20 R BX250
BX100
BX160
10 10 R, H
8 8
7 7
6 6
5 5
4 4
2 3 4 6 10 20 30 40 50 70 100 200 300 2 3 4 6 10 20 30 40 60 100 200 300
65
kA rms kA rms
20
Operating characteristics and performance
2-2 Breaking performance
2
Current-limiting curves
Thermal-stress curves
Voltage 400/440 V AC (1) Voltage 660/690 V AC
Limited energy Limited energy
BX800H
BX800R BX1000H BX800H
BX1000R BX1250H BX1000H
BX1250R BX1600H BX1250H
BX1600R BX1600H
BX800R
BX1000R
BX1250R
BX1600R
R H BX630 H BX630
BX400 BX400
R
R H BX250
BX250 R
BX100
BX100 BX160
BX160
Rated short-circuit current (kA rms) Rated short-circuit current (kA rms)
Current-limiting curves
Voltage 400/440 V AC (1) Voltage 660/690 V AC
Limited short-circuit current (k peak) Limited short-circuit current (k peak)
BX800H
BX1000H
BX1250H BX800H
BX1600H BX1000H
BX800R BX1250H
BX1000R BX1600H
BX1250R BX800R
BX1600R BX1000R
BX1250R
BX1600R
H BX630
R kÂ
k BX400
H BX630
H
R BX250 BX400
BX100 R BX250
BX160
BX100
BX160
Rated short-circuit current (kA rms) Rated short-circuit current (kA rms)
21
Operating characteristics and performance
2 2-2 Breaking performance
D3
A
D1
A
A
F
D3
B
C
B
D2
Fig 4 Fig 5 Fig 6
Basic type Bare earth plate Upper and lower Distance of side Distance of front plate Dimensions of taping or Wire
distance plate insulation barrier exposure
A B C Coated plate Bare plate In the case of taping In the case
F F Crimp Busbar of insulation
terminal connection barrier
MCCB ELCB 440V AC 230V AC 440V AC 230V AC 440V AC 230V AC 440V AC 230V AC 440V AC 230V AC D1 D2 D3
BW32SBG EW32SBG 10 10 20 20 10 10 0 0 − − − 20 −
BW50EBG EW50EBG 10 10 20 20 10 10 0 0 − − − 20 −
BW50SBG EW50SBG 10 10 20 20 10 10 0 0 − − − 20 −
BW63EBG EW63EBG 10 10 20 20 10 10 0 0 − − − 20 −
BW63SBG EW63SBG 10 10 20 20 10 10 0 0 − − − 20 −
BW32AAG EW32AAG − 10 − 10 − 10 − 0 − 0 10 10 5
− EW32EAG 10 10 30 30 20 15 0 0 0 0 30 30 5
BW32SAG EW32SAG 10 10 30 30 20 15 0 0 0 0 30 30 5
BW50AAG EW50AAG − 10 − − − 10 − 0 − 0 10 10 10
BW50EAG EW50EAG 10 10 30 30 25 15 0 0 0 0 30 30 10
BW50SAG EW50SAG 30 10 40 40 25 15 0 0 0 0 30 30 10
BW50RAG EW50RAG 50 25 50 50 25 15 0 0 10 5 Length of exposed section in live section + 20
50 50 10
BW50HAG EW50HAG 60 60 80 80 50 20 5 0 10 5 80 80 −
BW63EAG EW63EAG 10 10 30 30 25 15 0 0 0 0 30 30 −
BW63SAG EW63SAG 30 10 40 40 25 15 0 0 0 0 30 30 −
BW63RAG EW63RAG 50 25 50 50 25 15 0 0 10 5 50 50 −
BW100AAG EW100AAG − 10 − 20 − 15 − 0 − 0 50 50 −
BW100EAG EW100EAG 50 25 50 50 25 15 0 0 0 5 50 50 −
BW125JAG EW125JAG 40 40 50 50 25 20 0 0 10 5 50 50 −
BW125RAG EW125RAG 40 40 60 60 25 20 5 0 10 5 50 50 −
BW125HAG EW125HAG 60 60 80 80 50 20 5 0 10 5 80 80 −
BW250EAG EW250EAG 40 40 50 50 50 15 0 0 10 5 80 80 −
BW250JAG EW250JAG 40 40 60 60 50 20 0 0 10 5 80 80 −
BW250RAG EW250RAG 40 40 80 80 50 20 5 0 10 10 80 80 −
BW250HAG EW250HAG 60 60 80 80 60 60 5 0 10 10 80 80 −
BW400EAG EW400EAG 100 80 100 80 50 20 0 0 10 5 100 100 −
BW400SAG EW400SAG 100 80 100 80 50 20 0 0 10 5 100 100 −
BW400RAG EW400RAG 100 80 100 80 80 40 5 0 20 10 100 100 −
BW400HAG EW400HAG 100 80 100 80 80 40 5 0 20 10 100 100 −
BW630EAG EW630EAG 100 80 100 80 80 40 0 0 10 5 100 100 −
BW630RAG EW630RAG 100 80 100 80 80 40 5 0 20 10 100 100 −
BW630HAG EW630HAG 100 100 120 100 80 40 5 0 20 10 120 120 −
BW800EAG EW800EAG 100 80 100 80 80 40 0 0 10 5 100 100 −
BW800RAG EW800RAG 100 80 100 80 80 40 5 0 20 10 100 100 −
BW800HAG EW800HAG 120 100 120 100 80 40 5 0 20 20 120 120 −
BW1000RAE − 120 120 150 150 80 80 0 0 0 0 −
Larger than the dimensions of
BW1250RAE − 120 120 150 150 80 80 0 0 0 0 −
exposed section in live section
BW1600RAE − 150 150 150 150 100 100 0 0 0 0 −
Fig 1, 2, 3, 9 Fig 4, 5, 6, 9 Fig 8, 10 Fig 12 Fig 7 Fig 11 Fig 7, 8 Fig 1
22
Operating characteristics and performance
2-2 Breaking performance
2
Installation example
Safety clearance
Minimum distance between two Minimum distance between circuit
adjacent circuit breakers breaker and front or rear panels
Front F
panel
A1
B=0 F
Bare or painted sheetmetal Note: if F < 8 mm: an insulating screen or long
terminal shield is mandatory.
Minimum distance between circuit breaker and top, bottom or side panels
D1 D1 D1
D1
D2 C1
Devices without accessories. Devices with interphase barriers or long or short terminal shields.
23
Operating characteristics and performance
2 2-2 Breaking performance
146.5
F (*) An overhead clearance of 50 mm
is required to remove the arc chutes.
Installation example
Painted sheetmetal
Direct connection by bare Connection by cables with lugs, Connection by insulated bars, Rear connection or plug-in
cables, devices with terminal devices with terminal shields. devices with terminal shields. base, devices with terminal
shields. shields.
24
Operating characteristics and performance
2-2 Breaking performance
2
25
Operating characteristics and performance
2 2-3 Overload switching performance
26
Operating characteristics and performance
2-4 Performance with current at 100%
2
Table 2-10 MCCB and ELCB temperature rise at the rated current
27
Operating characteristics and performance
2 2-4 Performance with current at 100%
28
Operating characteristics and performance
2-5 Durability
2
2-5-3 Rated ultimate short-circuit breaking Table 2-13 Rated ultimate short-circuit breaking
29
Operating characteristics and performance
2 2-5 Durability
30
Operating characteristics and performance
2-6 Withstand voltage performance
2
2-6 Withstand voltage performance Fig. 2-12 Test circuit for rated impulse withstand voltage
characteristics
2-6-1 Rated power frequency withstand voltage
Impulse generator
(IEC 60947-1, 2) Rs L
(1) Circuit breaker body
The breaker should function normally with 2000V applied for
Air gap Specimen
one minute at the following locations if it is rated at 300V or
less, and with 2500V applied for one minute at the following
Capacitor
locations if it is rated at more than 300V and 600V or less. Ro To the CRT
s "ETWEEN TERMINALS ON THE POWER SUPPLY SIDE AND THE LOAD
side with the breaker in the open or tripped state.
s "ETWEEN OPPOSITE POLARITY TERMINALS WITH THE BREAKER CLOSED
(However, electronic components used for ground-fault
detection and overvoltage protection elements must be
electrically left open.)
s "ETWEEN THE LIVE PART AND GROUND WITH THE BREAKER OPEN AND Fig. 2-13 Impulse voltage waveform
closed. 100
Conduct the test on a new specimen. Use one that came with
the accessory, such as an auxiliary switch (W), alarm switch
(K), shunt trip device (F) or undervoltage trip device (R).
Fig. 2-14 shows the criteria for the test.
31
Operating characteristics and performance
2 2-7 Handle operating force and angle
Line side
ON
D
Trip
C
OFF
Reset
r A
B
MCCB ELCB (Reference) Operating force (N·m) Operating angle ( ) Dimensions (mm) Rotating
radius r
OFF ON Trip ON OFF Trip Reset A B C D (mm)
ON OFF Reset
BW32AAG-2P EW32AAG-2P 0.42 0.54 0.89 22 15 4 17.5 57 84 9.5 – 26.9
BW32SAG-2P
BW50AAG-2P EW50AAG-2P
BW50EAG-2P
BW50SAG-2P
BW50RAG-2P
BW63EAG-2P
BW63SAG-2P
BW63RAG-2P
BW100EAG-2P
BW32AAG-3P EW32AAG-3P 0.59 0.7 1.6 22 15 4 17.5 57 84 9.5 – 26.9
EW32EAG-3P
BW32SAG-3P EW32SAG-3P
BW50AAG-3P EW50AAG-3P
BW50EAG-3P EW50EAG-3P
BW50SAG-3P EW50SAG-3P
BW50RAG-3P EW50RAG-3P
BW63EAG-3P EW63EAG-3P
BW63SAG-3P EW63SAG-3P
BW63RAG-3P EW63RAG-3P
BW100AAG-3P EW100AAG-3P
EW100EAG-2P
BW100EAG-3P EW100EAG-3P
BW125JAG-2P 1.18 1.3 1.67 21 10 11 12.5 33.7 95 – 0.8 61.3
BW50HAG-3P 1.72 1.9 2.45 21 10 11 12.5 33.7 95 – 0.8 61.3
BW125JAG-3P EW125JAG-3P
BW125SAG-2P,3P EW125SAG-3P
BW125RAG-2P,3P EW125RAG-3P
BW125HAG-3P
BW125JAG-4P EW125JAG-4P 2.35 2.6 3.35 21 10 11 12.5 33.7 95 – 0.8 61.3
BW125SAG-4P EW125SAG-4P
BW125RAG-4P EW125RAG-4P
BW160EAG-3P EW160EAG-3P 3.37 3.8 4.9 21 10 11 12.5 33.7 95 – 0.8 61.3
BW160JAG-2P,3P EW160JAG-3P
BW160RAG-2P,3P EW160RAG-3P
BW250EAG-3P EW250EAG-3P
BW250JAG-2P,3P EW250JAG-3P
BW250RAG-2P,3P EW250RAG-3P
BW250HAG-3P
BW160JAG-4P EW160JAG-4P 4.6 5.21 6.74 21 10 11 12.5 33.7 95 – 0.8 61.3
BW160SAG-4P EW160SAG-4P
BW160RAG-4P EW160RAG-4P
BW250JAG-4P EW250JAG-4P
BW250SAG-4P EW250SAG-4P
BW250RAG-4P EW250RAG-4P
BW400EAG-2P,3P EW400EAG-3P 8 7.5 14 22 10.5 6.7 13.5 54.6 146 4.3 – 91.4
BW400SAG-2P,3P EW400SAG-3P
BW400RAG-2P,3P EW400RAG-3P
BW400HAG-2P,3P EW400HAG-3P
BW400RAG-4P EW400RAG-4P 10.93 10.25 19.13 22 10.5 6.7 13.5 54.6 146 4.3 – 91.4
BW400HAG-4P EW400HAG-4P
BW630EAG-3P EW630EAG-3P 11 10 20 22 10.5 6.7 13.5 54.6 146 4.3 – 91.4
BW630RAG-3P EW630RAG-3P
BW630HAG-3P EW630HAG-3P
BW800EAG-3P EW800EAG-3P
BW800RAG-3P EW800RAG-3P
BW800HAG-3P EW800HAG-3P
BW630RAG-4P 15.03 13.67 27.33 22 10.5 6.7 13.5 54.6 146 4.3 – 91.4
BW630HAG-4P
BW800RAG-4P
BW800HAG-4P
32
Selection and application
Chapter 3 CONTENTS
3-1 Selection check points
3-1-1 MCCB selection check points ...................................................................................... 34
3-1-2 Selecting and MCCB ratings ........................................................................................ 36
3-1-3 Overcurrent protection principle ................................................................................... 37
3-1-4 Protective coordination ................................................................................................ 37
33
Selection and application
3 3-1 Selection check points
(2) Location
s %NVIRONMENT CONDITIONS
s !MBIENT TEMPERATURE
2. Location
(4) Applications
s ,INE PROTECTION s -OTOR PROTECTION
s )NSTANTANEOUS TRIP s -ARINE USE
s 3PECIAL PURPOSE7ELDER CAPACITOR LIGHTS
6. Short-circuit current
(5) Short-circuit breaking capacity
7. Loads and wires
s &ULLY RATED s 3ELECTIVE TRIP
s #ASCADE BACKUP TRIP 8. Wire characteristics
(7) Loads
s -##" RATED CURRENT s 7IRE SIZE BUS BARS 4. Application
s #URRENT TIME CHARACTERISTICS Load 7. Loads
8. Equipment characteristics
(8) Characteristics
s 7IRE AND LOAD EQUIPMENT
Mechanical and allowable thermal characteristics
s "REAKER
Breaking characteristics
Operation characteristics
(9) Operation
s 3WITCHING FREQUENCYOPERATING DURABILITY
s /PERATION METHOD
Remote – manual, motor driven
External operating handle (V and N)
34
Selection and application
3-1 Selection check points
3
Check point Check points for system Check points for circuits Check points for MCCBs Specifications of MCCBs
designing and protective equipment
35
Selection and application
3 3-1 Selection check points
36
Selection and application
3-1 Selection check points
3
b c
a Protected region
Current
37
Selection and application
3 3-1 Selection check points
Kind of coordination Coordination between the protective Coordination between protective devices
device and equipment to be protected
Selective trip coordination Cascade (backup) trip coordination
Objective Protecting equipment Improved power supply reliability Economical protective coordination
Description A protective device protects the wiring Protective devices on the line An economical circuit breaker with a small-
and load equipment against thermal side and the load side working in short-circuit breaking capacity is used,
and mechanical damage due to coordination prevent the short- with the short-circuit breaking of short-
overcurrents. circuit fault from extending from circuit currents higher than the rated short-
the fault circuit to other cables and circuit breaking capacity being undertaken
also minimize the scope of power by protective devices connected in series
failure. on the source line side.
Coordination condition s 3AFE BREAKING OF FAULT CURRENTS The load side protection device If a short-circuit current higher than the Icu
s 0ROTECTION OF WIRING AND LOAD completes current breaking over of the load side protection device flows,
equipment against thermal or the entire fault current range line side protection devices connected
mechanical damage. before the line side protection in series break the current, protecting
device is tripped, or before starting the load side protection device against
irreversible trip operation. expected thermal and mechanical
damages.
Protective device state Single or combined Combined Combined
Typical system
(indicating the
MCCB Solid-state trip MCCB
relationship of Fuse
coordination) (Protective device) type MCCB
Wiring
(Protected equipment)
Motor starter
(Protective device) MCCB
Fuse
MCCB MCCB
MCCB
M Motor
(Protected equipment)
The breaker away from the shorting point on the power supply Overcurrent protection method:
side must trip whenever short-circuit current occurs, but it must An overcurrent breaker operates on the principle that one
protect equipment from the thermal and mechanical stresses protective device alone will cut off short-circuit current passing
generated as short-circuit current passes through the circuit as through it. This is called a fully-rated system. When a single
well. This means the current peak value ipb and the let-through protective device is insufficient, then another breaker is
current ³ ib2dt at the time of MCCB breaking must be below the installed at the power supply side. This is called a cascade
allowable current peak value ipa of the protected equipment (backup) system, and it is often used to take advantage of
as well as the ³ ia2dt in the breaking characteristics of the more economical breaking method.
overcurrent protective device. In short, the following must be In an effort to ensure a more reliable power supply, only the
true. breaker on the power supply side that is closest to the fault
ipa > ipb, ³ ia2dt > ³ ib2dt point will trip when a short-circuit fault occurs at a branching
circuit such as a distribution system terminal. The operating
This point is especially important because breakers with
times must be coordinated between the breakers as a result
relatively low rated currents and higher short-circuit braking
so they will not track the breaker on the power supply side.
capacity are used more offen in today’s branch circuits.
This is known as selective trip coordination as opposed to the
fully-rated system. (Table 3-3)
38
Selection and application
3-1 Selection check points
3
PA 10
1.0
(sec)
0.1
PB 0.01
Operating characteristic
of branch circuit breaker
0.001
F 2 4 8 2 4 8 2 4 8
10 100 1000
L1 L2 L3 LX Current (A)
Region protected by branch Region protected by
circuit breaker main circuit breaker
39
Selection and application
3 3-2 Cascade trip applications
3-2 Cascade trip applications 3-2-2 Criteria for cascade (backup) trip
coordination
3-2-1 Conditions for cascade (backup) trip
coordination Various breaker-based breaker-breaker or breaker-fuse
combinations suitable for backup have been reported.
A cascade (backup) system established between overcurrent However, testing and other standards are not well defined
circuit breakers can yield a very economical system as for backup protection at this point. Protective equipment
described in 3-1-4. combinations will have to be defined through uniform testing
When the main circuit breaker in a cascade (backup) system methods and criteria in order to ensure proper backup
has sufficient breaking capacity and trips quickly in the event protection with minimal confusion.
of a short-circuit fault, it can minimize the amount of energy Appendix A of IEC60947-2 stipulates protection coordination
passing through the branch MCCB. This depends on the standards for cascade (backup) systems. Table 3-4 shows
following conditions, however, which the main breaker alone criteria from that appendix.
or a branch MCCB connected in series with the main breaker
must satisfy: Table 3-4 Criteria for cascade (backup) systems (Appendix A of
(a) The peak let-through current must be kept below the IEC60947-2)
allowable mechanical strength limit of the branch MCCB. Item Items tested after the shorting test Criteria
IPL < IPA
1 Withstand voltage and insulation resistance Good
(b) The let-through I2t must be kept below the allowable
2 Contact welding Not welded
thermal strength limit of the branch MCCB.
³ i L 2dt < ³ i A 2dt 3 250% current tripping Good
40
Selection and application
3-2 Cascade trip applications
3
Tables 3-5 (a) and (b) show MCCB combination used for
cascade (backup) coordination.
Table 3-5 (a) Summary of combinations used for cascade (backup) coordination
230V AC
Branch circuit breaker Main BW BW BW BW BW BW BW BW BW BW BW BW BW BW BW BW BW BW
circuit 100 125 125 125 160 160 160 250 400 400 400 400 630 630 630 800 800 800
breaker EAG JAG RAG JAG EAG JAG RAG HAG EAG SAG RAG HAG EAG RAG HAG EAG RAG HAG
model BW BW BW
250 250 250
EAG JAG RAG
EW EW EW EW EW EW EW EW EW EW EW EW EW EW EW EW EW EW
100 125 125 125 160 160 160 250 400 400 400 400 630 630 630 800 800 800
EAG JAG RAG JAG EAG JAG RAG HAG EAG SAG RAG HAG EAG RAG HAG EAG RAG HAG
EW EW EW
250 250 250
EAG JAG RAG
MCCB ELCB Icu (kA) 25 50 100 125 36 50 100 125 50 85 100 125 50 100 125 50 100 125
(reference) sym
BW32AAG EW32AAG 2.5 5 10 10 10 5 7.5 7.5 7.5 – – – – – – – – – –
EW32EAG 2.5 5 10 10 10 5 7.5 7.5 7.5 – – – – – – – – – –
BW32SAG EW32SAG 5 22 50 60 60 10 30 30 30 – – – – – – – – – –
BW50AAG EW50AAG 2.5 5 10 10 10 5 7.5 7.5 7.5 – – – – – – – – – –
BW50EAG EW50EAG 5 22 50 60 60 10 30 30 30 – – – – – – – – – –
BW63EAG EW63EAG
BW50SAG EW50SAG 10 22 50 60 60 10 30 30 30 – – – – – – – – – –
BW63SAG EW63SAG
BW50RAG EW50RAG 25 – 50 85 85 36 50 50 50 35 50 50 50 42 50 50 42 50 50
BW63RAG EW63RAG
BW100AAG EW100AAG 5 22 50 60 60 10 30 30 30 – – – – – – – – – –
BW100EAG EW100EAG 25 – 50 85 85 36 50 50 50 35 50 50 50 35 50 50 35 50 50
BW125JAG EW125JAG 50 – – 100 100 – 50 100 100 50 85 85 85 50 85 85 50 85 85
BW125RAG EW125RAG 100 – – – – – – 100 100 – – 100 125 – 100 125 – 100 125
BW160EAG EW160EAG 36 – – – – – 50 60 60 42 50 50 50 42 42 50 42 50 50
BW250EAG EW250EAG
BW160JAG EW160JAG 50 – – – – – – 100 100 50 85 85 85 50 85 85 50 85 85
BW250JAG EW250JAG
BW160RAG EW160RAG 100 – – – – – – – – – – 100 125 – 100 125 – 100 125
BW250RAG EW250RAG
BW400EAG EW400EAG 50 – – – – – – – – – 85 85 100 50 85 85 50 85 85
BW400SAG EW400SAG 85 – – – – – – – – – – 100 125 – 100 125 – 100 125
BW400RAG EW400RAG 100 – – – – – – – – – – – 125 – 100 125 – 100 125
BW630EAG EW630EAG 50 – – – – – – – – – – – – – 85 100 50 85 100
BW630RAG EW630RAG 100 – – – – – – – – – – – – – – 125 – 100 125
41
Selection and application
3 3-2 Cascade trip applications
Table 3-5 (b) Summary of combinations used for cascade (backup) coordination
400V AC
Branch circuit breaker Main BW BW BW BW BW BW BW BW BW BW BW BW BW BW BW BW BW BW
circuit 100 125 125 125 160 160 160 250 400 400 400 400 630 630 630 800 800 800
breaker EAG JAG RAG JAG EAG JAG RAG HAG EAG SAG RAG HAG EAG RAG HAG EAG RAG HAG
model BW BW BW
250 250 250
EAG JAG RAG
EW EW EW EW EW EW EW EW EW EW EW EW EW EW EW EW EW EW
100 125 125 125 160 160 160 250 400 400 400 400 630 630 630 800 800 800
EAG JAG RAG JAG EAG JAG RAG HAG EAG SAG RAG HAG EAG RAG HAG EAG RAG HAG
EW EW EW
250 250 250
EAG JAG RAG
MCCB ELCB Icu (kA) 10 30 50 65 18 30 50 65 30 36 50 70 36 50 70 36 50 125
(reference) sym
BW32SAG EW32SAG 2.5 10 10 15 15 10 10 10 10 – – – – – – – – – –
BW50EAG EW50EAG 2.5 10 10 15 15 10 10 10 10 – – – – – – – – – –
BW63EAG EW63EAG
BW50SAG EW50SAG 7.5 10 10 15 15 10 10 10 10 – – – – – – – – – –
BW63SAG EW63SAG
BW50RAG EW50RAG 10 – 25 42 42 15 25 30 30 20 20 20 20 14 14 14 14 14 14
BW63RAG EW63RAG
BW100EAG EW100EAG 10 – 25 42 42 18 25 30 30 14 14 14 14 14 14 14 14 14 14
BW125JAG EW125JAG 30 – – 50 50 – 30 50 50 30 36 36 65 36 36 65 36 36 65
BW125RAG EW125RAG 50 – – – – – – – – – – 50 70 – 50 70 – 50 70
BW160EAG EW160EAG 18 – – – – – 25 30 30 30 30 30 42 18 25 25 18 25 25
BW250EAG EW250EAG
BW160JAG EW160JAG 30 – – – – – – – – 30 36 36 65 36 36 65 36 36 65
BW250JAG EW250JAG
BW160RAG EW160RAG 50 – – – – – – – – – – 50 70 – 50 70 – 50 70
BW250RAG EW250RAG
BW400EAG EW400EAG 30 – – – – – – – – – 30 35 65 30 35 65 30 35 65
BW400SAG EW400SAG 36 – – – – – – – – – – 50 70 36 50 70 36 50 70
BW400RAG EW400RAG 50 – – – – – – – – – – – 70 – 50 70 – 50 70
BW630EAG EW630EAG 36 – – – – – – – – – – – – – 42 65 36 42 65
BW630RAG EW630RAG 50 – – – – – – – – – – – – – – – – 50 70
42
Selection and application
3-3 Selective trip applications
3
Branch MCCB
Time
Branch MCCB
(Load side)
Relay time
Current
Range with protective Range with no protective
coordination coordination
43
Selection and application
3 3-3 Selective trip applications
44
Selection and application
3-3 Selective trip applications
3
45
Selection and application
3 3-3 Selective trip applications
46
Selection and application
3-3 Selective trip applications
3
47
Selection and application
3 3-3 Selective trip applications
3-3-2 Selective trip coordination between Fig. 3-7 PF·S high-voltage power receiving facility
MCCBs and high-voltage side protective
devices VCT
(1) Coordination between MCCBs and power fuses LBS with power fuse (PF)
s ! SHORT CIRCUIT CURRENT TIMES HIGHER THAN THE TRANSFORMER MCCB trip
current rating can be interrupted within 2 seconds to protect characteristic Short-circuit current
the transformer. Sometimes, an MCCB may be substituted (transformer
for the PF to provide this function. secondary side)
s $EGRADATION OF THE 0& DUE TO TRANSFORMER EXCITATION INRUSH
current can be prevented.
Table 3-7 lists the applicable combinations of FUJI MCCBs
Current
and FUJI high-voltage current-limiting fuses from the
standpoint of selective trip coordination. (Converted to transformer primary side)
48
Selection and application
3-3 Selective trip applications
3
49
Selection and application
3 3-3 Selective trip applications
Table 3-7 (b) Selective trip coordination between MCCB and 24kV power fuse
Transformer Capacity (kVA) 50 75 100 125 160 200 250 315 400 500 630 800 1,000 1,250 1,600 2,000
Primary current (A) 1.5 2.2 2.9 3.6 4.7 5.8 7.3 9.2 11.6 14.5 18.2 23.1 29 36 46.5 58
Secondary current (A) 72 108 144 180 230 290 360 455 576 720 910 1,160 1,440 1,800 2,300 2,890
% impedance (%) 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5
Primary short-circuit current when 36 54 72 90 115 145 180 228 288 360 455 464 576 720 920 1,156
the secondary side of the transformer
shorts (A)
Secondary short-circuit current (kA) 1.8 2.7 3.6 4.5 5.8 7.3 9.0 11.4 14.4 18.0 22.8 23.2 28.8 36.0 46.0 57.8
Primary PF. Rated current 6 6 10 10 16 16 25 25 32 40 50 63 63 80 80 80
DIN/VDE 0670 Part 402(A)
Series MCCB type Breaking capacity MCCB Rated Note 1 Selective trip coordination is not available.
Icu/Ics (kA) current Note 2 Selective trip coordination is available. (Instantaneous trip current must be adjusted
400V IEC 60947-2 (A) for coordination.)
Note 3 Selective trip coordination is available. Make sure however that the short-circuit
current where the MCCB is installed is less than its breaking capacity.
Note 4 Selective trip coordination is available.
AAG BW32 1.5/1 3, 5, 10, 15, 20 Note 3
30, 32
BW50 1.5/1 5, 10, 15, 20, 30 Note 3
32, 40, 50
BW100 1.5/1 60, 63, 75, 100 Note 3
EAG BW50 2.5/2 5, 10, 15, 20, 30 Note 4 Note 3
32, 40, 50
BW63 2.5/2 60, 63 Note 4 Note 3
BW100 10/5 50, 60, 63, 75 Note 4 Note 3
100
BW160 18/9 125 Note 1 Note 4 Note 3
150, 160 Note 1 Note 4 Note 3
BW250 18/9 175, 200 Note 1 Note 4 Note 3
225, 250 Note 1 Note 4 Note 3
BW400 30/15 250 Note 1 Note 4 Note 3
300, 350 Note 1 Note 4 Note 3
400 Note 1 Note 4 Note 3
BW630 36/18 500, 600, 630 Note 1 Note 4 Note 3
BW800 36/18 700 Note 1 Note 4 Note 3
800 Note 1 Note 4 Note 3
JAG BW125 30/15 15, 20, 30, 40, 50 Note 4 Note 3
60
75, 100, 125 Note 1 Note 4 Note 3
BW160 30/15 125 Note 1 Note 4 Note 3
150, 160 Note 1 Note 4 Note 3
BW250 30/15 175, 200 Note 1 Note 4 Note 3
225, 250 Note 1 Note 4 Note 3
SAG BW32 2.5/2 3, 5, 10, 15, 20 Note 4 Note 3
30, 32
BW50 7.5/4 5, 10, 15, 20, 30 Note 4 Note 3
32, 40, 50
BW63 7.5/4 60, 63 Note 4 Note 3
BW125 36/18 15, 20, 30, 40, 50 Note 4 Note 3
60
75, 100, 125 Note 1 Note 4 Note 3
BW160 36/18 125 Note 1 Note 4 Note 3
150, 160 Note 1 Note 4 Note 3
BW250 36/18 175, 200 Note 1 Note 4 Note 3
225, 250 Note 1 Note 4 Note 3
BW400 36/18 250 Note 1 Note 4 Note 3
300, 350 Note 1 Note 4 Note 3
400 Note 1 Note 4 Note 3
50
Selection and application
3-3 Selective trip applications
3
Table 3-7 (b) Selective trip coordination between MCCB and 24kV power fuse (Continued)
Transformer Capacity (kVA) 50 75 100 125 160 200 250 315 400 500 630 800 1,000 1,250 1,600 2,000
Primary current (A) 1.5 2.2 2.9 3.6 4.7 5.8 7.3 9.2 11.6 14.5 18.2 23.1 29 36 46.5 58
Secondary current (A) 72 108 144 180 230 290 360 455 576 720 910 1,160 1,440 1,800 2,300 2,890
% impedance (%) 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5
Primary short-circuit current when 36 54 72 90 115 145 180 228 288 360 455 464 576 720 920 1,156
the secondary side of the transformer
shorts (A)
Secondary short-circuit current (kA) 1.8 2.7 3.6 4.5 5.8 7.3 9.0 11.4 14.4 18.0 22.8 23.2 28.8 36.0 46.0 57.8
Primary PF. Rated current 6 6 10 10 16 16 25 25 32 40 50 63 63 80 80 80
DIN/VDE 0670 Part 402(A)
Series MCCB type Breaking capacity MCCB Rated Note 1 Selective trip coordination is not available.
Icu/Ics (kA) current Note 2 Selective trip coordination is available. (Instantaneous trip current must be adjusted
400V IEC 60947-2 (A) for coordination.)
Note 3 Selective trip coordination is available. Make sure however that the short-circuit
current where the MCCB is installed is less than its breaking capacity.
Note 4 Selective trip coordination is available.
RAG BW50 10/5 10, 15, 20, 30, 32 Note 4 Note 3
40, 50
BW63 10/5 60, 63 Note 4 Note 3
BW125 50/25 15, 20, 30, 40, 50 Note 4 Note 3
60
75, 100, 125 Note 1 Note 4 Note 3
BW160 50/25 125 Note 1 Note 4 Note 3
150, 160 Note 1 Note 4 Note 3
BW250 50/25 175, 200 Note 1 Note 4 Note 3
225, 250 Note 1 Note 4 Note 3
BW400 50/25 250 Note 1 Note 4 Note 3
300, 350 Note 1 Note 4 Note 3
400 Note 1 Note 4 Note 3
BW630 50/25 500, 600, 630 Note 1 Note 4 Note 3
BW800 50/25 700 Note 1 Note 4 Note 3
800 Note 1 Note 4 Note 3
HAG BW50 65/17 15, 20, 30, 32, 40 Note 4
50
BW125 65/17 15, 20, 30, 40, 50 Note 4
60
75, 100, 125 Note 1 Note 4
BW250 65/17 125 Note 1 Note 4
150, 160, 175 Note 1 Note 4
200
225, 250 Note 1 Note 4
BW400 70/35 250 Note 1 Note 4
300, 350 Note 1 Note 4
400 Note 1 Note 4
BW630 70/35 500, 600, 630 Note 1 Note 4
BW800 70/35 700 Note 1 Note 4
800 Note 1 Note 4
51
Selection and application
3 3-4 Wiring protection
Fig. 3-11 Temperature rise in PVC insulated conductors due to let-through I2t
1000
800
600
500
400
300
200
Temperature rise (K)
300
500
400
630
240
185
120
2.5
1.5
150
35
10
16
25
50
4
95
6
70
1
60
50
40
30
20
10
0.01 0.05 0.1 0.5 1 5 10 50 100 500 1000 5000 10000 100000
Let-through I2t (×106A2s)
52
Selection and application
3-4 Wiring protection
3
Table 3-9 (b) Conductor specifications The relationship of current to the rise in conductor temperature
in the continuous and short-time regions makes heat
Resistor temperature coefficient D 0.00427 (1/°C)
1/D 234 (°C) dissipation too important to ignore, yet it varies with conditions
like the type of installation. Although this is not impossible to
Initial conductor temperature * T0 IEC wiring: 70°C
calculate, it is not commonly done. IEC standards stipulate
JIS wiring: 60°C
allowable current for insulated wiring in the continuous region
Ultimate conductor temperature * T IEC wiring: 160°C using an ambient temperature of 30°C and a rise in conductor
JIS wiring: 150°C
temperature of 40°C.
Specific conductor resistance U 0.0000016 (:cm) The IEEE uses a minimum of 20s for the short-time region
Mechanical equivalent of heat J 4.19 (J/cal) where a conductor temperature as high as 100°C is allowable.
This temperature is sustainable in the conductor because of
Specific heat of the conductor C 0.092 (J/cm3°C)
the inverse time-delay trip time of the breaker. Fig. 3-12 shows
Specific gravity of the conductor V 8.93 (g/cm3) current-time characteristics for 600V PVC-insulated wiring
K2=Dp/JCV 1.985E–09 where conductor temperatures reach 100°C starting from
no-load conditions at an ambient temperature for the wiring of
Note: * Ambient temperature: 30°C 30°C.
Fig. 3-12 Current-time characteristics in which 600V PVC insulated conductors reach a temperature of 100°C (rise of 70°C)
1000
800
600
500
400
300
200
100
Wire sizes (mm2)
60
630
Time (sec)
500
400
50
300
240
185
150
40
120
95
70
50
30
35
25
16
10
20
6.0
4.0
2.5
1.5
1.0
10
6
5
4
3
1
0.1 0.2 0.3 0.4 0.6 0.8 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300 500 1000
Current (u102A)
53
Selection and application
3 3-4 Wiring protection
I2t = Constant
(short-circuit region)
Current
Table 3-10 MCCB protected wiring (up to the rated short-time range)
Wire Allowable Allowable MCCB rating (A)
size current (A) current
(mm2) considering
Open Duct
MCCB trip
3-wire 3-wire
characteristics
(A)
Amb. temp. 30°C 30°Co100°C 10 15 20 40 50 60 75 100 125 150 175 200 225 250 300 350 400 500 600 700 800 1000
Rise 40K
1 14.5 10.2 12
1.5 18.5 13.0 18
2.5 25 18 27
4 34 24 40 Unprotected region
6 43 30 52
10 60 42 68
16 80 56 98
25 101 71 123
35 126 88 154 Protected region
50 153 107 187
70 196 137 239
95 238 167 290
120 276 193 337
150 319 223 389
185 364 255 444
240 430 301 525
300 556 389 678
400 664 465 810
500 757 530 924
630 856 599 967
54
Selection and application
3-4 Wiring protection
3
Table 3-11a PVC wiring protected by rated breaking capacity (for short circuits)
Notes: 1 Wiring selection consideration: I2t of the wiring t maximum I2t of the MCCB (ELCB)
(Short-time wiring tempereture:160°C maximum, continuous region:70°C), and rated current of the wiring t rated current of the MCCB (ELCB).
2 The let-through current(I2t) is lower the MCCBs (ELCBs) in the table because short-circuit current can be limited by factors like wiring impedance in an actual
circuit. This lowers thermal stress on the wiring.
230V
MCCB (ELCB) PVC cable (Note: 1)
Icu Peak let- Max. let- Permissible I2t Minimum wire Permissible
(kA) through through (u10sA2s) size (mm2) current (A)
current current I2t
(kA: peak) (u10sA2s)
MCCB ELCB Rated current (A)
BW32AAG EW32AAG 3 (MCCB only), 5, 10, 15, 20, 30, 32 2.5 3.5 0.06 0.082 2.5 18
BW50AAG EW50AAG 5, 10, 15, 20, 30, 32, 40, 50 2.5 3.5 0.06 0.082 2.5 18
BW100AAG EW100AAG 60, 63, 75, 100 5.0 6.0 0.145 0.21 4 24
EW32EAG 5, 10, 15, 20, 30, 32 2.5 3.5 0.06 0.082 2.5 18
BW50EAG EW50EAG 5, 10, 15, 20, 30, 32, 40, 50 5.0 6.0 0.145 0.21 4 24
BW63EAG EW63EAG 60, 63 5.0 6.0 0.145 0.21 4 24
BW100EAG EW100EAG 50, 60, 63, 75, 100 25 12.0 0.50 1.31 10 42
BW160EAG EW160EAG 125, 150, 160 36 25.0 1.70 3.35 16 56
BW250EAG EW250EAG 175, 200, 225, 250 36 25.0 1.70 3.35 16 56
BW400EAG EW400EAG 250, 300, 350, 400 50 33.5 2.58 3.35 16 56
BW630EAG EW630EAG 500, 600, 630 50 47.0 5.10 8.2 25 71
BW800EAG EW800EAG 700, 800 50 47.0 5.10 8.2 25 71
BW125JAG EW125JAG 15 50 4.65 0.033 0.082 2.5 18
20 50 5.7 0.044 0.082 2.5 18
30 50 6.95 0.06 0.082 2.5 18
40, 50, 60, 75, 100, 125 50 20.0 0.62 1.31 10 42
BW160JAG EW160JAG 125, 150, 160 50 24.5 1.28 1.31 10 42
BW250JAG EW250JAG 175, 200, 225, 250 50 24.5 1.28 1.31 10 42
BW32SAG EW32SAG 3, 5, 10, 15, 20, 30, 32 5.0 6.0 0.145 0.21 4 24
BW50SAG EW50SAG 5, 10, 15, 20, 30, 32, 40, 50 10 8.5 0.27 0.471 6 30
BW63SAG EW63SAG 60, 63 10 8.5 0.27 0.471 6 30
BW125SAG EW125SAG 15 85 5.035 0.036 0.082 2.5 18
20 85 6.26 0.048 0.082 2.5 18
30 85 7.685 0.067 0.082 2.5 18
40, 50, 60, 75, 100, 125 85 23.5 0.746 1.31 10 42
BW160SAG EW160SAG 125, 150, 160 85 29.5 1.504 3.35 16 56
BW250SAG EW250SAG 175, 200, 225, 250 85 29.5 1.504 3.35 16 56
BW400SAG EW400SAG 250, 300, 350, 400 85 40.0 2.65 3.35 16 56
BW50RAG EW50RAG 10, 15, 20, 30, 32, 40, 50 25 12.0 0.50 1.31 10 42
BW63RAG EW63RAG 60, 63 25 12.0 0.50 1.31 10 42
BW125RAG EW125RAG 15 100 5.2 0.037 1.31 10 42
20 100 6.5 0.05 1.31 10 42
30 100 8.0 0.07 1.31 10 42
40, 50, 60, 75, 100, 125 100 25.0 0.08 1.31 10 42
BW160RAG EW160RAG 125, 150, 160 100 31.5 1.60 3.35 16 56
BW250RAG EW250RAG 175, 200, 225, 250 100 31.5 1.60 3.35 16 56
BW400RAG EW400RAG 250, 300, 350, 400 100 42.0 3.02 3.35 16 56
BW630RAG EW630RAG 500, 600, 630 100 61.5 6.50 8.18 25 71
BW800RAG EW800RAG 700, 800 100 61.5 6.50 8.18 25 71
BW50HAG 15 125 5.40 0.039 0.082 2.5 18
20 125 6.8 0.051 0.082 2.5 18
30 125 8.3 0.07 0.082 2.5 18
40, 50 125 26.5 0.85 1.31 10 42
BW125HAG 15 125 5.40 0.039 0.082 2.5 18
20 125 6.8 0.051 0.082 2.5 18
30 125 8.3 0.07 0.082 2.5 18
40, 50, 60, 75, 100, 125 125 26.5 0.85 1.31 10 42
BW250HAG 125, 150, 160, 175, 200, 225, 250 125 33.3 1.68 3.35 16 56
BW400HAG EW400HAG 250, 300, 350, 400 125 45.0 3.10 3.35 16 56
BW630HAG EW630HAG 500, 600, 630 125 66.5 6.8465 8.18 25 71
BW800HAG EW800HAG 700, 800 125 66.5 6.8465 8.18 25 71
55
Selection and application
3 3-4 Wiring protection
Table 3-11b PVC wiring protected by rated breaking capacity (for short circuits)
Notes: 1 Wiring selection consideration: I2t of the wiring t maximum I2t of the MCCB (ELCB)
(Short-time wiring tempereture:160°C maximum, continuous region:70°C), and rated current of the wiring t rated current of the MCCB (ELCB).
2 The let-through current(I2t) is lower the MCCBs (ELCBs) in the table because short-circuit current can be limited by factors like wiring impedance in an actual
circuit. This lowers thermal stress on the wiring.
440V
MCCB (ELCB) PVC cable (Note: 1)
Icu Peak let- Max. let- Permissible I2t Minimum wire Permissible
(kA) through through (u10sA2s) size (mm2) current (A)
current current I2t
(kA: peak) (u10sA2s)
MCCB ELCB Rated current (A)
BW32AAG 3, 5, 10, 15, 20, 30, 32 1.5 2.1 0.03 0.082 2.5 18
BW50AAG 5, 10, 15, 20, 30, 32, 40, 50 1.5 2.1 0.03 0.082 2.5 18
BW100AAG 60, 63, 75, 100 1.5 2.1 0.03 0.082 2.5 18
BW50EAG EW50EAG 5, 10, 15, 20, 30, 32, 40, 50 2.5 3.5 0.08 0.082 2.5 18
BW63EAG EW63EAG 60, 63 2.5 3.5 0.08 0.082 2.5 18
BW100EAG EW100EAG 50, 60, 63, 75, 100 10 10.0 0.60 1.31 10 42
BW160EAG EW160EAG 125, 150, 160 18 22.0 2.60 3.35 16 56
BW250EAG EW250EAG 175, 200, 225, 250 18 22.0 2.60 3.35 16 56
BW400EAG EW400EAG 250, 300, 350, 400 30 35.0 5.70 8.18 25 71
BW630EAG EW630EAG 500, 600, 630 36 47.0 8.75 16.0 35 88
BW800EAG EW800EAG 700, 800 36 47.0 8.75 16.0 35 88
BW125JAG EW125JAG 15 30 8.1 0.113 0.21 4 24
20 30 9.5 0.140 0.21 4 24
30 30 11.0 0.178 0.21 4 24
40, 50, 60, 75, 100, 125 30 10.0 1.65 3.35 16 56
BW160JAG EW160JAG 125, 150, 160 30 26.0 3.15 3.35 16 56
BW250JAG EW250JAG 175, 200, 225, 250 30 26.0 3.15 3.35 16 56
BW32SAG EW32SAG 3, 5, 10, 15, 20, 30, 32 2.5 3.5 0.08 0.082 2.5 18
BW50SAG EW50SAG 5, 10, 15, 20, 30, 32, 40, 50 7.5 8.3 0.41 0.471 6 30
BW63SAG EW63SAG 60, 63 7.5 8.3 0.41 0.471 6 30
BW125SAG EW125SAG 15 36 8.2 0.115 0.21 4 24
20 36 9.65 0.145 0.21 4 24
30 36 11.3 0.183 0.21 4 24
40, 50, 60, 75, 100, 125 36 21.5 1.815 3.35 16 56
BW160SAG EW160SAG 125, 150, 160 36 28.1 3.45 8.18 25 71
BW250SAG EW250SAG 175, 200, 225, 250 36 28.1 3.45 8.18 25 71
BW400SAG EW400SAG 250, 300, 350, 400 36 38.0 6.40 8.18 25 71
BW50RAG EW50RAG 10, 15, 20, 30, 32, 40, 50 10 10.0 0.60 1.31 10 42
BW63RAG EW63RAG 60, 63 10 10.0 0.60 1.31 10 42
BW125RAG EW125RAG 15 50 8.5 0.120 1.31 10 42
20 50 10.0 0.155 3.35 16 56
30 50 12.0 0.195 3.35 16 56
40, 50, 60, 75, 100, 125 50 25.0 2.20 3.35 16 56
BW160RAG EW160RAG 125, 150, 160 50 33.0 4.15 8.18 25 71
BW250RAG EW250RAG 175, 200, 225, 250 50 33.0 4.15 8.18 25 71
BW400RAG EW400RAG 250, 300, 350, 400 50 44.0 7.70 8.18 25 71
BW630RAG EW630RAG 500, 600, 630 50 54.5 10.30 16 35 88
BW800RAG EW800RAG 700, 800 50 54.5 10.30 16 35 88
BW50HAG 15 65 8.55 0.121 0.21 4 24
20 65 10.5 0.160 0.21 4 24
30 65 12.6 0.20 0.21 4 24
40, 50 65 27.3 2.40 3.35 16 56
BW125HAG 15 65 8.55 0.121 0.21 4 24
20 65 10.5 0.160 0.21 4 24
30 65 12.6 0.20 0.21 4 24
40, 50, 60, 75, 100, 125 65 27.3 2.40 3.35 16 56
BW250HAG 125, 150, 160, 175, 200, 225, 250 65 36.2 4.50 8.18 25 71
BW400HAG EW400HAG 250, 300, 350, 400 70 50.0 8.70 16 35 88
BW630HAG EW630HAG 500, 600, 630 70 63.5 11.97 16 35 88
BW800HAG EW800HAG 700, 800 70 63.5 11.97 16 35 88
56
Selection and application
3-5 Motor circuit applications
3
3-5 Motor circuit applications secs. Pump motors require a shorter starting time, while fans
and blowers require a longer time to reach operating speed.
3-5-1 Description
Fig. 3-14 Starting power factor example of induction motors
Individual or tandem overcurrent protective devices are
80
installed in motor circuits to provide the motor with overload 70
and locked rotor protection and to provide the wiring with
(d) Magnetic motor starter plus instantaneous trip type MCCB Motor output (kW)
The MCCBs in (a) and (b) provide both overcurrent and short-
circuit protection. With configurations (c) and (d), the motor
starter provides overload protection while a line protection or Fig. 3-15 DC component overlap ratio
instantaneous trip type MCCB provides short-circuit protection.
3.0 2.0
Combination (d) acts as a single overcurrent circuit breaker for
: Max. asymmetrical instantaneous coefficient
one panel. : Max. asymmetrical effective value coefficient
57
Selection and application
3 3-5 Motor circuit applications
(2) Motor circuit protection by motor breaker Fig. 3-16 Motor breaker protection coordination
The overcurrent trip characteristics of a single MCCB may Motor breaker characteristics
be used to protect the motor and the wiring at the same time. Cable allowable characteristics
(See Fig. 3-17 a.)
Often the operating characteristics of an MCCB make it Motor allowable characteristics
unsuitable in situations with long starting times or with
Time
significant current, like the inrush current generated by the
changeover from star to delta connection. However, MCCBs
are quite suitable for short (2s or less) starting times. Motor current
The need for frequent switching brings up other important
considerations, such as connecting magnetic contractors in
series. (See Fig. 3-17 b.) Fig. 3-16 shows the MCCB protection Current
coordination curve. Table 3-12 (a) shows applicable breakers
for 230V motors and Table 3-12 (b) shows breakers for 400V
motors.
M M M M
a b c d
Note: Motor full-load currents are based on FUJI’s standard type totally-enclosed
induction motors. Check the value of the full-load current before using.
58
Selection and application
3-5 Motor circuit applications
3
(a) 400V AC
Combined Motor output Motor rated Motor rated Manual motor Manual motor starter
magnetic (kW) current (A) current starter rated Icu (kA)
contactor multiplying current (A) 25 50 100
factor (A)u1.2
SC-03 0.2 0.55 0.66 0.7 – – BM3RSB-
0.4 0.95 1.14 1.4 BM3RHB-
0.75 1.65 1.98 2
1.5 3 3.6 4
2.2 4.05 4.86 5 BM3RSB- BM3VSB-
BM3VSB- BM3VHB-
SC-0, 05 3.7 6.75 8.1 8 BM3RSB- BM3RHB- –
SC-4-0 5.5 10 12 12 BM3VSB- BM3VHB-
SC-4-1, 5-1 7.5 13.25 15.9 16
SC-N1 11 19.5 23.4 24 BM3VSB- BM3VHB-
SC-N2 15 26 31.2 32
SC-N2S 18.5 31.5 37.8 40 – –
SC-N2S 22 38.5 46.2 45
SC-N3 30 51.5 61.8 60
SC-N4 37 63.5 76.2 75
SC-N5, N5A 45 76 91.2 90
SC-N6 55 94 112.8 125
SC-N7 75 128 153.6 150
SC-N8 90 152 182.4 175
SC-N10 110 185 222 225
Note: Motor full-load currents are based on FUJI’s standard type totally-enclosed
induction motors. Check the value of the full-load current before using.
59
Selection and application
3 3-5 Motor circuit applications
(3) Magnetic motor starter and MCCB motor circuit Fig. 3-18 Protection coordination characteristics curve in motor
protection circuits
Time
instantaneous trip type MCCBs are used. This is because Available
standard MCCBs for line protection are provided with bimetal short-circuit Rated short-
elements as tripping devices, which have limited overcurrent current circuit breaking
withstand values and which would cause damage due to capacity (Icu)
Motor current
overheating in the presence of short-circuit currents.
Fig. 3-18 gives an example of a protection coordination curve
of a motor circuit. Current
60
Selection and application
3-5 Motor circuit applications
3
Table 3-14 Selection of line protection MCCB and ELCB (for reference)
(a) 230V AC 3-phase induction motor
Contactor Thermal Motor ratings MCCB Icu (kA)
type overload Current Output rated 2.5 5 10 25 36 50 85 100 125
relay type (A) (kW) current
(A)
SC-03 TR-0N/3 1.3 0.2 5 BW32AAG BW32SAG BW50SAG
2.3 0.4 5 BW32AAG BW32SAG BW50SAG
3.5 0.75 10 BW32AAG BW32SAG BW50SAG BW50RAG
15 BW125JAG BW125SAG BW125RAG BW50HAG
6.9 1.5 20 BW32AAG BW32SAG BW50SAG BW50RAG BW125JAG BW125SAG BW125RAG BW50HAG
9.5 2.2 30 BW32AAG BW32SAG BW50SAG BW50RAG BW125JAG BW125SAG BW125RAG BW50HAG
SC-4-0 TR-5-1N/3 15.5 3.7 40 BW50AAG BW50EAG BW50SAG BW50RAG BW125JAG BW125SAG BW125RAG BW50HAG
SC-N1 TR-N2/3 21 5.5 50 BW50AAG BW50EAG BW50SAG BW50RAG BW125JAG BW125SAG BW125RAG BW50HAG
SC-N2 27.5 7.5 60 BW125JAG BW125SAG BW125RAG BW50HAG
75 BW100AAG BW100EAG
SC-N2S TR-N3/3 40 11 100 BW125JAG BW125SAG BW125RAG BW50HAG
SC-N3 54 15 100 BW125JAG BW125SAG BW125RAG BW50HAG
SC-N4 TR-N5/3 68 18.5 125 BW125JAG BW125SAG BW125RAG BW50HAG
SC-N5 84 22 125 BW160EAG BW160JAG BW160SAG BW160RAG BW250HAG
SC-N5A
SC-N6 TR-N6/3 116 30 175 BW250EAG BW250JAG BW250SAG BW250RAG BW250HAG
SC-N7 TR-N7/3 137 37 225 BW250EAG BW250JAG BW250SAG BW250RAG BW250HAG
SC-N8 TR-N8/3 166 45 250 BW250EAG BW250JAG BW250SAG BW250RAG BW250HAG
SC-N10 TR-N10/3 200 55 350 BW400EAG BW400SAG BW400RAG BW400HAG
SC-N11 TR-N12/3 272 75 500 BW630EAG BW630RAG BW630HAG
SC-N12 332 90 500 BW630EAG BW630RAG BW630HAG
380 110 500 BW630EAG BW630RAG BW630HAG
Notes 1 : The model numbers to use for direct-on-line starters are given for electromagnetic contractors.
2 : The model numbers for AC3-class electromagnetic contactors are given.
3 : The catalog values are given for the rated motor current (catalog number 24B2-E-0087) for Fuji 3-phase totally enclosed fan-cooled models (4-pole,
200V/50Hz with feet).
61
Selection and application
3 3-5 Motor circuit applications
Table 3-14 Selection of line protection MCCB and ELCB (for reference)
(b) 400V AC 3-phase induction motor
Contactor Thermal Motor ratings MCCB Icu (kA)
type overload Current Output rated 2.5 7.5 10 18 30 36 50 68 70
relay type (A) (kW) current
(A)
SC-03 TR-0N/3 0.65 0.2 5 BW32SAG BW50SAG
1.15 0.4 5 BW32SAG BW50SAG
1.8 0.75 5 BW32SAG BW50SAG
3.5 1.5 10 BW32SAG BW50SAG BW50RAG
4.8 2.2 15 BW32SAG BW50SAG BW50RAG BW125JAG BW125SAG BW125RAG BW50HAG
SC-0 TR-0N/3 7.8 3.7 20 BW32SAG BW50SAG BW50RAG BW125JAG BW125SAG BW125RAG BW50HAG
SC-05
SC-4-0 TR-5-1N/3 10.5 5.5 30 BW32SAG BW50SAG BW50RAG BW125JAG BW125SAG BW125RAG BW50HAG
SC-4-1 TR-5-1N/3 13.5 7.5 40 BW50EAG BW50SAG BW50RAG BW125JAG BW125SAG BW125RAG BW50HAG
SC-5-1
SC-N1 TR-N2/3 20 11 40 BW125JAG BW125SAG BW125RAG BW50HAG
60 BW63EAG BW63SAG BW63RAG
SC-N2 TR-N2/3 27 15 60 BW125JAG BW125SAG BW125RAG BW125HAG
75 BW100EAG
SC-N2S TR-N3/3 34 18.5 60 BW125JAG BW125SAG BW125RAG BW125HAG
100 BW100EAG
SC-N2S TR-N3/3 42 22 75 BW125JAG BW125SAG BW125RAG BW125HAG
100 BW100EAG
SC-N3 TR-N3/3 58 30 100 BW125JAG BW125SAG BW125RAG BW125HAG
SC-N4 TR-N5/3 69 37 125 BW125JAG BW125SAG BW125RAG BW125HAG
SC-N5 TR-N5/3 83 45 125 BW160JAG BW160SAG BW160RAG BW250HAG
SC-N5A
SC-N6 TR-N6/3 100 55 150 BW160JAG BW160SAG BW160RAG BW250HAG
SC-N7 TR-N7/3 136 75 200 BW250JAG BW250SAG BW250RAG BW250HAG
SC-N8 TR-N8/3 166 90 225 BW250JAG BW250SAG BW250RAG BW250HAG
SC-N10 TR-N10/3 190 110 300 BW400EAG BW400SAG BW400RAG BW400HAG
SC-N11 TR-N12/3 225 132 400 BW400EAG BW400SAG BW400RAG BW400HAG
Notes 1 : The model numbers to use for direct-on-line starters are given for electromagnetic contractors.
2 : The model numbers for AC3-class electromagnetic contactors are given.
3 : The catalog values are given for the rated motor current (catalog number 24B2-E-0087) for Fuji 3-phase totally enclosed fan-cooled models (4-pole,
400V/50Hz with feet).
62
Selection and application
3-6 Applications on the primary side of transformers
3
0 IN
øm
T IT1
t=0
Time
63
Selection and application
3 3-6 Applications on the primary side of transformers
64
Selection and application
3-6 Applications on the primary side of transformers
3
65
Selection and application
3 3-7 Welder circuit applications
66
Selection and application
3-7 Welder circuit applications
3
100 (A)
illustrated in Fig. 3-22, the MCCB to be used must meet the Rated capacity 50
following requirements: Thermal equivalent current= u
Rated voltage
(i) The rated current (IN) of the MCCB is higher than the
thermal equivalent current IB (IN > IB). Hence, the rated current of the MCCB must be at least equal
Allowing for possible supply voltage fluctuation, a margin of to this value.
some 10% would be recommended. (ii) Reviewing the method to prevent malfunctioning
(ii) The MCCB is not tripped by the primary input current. associated with the primary input current
The MCCB’s hot-start characteristic curves are positioned
above the points (tL, IL) and (TL, Ia) so that the currents IL The first step in reviewing the primary input current-time
and Ia (A) would not cause the MCCB to malfunction (Fig. characteristics of the resistance welder and the hot-start
3-23). characteristic of the MCCB is setting the operating time (tL)
(iii) The MCCB is free from malfunction due to inrush current associated with the allowable on-load factor (D) of the welder.
when the circuit is closed. Assuming that the intermittent loading cycle is 1 minute and
hence tL = 60·D/100 (seconds), the relationship between the
Fig. 3-23 Hot and cold MCCB operating characteristics operating time (tL) and the primary input current (IL) must be
represented.
Fig. 3-24 shows the relationship between the primary input
current and allowable operating time for a single-phase 200V
Cold resistance welder rated at 25kVA.
Hot
Since the equation
follows:
125A for 50% on-load factor, (tL = 30 seconds)
280A for 10% on-load factor, (tL = 6 seconds)
884A for 1% on-load factor, (tL = 0.6 seconds)
tL
Fig. 3-24 Relationship between maximum primary input current
and operating time
IB IN Ia IL
Current
60
(b) Selecting MCCB based on welder ratings
30
If the operating conditions for the welder are not definite,
the MCCB to be used should be selected by allowing for the
maximum operating limits of the welder considering its ratings
Operating time tL (sec.)
or specifications.
6
The rated capacity of a resistance welder is indicated in
terms of a 50% on-load factor. Namely, the rated capacity
is defined as an input load that would meet the temperature
rise requirement when the welder is used with a 50% on-load
factor.
If the welder is to be used with a current different from that
0.6
available with a 50% on-load factor, it must be used with an
on-load factor that would cause an equivalent temperature rise
observed with a 50% on-load factor or lower.
The relationship between the primary input capacity and the 88.4 125 280 340 884
allowable on-load factor can be stated in an equation as
Primary input current IL (A)
2
Allowable on-load factor= Rated capacity u 50%
Primary input capacity
This equation may be used to examine all possible
combinations of the primary input capacity and the allowable
on-load factor.
67
Selection and application
3 3-7 Welder circuit applications
However, since the standard maximum input is prescribed Table 3-19 Spot welder circuit motor breaker selection
for a resistance welder, even if the secondary circuit is fully Note: This table applies to models that can use a thyristor to perform phase
shorted, the maximum short-circuit current is some 30% control at startup for a synchronous or semi-synchronous system.
higher than the rated welding current (secondary current
Resistance welder Single-phase, 200V
corresponding to the standard maximum input) at most. Circuit short-circuit capacity (kA) (The
Consequently, allowance would be needed only for a value short-circuit current at the service entrance
about 30% higher than the current corresponding to the must be less than the following values.)
standard maximum input.
Assuming a standard maximum input of 55kVA at 230V AC Rated Maximu 5 25 36 50 100
capacity m input
single-phase, IL (max) is calculated as example example
(kVA) (kVA)
IL (max) = 55000 u 1.3 | 310 [A]
230 15 35 BW100 BW100 BW125JAG-
This result requires that the tL−IL curve shown in Fig. 3-24 AAG- EAG- 2P100
be positioned below the hot-start characteristic curve of the 2P100 2P100
MCCB in the range IL d 310 (A). A general guideline for filling 30 65 BW125JAG-2P125 BW125
this requirement is to set the rated current of the MCCB at RAG-
least 1.5 times higher than the thermal equivalent current 2P125
calculated in (i).
55 140 BW250EAG-2P225 BW250RAG-
(iii) Method to keep the MCCB free from malfunctioning 2P225
caused by the inrush current when the circuit is
closed.
Resistance welder Single-phase, 400V
With welders that use thyristors to permit closed circuit phase Circuit short-circuit capacity (kA)
control, such as those operating in synchronous or semi- (The short-circuit current at the
synchronous mode, the inrush current associated with the service entrance must be less
biased excitation of the transformer core would not be much than the following values.)
of a problem. Rather, only the inrush current associated with Rated Maximu 10 18 30 50
the superposed DC component needs to be considered. capacity m input
Specifically, a choice should be made of an MCCB having its example example
instantaneous tripping current at least two times the IL (max) (kVA) (kVA)
calculated in (ii).
15 35 BW50 BW125JAG- BW125
RAG- 2P050 RAG-
Table 3-19 lists typical MCCBs that are selected to work with 2P050 2P050
resistance welders that operate in synchronous or semi-
synchronous mode, pursuant to the requirements given in (i) 30 65 BW100 BW125JAG- BW125
to (iii) above. Since, generally, the standard maximum input EAG- 2P100 RAG-
2P100 2P100
of a welder is some three times its rated capacity, and the
instantaneous tripping current of an MCCB is eight times 55 140 BW250EAG-2P225 BW125
its rated current or higher, the following equation may be RAG-
used to select an MCCB to work with welders that operate in 2P125
synchronous or semi-synchronous mode:
Rated capacity
IN > 1.1 u IN = MCCB rated current
Rated voltage
Max. input capacity
Assumption: d3
Rated capacity
68
Selection and application
3-8 Selecting an MCCB for capacitor circuit
3
3-8 Selecting an MCCB for capacitor circuit (2) Transient inrush current when a circuit closes
When a capacitor circuit like the one shown in Fig. 3-25
3-8-1 Characteristics specific to capacitor closes, the capacitor must be charged with an equivalent of
circuits the voltage applied the instant the circuit closed. This causes
Note the following points when considering MCCBs for the circuit to be flooded with massive inrush current that has a
capacitor circuits: steep slope like that shown in Fig. 3-27.
If the circuit closes now with peak supply voltage present, then
(1) Arc reignition due to recovery voltage the transient current at this time is expressed by the following
equation.
When a capacitor circuit shown in Fig. 3-25 is opened, it
exhibits characteristics distinctly different from inductive loads If i = (Em/LE)HDt sinEt (1)
due to the effects of residual electric charge in the capacitor.
D = R/2L J= 4L/CR2
In a single-phase circuit like that shown in Fig. 3-26, the
capacitor voltage lags 90° behind the current, and a peak E = (4L/CR2)/2L, E = (1/LCR2/4L2)
voltage exists across the capacitor terminals when the circuit
is opened. The recovery voltage appearing between the switch which yields E = J/2L
contacts immediately after the circuit is opened is equal to Generally E > 0 (1/LC > R2/4L2) is true, and oscillating transient
the difference between the capacitor residual voltage and the current flows at the natural frequency as shown below.
supply voltage. Therefore, half a cycle after the circuit opens,
the voltage between the switch contacts rises to twice the Fig. 3-27 Transient current when a capacitor circuit closes
supply voltage or higher.
In a three-phase circuit, the recovery voltage appearing
between the contacts in the first interrupted phase could rise
as high as 2.5 times the supply voltage.
Unless the breaker contacts are fully open until half a cycle
after the capacitor circuit opens, restrike of arc will occur. If the
capacitor is discharged by damped oscillation at the oscillation
frequency according to the inductance (L) and capacitance (C)
of the circuit at re-ignition, then residual peak voltage will be
left at the terminal again if the arc is quenched (current cuts
off).
If restrike of arc is repeated, the voltage could continue to rise
to the dielectric breakdown point of the capacitor.
Hence, fast-interrupting circuit breakers with quick-make, Since the natural frequency at this time is as follows: f = Z/2S,
quick-break action are recommended for this type of circuit. equation (1) yields Z = E, and so
f = 1/(LCR2/4L2)/2S, f = J/4SL
Fig. 3-25 Residual electric charge in the capacitor
Then equation (1) above yields the following equation.
i = (2Em/J)H−tR/2Lsin (J/2L)t .....................(2)
Maximum current at this time is expressed as follows:
im = (Em/L/C)HR/JtanJ/R (3)
im = (Em/L/C)HDxø/E (3-1)
The first wave peak W0 is expressed as follows:
Fig. 3-26 Capacitor residual voltage W0 = (2L/J)tan−1J/R W0 = ø/E ...........(4)
ø = tan−1E/D (rad)
Since the time shown in equation (4) is very short, the voltage
in equation (3) or (3)-1 is essentially V = Em.
Since H−D·ø/E is approximately 1, the peak transient inrush
Vc=Em current is derived as follows from equation (3)-1.
im | Em C/L (5)
(Here, Em is √2/3 times the line voltage in a three-phase
circuit and is √2 times the line voltage in a single-phase
circuit.)
The preceding equations prove that transient inrush current
flowing to the capacitor is related to inductance (L), that is, it
is related to the power supply capacity and the presence or
absence of reactors connected in series with the capacitor.
69
Selection and application
3 3-8 Selecting an MCCB for capacitor circuit
If no reactors are connected in series with the capacitor, then (4) When capacitors are connected in parallel with
the R, L, and C defined by the power supply transformer individual motor circuits to improve the power
capacity, percentage impedance and capacitance will cause factor (See Fig. 3-28.)
wild fluctuations in the inrush current factor (first wave peak/
When selecting the rated current of an MCCB, choose one
effective rated capacitor current), oscillating frequency and
where startup inrush current-time characteristics for the
damping constant. The amount of fluctuation is especially
motor will not cause the MCCB to malfunction. If capacitance
significant when it comes to selecting a rated current for the
less than 30% of the motor capacity is used here, then the
MCCB. This is why inserting reactors totaling up to 6% of the
rated current of the MCCB should be at least three times the
impedance into capacitor circuits is highly recommended for
rated current of the capacitor. This will prevent the MCCB
improving the power factor.
from malfunctioning even without series-connected reactors
Series-connected reactors are needed because the inrush
because the capacitor is installed on the secondary side of
current from other capacitors is added to the current from
the magnetic motor starter. Refer to the Technical Information
the power supply if capacitors are inserted in parallel using
for the magnetic motor starter for more details on available
multiple banks without reactors.
models and durability characteristics.
(3) Selecting an MCCB for phase advance capacitor Fig. 3-28 Capacitors connected in parallel with the motor
circuits
MCCB MS
Table 3-20 shows the rated current (In) for applicable MCCBs
at various capacitances. Since the conditions for selecting
MCCBs are aimed at preventing mistripping, first find the
effective current (Ict), that is, the transient current plus the M
steady state current 0.01s after power is turned on. If that
current (Ict) is less than 1/10 the instantaneous tripping current
of the MCCB (10 times the rated current of the MCCB) or is
more than 1.5 times the rated current of the capacitor (Icn),
then use the main current approximating that value.
In > k u Ic Ic > Ict/10 or Ic > Icn
Icn: Capacitor rated current (effective value)
(Single phase: Icn = ZC·V, three-phase: Icn = ZC·V/ √3 ) Capacitors
In: MCCB rated current (effective value)
Ict: Inrush current 0.01s after power is turned ON (effective
value)
Ic: Ict/10 or Icn min
k: 1.5 (margin coefficient for the allowable fluctuation error)
V: Line voltage (effective value)
Z: 2Sf (f: frequency (Hz) of the applicable circuit)
.OTES s 4HE VALUE OF TIMES IS THE SUM OF THE MAXIMUM ALLOWABLE CURRENT
for the capacitor (1.3 times the rated current) and the allowable
capacitance error plus 15%.
s 4HE OSCILLATING FREQUENCY OF TRANSIENT CURRENT IS MUCH HIGHER THAN THE
fundamental harmonic. It ranges from several hundred hertz to several
kilohertz with no series-connected reactors, or less than several
hundred hertz (200 to 300Hz max.) regardless of the power supply
capacity with reactors totaling 6% of the impedance connected in
series.
s 4RANSIENT CURRENT ATTENUATION IS RELATIVELY FAST WITHOUT REACTORS
connected in series and is fairly slow with reactors connected in series.
70
Selection and application
3-8 Selecting an MCCB for capacitor circuit
3
Table 3-20 (1) MCCB rated current application examples for single-phase capacitor equipment capacity
Rated frequency Rated voltage Rated equipment Rated current Capacitor rating Series reactor 6% MCCB rated MC type
(Hz) (V) capacity (kvar) (A) (kvar) (μF) (kvar) (mH) current (A) (reference)
50 200 1.34 6.7 1.43 100 0.09 6.06 10 SC-0
2.67 13.4 2.84 200 0.17 3.04 20 SC-4-0
3.34 16.7 3.55 250 0.21 2.43 30 SC-4-1
4.01 20.1 4.27 300 0.26 2.03 30 SC-5-1
5 25.0 5.32 374 0.32 1.63 40 SC-N1
10 50.0 10.64 748 0.64 0.81 75 SC-N2S
15 75.0 15.96 1,122 0.96 0.54 125 SC-N4
20 100.0 21.28 1,496 1.28 0.41 150 SC-N6
25 125.0 26.60 1,870 1.60 0.33 200 SC-N7
30 150.0 31.91 2,244 1.91 0.27 225 SC-N8
40 200.0 42.55 2,992 2.55 0.20 300 SC-N11
50 250.0 53.19 3,740 3.19 0.16 400 SC-N12
75 375.0 79.79 5,610 4.79 0.11 600 SC-N14
100 500.0 106.38 7,480 6.38 0.08 800 SC-N16
150 750.0 159.57 11,220 9.57 0.05 1200
200 1000.0 212.77 14,961 12.77 0.04 1500
300 1500.0 319.15 22,441 19.15 0.03 2500
400 1.07 2.7 1.14 20 0.07 30.38 5 SC-03
1.60 4.0 1.70 30 0.10 20.32 10 SC-03
2.67 6.7 2.84 50 0.17 12.18 10 SC-0
4.01 10.0 4.27 75 0.26 8.11 15 SC-05
5 12.5 5.32 94 0.32 6.50 20 SC-4-0
10 25.0 10.64 187 0.64 3.25 40 SC-N1
15 37.5 15.96 281 0.96 2.17 60 SC-N2
20 50.0 21.28 374 1.28 1.63 75 SC-N2S
25 62.5 26.60 468 1.60 1.30 100 SC-N3
30 75.0 31.91 561 1.91 1.08 125 SC-N4
40 100.0 42.55 748 2.55 0.81 150 SC-N6
50 125.0 53.19 935 3.19 0.65 200 SC-N7
75 187.5 79.79 1,403 4.79 0.43 300 SC-N11
100 250.0 106.38 1,870 6.38 0.33 400 SC-N14
150 375.0 159.57 2,805 9.57 0.22 600 SC-N16
200 500.0 212.77 3,740 12.77 0.16 800 SC-N16
300 750.0 319.15 5,610 19.15 0.11 1200
60 220 0.97 4.4 1.03 50 0.06 12.17 10 SC-03
1.94 8.8 2.06 100 0.12 6.08 15 SC-0
2.91 13.2 3.10 150 0.19 4.06 20 SC-0
3.88 17.6 4.13 200 0.25 3.04 30 SC-4-1
5 22.7 5.32 258 0.32 2.36 40 SC-N1
10 45.5 10.64 515 0.64 1.18 75 SC-N2S
15 68.2 15.96 773 0.96 0.79 125 SC-N4
20 90.9 21.28 1,030 1.28 0.59 150 SC-N6
25 113.6 26.60 1,288 1.60 0.47 200 SC-N7
30 136.4 31.91 1,546 1.91 0.39 225 SC-N8
40 181.8 42.55 2,061 2.55 0.30 300 SC-N11
50 227.3 53.19 2,576 3.19 0.24 400 SC-N11
75 340.9 79.79 3,864 4.79 0.16 600 SC-N14
100 454.5 106.38 5,152 6.38 0.12 800 SC-N14
150 681.8 159.57 7,728 9.57 0.08 1200
200 909.1 212.77 10,303 12.77 0.06 1500
300 1363.6 319.15 15,455 19.15 0.04 2500
440 1.55 3.5 1.65 20 0.10 30.45 5 SC-03
2.33 5.3 2.48 30 0.15 20.26 10 SC-0
3.11 7.1 3.31 40 0.20 15.18 10 SC-0
3.88 8.8 4.13 50 0.25 12.17 15 SC-4-0
5 11.4 5.32 64 0.32 9.44 20 SC-4-0
10 22.7 10.64 129 0.64 4.72 40 SC-N1
15 34.1 15.96 193 0.96 3.15 60 SC-N2
20 45.5 21.28 258 1.28 2.36 75 SC-N2S
25 56.8 26.60 322 1.60 1.89 100 SC-N3
30 68.2 31.91 386 1.91 1.57 125 SC-N4
40 90.9 42.55 515 2.55 1.18 150 SC-N6
50 113.6 53.19 644 3.19 0.94 175 SC-N7
75 170.5 79.79 966 4.79 0.63 300 SC-N11
100 227.3 106.38 1,288 6.38 0.47 350 SC-N12
150 340.9 159.57 1,932 9.57 0.31 600 SC-N14
200 454.5 212.77 2,576 12.77 0.24 700 SC-N16
300 681.8 319.15 3,864 19.15 0.16 1000
71
Selection and application
3 3-8 Selecting an MCCB for capacitor circuit
Table 3-20 (2) MCCB rated current application examples for three-phase capacitor equipment capacity
Rated frequency Rated voltage Rated equipment Rated current Capacitor rating Series reactor 6% MCCB rated MC type
(Hz) (V) capacity (kvar) (A) (kvar) (μF) (kvar) (mH) current (A) (reference)
50 200 1.34 3.9 1.43 100 0.09 6.06 10 SC–03
2.67 7.7 2.84 200 0.17 3.04 15 SC–03
3.34 9.6 3.55 250 0.21 2.43 15 SC–03
4.01 11.6 4.27 300 0.26 2.03 20 SC–03
5 14.4 5.32 374 0.32 1.63 30 SC–4–0
10 28.9 10.64 748 0.64 0.81 50 SC–N1
15 43.3 15.96 1,122 0.96 0.54 75 SC-N2S
20 57.7 21.28 1,496 1.28 0.41 100 SC–N3
25 72.2 26.60 1,870 1.60 0.33 125 SC-N4
30 86.6 31.91 2,244 1.91 0.27 150 SC–N4
40 115.5 42.55 2,992 2.55 0.20 175 SC–N7
50 144.3 53.19 3,740 3.19 0.16 225 SC–N8 N10
75 216.5 79.79 5,610 4.79 0.11 350 SC–N11
100 288.7 106.38 7,480 6.38 0.08 500 SC–N12
150 433.0 159.57 11,220 9.57 0.05 700 SC–N14
200 577.4 212.77 14,961 12.77 0.04 900
300 866.0 319.15 22,441 19.15 0.03 1400
400 1.07 1.5 1.14 20 0.07 30.38 5 SC–03
1.60 2.3 1.70 30 0.10 20.32 5 SC–03
2.67 3.9 2.84 50 0.17 12.18 10 SC–03
4.01 5.8 4.27 75 0.26 8.11 10 SC–03
5 7.2 5.32 94 0.32 6.50 15 SC–03
10 14.4 10.64 187 0.64 3.25 30 SC–4–0
15 21.7 15.96 281 0.96 2.17 40 SC-N1
20 28.9 21.28 374 1.28 1.63 50 SC–N1
25 36.1 26.60 468 1.60 1.30 60 SC-N2
30 43.3 31.91 561 1.91 1.08 75 SC–N2S
40 57.7 42.55 748 2.55 0.81 100 SC–N3
50 72.2 53.19 935 3.19 0.65 125 SC–N4
75 108.3 79.79 1,403 4.79 0.43 175 SC–N7
100 144.3 106.38 1,870 6.38 0.33 225 SC–N8 N10
150 216.5 159.57 2,805 9.57 0.22 350 SC–N11
200 288.7 212.77 3,740 12.77 0.16 500 SC–N12
300 433.0 319.15 5,610 19.15 0.11 700 SC–N14
60 220 0.97 2.5 1.03 50 0.06 12.17 5 SC–03
1.94 5.1 2.06 100 0.12 6.08 10 SC–03
2.91 7.6 3.10 150 0.19 4.06 15 SC–03
3.88 10.2 4.13 200 0.25 3.04 20 SC–03
5 13.1 5.32 258 0.32 2.36 20 SC–03
10 26.2 10.64 515 0.64 1.18 40 SC–N1
15 39.4 15.96 773 0.96 0.79 60 SC-N2
20 52.5 21.28 1,030 1.28 0.59 100 SC–N2S
25 65.6 26.60 1,288 1.60 0.47 100 SC-N3
30 78.7 31.91 1,546 1.91 0.39 125 SC–N4
40 105.0 42.55 2,061 2.55 0.30 175 SC–N7
50 131.2 53.19 2,576 3.19 0.24 200 SC–N7
75 196.8 79.79 3,864 4.79 0.16 300 SC–N11
100 262.4 106.38 5,152 6.38 0.12 400 SC–N12
150 393.6 159.57 7,728 9.57 0.08 600 SC–N14
200 524.9 212.77 10,303 12.77 0.06 800 SC–N16
300 787.3 319.15 15,455 19.15 0.04 1200
440 1.55 2.0 1.65 20 0.10 30.45 5 SC–03
2.33 3.1 2.48 30 0.15 20.26 5 SC–03
3.11 4.1 3.31 40 0.20 15.18 10 SC–03
3.88 5.1 4.13 50 0.25 12.17 10 SC–03
5 6.6 5.32 64 0.32 9.44 10 SC–03
10 13.1 10.64 129 0.64 4.72 20 SC–03
15 19.7 15.96 193 0.96 3.15 30 SC-4-1
20 26.2 21.28 258 1.28 2.36 40 SC–N1
25 32.8 26.60 322 1.60 1.89 50 SC-N1
30 39.4 31.91 386 1.91 1.57 60 SC–N2
40 52.5 42.55 515 2.55 1.18 100 SC–N2S
50 65.6 53.19 644 3.19 0.94 100 SC–N3
75 98.4 79.79 966 4.79 0.63 150 SC–N5, N5A
100 131.2 106.38 1,288 6.38 0.47 200 SC–N7
150 196.8 159.57 1,932 9.57 0.31 300 SC–N11
200 262.4 212.77 2,576 12.77 0.24 400 SC–N12
300 393.6 319.15 3,864 19.15 0.16 600 SC–N14
72
Selection and application
3-9 MCCBs for semiconductor circuit
3
3-9 MCCBs for semiconductor circuit 3-9-1 Faults and overcurrents in thyristor
Circuits containing semiconductor devices such as thyristors converters
and diodes differ in the following respects: The possible causes of overcurrents in thyristor converters
s 4HE CURRENT mOWING THROUGH THE -##" DEPENDS ON WHERE can be broadly classified into two categories: internal faults
the MCCB is installed in the circuit. in the converters, and those external to the converters. Table
s 4HE FAULT CURRENT DEPENDS ON FAULT MODES 3-21 lists the typical possible causes of overcurrents in
s 4HE OVERCURRENT CAPACITY OF SEMICONDUCTOR DEVICES IS LOWER line- commutated thyristor converters and their associated
than that of other electrical apparatus. conditions. Fig. 3-29 shows examples of the path of
Allowance should be made for these characteristics when overcurrent flow.
selecting an MCCB.
Table 3-21 Possible causes of overcurrents in line-commutated thyristor converters
Faulty ignition SCRs fire when they should If SCRs are connected in parallel, current Commutation fails, resulting in a short
maintain forward blocking. concentrates in the SCRs that misfire, circuit occurring on the DC side.
Suspect an excessive forward resulting in an overcurrent.
voltage, excessive dv/dt, or
gate noise.
Device break- A short circuit has resulted A short circuit has occurred in the input An AC interphase short circuit generated
down from the loss of SCR forward AC source. a backward current that caused a transi-
blocking capability. Suspect an tion to commutation failure, resulting in a
excessive junction tempera- short circuit on the DC side.
ture or overvoltage input.
External Commutation Suspect power failure or a With an inductive load, current flows The loss of the commutating power
faults failure broken wire in the power sup- through the arm that had been turned on source causes a commutation failure,
ply circuit. until loss of the power source for a rela- resulting in a short circuit on the DC side.
tively long period of time raises junction
temperature.
Short circuit in Suspect a short circuit in the A short circuit in the AC input source. The Commutation fails as the AC voltage
load side DC circuit or flashover in the overcurrent flowing through the SCRs required for commutation is lost, but no
DC motor. varies with the short-circuit point, or the overcurrent flows through the SCRs.
presence or absence of a DC reactor.
Table 3-21 and Fig. 3-29 show that, to protect normal devices, provides two modes: one in which the thyristor converter is run
an overcurrent protection device must be installed, for each as a conversion (driving the DC motor), and one in which the
element (arm) in the conversion or on the AC side, for each thyristor converter is run as an inversion (regenerative braking
element in an inversion or on the DC side. of the DC motor). Installation of protective devices should be
The Ward-Leonard thyristor configuration in which the speed examined by considering possible failures in these two modes.
of the DC motor is controlled by thyristor phase control
Fig. 3-29 Example of the path of overcurrent flow in thyristor converters
During conversion During inversion Commutation failure
Device breakdown
M M
Short-circuit
73
Selection and application
3 3-9 MCCBs for semiconductor circuit
I Id I Id
I =Ia
Ia Ia
I =Ia=Id
Id
Current waveform
ip ip ip ip
1 + 3 ip | 0.553ip
6 4S
Current waveform
ip ip ip ip
3 + 3 3 ip | 0.956ip
6 4S
Current waveform
ip ip ip ip
AC side
1/f 1/f
1/f
1/f
S ip S ip Effective: I (eff)
2
ip
Effective: I (eff) 1 ip
2
Effective: I (eff) 1 ip
2 2 + 2 3 ip | 0.78ip
6 4S
Note: The loads are resistive, and the conduction angle of the device is 180°.
74
Selection and application
3-9 MCCBs for semiconductor circuit
3
3-9-3 Protecting thyristors from overcurrent Fig. 3-31 Coefficient for converting to effective values
No load
Rated load
MCCB
i
75
Selection and application
3 3-9 MCCBs for semiconductor circuit
Any examination of the scheme of protection coordination (4) Use of MCCBs on the DC side of thyristors
between MCCBs and devices should allow conversion of
When MCCBs are installed on the DC side of a converter Fig.
the device overcurrent immunity into effective values for
3-34, their primary duty will be interrupting the fault current
comparison. For example, in a three-phase bridge like that
that flows through the circuit when commutation fails during
shown in Fig. 3-32, the currents through the MCCBs differ
inversion in a thyristor Ward-Leonard or similar configuration.
from that in devices and they must be compared on the same
Typically, an instantaneous trip type circuit breaker is used with
current base.
the instantaneous trip current set to about two or three times
Fig. 3-33 Typical protection coordination curves
its rating. The scheme of protection coordination is considered
in terms of I2t.
(a)
Fig. 3-34 Using an MCCB in a DC circuit
5 4
t 2 Faulty device
1
MCCB
AC
3
Region B Region C
Region A
1. Thyristor overcurrent immunity characteristics
2. Instantaneous trip type circuit breaker operating characteristics
3. Semiconductor protection fuse operating characteristics
4. Overcurrent relay operating characteristics
5. Motor breaker operating characteristics
(b)
t 2
1
i
Region B Region C
76
Selection and application
3-10 Protecting SSCs using MCCBs or MMSs
3
Table 3-23 Protecting SSCs for heater circuits using MCCB (short-circuit region)
77
Selection and application
3 3-10 Protecting SSCs using MCCBs or MMSs
Rated voltage Motor capacity SSC Type Manual motor starter (MMS) Fuse
(kW)
Type Breaking capacity (kA) Type Breaking capacity (kA)
250V AC
230V AC 0.2 SS03 BMSRSB-1P6 100 CR2L(S)-10 100
3-phase 0.4 SS08 BM3RSB-2P5 *1 100 CR2L(S)-10 100
0.75 SS20 BM3RSB-004 100 CR2L(S)-30 100
1.5 SS30 BM3RSB-6P3 100 CR2L(S)-50 100
2.2 SS40 BM3RSB-010 100 CR2L(S)-75 100
3.7 SS50 BM3RSB-016 100 CR2L(S)-100 100
5.5 SS80 BM3RSB-025 50 CR2L-140 100
7.5 SS802 BM3RSB-032 50 CR2L-175 100
7.5 SS120 BM3RSB-032 50 CR2L-175 100
400V AC 1.5 SS30H BM3RSB-004 100 CR6L-30 100 *2
3-phase 2.2 SS30H BM3RSB-6P3 100 CR6L-50 100 *2
3.7 SS30H BM3RSB-010 100 CR6L-50 100 *2
5.5 SS50H BM3RSB-013 50 CR6L-75 100 *2
7.5 SS50H BM3RSB-016 50 CR6L-100 100 *2
15 SS80H BM3RSB-032 50 CR6L-200 100 *2
15 SS120H BM3RSB-032 50 CR6L-200 100 *2
Notes: Indicates SSCs mounted on standard cooling fins.
*1 Overload protection is not available in some regions.
*2 Breaking capacity at 600V AC.
78
Selection and application
3-11 Protecting inverter circuits using MCCBs
3
Rated voltage Motor Full load MCCB rated current (A) Rated voltage Motor Full load MCCB rated current (A)
output current With DC Without DC output current With DC Without DC
(kW) (A) reactor reactor (kW) (A) reactor reactor
200V AC 0.1 0.68 5 5 400V AC 0.4 1.15 5 5
3-phase 0.2 1.3 3-phase 0.75 1.8
0.4 2.3 1.5 3.5 10
0.75 3.5 10 2.2 4.8 15
1.5 6.9 10 15 3.7 7.8 10 20
2.2 9.5 20 5.5 10.5 15 30
3.7 15.5 20 30 7.5 13.5 20 40
5.5 21 30 50 11 20 30 50
7.5 27.5 40 75 15 27 40 60
11 40 50 100 18.5 34 75
15 54 75 125 22 42 50 100
18.5 68 100 150 30 58 75 125
22 84 175 37 69 100
30 116 150 200 45 83 150
37 137 175 250 55 100 125 200
45 166 200 300 75 136 175 -
55 200 250 350 90 166 200
75 272 350 - 110 190 250
90 332 400 132 225 300
110 380 500 160 273 350
Note: *1 U 200 342 500
220 376
280 600
315 800
355
400 1200
450
500
Note: For the MCCB types, the rated current values recommended for 50˚C or lower
panel inside temperature are shown. Select an actual type according to the
facility short-circuit interrupting capacity.
79
Selection and application
3 3-12 MCCBs for high frequency circuits
3-12 MCCBs for high frequency circuits Table 3-26 MCCBs for 400Hz circuits
Specify 400Hz when ordering an MCCB for a 400Hz circuit.
Hydraulic-magnetic type and solid-state trip type MCCBs
cannot be used in 400Hz circuits because their characteristics Frame Type Icu (kA) Rated current
size (A)
would vary considerably. 400V AC 230V AC
Since the instantaneous trip current of standard 125AF BW125JAG 30 50 15, 20, 30, 40, 50,
thermalmagnetic MCCBs models (magnetic element) will 60, 75, 100
BW125RAG 50 100
increase by 1.5 to 2.5 times the cataloged value around
400Hz, circuit breakers specially designed for use in 400Hz 250AF BW250EAG 18 30 125, 150, 160,
175, 200, 225
circuits should be used (these models are available on BW250JAG 30 50
request). Because highcurrent rating MCCB (400AF to 800AF) BW250RAG 50 100
generate increased heat due to the skin effect, their load
400AF *1 BW400EAG 30 50 250, 300, 350
capacity must be derated 20% to 30%.
Table 3-26 lists some FUJI MCCBs recommended for use in BW400SAG 36 85
400Hz circuits. BW400RAG 50 100
Note: *1 Use a load capacity 20 to 30% lower because of the skin effect.
80
Selection and application
3-13 MCCBs for DC circuit applications
3
3-13 MCCBs for DC circuit applications Operating characteristic changes for DC circuit application
While MCCBs are designed for an AC circuit, some may be Trip Inverse time-delay Instantaneous trip Operating
used in a DC circuit. The DC rating is cited in the catalog for device trip characteristic characteristics characteristic curve
those applicable to a DC circuit. If a MCCB adjusted for AC is Thermal- None The instantaneous trip
magnetic current is higher than
to be used in a DC environment, the operating characteristics
Operating time
that for an AC circuit.
DC
will change as indicated in the table on the right. Therefore, The rate of variation
depends on the AC
FAB adjusted for DC shall be used for a DC load. Further, due
ampere-frame size,
to the absence of a zero-crossing point, it is more difficult to rated current and Current
break a DC current than an AC current in high-voltage levels. Hydraulic- The minimum
model. The trip
current can be as high
Therefore, standard products cannot be used. magnetic operating current at
as 140% of the AC
Operating time
DC is
In such a case, it is necessary to use a breaker dedicated for value. DC
about 110–140% of
use with a DC high voltage. that for AC. AC
ELCB cannot be used because it cannot detect leakage of DC Current
current.
Solid state Not applicable
81
Selection and application
3 3-13 MCCBs for DC circuit applications
Note 1) While 400 - 800AF can be used for the standard products of DC500V(3-pole item) and DC600V(4-pole item), only DC250V is cited on the nameplate. If it is necessary to indicate
DC500V or DC600V, please specify “C5” or “C6” at the end of the type description.
N P N P N P
Load
Load
Load
82
Selection and application
3-14 MCCBs for UPS applications
3
83
Selection and application
3 3-15 MCCBs for servo amplifier applications
84
Selection and application
3-16 Ground fault protection in system applications
3
Notes: *1 The TN system is mainly used in Europe (except for France) while the s 4. # 3 4HE NEUTRAL CONDUCTOR AND PROTECTIVE CONDUCTOR FUNCTIONS
TT system is mainly used in Japan and France for direct grounding. are combined into a single conductor in one part of a TN-S system.
A TN system is grounded to one point. Here, all exposed conductive Table 3-31 shows a comparison of various characteristics for
parts at the load side are grounded at one point through protective grounding systems as well as precautions regarding their use.
conductors. The neutral conductor and protective conductor are A TT system is grounded to one point in the system. All exposed
handled in one of the following ways. conductive parts at the load side are grounded to a ground electrode
s 4. 3 4HE NEUTRAL CONDUCTOR AND PROTECTIVE CONDUCTOR FOR THE OVERALL that is electrically separate from the ground terminal for the system.
system are completely separate. *2 A system that uses no grounding is referred to as an IT system.
s 4. # 4HE NEUTRAL CONDUCTOR AND PROTECTIVE CONDUCTOR FUNCTIONS FOR
the overall system are combined into a single conductor.
85
Selection and application
3 3-16 Ground fault protection in system applications
Table 3-31 Comparison of grounding system (TN, TT and IT systems) characteristics and precautions for their use
Features s 4HE NEUTRAL CONDUCTOR AND PROTECTIVE s 4HE NEUTRAL CONDUCTOR AND PROTECTIVE s 4HE NEUTRAL CONDUCTOR AND PROTECTIVE
conductor functions for the overall conductor for the overall wiring system conductor functions for part of the wiring
system are combined into a single are completely separate. system are combined into a single
conductor. s 4HE PROTECTIVE CONDUCTOR 0% IS EITHER A conductor.
s !LL EXPOSED CONDUCTIVE PARTS OF THE metal sheath on the supply cable for the s 4HE MOST COMMON CONlGURATIONS ARE
equipment are connected to a PEN equipment or a conductor completely the TN-C wiring system on the power
conductor. separate from the system. supply side and a TN-S wiring system
s #ALCULATE THE FAULT LOOP IMPEDANCE FOR s !LL EXPOSED CONDUCTIVE PARTS OF THE on the equipment side.
shock protection and use an MCCB for equipment are connected to the s !LL EXPOSED CONDUCTIVE PARTS OF
system protection. conductor through the main ground the equipment are connected to a
s 7IDELY USED IN &RANCE THE 5+ AND THE terminal on the equipment. conductor through the main ground
United States terminal and the neutral line terminal
on the equipment, which are connected
together.
Indirect From the phase conductor to the ground for the exposed parts of the load equipment: Contact voltage of 50V max.
contact Zero impedance short-circuiting from the phase conductor in the equipment to the protective conductor or exposed parts:
protection U0 t la × Zs where U0 is the nominal voltage to ground (effective AC value), Ia is the maximum breaking time from the following
standards table as a function of U0 or the current that causes the protective device to trip automatically within the conditional time setting
of five seconds, and Zs is the fault loop impedance derived from the charging conductor from the power supply to the fault point
and the protective conductor between the fault point and the power supply.
s -AXIMUM BREAKING TIME FOR A 4. SYSTEM
s #ONDITIONS FOR A MAXIMUM BREAKING TIME OF S 4HE MAXIMUM BREAKING TIME IN THE TABLE ABOVE MAY BE EXCEEDED IN BRANCH
circuits that supply power to stationary equipment only, but 5 s or less is the allowable breaking time. Supplemental conditions
must be provided separately if other branch circuits that require the maximum breaking time given in the table are connected to
those branch circuits.
MCCB
s 7ITH INVERSE TIME DELAY CHARACTERISTICS )A IS THE CURRENT THAT CAN TRIP THE -##" AUTOMATICALLY WITHIN S
s 7ITH INSTANTANEOUS TRIPPING CHARACTERISTICS )A IS THE SMALLEST CURRENT THAT CAN TRIP THE -##" AUTOMATICALLY
Applicable s -##" s -##" s -##"
protective s %,#" s %,#" APPLICABLE ONLY IN 4. 3 WIRING
device circuits only)
Application 1. Use only MCCBs. 1. Select a suitable ground fault 1. Select a suitable ground fault
(design) 2. Calculate the fault loop impedance. protection device for the protection protection device for the protection
precautions 3. Ignore the fault point impedance system. system.
between the phase conductor and the 2. Overcurrent breaking precautions: 2. ELCBs can only be installed in certain
protective conductor. Same as TN-C items 2 and 3. locations.
3. Overcurrent breaking precautions:
Same as TN-C items 2 and 3.
Note: The number of ground fault protection devices can be reduced once
potential equalization work and fault loop impedance calculations are
completed with TN systems, but never install low-voltage electrical
equipment using both TN and TT systems together in the same location.
86
Selection and application
3-16 Ground fault protection in system applications
3
Continued
Features s !LL EXPOSED CONDUCTIVE PARTS OF THE EQUIPMENT ARE CONNECTED s !LL EXPOSED CONDUCTIVE PARTS OF THE EQUIPMENT ARE CONNECTED
to a ground electrode that is completely separate from the to a ground electrode that is completely separate from the
power supply ground. power supply ground.
s 4HIS SYSTEM IS THE MOST COMMONLY USED IN *APAN s 4HE POWER SUPPLY IS CONNECTED TO GROUND THROUGH INSERTED
ground impedance or is completely disconnected from
ground.
s 4HIS WIRING SYSTEM IS WIDELY USED IN .ORWAY )N *APAN
however, greater emphasis is placed on circuits that supply
power without interruption rather than on those that shut down
the power supply.
Indirect 50V t Ia × RA 50V t Id × RA
contact RA: Sum of the ground resistance and the protective conductor RA: Same as that on the left.
protection resistance connected to exposed conductive parts. Id: Ground fault current at the first occurrence of a ground
standards Ia: Current that trips the MCCB automatically. (With an ELCB, fault where impedance between the phase conductor and
Ia is the rated sensitivity current I'n.) exposed conductor parts can be ignored. It is derived
The MCCB is as follows. from the leak current and total ground impedance of the
s 7ITH INVERSE TIME DELAY CHARACTERISTICS )A IS THE CURRENT THAT electrical equipment.
can trip the MCCB automatically within 5 s. s )NSTALL AN INSULATION MONITORING DEVICE THAT INDICATES THE
s 7ITH INSTANTANEOUS TRIPPING CHARACTERISTICS )A IS THE SMALLEST first occurrence of a ground fault in order to maintain an
current that can trip the MCCB automatically. uninterrupted power supply.
s 0OWER SUPPLY SHUTDOWN CONDITIONS FOLLOWING THE lRST
occurrence of a ground fault or with the second occurrence of
a ground fault should be provided separately.
Applicable s -##" ONLY IF 2A is very low however) s )NSULATION MONITORING DEVICE
protective s %,#" s -##"
device s %,#"
Application 1. Select a suitable ground fault protection device for the 11.Select a suitable ground fault protection device for the
(design) protection system. protection system.
precautions 2. Overcurrent breaking precautions: 2. The power supply can shut down automatically when a
s 4HE ADDITIONAL CONDITIONS OUTLINED ABOVE MUST BE PROVIDED second ground fault occurs with overcurrent breaking.
separately. 3. Id t I'n when leak current breaking is used. Here, the power
s /THER PRECAUTIONS ARE THE SAME AS 4. # ITEMS AND supply can shut down automatically when the first ground
fault occurs.
87
88
Environment and usage
Chapter 4 precautions
CONTENTS
89
Environment and usage precautions
4 4-1 Standard conditions
90
Environment and usage precautions
4-2 Application to special environments
4
50 90% max.
60 80% max.
91
Environment and usage precautions
4 4-2 Application to special environments
92
Environment and usage precautions
4-3 Connection precautions
4
OFF OFF
93
Environment and usage precautions
4 4-4 Malfunction due to transient inrush current
94
Maintenance inspections
Chapter 5
CONTENTS
95
Maintenance inspections
5 5-1 Faults and causes
Note: * Do not inspect or take any other action until you are sure there is no voltage applied to the MCCB terminals.
96
Maintenance inspections
5-1 Faults and causes
5
Continued
Type of fault Fault status or location Possible cause Countermeasure
Faulty Faulty operation at higher than the s ,ACK OF COORDINATION WITH AN UPSTREAM CURRENT LIMITING FUSE Re-evaluate coordination or change the
operation due specified operating current or with an upstream circuit breaker. selection.
to overcurrent s !MBIENT TEMPERATURE IS EXTREMELY LOW Check the current correction.
s 4HE AMMETER GIVES AN INCORRECT READING BECAUSE OF HIGH
frequency current.
Accessory Motor operating mechanism fault s )MPROPER CONTROL CIRCUIT CABLE CONNECTION CAUSES FAULTY Inspect and repair the cables. *
fault operation.
s )MPROPER CONTROL CIRCUIT CABLE CONNECTION CAUSES OPERATION
to start and stop repeatedly. (Snake circuit formed by
connecting the control signal circuit in parallel.)
s ! DROP IN VOLTAGE DUE TO INSUFlCIENT CAPACITY ON THE POWER Use heavier gauge cable.
supply circuit cable causes faulty operation. Increase the power supply capacity
s )NSUFlCIENT CAPACITY OF THE CONTROL CIRCUIT POWER SUPPLY (transformer capacity, etc.).
s -AKE RUN AND RESET DO NOT WORK PROPERLY BECAUSE THE Re-adjust the stroke. *
moving distance of the control mechanism is not properly
adjusted.
Shunt trip device fault s ! DROP IN POWER SUPPLY VOLTAGE DUE TO INSUFlCIENT POWER Increase the power supply capacity. *
capacity for the control circuit causes faulty operation.
s ! DROP IN POWER SUPPLY CURRENT DUE TO INSUFlCIENT POWER
supply capacity causes faulty operation.
s #ONTINUOUS EXCITATION AN INCORRECT COIL RATING AND FAULTY COIL Replace the coil and replace the
anti-burnout contact operation or coil burnout due to welded contacts with coil anti-burnout
contacts. contacts. *
Undervoltage trip device fault s 4HE -##" DOES NOT TRIP DUE TO RESIDUAL MAGNETIC mUX AND Repair or replace with a new part. *
no voltage.
s 4HE -##" DOES NOT TRIP DUE TO AN IMPROPERLY MOVING STROKE
and no voltage.
Auxiliary switch and alarm switch s #URRENT EXCEEDING THE MICROSWITCH CONTACT RATING BURNS OUT Replace the accessories and insert
fault the contacts or welds them together. a control relay to reduce the load on
internal switch contacts.
s !N IMPROPER MICROSWITCH MOVING STROKE CAUSES FAULTY Replace or repair the microswitch. *
operation.
97
Maintenance inspections
5 5-2 Periodic inspections
Table 5-2 Initial inspection and judgment criteria prior to the operation starting
Inspection item Criteria Countermeasures for defects
1. Inspect the area around the terminals to make sure no dust, frag- No foreign matter Vacuum up foreign matter. Wipe the
ments, pieces of wiring, screws, or other conductive foreign matter area with a dry cloth.
were left behind.
2. Inspect the MCCB case and cover to make sure there are no cracks No cracks or damage Replace the enclosure.
or damage.
3. Inspect the connector to make sure the conductors are securely Conductors are tightened to the Tighten conductors to the specified
tightened. specified torque torque.
4. Measure insulation resistance with a 500V DC megger. 5M: min. Replace with a new part.
Note: Do not inspect until you are sure there is no voltage applied to the MCCB terminals.
Table 5-3 Inspection and judgment criteria within one month after the operation starting
Inspection item Criteria Countermeasure for defects
1. Loose conductor connectors? Conductors tightened at the Tighten conductors at the specified
specified torque torque.
2. Inspect the area around the terminals to make sure no dust, frag- No noticeable dust, oil or Vacuum up the foreign matter. Wipe
ments, pieces of wiring, screws, or other conductive foreign matter conductive foreign matter the area with a dry cloth.
were left behind.
3. No abnormal temperature rise? No discoloration of the terminal Replace with a new part.
connectors or molded plastic due
to excessive heat
Note: Do not inspect until you are sure there is no voltage applied to the MCCB terminals.
98
Maintenance inspections
5-2 Periodic inspections
5
99
Maintenance inspections
5 5-3 Replacement recommendations
Table 5-8 Guidelines for the timing of MCCB deterioration diagnosis and replacement
(Technical Rep. 142, Standard of Japan Electrical Manufactures)
Environment Example Guidelines for the timing Guidelines for the timing
of deterioration diagnosis of MCCB replacement
Normal A location with a constant supply of A dustproof, air-conditioned electrical 10 years 15 years
environment clean and dry air equipment room
An indoor location with minimal dust Installed in a control panel in a 7 years 13 years
and no corrosive gases separate electrical equipment
room with no dustproofing or air
conditioning, or inside an enclosure.
Poor A location with high humidity and Geothermal power generation 3 years About 3 to 7 years
environment minimal dust containing salt or equipment and sewage plants as well
gases like nitrous acid gas and as paper, steel, and pulp plants
hydrogen sulfide gas
A location where people could not Chemical factories, quarries, or mines 1 year About 1 to 3 years
stay for long periods, or a location
with excessive dust or corrosive gas
100
Short-circuit current
Chapter 6 calculation
CONTENTS
101
Short-circuit current calculation
6 6-1 Calculating short-circuit current
IB = IT = PT u 103 (A) PM = PB
3VT %Xm' %Xm
Reference impedance (Formula for converting into another capacity)
ZB = VB2 VT2
= (:)
PB u 103 PT u 103 (4) Bus duct and cable impedance
These are normally expressed by cross sections (rated current
Fig. 6-1 Short-circuit capacity or
for the bus duct) and length.
ZC = (Ohms per unit length) u (Length) (:)
breaking capacity
Convert this value into a percentage.
Q (MVA) o j%X1
%ZC = ZC u 100%
PT (kVA) ZB
/VT (V) %ZT = %RT + j%XT
Bus duct jX3 (:) o j%X3 (If the value is given in ohms, convert it to a
percentage.)
Cable Cable
jX2 (:) o j%X2
R4 (:) + jX4 (:) R5n (:) + jX5n (:)
%R4 + j%X4 %R5n + j%X5n
F
j%Xm M Total capacity PM (kVA)
PM (kVA) = 1.5x (kW sum total)
102
Short-circuit current calculation
6-1 Calculating short-circuit current
6
%Z = (%R)2 + (%X)2
= PB u 10 u 100
3
3VB%Z
= IB u 100 [A]
%Z
Fig. 6-2
Infinite busbar
j%X1 j%X5 j%Xn
%RT %R5 %Rn
j%XT j%X5 j%Xn
j%X3
j%X2
%R4
j%X4
F
Fig. 6-3
Infinite busbar
%R
j%X
F
103
Short-circuit current calculation
6 6-1 Calculating short-circuit current
104
Short-circuit current calculation
6-1 Calculating short-circuit current
6
.OTES s !DD REACTANCE ON THE POWER SUPPLY SIDE TO lND THE VALUE BECAUSE
reactance is 1.2 times higher at 60Hz.
s 5SE OR THE ACTUAL CABLE LENGTH TO CALCULATE REACTANCE AND
resistance when using two or three cables connected in parallel.
Table 6-4 Bus bar and bus duct impedance examples (50Hz) Data: Furukawa Electric Co., Ltd.
Material Rated current Regular bus duct
(A) Conductor dimensions Resistance Reactance X Impedance Z
(mm) (:/m) (:/m) (:/m)
Aluminum 200 6 u 25 1.93 u 10-4 1.25 u 10-4 2.3 u 10-4
(Al) 400 6 u 50 0.97 u 10 -4
0.909 u 10 -4
1.33 u 10-4
600 6 u 75 0.657 u 10-4 0.72 u 10-4 0.974 u 10-4
800 6 u 125 0.404 u 10-4 0.516 u 10-4 0.655 u 10-4
1000 6 u 150 0.343 u 10 -4
0.45 u 10-4
0.566 u 10-4
1200 6 u 100 u 2 0.249 u 10 -4
0.882 u 10 -4
0.916 u 10-4
1500 6 u 125 u 2 0.201 u 10 -4
0.790 u 10 -4
0.815 u 10-4
2000 6 u 200 u 2 0.133 u 10-4 0.588 u 10-4 0.603 u 10-4
Copper 200 3 u 25 2.41 u 10-4 1.312 u 10-4 2.74 u 10-4
(Cu) 400 6 u 40 0.751 u 10 -4
1.02 u 10-4
1.267 u 10-4
600 6 u 50 0.607 u 10 -4
0.91 u 10-4
1.094 u 10-4
800 6 u 75 0.412 u 10 -4
0.72 u 10-4
0.830 u 10-4
1000 6 u 100 0.315 u 10 -4
0.60 u 10-4
0.678 u 10-4
1200 6 u 125 0.261 u 10-4 0.511 u 10-4 0.573 u 10-4
1500 6 u 150 0.221 u 10-4 0.449 u 10-4 0.500 u 10-4
2000 6 u 125 u 2 0.129 u 10 -4
0.79 u 10-4
0.800 u 10-4
105
Glossary
Glossary
Alarm switch An auxiliary switch which operates only upon the tripping of the circuit
breaker with which it is associated.
Ambient air temperature Temperature, determined under prescribed conditions, of the air surrounding
the complete switching device or fuse.
Anti-pumping device A device which prevents reclosing after a close-open operation as long as the
device initiating closing is maintained in the position for closing.
Applied voltage (for a switching Voltage which exists across the terminals of a pole as a switching device just
device) before the making of the current.
NOTE: This definition applies to a single-pole device. For a multipole device it
is the phase-to-phase voltage across the supply terminals of the device.
Arcing time (of a multipole switching Interval of time between the instant of the first initiation of an arc and the
device) instant of final arc extinction in all poles.
Auxiliary contact Contact included in an auxiliary circuit and mechanically operated by the
switching device.
Auxiliary switch (of a mechanical Switch containing one or more control and/or auxiliary contacts mechanically
switching device) operated by a switching device.
Breaking capacity (of a switching Value of prospective breaking current that a switching device or a fuse is
device or a fuse) capable of breaking at a stated voltage under prescribed conditions of use
and behavior.
Breaking current (of a switching device Current in a pole of a switching device or a fuse at the instant of initiation of
or a fuse) the arc during a breaking process.
Break time Interval of time between the beginning of the opening time of a mechanical
switching device (or the pre-arcing time of a fuse) and the end of the arcing
time.
Circuit breaker Mechanical switching device, capable of making, carrying and breaking
currents under normal circuit conditions and also making, carrying for
a specified time and breaking currents under specified abnormal circuit
conditions such as those of short- circuit.
Clearance Distance between two conductive parts, along a string stretched the shortest
way between these conductive parts.
Closing time Interval of time between the initiation of the closing operation and the instant
when the contacts touch in all poles.
Conditional short-circuit current Prospective current that a circuit or a switching device, protected by a
(of a circuit or a switching device) specified short- circuit protective device, can satisfactorily withstand for the
total operating time of that device under specified conditions of use and
behavior.
Conductive part Part which is capable of conducting current although it may not necessarily
be used for carrying service current.
Control circuit (of a switching device) All the conductive parts (other than the main circuit) of a switching device
which are included in a circuit used for the closing operation or opening
operation, or both, of the device.
106
Glossary
Glossary
Conventional free-air thermal current The conventional free-air thermal current is the maximum value of test current
(Ith) to be used for temperature-rise tests of unenclosed equipment in free-air. The
value of the conventional free-air thermal current shall be at least equal to the
maximum value of the rated operational current of the unenclosed equipment
in eight-hour duty.
Conventional non-tripping current Specified value of current which the relay or release (trip device) can carry for
(of an overcurrent relay or release a specified time (conventional time) without operating.
(trip device))
Conventional tripping current Specified value of current which causes the relay or release (trip device) to
(of an overcurrent relay or release operate within a specified time (conventional time).
(trip device))
Creepage distance Shortest distance along the surface of an insulating material between two
conductive parts.
NOTE: A joint between two pieces of insulating material is considered part of
the surface.
Critical load current Value of breaking current, within the range of service conditions, at which the
arcing time is significantly extended.
Critical short-circuit current Value of breaking current, less than the rated short-circuit breaking capacity,
at which the arc energy is significantly higher than at the rated short-circuit
breaking capacity.
Current-limiting circuit breaker A circuit breaker with a break-time short enough to prevent the short-circuit
current reaching its otherwise attainable peak value.
Cut-off current (Let-through current) Maximum instantaneous value of current attained during the breaking
operation of a switching device or a fuse.
NOTE: This concept is of particular importance when the switching device or
the fuse operates in such a manner that the prospective peak current of the
circuit is not reached.
Disconnector Mechanical switching device which, in the open position, complies with the
requirements specified for the isolating function.
Exposed conductive part Conductive part which can readily be touched and which is not normally
alive, but which may become alive under fault conditions.
NOTE: Typical exposed conductive parts are walls of enclosures, operating
handles, etc.
Frame size A term designating a group of circuit breakers, the external physical
dimensions of which are common to a range of current ratings. Frame size
is expressed in amperes corresponding to the highest current rating of the
group. Within a frame size, the width may vary according to the number of
poles.
Fuse Device that, by the fusing of one or more of its specifically designed and
proportioned components, opens the circuit in which it is inserted by breaking
the current when this exceeds a given value for a sufficient time. The fuse
comprises all the parts that form the complete device.
Fuse-element Part of the fuse-link designed to melt under the action of current exceeding
some definite value for a definite period of time.
Impulse withstand voltage (Uimp) Highest peak value of an impulse voltage, of prescribed form and polarity,
which does not cause breakdown under specified conditions of test.
Instantaneous relay or release Relay or release (trip device) which operates without any intentional time-
(trip device) delay.
107
Glossary
Glossary
Inverse time-delay overcurrent relay or An overcurrent relay or release (trip device) which operates after a time-delay
release (trip device) inversely dependent upon the value of the overcurrent.
NOTE: Such a relay or release (trip device) may be designed so that the time-
delay approaches a definite minimum value for high values of overcurrent.
Isolating distance (of a pole of a Clearance between open contacts meeting the safety requirements specified
mechanical switching device) for disconnectors.
I2t characteristic of a circuit breaker Information (usually a curve) giving the maximum values of I2t related to
break time as a function of prospective current (r.m.s. symmetrical for AC) up
to the maximum prospective current corresponding to the rated short-current
breaking capacity and associated voltage.
Joule integral (I2t) Integral of the square of the current over a given time interval:
I 2t = ³ i 2dt
Let-through current ( = Cut-off current) See "Cut-off current."
Magnetic overload relay or release Overload relay or release (trip device) depending for its operation on the force
(trip device) exerted by the current in the main circuit exciting the coil of an electromagnet.
NOTE: Such a relay or release (trip device) usually has an inverse time-delay/
current characteristic.
Main circuit (of a switching device) All the conductive parts of a switching device included in the circuit which it is
designed to close or open.
Main contact Contact included in the main circuit of a mechanical switching device,
intended to carry, in the closed position, the current of the main circuit.
Make time Interval of time between the initiation of the closing operation and the instant
when the current begins to flow in the main circuit.
Maximum prospective peak current Prospective peak current when initiation of the current takes place at the
(of an AC circuit) instant which leads to the highest possible value.
NOTE: For a multipole device in a polyphase circuit, the maximum
prospective peak current refers to one pole only.
Molded case circuit breaker A circuit breaker having a supporting housing of molded insulating material
forming an integral part of the circuit breaker.
Neutral conductor (symbol N) Conductor connected to the neutral point of a system and capable of
contributing to the transmission of electrical energy.
NOTE: In some cases, the functions of the neutral conductor and the
protective conductor may be combined under specified conditions in one and
the same conductor referred to as the PEN conductor [Symbol PEN].
Opening time (of a mechanical Interval of time between the specified instant of initiation of the opening
switching device) operation and the instant when the arcing contacts have separated in all
poles.
NOTE: The instant of initiation of the opening operation, i.e. the application of
the opening command (e.g. energizing the release), is given in the relevant
product standard.
108
Glossary
Glossary
Overcurrent protective coordination Coordination of two or more overcurrent protective devices in series to ensure
overcurrent discrimination (selectivity) and/or backup protection.
Overcurrent relay or release Relay or release (trip device) which causes a mechanical switching device to
(trip device) open with or without time-delay when the current in the relay or release (trip
device) exceeds a predetermined value.
NOTE: This value can in some cases depend upon the rate-of-rise of current.
Overload relay or release (trip device) Overcurrent relay or release (trip device) intended for protection against
overloads.
Pollution Any condition of foreign matter, solid, liquid or gaseous (ionized gases), that
may affect dielectric strength or surface resistivity.
Pollution degree (of environmental Conventional number based on the amount of conductive or hygroscopic
conditions) dust, ionized gas or salt and on the relative humidity and its frequency of
occurrence, resulting in hygroscopic absorption or condensation of moisture
leading to reduction in dielectric strength and/or surface resistivity.
Prospective breaking current (for a Prospective current evaluated at a time corresponding to the instant of the
pole of a switching device or a fuse) initiation of the breaking process.
Prospective making current (for a pole Prospective current when initiated under specified conditions.
of a switching device) NOTE: The specified conditions may relate to the method of initiation, e.g.
by an ideal switching device, or to the instant of initiation, e.g., leading to the
maximum prospective peak current.
Prospective peak current Peak value of a prospective current during the transient period following
initiation.
Prospective symmetrical current Prospective current when it is initiated at such an instant that no transient
(of an AC circuit) phenomenon follows the initiation.
Rated current (In) For circuit breakers, the rated current is the rated uninterrupted current (Iu)
and is equal to the conventional free-air thermal current (Ith).
Rated insulation voltage (Ui) The insulation voltage of an equipment is the value of voltage to which
dielectric tests and creepage distances are referred.
Rated operational voltage (Ue) A rated operational voltage of an equipment is a value of voltage which,
combined with a rated operational current, determines the application of the
equipment and to which the relevant tests and the utilization categories are
referred.
Rated uninterrupted current (Iu) The rated uninterrupted current of an equipment is a value of current, stated
by the manufacturer, which the equipment can carry in uninterrupted duty.
Selectivity limit current (Is) The selectivity limit current is the current coordinate of the intersection
between the total time-current characteristic of the protective device on the
load side and the pre- arcing (for fuses), or tripping (for circuit breakers) time-
current characteristic of the other protective device.
Service short-circuit breaking capacity A breaking capacity for which the prescribed conditions according to a
(Ics) specified test sequence include the capability of the circuit breaker to carry
its rated current continuously.
109
Glossary
Glossary
Short-circuit breaking capacity Breaking capacity for which prescribed conditions include a short-circuit at
(Icn) the terminals of the switching device.
Short-circuit making capacity Making capacity for which prescribed conditions include a short-circuit at the
(Icm) terminals of the switching device.
Short-circuit protective device Device intended to protect a circuit or parts of a circuit against short-circuit
(SCPD) currents by interrupting them.
Short-time delay Any intentional delay in operation within the limits of the rated short-time
withstand current.
Short-time withstand current Current that a circuit or a switching device in the closed position can carry
(Icw) during a specified short time under prescribed conditions of use and behavior.
Shunt release (trip device) A release (trip device) energized by a source of voltage.
NOTE: The source of voltage may be independent of the voltage of the main
circuit.
Take-over current (IB) Current coordinate of the intersection between the time-current characteristics
of two overcurrent protective devices.
Thermal overload relay or release Inverse time-delay overload relay or release (trip device) depending for
(trip device) its operation (including its time-delay) on the thermal action of the current
flowing in the relay or release (trip device).
Time-current characteristic Curve giving the time, e.g. pre-arcing time or operating time, as a function of
the prospective current, under stated conditions of operation.
Ultimate short-circuit breaking A breaking capacity for which the prescribed conditions according to a
capacity (Icu) specified test sequence do not include the capability of the circuit breaker to
carry its rated current continuously.
Undervoltage relay or release Relay or release (trip device) which permits a mechanical switching device
(trip device) to open or close, with or without time-delay, when the voltage across the
terminals of the relay or release (trip device) falls below a predetermined
value.
Working voltage Highest r.m.s. value of the AC or DC voltage across any particular insulation
which can occur when the equipment is supplied at rated voltage.
110
Safety Considerations
Operate (keep) in the environment specified in the operating instructions and manual. High temperature, high humidity, condensation, dust,
corrosive gases, oil, organic solvents, excessive vibration or shock might cause electric shock, fire, erratic operation or failure.
For safe operation, before using the product read the instruction manual or user manual that comes with the product carefully or consult the
Fuji sales representative from which you purchased the product.
Products introduced in this catalog have not been designed or manufactured for such applications in a system or equipment that will affect
human bodies or lives.
Customers, who want to use the products introduced in this catalog for special systems or devices such as for atomic-energy control,
aerospace use, medical use, passenger vehicle, and traffic control, are requested to consult with Fuji Electric FA.
Customers are requested to prepare safety measures when they apply the products introduced in this catalog to such systems or facilities
that will affect human lives or cause severe damage to property if the products become faulty.
For safe operation, wiring should be conducted only by qualified engineers who have sufficient technical knowledge about electrical work or
wiring.
Follow the regulations of industrial wastes when the product is to be discarded.
For further questions, please contact your Fuji sales representative or Fuji Electric FA.
Information in this catalog is subject to change without notice. Printed in Japan 2017-9 PDF FOLS 62D4-E-0058