0% found this document useful (0 votes)
37 views88 pages

Quadlog - Критический модуль дискретного входа CDM+

This document serves as an installation and service instruction manual for the QUADLOG Critical Discrete Module (CDM) by Siemens Energy & Automation, Inc. It includes detailed sections on product description, installation procedures, maintenance, circuit descriptions, and specifications. The manual emphasizes safety precautions and is intended for qualified personnel familiar with the equipment and its hazards.

Uploaded by

hakimrv
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
37 views88 pages

Quadlog - Критический модуль дискретного входа CDM+

This document serves as an installation and service instruction manual for the QUADLOG Critical Discrete Module (CDM) by Siemens Energy & Automation, Inc. It includes detailed sections on product description, installation procedures, maintenance, circuit descriptions, and specifications. The manual emphasizes safety precautions and is intended for qualified personnel familiar with the equipment and its hazards.

Uploaded by

hakimrv
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 88

Siemens

Energy & Automation, Inc. Installation and Service Instruction

SDQLCDM-1
Rev: 10
July 2008
(Updated September 2010)

QUADLOG®
Critical Discrete Module (CDM)
Trademarks
ProcessSuite, QUADLOG, 4-mation, and APACS+ are trademarks of Siemens Energy & Automation, Inc.
Other names in this publication might be trademarks, the use of which by third parties for their own purposes may
violate the rights of the registered holder.

Copyright Siemens Energy & Automation, Inc. 2008 Disclaimer of Liability


All rights reserved
We have checked the contents of this manual for
The reproduction, transmission or use of this document or agreement with the hardware and software described.
its contents is not permitted without express written Since deviations cannot be precluded entirely, we cannot
authority. Offenders will be liable for damages. All rights, guarantee full agreement. However, the data in this
including rights created by patent or registration of a utility manual is reviewed regularly and any necessary
model or design, are reserved. corrections included in subsequent editions. Suggestions
Siemens Energy & Automation, Inc. for improvement are welcomed.
1201 Sumneytown Pike ©Siemens Energy & Automation, Inc. 2008
P.O. Box 900 Technical data subject to change.
Spring House, PA 19477-0900
Table of Contents
Section Title Page

1 Introduction....................................................................................................................1-1
1.1 Product Description ......................................................................................................1-4
1.1.1 Channel Types........................................................................................................1-5
1.1.2 Configuration .........................................................................................................1-5
1.1.3 I/O Power Supplies ................................................................................................1-8
1.1.4 Soft-Fuse Feature ...................................................................................................1-9
1.1.5 Terminations ..........................................................................................................1-9
1.2 Product Support ..........................................................................................................1-10
1.3 Related Literature .......................................................................................................1-12

2 Installation......................................................................................................................2-1
2.1 Hardware Identification................................................................................................2-1
2.1.1 CDM Termination Strip Identification...................................................................2-1
2.1.2 CDM Marshalled Termination Assembly Identification .......................................2-1
2.1.3 SDM/CDM Fused Marshalled Termination Assembly Identification ...................2-2
2.2 Considerations and Preparation ....................................................................................2-2
2.2.1 EMC Directive Installation Considerations ...........................................................2-2
2.2.2 Installation Preparation ..........................................................................................2-3
2.3 I/O Wiring Considerations............................................................................................2-3
2.3.1 Interconnect I/O Cable Connections ......................................................................2-4
2.3.2 Rail Termination Assembly Connections ..............................................................2-5
2.3.3 Fused Marshalled Termination Assembly Connections.........................................2-7
2.3.4 Determining Field Wiring Gauge...........................................................................2-9
2.3.5 Selecting An Interconnect I/O Cable for Marshalled or Rail Terminations...........2-9
2.3.5.1 Determining Optimum Interconnect I/O Cable Length................................2-9
2.4 Critical I/O Device Considerations.............................................................................2-12
2.4.1 CDM Critical Inputs and SRSAs .........................................................................2-12
2.4.2 CDM Critical Channels and Intrinsic Safety Barriers..........................................2-12
2.5 I/O Power Supply Considerations ..............................................................................2-12
2.5.1 Sizing An I/O Power Supply................................................................................2-13
2.5.2 Determining Power Supply Mounting Location ..................................................2-13
2.6 Environmental Considerations ...................................................................................2-15
2.7 Equipment Delivery and Handling .............................................................................2-15
2.7.1 Predelivery Test ...................................................................................................2-15
2.7.2 Factory Shipment .................................................................................................2-15
2.7.3 Receipt of Shipment.............................................................................................2-15
2.7.4 Return of Equipment within North America........................................................2-16
2.7.5 Return of Equipment outside North America ......................................................2-16
2.7.6 Equipment Handling and Storage ........................................................................2-16
2.8 Termination Strip Installation.....................................................................................2-16
2.9 Termination Assembly and I/O Cable Installation .....................................................2-19
2.9.1 DIN Rail Installation Procedures .........................................................................2-19
2.9.1.1 Marshalled Termination Assembly ............................................................2-19
2.9.1.2 Rail Termination Assembly........................................................................2-23
2.9.2 Flat Surface Termination Assembly Installation..................................................2-23

July 2008 i
Contents SDQLCDM-1r9

2.9.3 Interconnect I/O Cable Installation ......................................................................2-24


2.10 CDM Installation ........................................................................................................2-26
2.10.1 CDM and Rack Slot Keying ................................................................................2-26
2.10.2 Inserting the CDM into its Rack Slot...................................................................2-28
2.11 Electrical Installation..................................................................................................2-29
2.11.1 AC Supply Connections.......................................................................................2-29
2.11.2 I/O Power Supply and Field Wiring Connections................................................2-30
2.11.3 Safety-Related Switch Adapter (SRSA) Installation ...........................................2-31
2.12 Output Fuse Reset Switch Operation..........................................................................2-34
2.13 Configuration..............................................................................................................2-36

3 Maintenance ...................................................................................................................3-1
3.1 Tool And Equipment Requirements .............................................................................3-1
3.2 Visual Inspection ..........................................................................................................3-1
3.3 Cleaning........................................................................................................................3-2
3.4 CDM Removal/Replacement........................................................................................3-4
3.4.1 Removal .................................................................................................................3-4
3.4.2 Replacement...........................................................................................................3-4
3.5 Termination Strip Removal/Replacement ....................................................................3-5
3.5.1 Removal .................................................................................................................3-5
3.5.2 Replacement...........................................................................................................3-5
3.6 Marshalled Termination Assembly Removal/Replacement .........................................3-5
3.6.1 Removal .................................................................................................................3-6
3.6.2 Replacement...........................................................................................................3-6
3.7 Interconnect I/O Cable Removal/Replacement ............................................................3-6
3.7.1 Removal .................................................................................................................3-6
3.7.2 Replacement...........................................................................................................3-7
3.8 Spare and Replacement Parts........................................................................................3-7
3.8.1 Accessories.............................................................................................................3-7
3.8.2 Options ...................................................................................................................3-9

4 Circuit Description ........................................................................................................4-1


4.1 Diagnostics ...................................................................................................................4-1
4.2 Input/Output Channel Circuitry....................................................................................4-2
4.2.1 External Power Supply Input .................................................................................4-3
4.2.2 Protected Outputs...................................................................................................4-3
4.2.3 Output Channel ......................................................................................................4-3
4.2.4 Input Channel.........................................................................................................4-3
4.3 Pulse Test Channel Diagnostics ...................................................................................4-4
4.3.1 CDM Output Channels...........................................................................................4-4
4.3.2 CDM Input Channels .............................................................................................4-6

5 Specifications..................................................................................................................5-1
5.1 Model Number Designation .........................................................................................5-1
5.2 Module Specifications ..................................................................................................5-2
5.3 Maximum I/O Related Power Dissipation Versus Temperature ..................................5-4
5.4 Environmental Specifications.......................................................................................5-5
5.5 Electrical Classification ................................................................................................5-6
5.5.1 CSA Hazardous Locations Precautions .................................................................5-7

1-2 July 2008


SDQLCDM-1r9 Contents

5.5.2 Special Conditions for Safe Use ............................................................................5-9

Declaration of Conformity

List of Tables
Table Title Page

2–1 Fused Marshalled Termination Assembly Terminal Identification ..................................................2-8

3–1 LED Status Indications .....................................................................................................................3-2


3–2 CDM Accessories .............................................................................................................................3-7
3–3 CDM Options....................................................................................................................................3-9
3–4 Interconnect I/O Cable Pin Out.......................................................................................................3-10

4–1 Open Load Thresholds for 24 V and 48 V CDMs ............................................................................4-5


4–2 Possible Output Channel Fault Errors...............................................................................................4-6
4–3 Possible Input Channel Fault Errors .................................................................................................4-7

5–1 CDM Specifications..........................................................................................................................5-2


5–2 CDM Total Current vs. Ambient Temperature .................................................................................5-3
5–3 Maximum I/O Related Power Dissipation Versus Temperature.......................................................5-4
5–4 Environmental Specifications ...........................................................................................................5-5
5–5 SRSA Environmental Specifications ................................................................................................5-6

July 2008 1-3


Contents SDQLCDM-1r9

List of Illustrations
Figure Title Page

Figure 1–1 CDM and Associated Assemblies ..........................................................................................1-2


Figure 1–2 Fused SDM/CDM Marshalled Termination Assembly ..........................................................1-3
Figure 1–3 SDM Rail and Relay Marshalled Termination Assemblies....................................................1-4

Figure 2–1 Basic Local and Marshalled I/O Connections ........................................................................2-5


Figure 2–2 Rail Termination Assembly....................................................................................................2-6
Figure 2–3 Basic Fused Marshalled I/O Connections...............................................................................2-7
Figure 2–4 Voltage at Field Device ........................................................................................................2-11
Figure 2–5 Part # 16114-12 Utility Panel ...............................................................................................2-14
Figure 2–6 Termination Strip and Interconnect I/O Cable Mounting.....................................................2-18
Figure 2–7 Marshalled Termination Assembly With J1 and J2 Connector Keying Patterns..................2-21
Figure 2–8 DIN Rail Mounted Termination Assembly Installation and Removal .................................2-22
Figure 2–9 SDM Marshalled Termination Assembly, Mounting Ear Installation..................................2-23
Figure 2–10 Interconnect I/O Cable Assembly and Cable Keying.........................................................2-25
Figure 2–11 CDM Keying Assignment and Installation.........................................................................2-27
Figure 2–12 Using a Pin-type Crimp-on Connector ...............................................................................2-31
Figure 2–13 Sample Input and Output Connections ...............................................................................2-32
Figure 2–14 Additional Sample I/O Connections...................................................................................2-33
Figure 2–15 Safety-Related Switch Adapter (SRSA).............................................................................2-34
Figure 2–16 Tripped Fuse Reset Switch .................................................................................................2-35

Figure 4–1 CDM Block Diagram..............................................................................................................4-1


Figure 4–2 Output Channel Diagnostic Pulse Timing ..............................................................................4-5
Figure 4–3 Input Channel Diagnostic Pulse Timing.................................................................................4-6

Significant Changes for Revision 9


Section Description

1 Figure 1-3 modified to reflect current product availability.

1-4 July 2008


PREFACE

Conventions and Symbols

The following symbols may appear in this manual and may be applied to the equipment. The reader
should become familiar with the symbols and their meaning. Symbols are provided to quickly alert the
user to safety related situations, issues, and text.

Symbol Meaning
Indicates an immediate hazardous situation which, if not avoided, will result in
DANGER death or serious injury.

Indicates a potentially hazardous situation which, if not avoided, could result


WARNING in death or serious injury.

Indicates a potentially hazardous situation which, if not avoided, may result in


CAUTION minor or moderate injury.

Indicates a potentially hazardous situation which, if not avoided, may result in


CAUTION property damage.

Indicates a potential situation which, if not avoided, may result in an


NOTICE undesirable result or state.

Important Identifies an action that should be taken to avoid an undesirable result or state.
Note Identifies additional information that should be read.
Electrical shock hazard. The included Warning text states that the danger of
electrical shock is present.
Electrical shock hazard. Indicated that the danger of electrical shock is
present.

Explosion hazard. Indicates that the danger of an explosion hazard exists.

Electrostatic discharge. The presence of this symbol indicates that


electrostatic discharge can damage the electronic assembly.

July 2008 v
SDQLCDM-1r9 Preface

Qualified Persons

The described equipment should be installed, configured, operated, and serviced only by qualified persons
thoroughly familiar with this publication. The current version, in Portable Document Format (PDF), is
available at http://sitescape.sea.siemens.com/.
1

For the purpose of this publication and product labels, a qualified person is one who is familiar with the
installation, construction, and operation of the equipment, and the involved hazards. In addition, he or she
has the following qualifications:

• Is trained and authorized to energize, de-energize, clear, ground and tag circuits and equipment in
accordance with established safety practices.

• Is trained in the proper care and use of protective equipment such as rubber gloves, hard hat, safety
glasses or face shields, flash clothing, etc., in accordance with established safety practices.

• Is trained in rendering first aid.

Scope

This publication does not purport to cover all details or variations in equipment, nor to provide for every
possible contingency to be met in connection with installation, operation, or maintenance. Should further
information be desired or should particular problems arise which are not covered sufficiently for the
purchaser’s purposes, the matter should be referred to one of the support groups listed in the Product
Support section of this manual.

The contents of this manual shall not become part of or modify any prior or existing agreement,
commitment or relationship. The sales contract contains the entire obligation of Siemens. The warranty
contained in the contract between the parties is the sole warranty of Siemens. Any statements continued
herein do not create new warranties or modify the existing warranty.

General Warnings and Cautions

WARNING

This equipment contains hazardous voltages, and it has been certified for use in the hazardous locations
specified on the product nameplate and in the Model Designation and Specifications section. Death,
serious personal injury, or property damage can result if safety instructions are not followed. Only
qualified personnel should work on or around this equipment after becoming thoroughly familiar with all
warning, safety notices, and maintenance procedures contained herein. The successful and safe operation
of this equipment is dependent upon proper handling, installation, operation, and maintenance.

The perfect and safe operation of the equipment is conditional upon proper transport, proper storage,
installation and assembly, as well as, on careful operation and commissioning.

The equipment may be used only for the purposes specified in this publication.

1-6 July 2008


SDQLCDM-1r9 Preface

CAUTION

Electrostatic discharge can damage or cause the failure of semiconductor devices such as
integrated circuits and transistors. The symbol at right may appear on a circuit board or other
electronic assembly to indicate that special handling precautions are needed.

• A properly grounded conductive wrist strap must be worn whenever an electronics


module or circuit board is handled or touched. A service kit with a wrist strap and static dissipative
mat is available from Siemens (PN15545-110). Equivalent kits are available from both mail order and
local electronic supply companies.

• Electronic assemblies must be stored in anti-static protective bags when not installed in equipment.

DANGER

Electrical shock hazard


Explosion hazard

Will cause death, serious injury or property damage

• Remove power from all wires and terminals and verify that there
are no hazardous voltages before working on equipment.
• In potentially hazardous atmosphere, remove power from
equipment before connecting or disconnecting power, signal, or
other circuit, or extracting/inserting module.
• Observe all pertinent regulations regarding installation in
hazardous area.
• Ensure all devices are rated for hazardous (classified) locations.

July 2008 1-7


1 Introduction
This document provides installation and service information for the QUADLOG Critical Discrete Module
(CDM) and its supporting hardware. The products described in this book are identified below and
illustrated in Figure 1–1 through 1-3:

• Model QLCDM024DCXXX, 24 VDC CDM

• Model QLCDM048DCXXX, 48 VDC CDM

• Part # 16167-1 SDM/CDM Marshalled Termination Assembly

• Part # 16436-1 Fused SDM/CDM Marshalled Termination Assembly

• Part # 16201-1 SDM/CDM Relay Marshalled Termination Assembly

• Interconnect I/O Cables (Refer to Section 3 , Maintenance, for available part numbers and lengths)

As indicated above, the CDM uses the same Termination Strip and Termination Assemblies as the SDM.
The Marshalled Termination Assemblies are supplied with CDM labels, which can be affixed when the
Assemblies are used with CDMs.

This manual is divided into five major sections:

• Section 1, Introduction – Contains product description, product support, and lists related literature.

• Section 2, Installation – Describes environmental considerations and mechanical and electrical


installation procedures.

• Section 3, Maintenance – Includes preventive maintenance, troubleshooting, and assembly


replacement procedures, as well as spare parts suggestions.

• Section 4, Circuit Description – Contains a brief system level description of the CDM.

• Section 5, Specifications – Describes the CDM’s model designation and specifications.

July 2008 1-1


SDQLCDM-1r9 Introduction

Figure 1–1 CDM and Associated Assemblies

1-2 July 2008


Introduction SDQLCDM-1r9

The dimensions of the Fused SDM/CDM MTA are 13.16" (33.43 cm) x 4.7" (11.94 cm).

Figure 1–2 Fused SDM/CDM Marshalled Termination Assembly

July 2008 1-3


SDQLCDM-1r9 Introduction

Field I/O Connections

3 3 3 3 3 3 3

2
Fuse Plug or plug
type Safety Related
Switch Adapter (SRSA)
Left End Profile

1 1 Quick Disconnect Link

Interconnect I/O Cable Connections

Redundant Interconnect
I/O Cable Connection
24 VDC Power
Supply Terminals Interconnect I/O
Note 2 Cable Connection
Channel 1
Relay Module

Channel 31
Channel 1
Channel 32
Channel 2
Channel 18
Note 1 Note 3
Channel 17
Channel 15
Channel 16
NO COM1 NC

Channel/
Relay 1
Notes:
Channel/
Relay 2 1. Label to identify I/O cable connecting
to Connector "A" (J1).
NO COM2 NC
Top View 2. Label to identify redundant I/O cable
connecting to connector "B" (J2).
NO COM1 NC 3. Numbers identify bottom terminal blocks
associated with the "even" numbered relays
(2 TO 32). Top terminal blocks are associated
with "odd" numbered relays (1 TO 31).
NO COM2 NC

Front View
Detail
Field Wiring Terminals

Figure 1–3 SDM Rail and Relay Marshalled Termination Assemblies

1.1 Product Description

The CDM is an I/O module that equips a QUADLOG controller with up to 32 discrete input and output
channels. Whether a channel is a discrete input or output is user selectable through 4-mation™
configuration software. In a QUADLOG controller, the CDM communicates with control modules via
IOBUS and supports:

• A “hot insert” feature that permits it to be plugged into or removed from a controller without having
to power down or reconfigure the controller, or disturb its field wiring.

• A “safety critical” rating for TÜV AK 1 to 6 applications.

1-4 July 2008


Introduction SDQLCDM-1r9

• Input short circuit detection in conjunction with Safety Rated Switch Adapters (SRSAs).

• Failed input channel detection in conjunction with SRSAs.

• Open circuit detection on output leads to field devices.

• Fail safe output control through its unique Protected Outputs™ feature

• The use of resettable soft-fuses that protect output channels from short circuits and overload
conditions.

• Improved channel error checking that does not require additional input channel wiring or error
detection programming.

• Low and high temperature operations (-25 to 70 °C) with diagnostics that detect when temperature
limits are exceeded.

• Software-configurable channels that eliminate the need for DIP switches and jumpers.

• Electrical isolation of all I/O channels from the QUADLOG controller’s back plane

• High-speed Sequence of Events (SOE) recording (refer to Document # AD39SOE-1 for details).

• Compliance with the European Union’s Electromagnetic Compatibility (EMC) Directive, which
defines device requirements for electromagnetic interference immunity and emissions. See Document
# PIQL-15, High Strength for Increased Reliability and Safety, for more information.

1.1.1 Channel Types

The CDM provides 32 channels, each configurable as a discrete input, discrete output, or discrete pulse
output. This reduces system hardware costs and spare parts requirements. Each channel exchanges signals
with field devices through wires tied to the CDM’s termination strip and termination assemblies. The strip
and assemblies include terminal arrangements that facilitate organizing and grouping together wiring for
related discrete signals. Organized field wiring helps reduce response time to faults.

1.1.2 Configuration

Like all QUADLOG I/O modules, the CDM is configured through 4-mation software. Its configuration
plus those of other I/O modules in a QUADLOG controller collectively form a complete controller
configuration. Through 4-mation, an I/O module’s configuration is:

• written to that I/O module’s memory.

• copied to the non-volatile memory of the controller’s control module.

July 2008 1-5


SDQLCDM-1r9 Introduction

When an I/O module fails, its replacement is automatically loaded with the configuration the control
module stores. This occurs immediately after the replacement is installed and enables the new I/O module
to quickly begin operating. No 4-mation adjustments are necessary when a faulty CDM is replaced with a
new one.

When configuring a CDM in 4-mation, you must specify how its 32 channels are to operate. Any
combination of discrete inputs, outputs, or pulse outputs are possible. 4-mation also enables you to set the
following:

• Discrete Input Channel Parameters

InputFaultState – If the input channel being configured experiences a fault, it will automatically
report the logic state to which this parameter has been set.

ShutdownChannel – If this parameter is enabled, a class 4 error is reported upon detection of a


channel fault. This will initiate a shutdown of the part of the process tied to the CDM.

PulseDiagTest – This parameter enables pulse diagnostic testing and requires that the input channel
be wired with an SRSA. Refer to section 2.4.1 for details.

CAUTION

To be TÜV compliant, safety critical discrete inputs must be wired with


SRSAs and configured with the PulseDiagTest parameter enabled.

• Discrete Output Channel Parameters

ProtectedOutputChannel – If enabled, the CDM will disable all its output channels if the channel
being configured fails to de-energize when instructed.

ReadBack – If enabled, this parameter activates a diagnostic routine in which the output state of the
channel being configured is read back to the internal electronics driving it. The output is deemed
normal if the state called for by internal electronics matches that which is read back.

ShutdownChannel – If this parameter is enabled, a class 4 error is reported upon detection of a


channel fault. This will initiate a shutdown of the part of the process tied to the CDM.

PulseDiagTest – This parameter enables pulse diagnostic testing.

1-6 July 2008


Introduction SDQLCDM-1r9

CAUTION

A safety critical output is not TÜV compliant unless its PulseDiagTest


parameter is enabled.

• Sequence of Events (SOE) Discrete Input Channel Parameters

InputFaultState – If the input channel being configured experiences a fault, it will automatically
report the logic state to which this parameter has been set.

ShutdownChannel – If this parameter is enabled, a class 4 error is reported upon detection of a


channel fault. This will initiate a shutdown of the part of the process tied to the CDM.

Description – This parameter specifies a channel description that may be up to 28 characters long.

Event Priority – This parameter establishes the priority of the event associated with the configured
input. The priority can range between 1 (highest) and 4 (lowest).

AlarmState – This parameter establishes whether a TRUE or FALSE designation indicates an alarm
condition associated with the input.

PulseDiagTest – This parameter enables pulse diagnostic testing.

CAUTION

To be TÜV compliant, safety critical discrete inputs must be wired with


SRSAs and configured with the PulseDiagTest parameter enabled.

• Sequence of Events (SOE) Discrete Output Channel Parameters

ProtectedOutputChannel – If enabled, the CDM will disable all its output channels if the channel
being configured fails to de-energize when instructed.

ReadBack – If enabled, this parameter activates a diagnostic routine in which the output state of the
channel being configured is read back to the internal electronics driving it. The output is deemed
normal if the state called for by internal electronics matches that which is read back.

ShutdownChannel – If this parameter is enabled, a class 4 error is reported upon detection of a


channel fault. This will initiate a shutdown of the part of the process tied to the CDM.

Description – This parameter specifies a channel description that may be up to 28 characters long.

July 2008 1-7


SDQLCDM-1r9 Introduction

Event Priority – This parameter establishes the priority of the event associated with the configured
output. The priority can range between 1 (highest) and 4 (lowest).

AlarmState – This parameter establishes whether a TRUE or FALSE designation indicates an alarm
condition associated with the output.

PulseDiagTest – This parameter enables pulse diagnostic testing.

CAUTION

The PulseDiagTest parameter must be enabled for safety critical


discrete outputs to be TÜV compliant.

• Discrete Pulse Output Channel Parameters

ReadBack – If enabled, this parameter activates a diagnostic routine in which the output state of the
channel being configured is read back to the internal electronics driving it. The output is deemed
normal if the state called for by internal electronics matches that which is read back.

Duration – This parameter specifies the channel’s pulse output duration. Pulses may be configured to
be between 10 and 2000 milliseconds long and 10 milliseconds apart.

ProtectedOutputChannel – If enabled, the CDM will disable all its output channels if the channel
being configured fails to de-energize when instructed.

ShutdownChannel – If this parameter is enabled, a class 4 error is reported upon detection of a


channel fault. This will initiate a shutdown of the part of the process tied to the CDM.

For more detailed information on the above parameters, consult Document # CG39-20, Using
ProcessSuite 4-mation Configuration Software Version 4.30 or Higher.

1.1.3 I/O Power Supplies

To power field devices and the CDM’s discrete input channels, an external safety rated 24 or 48 VDC I/O
power supply must be supplied by the user or system integrator. Contact or switch closures to be detected
by CDM input channels must be wired to enable 24 or 48 VDC to be applied to input channel terminals
when closed. Channels configured as outputs use MOSFETs to switch 24 or 48 VDC to field devices.

1-8 July 2008


Introduction SDQLCDM-1r9

1.1.4 Soft-Fuse Feature

The CDM’s Soft-Fuse feature protects its output channels from over-current conditions caused by field
wiring or device problems. Each channel contains an over-current detection circuit that acts as a resettable
fuse. When over-current conditions are detected, the fuses switch off before output channel damage can
occur. Channels with blown soft fuses are reported on ProcessSuite™ Vision WindowViewer diagnostic
screens, which also provide an interface through which soft fuses can be reset. Blown soft fuses can also
be reset at the CDM itself using a built-in push button located behind its bezel door.

1.1.5 Terminations

A CDM’s field I/O wiring terminations may be locally mounted within the enclosure containing the
CDM’s rack or mounted remotely in a separate enclosure known as a “marshalling cabinet.”

NOTE

In this manual, a “rack” can be a MODULRAC, SIXRAC, Remote I/O


Rack, or UNIRAC unless otherwise noted.

Local terminations tie to an SDM/CDM Termination Strip, which can be used only if the CDM is
installed in a MODULRAC. Remote terminations can be implemented with any rack type and tie to
SDM/CDM Marshalled or Rail Termination Assemblies housed in a marshalling cabinet.

Signals from the Termination Strip, Marshalled Termination Assembly, or Rail Termination Assembly
are applied to the CDM at its lower rear P2 connector. When installing the CDM in a rack slot, P2 mates
with a connector on one of two possible devices attached to the back of that slot:

• The SDM/CDM Termination Strip itself (applicable to MODULRAC only).

• An Interconnect I/O Cable linked to either a Marshalled or Rail Termination Assembly.

July 2008 1-9


SDQLCDM-1r9 Introduction

1.2 Product Support

Our Technical Support Centers (TSC) offer a variety of technical support services that are designed to
assist you with Siemens products and systems. Our support engineers have experience with
troubleshooting, development, system startup, and system test. They will help you to solve your issues in
an efficient and professional manner.

Customers in North America can contact Siemens Technical Support Center at 1-800-333-7421, on the
web at: http://support.automation.siemens.com, or by e-mail: [email protected]

Customers outside North America can contact their local Siemens subsidiary; addresses and telephone
numbers are listed on the Internet at the web site: http://support.automation.siemens.com.

When contacting Siemens, customers will be asked to provide site-contact information (name, address,
and phone number), the product involved and detailed information regarding the nature of the issue.

Product documentation is now located in the Library forum of the Process Automation User Connection
at: http://sitescape.sea.siemens.com/. The Process Automation User Connection is a secure site.
Registration is open to all verified users of Siemens process automation systems. If you are not already,
and would like to become a member, please visit our Process Automation User Connection web page at:
http://www.sea.siemens.com/process/support/papauc.html

Contained within the Process Automation User Connection is the APACS+/QUADLOG Secure Site at:
http://sitescape.sea.siemens.com/forum/aca-1/dispatch.cgi/f.apacsquadlo forum. This site is only open to
customers with an active service agreement. It contains all service manuals, service memos, service notes,
configuration manuals, etc. for the APACS+ and QUADLOG family of products. If you are experiencing
technical difficulties with the site, please contact SiteScape technical support at: toll free 1-877-234-1122
(US) or 1-513-336-1474.

1-10 July 2008


Introduction SDQLCDM-1r9

A&D Technical Support


Worldwide, available 24 hours a day:

Nürnberg

Johnson City Beijing

United States: Johnson City, TN Worldwide: Nürnberg Asia / Australia: Beijing


Technical Support and Authorization Technical Support Technical Support and Authorization
Local time: Monday to Friday 24 hours a day, 365 days a year Local time: Monday to Friday
8:00 AM to 5:00 PM Phone:+49 (180) 5050-222 8:00 AM to 5:00 PM
Telephone:+1 (423) 262 2522 Fax:+49 (180) 5050-223 Phone:+86 10 64 75 75 75
or +1 (800) 333-7421 (USA only) E-Mail: [email protected] Fax:+86 10 64 74 74 74
Fax:+1 (423) 262 2289 GMT:+1:00 Mail to:[email protected]
Mail to: [email protected] Authorization GMT:+8:00
GMT: -5:00 Local time: Monday to Friday
8:00 AM to 5:00 PM
Phone: +49 (180) 5050-222
Fax: +49 (180) 5050-223
Mail to: [email protected]
GMT: +1:00
Automation and Drives Service and Support International
http://www.siemens.com/automation/service&support
The languages of the SIMATIC Hotlines and the authorization hotline are generally German and English.

July 2008 1-11


SDQLCDM-1r9 Introduction

1.3 Related Literature

The following literature should be consulted when performing CDM installation and are available in PDF
form on the APACS+ Electronic Manuals CD.

• APACS+/QUADLOG MODULRAC Installation and Service Instruction


(Document # SD39MODULRAC-1)

• APACS+/QUADLOG SIXRAC Installation and Service Instruction (Document # SD39SIXRAC-1)

• APACS+ MODULPAC 2000 Installation and Service Instruction (Document # SD39MODULPAC-2)

• APACS+ Relay Marshalled Termination Assembly Installation and Service Instruction


(Document # SD39RMTA-1)

• QUADLOG I/O Module Configuration for QUADLOG Version 3.30 or Higher


(Document # CGQL-4)

• QUADLOG Safety Manual (Document # CGQLSAFETY-1)

1-12 July 2008


2 Installation
This section describes procedures for installing CDM hardware, determining appropriate field wiring
gauges, and connecting field wiring to CDM termination strips and assemblies.

IMPORTANT

Installation should be performed in accordance with the National


Electrical Code (NEC) and other applicable construction and
electrical codes.

2.1 Hardware Identification

The letters “CDM” are printed on the Critical Discrete Module’s front bezel. Two labels – a large one
located on the module’s left side and a smaller one found within its bezel compartment – specify its
model designation, part number, ROM version, software compatibility identification, and serial number.
The larger label also includes current and voltage requirements and space for additional information such
as agency approval certifications.

2.1.1 CDM Termination Strip Identification

The CDM uses the same Part # 16128-21 Termination Strip as the SDM. A silk-screened label, which is
illustrated below, identifies the part.

SDM
Standard Discrete Module
Siemens Energy & Automation, Inc.
Termination Strip
PN 16128-21

2.1.2 CDM Marshalled Termination Assembly Identification

The CDM uses the SDM’s Part # 16167-1 Marshalled Termination Assembly. The following is silk-
screened to the Termination Assembly’s component side:

SDM
Standard Discrete Module
Siemens Energy & Automation, Inc.
Marshalled Termination Assembly
PN 16167-1

July 2008 2-1


SDQLCDM-1r9 Installation

2.1.3 SDM/CDM Fused Marshalled Termination Assembly Identification

The CDM uses an SDM/CDM Fused Marshalled Termination Assembly, whose silk-screened label is
depicted below:
SDM/CDM
Standard Discrete Module/
Critical Discrete Module
Siemens Energy & Automation, Inc.
Fused Marshalled Termination Assembly
PN 16436-1

2.2 Considerations and Preparation

Steps to ensure that QUADLOG modules comply with the European Union’s Electromagnetic
Compatibility (EMC) Directive are described below, along with guidelines for preparing CDM support
hardware and I/O wiring.

2.2.1 EMC Directive Installation Considerations

The CDM alone meets EMC emission and immunity standards as certified by a “Declaration of
Conformity” statement provided at the back of this manual. This statement also identifies QUADLOG’s
Technical Construction File certificate number.

For a complete QUADLOG system to be EMC directive compliant, equipment enclosures must:

• Provide sufficient RF attenuation.

• House only QUADLOG equipment whose AC power input conductors and MODULBUS (M-BUS)
cables are filtered.

• Be grounded and tied to the shields of all shielded cables entering or exiting them.

NOTE

Personnel safety standard EN61010-1 requires that equipment be


installed in locked enclosures that cannot be opened without a key or
similar tool.

Consult Siemens for additional information concerning EMC Directive compliance and the availability of
enclosures and other required hardware.

2-2 July 2008


Installation SDQLCDM-1r9

2.2.2 Installation Preparation

The following are guidelines for preparing CDM support hardware and I/O wiring.

1. The CDM’s controller rack should be installed in its enclosure. If using a MODULRAC and local
terminations, install a Part # 16128-21 Termination Strip for each of the rack’s CDMs. The actual
CDMs should not be plugged into their slots at this time, but their node, rack, and slot numbers
should be known.

2. Determine the field wiring lengths required by CDM I/O channels. For local terminations, these
lengths cover distances between the 16128-21 Termination Strip and field devices. For remote
terminations, wiring lengths correspond to how far away field devices are from Marshalled or Rail
Termination Assemblies. Additionally, Interconnect I/O Cable lengths linking Marshalled or Rail
Termination Assemblies to CDMs must be determined. See Section 2.3, I/O Wiring Considerations,
for more information.

3. I/O cables to be locally terminated should be tagged and routed into the rack enclosure. Once in the
enclosure, they can be readied for connection to 16128-21 Termination Strips.

4. I/O cables to be remotely terminated should also be tagged and readied for cable end preparation, but
routed into the marshalling cabinet containing their corresponding Marshalled or Rail Termination
Assemblies. Interconnect I/O cables should also be routed between the marshalling cabinet and the
enclosure containing the CDMs’ rack.

5. Determine the I/O power supply amperage needed to support field devices per the instructions of
Section 2.5, I/O Power Supply Considerations.

6. Determine the number of SRSAs required. Wire and plug-type SRSAs are available in kits identified
in Table 3–3. SRSAs are discussed in Section 4.3, Pulse Test Channel Diagnostics, and illustrated in
Figure 2–16.

2.3 I/O Wiring Considerations

Figure 2–1 through 2-3 show typical local, marshalled, and fused marshalled I/O wiring. I/O connections
between field devices and local or marshalled terminations are made with user-supplied cable. This cable
consists of two insulated conductors that may be:

• Stranded or solid wire.


• Unshielded with a jacket and arranged in a twisted pair.
• Shielded and certified as having passed EMC 61000-4-5 testing to level 3.

July 2008 2-3


SDQLCDM-1r9 Installation

2.3.1 Interconnect I/O Cable Connections

In the marshalled I/O connection depicted in Figure 2–1, an Interconnect I/O Cable links a Marshalled
Termination Assembly to a CDM. The Interconnect I/O Cable’s P2 connector mates with the J1
connector of the Marshalled Termination Assembly. The cable’s J1 connector engages the CDM’s rear
P2 connector. If the CDM has a redundant back up, a second Interconnect I/O Cable would run from the
Termination Assembly’s J2 connector to the P2 connector of the back up CDM. See Table 3-3 for
available Interconnect I/O Cable part numbers and standard lengths.

NOTE

For marshalled I/O connections, Interconnect I/O cable lengths must be


specified before designing your QUADLOG system’s physical layout.
See section 2.3.5, Selecting An Interconnect I/O Cable for Marshalled or
Rail Terminations.

DANGER

Electrical shock hazard


Explosion hazard

Will cause death, serious injury or property damage

• Remove power from all wires and terminals and verify that there are no
hazardous voltages before working on equipment.
• In potentially hazardous atmosphere, remove power from equipment
before connecting or disconnecting power, signal, or other circuit, or
extracting/inserting module.
• Observe all pertinent regulations regarding installation in hazardous
area.
• Ensure all devices are rated for hazardous (classified) locations.

2-4 July 2008


Installation SDQLCDM-1r9

Figure 2–1 Basic Local and Marshalled I/O Connections

2.3.2 Rail Termination Assembly Connections

Figure 2-2 illustrates a DIN rail-mounted Rail Termination Assembly, which links to its CDM through an
unterminated Interconnect I/O Cable. Unterminated Interconnect I/O Cables do not have a P2 connector.
They instead have bare wires that tie to Rail Termination Assembly terminals identified by wire and stripe
color. See Table 3–3 for available Interconnect I/O Cable part numbers and standard lengths.

July 2008 2-5


SDQLCDM-1r9 Installation

Figure 2–2 Rail Termination Assembly

NOTE

Unterminated Interconnect I/O cable lengths must be specified before


designing your QUADLOG system’s physical layout. See Section 2.3.5,
Selecting An Interconnect I/O Cable for Marshalled or Rail
Terminations.

Note that the Rail Termination Assembly does not support CDM redundant back ups. It features 33
terminals spread across eight terminal blocks, which snap into a user-supplied DIN rail. The first terminal
block includes connections for a 24 or 48 VDC I/O power supply. The power supply connection features
a quick-disconnect link for facilitating system maintenance. The remaining terminal blocks are for I/O
channel field wiring.

2-6 July 2008


Installation SDQLCDM-1r9

A 0.25 A, field-replaceable fuse, with “fuse open” LED indicator, protects Rail Termination Assembly
terminals assigned to CDM discrete inputs. Input-configured channels that are user-designated as “safety
critical” or “shutdown” channels must have the fuse assembly replaced with a plug-type Safety Related
Switch Adapter (SRSA). Channels configured as discrete outputs do not use physical fuses or SRSAs, but
are protected from overloads by the CDM’s internal soft fuse feature.

2.3.3 Fused Marshalled Termination Assembly Connections

Figure 2–3 Basic Fused Marshalled I/O Connections

Figure 2-3 illustrates basic connections to a Fused Marshalled Termination Assembly. This assembly
features:

• Redundant I/O Power connections with “power present” LED indicators for each power input.

• Individual input power fuses with “power present/fuse OK” LED indicators.

• An I/O wiring shield terminal on each channel terminal set.

Terminal identifications for the Fused Marshalled Termination Assembly are provided in Table 2-1:

July 2008 2-7


SDQLCDM-1r9 Installation

Table 2–1 Fused Marshalled Termination Assembly Terminal Identification

Terminal Description Terminal Description


1 I/O Channel 1 65 Power Out + for Channel 1
2 Shield for Channel 1 66 COMMON for Channel 1
3 I/O Channel 2 67 Power Out + for Channel 2
4 Shield for Channel 2 68 COMMON for Channel 2
5 I/O Channel 3 69 Power Out + for Channel 3
6 Shield for Channel 3 70 COMMON for Channel 3
7 I/O Channel 4 71 Power Out + for Channel 4
8 Shield for Channel 4 72 COMMON for Channel 4
9 I/O Channel 5 73 Power Out + for Channel 5
10 Shield for Channel 5 74 COMMON for Channel 5
11 I/O Channel 6 75 Power Out + for Channel 6
12 Shield for Channel 6 76 COMMON for Channel 6
13 I/O Channel 7 77 Power Out + for Channel 7
14 Shield for Channel 7 78 COMMON for Channel 7
15 I/O Channel 8 79 Power Out + for Channel 8
16 Shield for Channel 8 80 COMMON for Channel 8
17 I/O Channel 9 81 Power Out + for Channel 9
18 Shield for Channel 9 82 COMMON for Channel 9
19 I/O Channel 10 83 Power Out + for Channel 10
20 Shield for Channel 10 84 COMMON for Channel 10
21 I/O Channel 11 85 Power Out + for Channel 11
22 Shield for Channel 11 86 COMMON for Channel 11
23 I/O Channel 12 87 Power Out + for Channel 12
24 Shield for Channel 12 88 COMMON for Channel 12
25 I/O Channel 13 89 Power Out + for Channel 13
26 Shield for Channel 13 90 COMMON for Channel 13
27 I/O Channel 14 91 Power Out + for Channel 14
28 Shield for Channel 14 92 COMMON for Channel 14
29 I/O Channel 15 93 Power Out + for Channel 15
30 Shield for Channel 15 94 COMMON for Channel 15
31 I/O Channel 16 95 Power Out + for Channel 16
32 Shield for Channel 16 96 COMMON for Channel 16
33 I/O Channel 17 97 Power Out + for Channel 17
34 Shield for Channel 17 98 COMMON for Channel 17
35 I/O Channel 18 99 Power Out + for Channel 18
36 Shield for Channel 18 100 COMMON for Channel 18
37 I/O Channel 19 101 Power Out + for Channel 19
38 Shield for Channel 19 102 COMMON for Channel 19
39 I/O Channel 20 103 Power Out + for Channel 20
40 Shield for Channel 20 104 COMMON for Channel 20
41 I/O Channel 21 105 Power Out + for Channel 21
42 Shield for Channel 21 106 COMMON for Channel 21
43 I/O Channel 22 107 Power Out + for Channel 22
44 Shield for Channel 22 108 COMMON for Channel 22
45 I/O Channel 23 109 Power Out + for Channel 23
46 Shield for Channel 23 110 COMMON for Channel 23
47 I/O Channel 24 111 Power Out + for Channel 24
48 Shield for Channel 24 112 COMMON for Channel 24
49 I/O Channel 25 113 Power Out + for Channel 25
50 Shield for Channel 25 114 COMMON for Channel 25
51 I/O Channel 26 115 Power Out + for Channel 26
52 Shield for Channel 26 116 COMMON for Channel 26
53 I/O Channel 27 117 Power Out + for Channel 27
54 Shield for Channel 27 118 COMMON for Channel 27
55 I/O Channel 28 119 Power Out + for Channel 28
56 Shield for Channel 28 120 COMMON for Channel 28
57 I/O Channel 29 121 Power Out + for Channel 29
58 Shield for Channel 29 122 COMMON for Channel 29
59 I/O Channel 30 123 Power Out + for Channel 30
60 Shield for Channel 30 124 COMMON for Channel 30
61 I/O Channel 31 125 Power Out + for Channel 31
62 Shield for Channel 31 126 COMMON for Channel 31
63 I/O Channel 32 127 Power Out + for Channel 32
64 Shield for Channel 32 128 COMMON for Channel 32

2-8 July 2008


Installation SDQLCDM-1r9

2.3.4 Determining Field Wiring Gauge

Review your QUADLOG system’s physical layout and identify the field device that will be the greatest
distance away from local or remote CDM terminations. This distance determines the wire gauge to use for
all CDM field wiring connections. For runs of less than 100 feet, use any gauge between 24 and 14 AWG
(0.38 to 2.1 mm2). For greater than 100 feet, use 18 AWG (0.82 mm2) or thicker wire.

2.3.5 Selecting An Interconnect I/O Cable for Marshalled or Rail Terminations

An Interconnect I/O Cable connects a Marshalled or Rail Termination Assembly to its corresponding
CDM. This cable is available with or without a Termination Assembly connector and in standard lengths
of between 1.75 and 30 meters. Your QUADLOG system’s physical layout should be designed around
this cable length range, which specifies allowable CDM-to-Termination-Assembly distances.

An Interconnect I/O Cable length must be selected based on how CDM channels will be configured. If all
32 channels will be discrete inputs, a length in the permitted range can be chosen at random. Cable length
must be more methodically selected if the CDM is to support discrete outputs.

Field devices driven by CDM discrete outputs are energized by 24 or 48 VDC applied to specific
Termination Assembly terminals. Because of Interconnect I/O Cable and Termination Assembly
interactions, trade-offs exist among:

• DC voltage levels actually fed to field devices through the Termination Assembly.

• Field device current requirements.

• Interconnect I/O Cable lengths greater than or equal to 3 meters.

NOTE
No trade-offs exist for lengths less than 3 meters.

Long cable lengths and high current drawing field devices will result in increased power losses and the
power available to field devices will dip proportionately lower than the expected 24 or 48 VDC.
Interconnect I/O Cable length should therefore be chosen to minimize DC voltage losses and ensure that
enough power is available to field devices when CDM outputs energize. Procedures for optimizing
Interconnect I/O Cable length are provided below.

2.3.5.1 Determining Optimum Interconnect I/O Cable Length

A CDM that supports both remote terminations and discrete output channels should operate with an
Interconnect I/O Cable length selected using these steps:

1. Obtain the specifications of all field devices to be driven by CDM discrete outputs. Record (write
down) each device’s DC voltage and current requirements.

2. Take the current requirements recorded in step 1 and add them together. The resulting value is the
total amperage used by all field devices and should be recorded. The I/O Power Supply you connect
to the Termination Assembly must be able to source this current.

July 2008 2-9


SDQLCDM-1r9 Installation

3. Review the data gathered in step 1 and identify the field device that consumes the most current.

4. If the total amperage calculated in step 2 is less than or equal to 6 A, refer to Graph A of Figure 2-4.
If total amperage exceeds 6 A, refer to Graph B of Figure 2–4.

24 3 m ete r c a ble

8 m e t er c a ble

23.5 1 5 m e te r c a b le
The graphs of
Figures 2-4 and 2-5 3 0 m e ter ca b le

provide estimates 23
of how much a 24
VDC power signal
22.5
degrades when fed,
through a
Marshalled or Rail 22
Termination
Assembly, to a
21.5
CDM discrete
output’s field
device. 21

20.5

Field device current


draw is plotted on 20
each graph’s 0.2 0.3 0.4 0.5 0.6
horizontal axis and
L o a d C u r re n t P e r C h a n n e l (A m p s )
curves are shown
for various standard
Interconnect I/O Graph A: Voltage at Field Device, Total Load Current ≤ 6 A
Cable lengths.
24 3 m e t e r c a b le

8 m ete r ca ble

23.5 1 5 m e te r c a b le
For I/O Power 3 0 m e t er c ab le
Supply voltages
23
greater than 24
VDC, add the
difference between 22.5
the power supply’s
output and 24 VDC 22
to voltage levels
read from either
21.5
graph.

21

20.5

20
0.2 0.3 0.4 0.5 0.6

L o a d C u rr e n t P e r C h a n n e l ( A m p s )

Graph B: Voltage at Field Device, Total Load Current > 6 A

2-10 July 2008


Installation SDQLCDM-1r9

Figure 2–4 Voltage at Field Device

5. On the horizontal axis of the graph selected in step 4, find the amperage value corresponding to the
field device identified in step 3 that draws the most current.

6. Read the corresponding DC voltage levels that would be supplied the field device, given the various
choices of Interconnect I/O Cable lengths.

7. Select an Interconnect I/O Cable length by analyzing the curves that correspond to available lengths.
Base your decision on the minimum DC Voltage level required by the field device to energize, as
well as on whether your I/O Power Supply can be adjusted to compensate for Interconnect I/O Cable
and Termination Assembly losses.

NOTE

Losses within wire connecting a field device to a Termination Assembly


may also impact the DC voltage level that the field device sees. Such
losses can be ignored for wire runs under 100 feet or for wire gauges
exceeding 18 AWG. If field wiring loss cannot be ignored, subtract it
from the voltage levels read from the graphs.

Example Calculation:

Can a 30 meter Interconnect I/O Cable be used to link a CDM to its Termination Assembly if:

• A 24 VDC field device that draws 0.3 A is tied to a CDM discrete output channel?

• The total load current for CDM output channels is 6 A?

• Ignore field wiring line loss.

Solution:

Graph A of Figure 2–4covers a total load current range of 6A or less and is the graph appropriate to this
example. At the intersection of the curve representing a 30 meter cable and 0.3 A, an output channel
power voltage of approximately 22 VDC can be read.

A 30 meter Interconnect I/O cable can therefore be used if 22 VDC is enough energy to activate the field
device. If it is not, the cable length must be shortened, or the 24 VDC tied to the Termination Assembly
should be increased slightly to compensate for the loss estimated from Graph A of Figure 2–4.

CAUTION

I/O Power Supply voltage levels should never be increased past CDM
tolerances. Refer to CDM specifications in Section 5 .

July 2008 2-11


SDQLCDM-1r9 Installation

2.4 Critical I/O Device Considerations

Field devices tied to safety critical CDM inputs and outputs must be wired with other equipment to meet
safety standards. These are described below.

2.4.1 CDM Critical Inputs and SRSAs

CDM critical input channels require that SRSAs be wired in series with input devices. Refer to Section
4.2.4 for a discussion on using SRSAs.

2.4.2 CDM Critical Channels and Intrinsic Safety Barriers

When wiring Intrinsic Safety (IS) barriers to CDM critical I/O channels, Siemens recommends:

• Using only active barriers (isolators)

• That customers examine fault detection issues on the barriers’ hazardous (field) side.

Pulse diagnostic tests cannot detect wiring or short faults on the hazardous sides of the barriers. For
critical channels, another means of fault detection must therefore be implemented. One suggested method
is using safety-rated isolators that provide hazardous side channel diagnostics of their own. Contact
Siemens application engineering support with questions regarding intrinsic safety.

2.5 I/O Power Supply Considerations

A Model # PSR4A rack-mounted power supply or user-supplied I/O power supply is required for all
CDM applications. This power supply:

• Energizes field devices and CDM channel circuitry.

• Must be sized by the user.

• Must have appropriate safety ratings.

2-12 July 2008


Installation SDQLCDM-1r9

2.5.1 Sizing An I/O Power Supply

Use the following formula to size an I/O Power Supply:

IPS = IL + 0.45N

Where:

IPS = The minimum DC current that the I/O Power Supply must provide in Amps

IL = Summation of the maximum DC load currents in Amps of all load devices tied to CDM
channels.

N = 1 for a single non-redundant CDM, or 2 for redundant CDMs

Example Calculation:

Calculate IPS for rack-to-rack redundant CDMs with 12 I/O channels connected to 0.2A loads and 20
channels used as inputs.

Solution:

IPS = (12) × (0.2) + (0.45) × (2) = 3.3 A minimum

2.5.2 Determining Power Supply Mounting Location

I/O power supplies should be mounted to a Part # 16114-12 Utility Panel and housed in a separate
MODULPAC or user-supplied enclosure. Design your power supply mounting using Utility Panel
dimensions provided in Figure 2–5.

For CDMs that use local terminations, power supply enclosures should be attached to, or placed in close
proximity to MODULRAC enclosures. This ensures short power cable runs to CDM Termination Strips.

When marshalled terminations are used, both Termination Assemblies and I/O power supplies can be
mounted to the same Utility Panel. Typically, four Marshalled Termination Assemblies, or two Relay
Marshalled Termination Assemblies, can be mounted on a Utility Panel with two I/O Power Supplies.

July 2008 2-13


SDQLCDM-1r9 Installation

Figure 2–5 Part # 16114-12 Utility Panel

2-14 July 2008


Installation SDQLCDM-1r9

2.6 Environmental Considerations

Industrial environments may subject equipment to severe operating conditions. The conditions at each
CDM location must be within the specifications described in Section 5 .

To ensure reliable system communications, locate all QUADLOG system hardware away from
electromagnetic interference sources, such as high-current electrical machinery.

2.7 Equipment Delivery and Handling

CDM shipping, receiving, and warehouse storage considerations are described below.

2.7.1 Predelivery Test

A CDM is factory tested and inspected to ensure proper operation. If the CDM is ordered factory-installed
in an enclosure, the CDM is tested and inspected as a QUADLOG system enclosure component.

2.7.2 Factory Shipment

CDMs to be installed by the user are placed in static shielding bags and packaged for shipment.
Accessories are packaged separately. If the CDM is ordered factory-installed in an enclosure, the
enclosure is bolted to a pallet and wrapped for protection during shipment.

2.7.3 Receipt of Shipment

All cartons should be inspected at the time of their delivery for possible external damage. Any visible
damage should be immediately recorded on the carrier’s copy of the delivery slip. Each carton should be
carefully unpacked and its contents checked against the enclosed packing list. At the same time, each item
should be inspected for hidden damage that may or may not have been accompanied by exterior carton
damage.

If it is found that some items have been damaged or are missing, notify Siemens immediately and provide
full details. Refer to sections 2.7.4 and 2.7.5. Damages must be reported to the carrier with a request for
their on-site inspection of the damaged item and its shipping carton.

July 2008 2-15


SDQLCDM-1r9 Installation

2.7.4 Return of Equipment within North America

US Customers:

• Call the Repair Order PAS Inside Sales/Order Management Group at (215) 646-7400, ext 4RMA
(4762) weekdays between 8:00 a.m. and 4:45 p.m. eastern time to obtain an RMA number. Mark the
RMA number prominently on the outside of the shipment.

• When calling for an RMA number, provide the reason for the return. If returning equipment for
repair, a detailed description of failure symptoms and system behavior will be requested. Supply a
purchase order number for repairs. Follow the TSC specialist's recommendation for battery
connection, if applicable.

• If applicable, you must supply a Material Safety Data Sheet (MSDS) with each item being returned if
it was stored or used in a location where hazardous materials were present.

• Package items to be returned in their original shipping containers. Otherwise, package it for safe
shipment or contact the factory for shipping recommendations. A module must be placed inside a
static shielding bag to protect it from electrostatic discharge.

Canadian customers:

Contact Siemens Canada.

2.7.5 Return of Equipment outside North America

Contact your Siemens Representative.

2.7.6 Equipment Handling and Storage

The CDM is completely enclosed. It may be safely handled without undertaking electrostatic discharge
handling procedures as long as its bezel compartment door is closed and secured. DO NOT TOUCH the
connector pins on the back of the module. Handle the module carefully and do not subject it to excessive
shock or vibration. The storage temperature and humidity parameters of Section 5 must be met when
storing a CDM.

2.8 Termination Strip Installation

A Part # 16128-21 Termination Strip must be installed at the rack slot location of each CDM when local
I/O termination is employed. A Local Termination Panel must also be installed.

NOTE

Local Termination is only supported in MODULRACs. If any other rack


is used, Marshalled or Rail Terminations must be used.

2-16 July 2008


Installation SDQLCDM-1r9

Refer to Figure 2–6 and the following mounting instructions:

1. Record the slot locations assigned to each CDM in each MODULRAC.

2. Note the following on the MODULRAC and Termination Strip:

• On the MODULRAC, locate and identify the extruded spacer to which the lower edge of the back
plane is mounted. The bottom of the extruded spacer is grooved. The top edge of the Termination
Strip rests in this groove.

• Identify ten alignment pins located below the MODULRAC frame that span the width of the
MODULRAC panel. One of these pins engages a hole located on the Termination Strip above the
Siemens logo. The left-most pin corresponds to MODULRAC slot #1.

• The Termination Strip’s captive mounting screws can be seen projecting from the bottom of the
plastic extrusion panel.

July 2008 2-17


SDQLCDM-1r9 Installation

Figure 2–6 Termination Strip and Interconnect I/O Cable Mounting

2-18 July 2008


Installation SDQLCDM-1r9

3. Mount each Termination Strip at its assigned location as follows:

a. At the CDM slot, angle the top edge of the strip toward the back plane’s extruded spacer. Insert
the tip of the strip in the spacer’s groove.

b. Slide the strip in the groove until it is vertically and horizontally aligned with the appropriate slot
pin.

c. Carefully lower the strip and engage the pin with the extrusion and board pin mounting hole.
Firmly push down to seat the strip on the pin. When the strip is properly seated, the pin is flush
with, or projects slightly above the top surface of the strip.

d. Tighten the strip’s captive mounting screws, which should be automatically aligned with their
respective panel mounting holes.

2.9 Termination Assembly and I/O Cable Installation

The following describes a Termination Assembly’s DIN rail and flat surface installation within a cabinet
or enclosure. Interconnect I/O Cable installation is also described.

2.9.1 DIN Rail Installation Procedures

The Termination Assemblies shown in Figure 1–1 through 1-3 can be snapped onto DIN rails, which are
mounted on panels within Termination Assembly enclosures. Suggested DIN rails include the following:

• Preferred: Top hat profile EN 50 022-35 mm × 7.5 mm or EN 50 022-35 mm × 15 mm

• Alternate: G-profile EN 50 035-G 32 mm

2.9.1.1 Marshalled Termination Assembly

DIN rail installation of a Marshalled Termination Assembly is described as follows:

1. Mount user-supplied DIN rails and wire duct to a Utility Panel, Marshalling Utility Panel, or user-
fabricated panel. Mount one DIN rail for each Termination Assembly to be placed on the panel. Refer
to these steps:

a. Determine the mounting layout of the Termination Assembly and its corresponding wire duct.
Part # 16114-12 Utility Panel dimensions are provided in Figure 2–6. Figure 2–8 shows
Marshalled Termination Assembly dimensions.

July 2008 2-19


SDQLCDM-1r9 Installation

NOTE

Different Termination Assemblies are used for each type of I/O module
to be installed in a QUADLOG controller. Their dimensions can vary
and they are not always interchangeable.

b. Drill and tap DIN rail mounting holes in the panel. Remove all burrs and metal debris and clean
the panel.

c. Screw the DIN rails onto the panel using the holes made in step 1b.

2. Mount the panel with newly installed DIN rails in a MODULPAC marshalling or user-supplied
cabinet. Refer to Document #’s SD39MODULPAC-1 and SD39MODULPAC-2 for installation and
service instructions for the MODULPAC 1000 and 2000 cabinets.

3. Prepare Marshalled Termination Assemblies to be mounted on panel DIN rails in the cabinet.

a. Assign a rack address number (1 to 16) and slot number (1 to 10) to each of the CDMs tied to
each Termination Assembly to be mounted. Rack address and slot numbers should also be
assigned to redundant CDMs, if applicable. For rack-to-rack redundant controllers connected to
MODULNET, the MODULNET node address for each controller should be known.

b. Obtain CDM labels from the supplied bag of labels and mark them with the rack and slot
numbers assigned in step 3a. If MODULNET redundancy is applicable, make sure that all CDM
labels are marked with appropriate node addresses.

A CDM label and the locations of where it can be affixed are illustrated in Figure 1–1. Affix primary
CDM labels to the space adjacent to each Marshalled Termination Assembly’s J1 connector. Secondary
(redundant) CDM labels should be placed next to each Assembly’s J2 connector.

Verify that the J1 and J2 connectors are keyed according to the patterns shown in Figure 2–7.

NOTE

The J1 and J2 connectors are where Interconnect I/O Cables attach so


that Marshalled Termination Assemblies can be linked to corresponding
CDMs. Interconnect I/O Cable connectors have a key pattern that
matches that of the J1 and J2 connectors. This prevents the cables of
other QUADLOG I/O modules from being accidentally tied to CDM
Marshalled Termination Assemblies. Arranging the key pattern for a
CDM’s Interconnect I/O Cable is discussed in section 0.

2-20 July 2008


Installation SDQLCDM-1r9

Figure 2–7 Marshalled Termination Assembly With J1 and J2 Connector Keying Patterns

4. Refer to Figure 2–8 to snap a Termination Assembly to a DIN rail within the cabinet.

July 2008 2-21


SDQLCDM-1r9 Installation

Figure 2–8 DIN Rail Mounted Termination Assembly Installation and Removal

2-22 July 2008


Installation SDQLCDM-1r9

2.9.1.2 Rail Termination Assembly

Consult Document # 15900-343 for complete instructions for installing a Rail Termination Assembly to a
user-supplied DIN rail. Rail Termination Assembly dimensions are shown in Figure 2–2.

2.9.2 Flat Surface Termination Assembly Installation

A Marshalled Termination Assembly can be flat mounted to a panel by removing its DIN rail mounting
feet and replacing them with four Part # 16056-562 Mounting Ears.

Refer to Figure 2–9 and the following installation procedure:

1. At one end of the Marshalled Termination Assembly, remove the three securing screws from the card
holder end cap. Remove and set the end cap aside.

2. Remove the DIN rail mounting feet by sliding them from the grooves at the bottom of the Marshalled
Termination Assembly’s card holder. Re-install the card holder end cap.

3. Install four Part # 16056-562 Mounting Ears the mounting holes provided on the end caps. Refer to
Figure 2–9.

4. Use the Marshalled Termination Assembly as a template to mark the location of the mounting ear
holes on the surface of the panel. After drilling or punching the holes, the holes should be threaded.
Typical mounting screw size is M4, or users can select another size. See Figure 2–7 for Marshalled
Termination Assembly dimensions.

Figure 2–9 SDM Marshalled Termination Assembly, Mounting Ear Installation

July 2008 2-23


SDQLCDM-1r9 Installation

2.9.3 Interconnect I/O Cable Installation

Use the procedure below to install the Interconnect I/O Cable you selected using the steps of section
2.3.5.

1. Observe the following on the cable’s molded J1 connector, which engages a CDM’s P2 connector:

• As shown in Figure 2–10, the bottom face of the molded connector has a pin mounting hole
located above a captive mounting screw. This hole engages alignment pins in the panel on which
the rack containing the cable’s CDM is mounted.

• The top edge of the molded J1 connector rests in the groove of the backplane’s extruded spacer as
detailed in Figure 2–6.

2. Make sure that the MODULNET node address (if applicable), rack address number (1 to 16) and slot
number (1 to 10) assigned to the CDM are known. The molded J1 connector will be mounted at the
CDM’s slot.

3. Install the molded J1 connector at its assigned location as follows:

a. Per Figure 2-6, angle the top edge of the molded connector toward the backplane’s extruded
spacer. Insert its tip in the spacer’s groove.

b. Slide the connector in the groove until it is vertically and horizontally aligned with the
appropriate slot number pin.

c. Carefully lower the molded connector and engage the alignment pin with the connector’s pin
mounting hole. Firmly push down to seat the connector on the pin. When the connector is
properly seated, the pin is flush with or projects slightly above the connector’s face.

d. Tighten the connector’s captive mounting screw, which should be automatically aligned with its
respective panel mounting hole.

4. Connect the opposite end of the Interconnect I/O Cable to its corresponding Termination Assembly.
Perform one of the following depending upon Interconnect I/O Cable and Termination Assembly
type.

a. Terminated Interconnect I/O Cable-to-Marshalled Termination Assembly Connection

• Obtain a Part # 16056-435 Cable Keying Kit. The kit contains keying pins for the Terminated
Interconnect I/O Cable’s P2 connector and instructions.

• Install the pins per kit instructions. Figure 2–10 depicts the P2 connector’s keying pattern

2-24 July 2008


Installation SDQLCDM-1r9

Figure 2–10 Interconnect I/O Cable Assembly and Cable Keying

• Connect cable connector P2 to the Marshalled Termination Assembly’s J1 connector (Figure


1–1). The P2 connector’s keying pins ensures correct mating. Press P2 firmly onto J1.
Torque P2’s securing screw using no more than 50 inch-pounds of force.

July 2008 2-25


SDQLCDM-1r9 Installation

• Get two labels from the CDM label bag. Mark each label with the node, rack, and slot
numbers noted in step 2. Refer to Figure 1–1 and attach one label to the molded J1 connector.
Attach the second label to the cable’s P2 connector.

If applicable, repeat the above steps for the Interconnect I/O Cable that links the Marshalled Termination
Assembly to a redundant back up CDM. The cable for the redundant CDM mates with the Marshalled
Termination Assembly’s J2 connector.

b. Unterminated Interconnect I/O Cable-to-Rail Termination Assembly

• Unterminated Interconnect I/O Cables do not include a P2 connector. Follow Figure 2–2’s
wiring diagram to connect the unterminated cable’s color-coded wires to Rail Termination
Assembly terminals.

• Get a label from the CDM label bag. Mark it with the node, rack, and slot numbers noted in
step 2. Refer to Figure 1–1 and attach the label to the unterminated cable’s J1 connector.

2.10 CDM Installation

CDM installation procedures are described below, which include:

• Keying the CDM’s rack slot.

• Inserting the CDM into its rack slot.

2.10.1 CDM and Rack Slot Keying

Each MODULRAC, SIXRAC, Remote I/O Rack or UNIRAC slot and their corresponding modules must
be keyed to prevent problems associated with accidentally installing a module in an incompatible slot.

Modules are keyed at the factory. Every module type has its own unique the keying pattern. The CDM’s
keying pattern is depicted in Figure 2–11.

2-26 July 2008


Installation SDQLCDM-1r9

Figure 2–11 CDM Keying Assignment and Installation

A factory-assembled MODULRAC, SIXRAC, Remote I/O Rack, or UNIRAC is keyed at the factory. If
you assembled your MODULRAC, SIXRAC, Remote I/O Rack, or UNIRAC yourself, make sure that its
slots are keyed according to the module type assigned each slot. Slot keying patterns complement those
on I/O modules. Stop plugs for establishing keying patterns are supplied with all rack types.

July 2008 2-27


SDQLCDM-1r9 Installation

Perform the following to key a CDM rack slot:

1. Obtain the Keying Kit supplied with the rack.

2. Locate the rack’s top and bottom rails and refer to Figure 2–11 for the rack keying pattern.

3. To key the rack slot, press stop plugs into the rack rail holes identified in Figure 2–11.

2.10.2 Inserting the CDM into its Rack Slot

Use the following procedure to insert the CDM into its rack slot.

1. Remove the CDM from its static shielding bag and verify that both it and its rack slot are keyed per
the patterns of Figure 2–11.

2. Insert the CDM into its rack slot. Use uniform pressure to firmly seat the module in the backplane and
transition board connectors. If the module does not seat, double-check the keying. A properly seated
module will have the rear of its bezel flush against the rack’s front rails. A keyed module that is not
matched to a slot will not engage the backplane or transition board connectors or seat flush against the
rack’s front rails.

3. Pull open the CDM bezel’s pivoting top and bottom handles to expose the slotted captive mounting
screws and secure the module to the top and bottom rails. Close the bezel handles when finished.

CAUTION

Do not use the captive mounting screws to seat the module. This may
damage the module’s bezel.

2-28 July 2008


Installation SDQLCDM-1r9

2.11 Electrical Installation

DANGER

Electrical shock hazard


Explosion hazard

Will cause death, serious injury or property damage

• Remove power from all wires and terminals and verify that there
are no hazardous voltages before working on equipment.
• In potentially hazardous atmosphere, remove power from
equipment before connecting or disconnecting power, signal, or
other circuit, or extracting/inserting module.
• Observe all pertinent regulations regarding installation in
hazardous area.
• Ensure all devices are rated for hazardous (classified) locations.

This section describes power supply and field I/O connections to the CDM’s Termination Strip and
Marshalled Termination Assembly. It is assumed that tagged field I/O wires have been pulled into the
rack enclosure or marshalling cabinet and are ready for preparation and connection.

NOTE

The same procedures for making power supply and field I/O connections
to the CDM’s Termination Strip and Marshalled Termination Assembly
can be applied to the Fused and Relay Marshalled Termination
Assemblies. Consult Document # SD39RMTA-1 for wiring a Relay
Marshalled Termination Assembly. Wiring information for the Rail
Termination Assembly is available in Document # 15900-343.

Safety Related Switch Adapter (SRSA) installation on safety-critical discrete input channel terminals is
also discussed. Figure 2–12 and Figure 2–13 show sample I/O wiring configurations.

2.11.1 AC Supply Connections

AC input connections route power from a power input assembly to the I/O Power Supply described in
Section 2.5. For AC input cable connections between the I/O Power Supply and a Power Distribution
Assembly (PDA), refer to the PDA’s Installation and Service Instruction (Document # SD39PDA-1).
Alternatively, fabricate a cable to suit the installed AC power input assembly and I/O Power Supply.

July 2008 2-29


SDQLCDM-1r9 Installation

DANGER

ELECTRICAL SHOCK HAZARD


Will cause death or serious injury
Remove power from all involved wires and terminals before handling.

2.11.2 I/O Power Supply and Field Wiring Connections

Follow the steps below to complete I/O Power Supply and field wiring connections to CDM Termination
Strips and Assemblies.

1. Refer to the user or system integrator drawings to identify the Termination Strip or Assembly
terminals to which field I/O wiring should be tied. I/O power supplies should be connected to DC
power input terminals as identified in Figure 1–1, Figure 1–3, and Figure 2–2.

2. Note the following when preparing I/O Power Supply and field device cable ends:.

• Do not solder multiple wires or the strands of multiple-strand wires for insertion into terminals.
Solder is a malleable material and can loosen, causing open connections. Also, corrosion to the
terminal block can result from the pickling agents or flux used with solder.

• Use a pin-type crimp-on connector when two or more wires or a combination of wires and
component leads must be inserted into terminal. Also, use a pin-type crimp-on connector for
connections that will be moved regularly.

Wires and leads are crimped into the connector and the connector pin is inserted into the selected
terminal. This is demonstrated in Figure 2–12. The use of insulated crimp-on connectors is
recommended.

NOTE

Use a crimping tool recommended by the connector manufacturer to


ensure a mechanically strong, low-electrical-resistance connection.

Crimp-on
Signal Input Wire Connector

Range Resistor

2-30 July 2008


Installation SDQLCDM-1r9

Figure 2–12 Using a Pin-type Crimp-on Connector

3. Use the following torque specifications when screwing wires into terminals:

• LMI (gray) local termination terminal blocks: 3.5 to 5.5 in. lbs.

• Phoenix (green) terminal blocks: 6.5 to 8.5 in. lbs.

4. Complete the necessary connections for each configured channel per user or system integrator
drawings.

IMPORTANT

A suppression diode (1N4005 or equivalent) is recommended for


connection across inductive loads. Connect the diode as close as possible
to the load device for maximum benefit. Connect the cathode (banded
end) to the positive terminal of the load and the anode to the negative
terminal of the load. See Figure 2–12.

2.11.3 Safety-Related Switch Adapter (SRSA) Installation

Safety-Related Switch Adapters (plug type or wire type) are installed in series with channels configured
as discrete inputs. The SRSA is discussed in section 4.3 and illustrated in Figure 2–13, Figure 2–14, and
Figure 2–15.

SRSAs are available in eight piece kits identified in Table 3–3. Refer to the Instruction provided in the kit
for details concerning their mounting and wiring. SRSAs are voltage specific – the correct ones must be
installed with the 24 or 48 VDC I/O Power Supply used.

July 2008 2-31


SDQLCDM-1r9 Installation

Optional Fuse

Figure 2–13 Sample Input and Output Connections

2-32 July 2008


Installation SDQLCDM-1r9

Optional Fuse

Figure 2–14 Additional Sample I/O Connections

July 2008 2-33


SDQLCDM-1r9 Installation

Figure 2–15 Safety-Related Switch Adapter (SRSA)

2.12 Output Fuse Reset Switch Operation

As shown in Figure 2–16, a reset switch is located inside the CDM front bezel compartment. The purpose
of the reset switch is to clear error flags from all configured output channels that have posted the
following error in the 4-mation configuration program:

System Service Code Error Code Description


07 07 Output Channel XX Tripped Fuse

The error description indicates that an output channel fuse has soft fuse has tripped as a result of an
overload condition. Soft fuse functionality is discussed in section 4.2.3.

2-34 July 2008


Installation SDQLCDM-1r9

When a reset is initiated at the CDM, it is recorded as a system event, which displays in 4-mation or HMI
software such as APACS+ ProcessSuite or APACS+ Process Supervisor. A warning is also posted,
indicating that a reset has occurred. The warning is posted each and every time a reset is initiated at the
module. Since the error(s) also can be cleared on a per channel basis by 4-mation, the warning serves to
alert control room personnel on HMI computers that error clearing has been initiated by someone at the
module’s locale.

NOTE

Pressing the output fuse reset switch when no tripped fuse errors are
present does not affect the operation of CDM I/O channels.

Figure 2–16 Tripped Fuse Reset Switch

July 2008 2-35


SDQLCDM-1r9 Installation

2.13 Configuration

The CDM and its associated control module must be configured before being placed on-line.

CAUTION

When a CDM channel is used in a safety application, specific softlist


parameters must be configured. Details are provided in 4-mation and
Safety Manual documentation. Refer to the manuals I/O Module
Configuration for QUADLOG (Document # CGQL-4) and the
QUADLOG Safety Manual (Document # CGQLSAFETY-1) for more
information.

After the initial CDM power-up routine has been successfully completed, the CDM’s green OK LED
flashes on and off, indicating an unconfigured module. When the control module recognizes that the
CDM is on-line, it automatically downloads the proper configuration to the CDM. When the
configuration is accepted, the OK LED is set to solid green.

If the CDM is non-redundant, the control module enables the CDM by setting its ACTIVE LED to solid
green, indicating that it is in service. If the CDM is one of a redundant pair, and the other CDM is in the
Calculate mode, the control module disables the CDM, places it in the Verify mode, and turns its ACTIVE
LED turning off.

2-36 July 2008


3 Maintenance

DANGER

Electrical shock hazard


Explosion hazard

Will cause death, serious injury or property damage

• Remove power from all wires and terminals and verify that there are no
hazardous voltages before working on equipment.
• In potentially hazardous atmosphere, remove power from equipment
before connecting or disconnecting power, signal, or other circuit, or
extracting/inserting module.
• Observe all pertinent regulations regarding installation in hazardous
area.
• Ensure all devices are rated for hazardous (classified) locations.

The QUADLOG Critical Discrete Module (CDM) and its associated assemblies require minimal
maintenance. Some routine maintenance is recommended in the form of a visual inspection and a possible
cleaning.

3.1 Tool And Equipment Requirements

The following tools and equipment are necessary for CDM servicing:

• Common electronic servicing hand tools

• A digital voltmeter that meets the following requirements:

- Accuracy: +/- 1% of reading

- Resolution: 1.0 millivolt

- Input Impedance: 10 Megohms

3.2 Visual Inspection

The CDM and its associated assemblies should be subjected to a periodic visual inspection. The
frequency of inspection will depend on the severity of the operating environment. The primary aim of the
inspection is to reveal any excessive accumulation of dust, dirt, or other foreign material adhering to the
surfaces of the termination assembly and the CDM’s protective covers. Excessive accumulation of dirt
and dust prevents efficient heat dissipation and may cause module or system failure. A CDM installed in a
cabinet complying with the NEMA 12/IP65 specifications need not be inspected for cleanliness. See
Section 3.3 for cleaning instructions).

July 2008 3-1


SDQLCDM-1r9 Maintenance

3.3 Cleaning

Cleaning the CDM involves brushing or vacuuming its protective covers to restore cooling efficiency that
may have been degraded by accumulated dust. Cleaning an Termination Strip or Marshalled Termination
Assembly involves careful brushing and vacuuming to remove accumulated dust and dirt. Be careful not
to dislodge wiring.

3.4 Troubleshooting

There are 34 LED indicators on the CDM bezel. In addition, 4-mation software provides comprehensive
on-line error reporting. Refer to Configuring APACS+ and QUADLOG Hardware (Document # UM39-
14) for additional information. See Table 3-1 for CDM LED status indication. The CDM contains no user
replaceable parts.

Table 3–1 LED Status Indications

LED LED MODULE STATUS USER ACTION


INDICATOR INDICATION

OK Solid Green Module OK. Configured with no faults


Flashing Green/ Module not configured Configure module
Black
Flashing Class 2 Error Detected; one or more channel Check 4-mation error
Red/Green specific errors, or a less severe board level description for user action
error
Flashing 1. Low or defective I/O supply 1.Check 4-mation error
Red/Black 2. Class 3 Error Detected; board level description for user action
(1 per second) problem affecting more than one channel 2.Replace module
Flashing IOBUS communication error 1.Check 4-mation error
Red/Black description for user action
(5 per second) 2.Check IOBUS cables
3.Check CCM
4.Replace module
Solid Red Module fault, severe (Class 4 Error) 1.Check 4-mation error
description for user action
2.Replace module
Black Module not powered 1.Power-up the module
2.Properly seat the module
3.Replace module
Solid Green Module in control (Calculate Mode)
ACTIVE
Black Redundant CDM in Verify Mode or off-line
INPUT/OUTPUT CHANNEL STATUS

3-2 July 2008


Maintenance SDQLCDM-1r9

LED LED MODULE STATUS USER ACTION


INDICATOR INDICATION

CHANNEL Solid Green Channel is energized


1-32
Black Channel is not energized

July 2008 3-3


SDQLCDM-1r9 Maintenance

NOTE

Depending on module software level or configuration, forcing an output


(by externally applying power to an output terminal) may cause a
channel error indication or a channel shutdown (see channel 1 circuit in
Figure 2–14.

3.4 CDM Removal/Replacement

A module can be removed from or installed in the rack without removing power from the module slot,
from I/O circuits, or from the rack. However, removing a module from a functioning system generates a
Class 4 error and, in a non-redundant system configuration, may cause a system shutdown.

3.4.1 Removal

1. As shown in Figure 2–11, pull open the bezel’s pivoted top and bottom handles to expose the
module’s slotted captive mounting screws. Loosen the screws.

2. Grasp the top and bottom handles and pull the module from the card cage.

3. Place the module in a static shielding bag and package for return. See Sections 2.7.4 and 2.75 for
return instructions.

3.4.2 Replacement

1. Remove the replacement CDM from its protective bag. The module may be safely handled since its
circuitry is shielded from access by protective covers.

2. Confirm that the new module’s keying matches that of the removed module. If not, key the
replacement CDM as described in Section 2.10.

3. Insert the CDM in its rack slot. Firmly seat the module in the backplane and termination board
connectors. If the module does not seat, verify its keying. A properly seated module will have the rear
of its bezel flush against the rack’s rails. A keyed module that is not matched to a slot will not engage
the backplane and termination strip connectors or seat flush against the rack’s front rails.

4. As shown in Figure 2–11, pull open the bezel’s pivoted top and bottom handles to expose the
module’s slotted captive mounting screws and secure the module to the top and bottom rails. Close
the bezel’s handles when finished.

3-4 July 2008


Maintenance SDQLCDM-1r9

CAUTION

Do not use the captive mounting screws to seat the module. This may
damage the CDM’s bezel.

3.5 Termination Strip Removal/Replacement

Use the following procedures to remove and replace a CDM’s Termination Strip.

3.5.1 Removal

Refer to Figure 2–5 and the following removal procedure:

1. Take appropriate steps to shut down the process monitored or controlled by the field devices
connected to the Termination Strip.

2. Refer to Section 3.5 to remove the associated CDM from its rack slot. Place the CDM in a static
shielded bag for protection.

3. Unplug signal terminals from the Termination Strip. Disconnect its power leads.

4. Loosen the Termination Strip’s captive mounting screws. Gently lift the bottom of the strip in an arc
until it is free of its alignment pin located immediately above the Siemens logo. Pull the top of the
Termination Strip from the grooved backplane spacer and lift it from the rack.

3.5.2 Replacement

Refer to Figure 2–6 and perform the following replacement procedure:

1. See Section 2.8 and install the replacement termination strip.

2. Reconnect (plug in) the signal terminals and reconnect power leads to terminals.

3. Install the CDM per Section 3.5.

3.6 Marshalled Termination Assembly Removal/Replacement

Use the following procedures to remove and replace a CDM’s Marshalled Termination Assembly.

July 2008 3-5


SDQLCDM-1r9 Maintenance

3.6.1 Removal

Refer to Figure 2–8 and perform the following removal procedure:

1. Take appropriate steps to shut down the processes monitored or controlled by the field devices
connected to the Marshalled Termination Assembly.

2. Disconnect the signal and power wiring.

3. Remove the Marshalled Termination Assembly from its DIN Rail as depicted in Figure 2–8. For flat
surface mounted configurations, remove Assembly Mounting Ear screws as depicted in Figure 2–9.

3.6.2 Replacement

Refer to Figure 2–8 and Figure 2–9 and perform the following replacement procedure:

1. Install the replacement Marshalled Termination Assembly per Section 2.9’s procedures.

2. Reconnect signal and power wiring.

3.7 Interconnect I/O Cable Removal/Replacement

Use the following procedures to remove and replace a CDM’s Interconnect I/O Cable.

3.7.1 Removal

Refer to Figure 2–6 and Figure 2–10 and perform the following removal procedure:

1. Take appropriate steps to shut down the process controlled by the CDM.

2. Remove the CDM from its rack slot per Section 3.5’s instructions. Place the CDM in a static shielded
bag for protection.

3. At the Termination Assembly, disconnect Interconnect I/O Cable connector P2 or Unterminated I/O
Cable from individual color-coded connections.

4. At the rack, loosen the cable’s captive mounting screws. Gently lift the bottom of the cable in an arc
until the cable is free of its alignment pin. Pull the top of the cable from the grooved backplane spacer
and lift it from the rack.

5. Remove the cable from the cable tray or other cable routing equipment.

3-6 July 2008


Maintenance SDQLCDM-1r9

3.7.2 Replacement

Refer to Figure 2–8 and Figure 2–9 and perform the following replacement procedure:

1. Route the Interconnect I/O Cable between the rack and the marshalling cabinet containing its
Termination Assembly.

2. Install the cable as described in Section 0.

3. Install the CDM per Section 3.5.

3.8 Spare and Replacement Parts

One spare CDM should be stocked for every 1 to 20 in service. A spare or replacement module or
Termination Assembly can be ordered from one of the addresses in the Warranty statement or through a
local Siemens representative. Part numbers are in the tables that follow and are printed on most
components.

When ordering a new module, provide the model, part, and serial numbers of the module to be replaced or
spared. A purchase order number should also be provided.

There are no user serviceable parts within a CDM, Termination Strip, or standard or fused Marshalled
Termination Assemblies.

3.8.1 Accessories

Table 3-2 lists the available CDM accessories.

Table 3–2 CDM Accessories

PART NUMBER DESCRIPTION

16114-97 Marshalling Utility Panel. Includes installed wire ducts and DIN rails for
mounting marshalled termination assemblies. For installation in an APACS+
MODULPAC cabinet.
16114-12 Blank Utility Panel. Similar to preceding panel, but without installed ducts and
rails. For installation in an APACS+ MODULPAC cabinet.
16056-468 End Stop Kit. End stops prevent the sliding of an SDM Marshalled
Termination Assembly along the mounting DIN rail.
16201-1 SDM Relay Marshalled Termination Assembly. Features 32 Part # 7447-222
SPDT channel control relays. For use when all CDM channels will be
configured as outputs.
16056-562 Mounting Ear (see Figure 2–9). Provides for a flat mounting of the Marshalled
Termination Assembly. Order quantity of four.

July 2008 3-7


SDQLCDM-1r9 Maintenance

3-8 July 2008


Maintenance SDQLCDM-1r9

3.8.2 Options

Table 3-3 lists available CDM options.

Table 3–3 CDM Options

PART NUMBER DESCRIPTION


16128-1 SDM Termination Strip
16167-1 SDM/CDM Marshalled Termination Assembly
16436-1 SDM/CDM Fused Marshalled Termination
16805-3 DIN Rail Mounted SDM Rail Termination Assembly Kit. See section
5.2.1 and Figure 5-1.
16809-6 24 VDC Safety Related Switch Adapter (SRSA) Kit, Wire Type (8
pieces of Part # 16809-5 SRSAs with Installation Instructions)
16809-8 24 VDC Safety Related Switch Adapter (SRSA) Kit, Plug Type (8 pieces
of Part # 16809-7 SRSAs with Installation Instructions)
16809-10 48 VDC Safety Related Switch Adapter (SRSA) Kit, Wire Type (8
pieces of Part # 16809-9 SRSAs with Installation Instructions)
16809-12 48 VDC Safety Related Switch Adapter (SRSA) Kit, Plug Type (8 pieces
of Part # 16809-11 SRSAs with Installation Instructions)
16137-122 Interconnect I/O Cable Assembly 5.7 ft. (1.75 m)
16137-114 Interconnect I/O Cable Assembly 10 ft. (3 m)
16137-115 Interconnect I/O Cable Assembly 26.2 ft. (8 m)
16137-116 Interconnect I/O Cable Assembly 49.2 ft. (15 m)
16137-117 Interconnect I/O Cable Assembly 98.4 ft. (30 m)
16137-118 Unterminated Interconnect I/O Cable Assembly 10 ft. (3 m)
16137-119 Unterminated Interconnect I/O Cable Assembly 26.2 ft. (8 m)
16137-120 Unterminated Interconnect I/O Cable Assembly 49.2 ft. (15 m)
16137-121 Unterminated Interconnect I/O Cable Assembly 98.4 ft. (30 m)

July 2008 3-9


SDQLCDM-1r9 Maintenance

Table 3-4 below details Interconnect I/O Cable pin outs.

Table 3–4 Interconnect I/O Cable Pin Out

WIRE/STRIPE WIRE
J1 PIN P2 PIN
COLOR IDENTITY
A2 75 WH/BLK DC -
Notes: C2 74 WH/RED CH 1 +
E2 73 WH/BLUE CH 2 +
1. CH = Channel A4 65 WH/GRN CH 3 +
C4 49 WH/BRN CH 4 +
2. DC - = I/O E4 64 WH/OR CH 5 +
Power Supply A6 91 WH/YEL CH 6 +
DC negative C6 104 WH/VIO CH 7 +
E6 90 WH/GRAY CH 8 +
(I/O Common)
A8 100 RED/WH CH 9 +
C8 101 RED/BLK CH 10 +
3. DC + = I/O E8 102 RED/BLUE CH 11 +
Power Supply A10 36 RED/GRN CH 12 +
DC positive C10 47 RED/BRN CH 13 +
E10 46 RED/OR CH 14 +
4. P2 omitted on A12 11 RED/YEL CH 15 +
unterminated C12 10 RED/VIO CH 16 +
cable assembly E12 24 RED/GRAY DC -
A14 22 BLUE/WH CH 17 +
C14 8 BLUE/BLK CH 18 +
E14 21 BLUE/RED CH 19 +
A16 14 BLUE/GRN CH 20 +
C16 27 BLUE/BRN CH 21 +
E16 13 BLUE/OR CH 22 +
A18 44 BLUE/YEL CH 23 +
C18 43 BLUE/VIO CH 24 +
E18 45 BLUE/GRAY CH 25 +
A20 56 GRN/WH CH 26 +
C20 57 GRN/BLK CH 27 +
E20 41 GRN/RED CH 28 +
A22 16 GRN/BLUE CH 29 +
C22 3 GRN/BRN CH 30 +
E22 17 GRN/OR CH 31 +
A24 6 GRN/YEL CH 32 +
C24 19 GRN/VIO DC -
E24 5 GRN/GRAY DC -
A26 70 OR/WH DC +
C26 71 OR/BLK DC +
E26 72 OR/RED DC +
A28 85 OR/BLUE DC +
C28 98 OR/GRN DC +
E28 84 OR/BRN DC +
A30 96 OR/YEL DC +
C30 94 OR/VIO DC +
E30 95 OR/GRAY DC +
A32 92 YEL/WH DC +
C32 78 YEL/BLK DC +
E32 79 YEL/RED DC +
Shield Wire 1 Shield Wire -

3-10 July 2008


4 Circuit Description
A simplified block diagram of the CDM is shown in Figure 4-1.

Figure 4–1 CDM Block Diagram

The CDM consists of the following elements:

• CPU (68302)

• Memory (RAM and EPROM) - Stores module configuration parameters.

• IOBUS Interface - Provides digital data and command conversion needed for communication.

• 32 Critical Discrete I/O Circuits (24 VDC or 48 VDC) - Process discrete input and output signals.

• LED Indicators (on module bezel) - One LED per channel indicates channel status. An ACTIVE LED
indicates that the module is enabled. An OK LED indicates the status of the module.

4.1 Diagnostics

The CDM is safety critical-rated. As such, no known dangerous undetected failures are permitted in the
design. This requirement in turn requires extremely effective self diagnostics verified by full Failure

July 2008 4-1


SDQLCDM-1r9 Circuit Description

Modes and Effects Analysis (FMEA) and fault injection testing. The goals of CDM diagnostics are as
follows:

• Notify the appropriate personnel of a module malfunction or wiring error.

• Perform automatic switchover in a fully redundant (1oo2D) QUADLOG system.

• Perform automatic shutdown of a channel or a module if a dangerous fault is detected (for failsafe
operation)

CDM diagnostics consist cover individual channels and common circuits. Each CDM channel can detect
the following faults:

• Input channel failed (stuck at “1”, stuck at “0”, diagnostic circuit fail)

• Output channel failed (ON, OFF, diagnostic circuit fail)

• Output channel tripped fuse

• Shorted redundancy diode

• Discrete pulse output channel (DPOC) duration limit exceeded

There are numerous other module diagnostics, some of which are categorized as follows:

• Power supply diagnostics

• Memory diagnostics

• Communication diagnostics

• Redundancy diagnostics

• Watchdog reset diagnostics

• Miscellaneous diagnostics

Any errors detected by these diagnostics are reported to the control module. The control module and the
CDM maintain a log of current and historical errors that can be reviewed using the operator interface or
the APACS+ 4-mation configuration software. In addition, the module’s LED’s indicate errors.

4.2 Input/Output Channel Circuitry

Each configured input channel can read a discrete signal from the field. Each configured output channel
can supply an output voltage and current to a load.

4-2 July 2008


Circuit Description SDQLCDM-1r9

4.2.1 External Power Supply Input

As shown in Figure 4–1, an external 24/48 VDC I/O power supply provides power for the module’s
isolated I/O circuits and field loads. This power supply must meet all necessary safety approvals. The
module’s CPU and signal processing circuits are powered by a separate 24 VDC power supply that
provides operating power to the modules via the rack backplane. It is highly recommended that the I/O
power supply be separate from the backplane power supply.

DC+ from the external power supply is connected to the Termination Assembly and is routed across the
assembly to the 12 terminals of the module’s P2 connector to distribute the total load current.

DC+ is switched through “diagnostic cut-off relays,” which isolate the module from the external power
supply when the module is not enabled (active) or when the module detects a solid state switch failure.

4.2.2 Protected Outputs

The CDM uses a combination of extensive on-line diagnostics and an internal “diagnostic cut-off relay”
to automatically protect against energized output failures. As shown in Figure 4–1, output energy flows
through “dual-switches” to the load. A solid state switch provides the normal output. A relay, controlled
by built-in diagnostics, supplies the second switch through a pair of normally open contacts. If any
dangerous failure is detected, the relay contacts are opened. This action de-energizes the output, ensuring
the output fails in a safe manner. Using this technique, CDM-protected outputs ensure that outputs fail
safe, even in the presence of faults.

4.2.3 Output Channel

All output channels are electrically identical. As shown in Figure 4–1, the Output Switch supplies 24/48
VDC to a field device when the channel is configured as an output. A channel control signal is supplied
from the processor. An output protection diode connects the switch to an I/O terminal.

Each output configured channel features a Soft-Fuse circuit that provides over-current protection. Should
a fault increase the channel load current to a level that would damage the circuit, the Output Switch turns
off. A “tripped” Soft-Fuse can be reset from an operator interface or by a local reset switch located in the
CDM bezel compartment.

An output circuit is optimized for normally energized usage and provides full self-diagnostic capability.
Diagnostics use a combination of pulse-testing, voltage/current measurement, and constant switching in
the 1oo2D architecture. Circuitry measures voltage at the input to the “diagnostic cut-off relay,” at the
Output Switch, and at the field terminals. Momentary pulse-off testing provides a dynamic signal that
allows detection of open-circuit, short-circuit, and diagnostic-circuit failures.

4.2.4 Input Channel

All input channels are electrically identical. An input circuit is optimized for normally energized sensor
inputs (input switch closed under normal operation). This circuit offers full self-diagnostic capability,
including field wiring faults when used with Safety-Related Switch Adapters (SRSAs) and the
PulseDiagTest parameter enabled.

July 2008 4-3


SDQLCDM-1r9 Circuit Description

The positive external power supply voltage input from an I/O field input is applied to an analog input
circuit. When the processor selects a group of channels to read, the output from the analog circuit is
routed to the input/output diagnostic read logic circuit for conversion into a digital logic signal for the
processor to read.

Full diagnostic coverage is obtained by a combination of test pulses that superimpose bipolar dynamic
signals onto the input. The analog circuit has a variable analog threshold that allows the CDM processor
to read the voltage at the input terminal. This combination of dynamic test pulses and analog monitoring
allows detection of electronic component failures, and short circuit (wiring) failures between the field
device and the input channel terminals or 24/48 VDC I/O power at the CDM termination assembly.

There are two types of SRSAs: a plug type and a wire type. See Figure 2–15. Eight-piece SRSA kits are
listed in Table 3–3. The plug type is for use with an SDM Rail Termination Assembly (see Figure 2–2),
for non-redundant systems, or with user-supplied Phoenix Contact blocks. The wire-type SRSA is
designed for use with a local SDM Termination Strip, a Marshalled Termination Assembly, or Fused
Marshalled Termination Assembly.
NOTE

Input diagnostics can only detect field wiring faults between the CDM
module and the point of SRSA installation. It is recommended that
SRSAs be installed as close as possible to the input device.

4.3 Pulse Test Channel Diagnostics

Pulse Diagnostic Test (PulseDiagTest) functionality is explained in the sections that follow.

4.3.1 CDM Output Channels


NOTE

CDM output channels must not be used with SRSAs.

CDM output channels with the PulseDiagTest soft list parameter set to Enabled runs pulse testing on
energized outputs only. The channel is turned off for approximately 200 µs so that the channel state can
be read back without the output voltage enabled. Pulse testing is run every 3.2 seconds on each channel
with PulseDiagTest enabled. The 3.2-second time interval is one diagnostic cycle for all pulse tested
channels. Figure 4–2 illustrates approximate timing of the pulses generated on a single channel every
diagnostic cycle. The CDM collects channel data during the pulse test. The data is then compared to
expected results to determine if there are any faults. Multiple channel pulses allow duplicate channel data
recording. The duplicate data is used to reduce the chance of detecting faults in harsh electrical
environments.

For de-energized output channels, there is no pulse testing. However, during the interval reserved for
diagnostic testing, the CDM measures the output voltage on each channel. For de-energized channels, the
voltage should be low, and the CDM can distinguish between a load and an open load condition.
Table 4–1 lists the open load thresholds in ohms for 24 and 48 VDC CDM models.

4-4 July 2008


Circuit Description SDQLCDM-1r9

25 mS 25 mS
Voltage
200 μS 200 μS 200 μS

24 VDC

0 VDC
Time

Figure 4–2 Output Channel Diagnostic Pulse Timing

Table 4–1 Open Load Thresholds for 24 V and 48 V CDMs

OPEN LOAD THRESHOLDS


REPORTED ERRORS
24 V CDM 48 V CDM
< 496 Ω < 622 Ω None
496 - 4050 Ω 622 - 4271 Ω Possible
> 4050 Ω > 4271 Ω Yes

July 2008 4-5


SDQLCDM-1r9 Circuit Description

Table 4–2 lists possible errors generated during the pulse test interval for output channels whose

PulseDiagTest soft list parameter is enabled. There are many more CDM errors possible, but these are
the most likely output channel fault errors.

Table 4–2 Possible Output Channel Fault Errors

SSC ERROR CLASS DESCRIPTION


7 32 2 Critical Output Failed Energized
7 33 2 Critical Output Failed De-Energized
7 37 2 Open Load on Output Channel

4.3.2 CDM Input Channels

CDM input channels configured with PulseDiagTest enabled must be wired with an SRSA in series with
the input switch or contact closure. The SRSA is a passive device designed to drop a fixed voltage (6
VDC for 24 VDC CDM, 12VDC for 48VDC CDM).

A CDM input is pulse tested with the same timing as an output channel. However, input channels are
pulsed on (energized). For every channel with PulseDiagTest enabled, the channel is pulsed with several
200 µS pulses every 3.2 seconds. Refer to Figure 4–3 for approximate times and voltages of the pulses
used. Multiple data sets are recorded and analyzed to generate fault information.

Voltage 200 μS 200 μS 200 μS

24 VDC

18 VDC
25 mS 25 mS

Time
Figure 4–3 Input Channel Diagnostic Pulse Timing

4-6 July 2008


Circuit Description SDQLCDM-1r9

For de-energized inputs, the channel state pulses from approximately 0 VDC up to 24 VDC during each
test pulse. For inputs that are energized, the channel state (between the CDM and the SRSA) pulses from
approximately 18 VDC to 24 VDC for 24 VDC CDM models; 36 VDC to 48 VDC for 48 VDC CDM
models.

Table 4-3 lists possible errors generated during the pulse test interval for input channels whose
PulseDiagTest soft list parameter is enabled. There are many more CDM errors possible, but these are
the most likely input channel fault errors.

Table 4–3 Possible Input Channel Fault Errors

SSC ERROR CLASS DESCRIPTION


7 30 2 Critical Input Failed De-Energized
7 31 2 Critical Input Failed Energized

July 2008 4-7


5 Specifications
This section provides specifications for the QUADLOG Critical Discrete Module (CDM).

5.1 Model Number Designation

Use the following to decode a CDM’s model number:

QLCDM 024DC X X X QUADLOG Critical Discrete Module (CDM)

Electrical Approvals: N = Not Required. Refer to CDM


nameplate for current agency approvals.

Design Level

Revision Level (A to Z)

I/O Power Supply Voltage: 024DC = 24 VDC, 048DC


= 48 VDC

July 2008 5-1


SDQLCDM-1r9 Specifications

5.2 Module Specifications

Table 5-1 lists the mechanical and electrical specifications of the Critical Discrete Module (CDM). Table
5–2 lists the CDM’s total current versus ambient temperature.

Table 5–1 CDM Specifications

TYPE SPECIFICATION DATA


Mechanical Module Weight 4.25 lbs. (1.9 kg)
Electrical Backplane Input Voltage 24 VDC - 10%, + 20%
Backplane Input Current 0.23 A maximum
Heat Dissipation 27 Watts maximum
I/O per Module 32 isolated channels, input or output, user
configurable
I/O Operating Voltage 24 V Model: 24 VDC +/- 5%
48 V Model: 48 VDC +/- 5%
Isolation 300 V
Tested to 1,950 Vrms per EN61010-1:1993
Module Module Scan Rate 25ms
Output Configured Output Current per Channel 600 mA maximum
Channel Total Output Current 12.8 maximum
Surge Current 2.0 A maximum for 10 ms
OFF State Leakage Current 24 V Model: 1.6 mA maximum
48 V Model: 1.0 mA maximum
Soft-Fuse Trip Point 1.53 A typical
Pulse Out Configured Pulse Duration Configurable 10 to 6500* ms in 10 ms
Channel increments
Input Configured Channel Input Delay Filter Time <30 μS OFF-ON and ON-OFF
Input Wetting Current 9.96 mA @ 24 VDC typical
6.10 mA @ 48 VDC typical
Maximum OFF State Current 24 V Model: 5.8 mA
OFF State Voltage Range 48 V Model: 3.7 mA
24 V Model: -0.5 to 14.0 VDC
48 V Model: -0.5 to 29.5 VDC
Module Scan Rate, Tms** 25 ms
Input Configured Channel - ON State Voltage Range 24 V Model: 17.0 to 30.0 VDC
PulseDiagTest Disabled 48 V Model: 32.3 to 52.0 VDC
Input Configured Channel - ON State Voltage Range at 24 V Model: 17.0 to 19.8 VDC
PulseDiagTest Enabled Termination 48 V Model: 32.3 to 40.5 VDC
(with installed SRSA) Channel Failed ON 24 V Model: >21.6 VDC
48 V Model: >43.8 VDC

* 2000 ms via soft list

** Tms for sequence of events (SOE) inputs have a scan rate of 1 ms

5-2 July 2008


Specifications SDQLCDM-1r9

Table 5–2 CDM Total Current vs. Ambient Temperature

Channels At
Specified Ambient Temperature
Current And
Total Current 30°C (86°F) 35°C (95°F) 45°C (113°F) 70°C (140°F)

Number of 19 15 10 4
channels at
0.6A/channel

Total Current 11.4A 9.0A 6.0A 2.4A

Number of 24 19 13 5
channels at
0.5A/Channel

Total Current 12.0A 9.5A 6.5A 2.5

Number of 32 27 18 8
channels at
0.4A/channel

Total Current 12.8A 10.8A 7.2A 3.2A

Number of 32 32 27 12
channels at
0.3A/channel

Total Current 9.6A 9.6A 8.1A 3.6A

Number of 32 32 32 21
channels at
0.2A/channel

Total Current 6.4A 6.4A 6.4A 4.2A

Number of 32 32 32 32
channels at
0.1A/channel

Total Current 3.2A 3.2A 3.2A 3.2A

July 2008 5-3


SDQLCDM-1r9 Specifications

5.3 Maximum I/O Related Power Dissipation Versus Temperature

Table 5-3 lists the maximum I/O related power dissipation versus temperature. A calculation of the CDMs
power dissipation should be made to determine the allowable operating ambient temperature.

Table 5–3 Maximum I/O Related Power Dissipation Versus Temperature

TEMPERATURE MAXIMUM POWER DISSIPATION (PD)


+30 ˚C 21 Watts
+35 ˚C 18 Watts
+45 ˚C 14 Watts
+60 ˚C 10 Watts

The following formula calculates the related I/O power dissipation in Watts:

Formula for I/O Related Power Dissipation


0.24(NIE + NOE) + 0.0284 IT2 + 0.248 IT + (1.046)∑ik2 = PD (Watts)

NIE = Number of energized inputs at a particular time


NOE = Number of energized outputs at a particular time
ik = Current load of output channel “k” in Amps at this instance of time (0 when not energized)
IT = ∑ik = Total output current from all output configured channels at this instance of time
∑ik2= (N1)(ik1)2 + (N2)(ik2)2 + .......... (Nn)(ikn)2

Where: N1 = The total number of output channels having the same load current ik1
N2 = The total number of output channels having the same load current ik2
Nn = The total number of remaining output channels having the same load current ikn

Example Calculation:

Given: 24 Inputs = 20 energized and 4 non-energized


8 Outputs = (2) @ 0.6A normally energized and (6) @ 0.15A normally energized
IT =∑ik = (2)(0.6) + (6)(0.15) = 1.2 + 0.9 = 2.1A

Substitute data in the formula and perform the indicated mathematical operations:

PD = 0.24(NIE + NOE) + 0.0284 IT2 + 0.248 IT + (1.046) ∑ik2


= 0.24(20 +8) + 0.0284(2.1)2 + 0.248 (2.1) + (1.046)[(2)(0.6)2 + (6)(0.15)2]
= 6.72 + 0.125 + 0.520 + 0.753 + 0.141
= 8.26 Watts

The allowable ambient temperature for the calculated 8.26 Watts is +60 ˚C, per Table 5–3.

5-4 July 2008


Specifications SDQLCDM-1r9

5.4 Environmental Specifications

The environmental specifications of the CDM are provided in Table 5-4. The SRSA environmental
specifications are provided in Table 5–5.

Table 5–4 Environmental Specifications

SPECIFICATIONS DATA REFERENCE STANDARDS


Ambient Temperature Range: IEC 68-2-2 Test Bb
• Operating -25 to 70 ˚C, 0.5 ˚C/min IEC 68-2-14 Tests Na, Nb
• Storage -25 to 85 ˚C, 10 ˚C/min IEC 68-2-1 Tests Ab, Ad
Relative Humidity:
• Operating: IEC 1131-2-RH2 5 to 95%, non-condensing IEC 68-2-3 Test Ca
• Storage 0 to 100%, condensing IEC 68-2-30 Test Dd
Vibration 10-150 Hz IEC 68-2-6 Test Fc
2 g max
Mechanical Shock:
• Acceleration 15 g IEC 68-2-27 Test EA
• Duration 11 ms
Corrosives Class G3, 10+ years ANSI/ISA S71.04
Radiated Emission, E-Field 30 MHz-230 MHz EN 55011
30 db (μV/m) at 30 m
230 MHz-1000 MHz EN 50081-2
37 db (μV/m) at 30 m
Conducted Emission Power Lines 0.15 MHz-0.5 MHz EN 55011
79 dBm quasi-peak
0.5 MHz-30 MHz EN 50081-2
73 dBm quasi-peak
Immunity, Conducted 150 KHz-80 MHz, 10 V IEC 801-6/IEC 1000-4-6
Electromagnetic Field 10 k Hz-50 MHz, 1V IE 801-6
Immunity, Power Lines Surge 4 kV IEC 801-5
2 kV ANSI/IEEE C62.41 (IEEE 587)
Immunity, Electrical Fast 4 kV Power Lines, 2 kV I/O IEC 801-4/IEC 1000-4-4
Transients and Signal Line Surge 2.5 kV I/O ANSI/IEEE C37.90
(Formally IEEE 472)
Immunity, Radiated E-Field 10 V/m, 27 MHz-1000 MHz IEC 801-3
10 V/m, 80 MHz-1000 MHz IEC 1000-4-3
10 V/m, 30 kHz-150 kHz IEC 801-3
Immunity, Electrostatic Discharge 8 kV contact, 15 kV air IEC 801-2/IEC 1000-4-2, Level 4
Altitude: IEC 1131-2 Up to 2000 meters

July 2008 5-5


SDQLCDM-1r9 Specifications

Table 5–5 SRSA Environmental Specifications

SPECIFICATIONS DATA
Ambient Temperature Range:
• Operating -25 to 70 ˚C

5.5 Electrical Classification

Before installing, applying power to, or servicing a CDM, see the module’s nameplate for electrical
classification.

This product has been tested per the European Union’s EMC Directive. See the Declaration of
Conformity statement at the back of this Instruction. Refer to section 2.2.1 for considerations affecting
EMC compliance.

• FM Approved for use in Class I. Division 2, Groups A,B,C,D hazardous (classified) locations,
Temperature code T3C at 70°C Ambient.

• CSA Certified for use in Class I. Division 2, Groups A,B,C,D hazardous (classified) locations,
Temperature code T3C at 70°C Ambient.

• ABS Type Approved

• UL Listed Industrial Control Equipment

• TUV Approved

• CE marked (See Declaration of Conformity in the next section.)

5-6 July 2008


Specifications SDQLCDM-1r9

5.5.1 CSA Hazardous Locations Precautions

This section provides CSA hazardous location precautions that should be observed by the user when
installing or servicing the equipment described in this Instruction. These statements supplement those
given in the preceding section.

DANGER

Electrical shock hazard


Explosion hazard

Will cause death, serious injury or property damage

• Remove power from all wires and terminals and verify that there
are no hazardous voltages before working on equipment.
• In potentially hazardous atmosphere, remove power from
equipment before connecting or disconnecting power, signal, or
other circuit, or extracting/inserting module.
• Observe all pertinent regulations regarding installation in
hazardous area.
• Ensure all devices are rated for hazardous (classified) locations.

Precautions - English

For Class I, Division 1 and Class I, Division 2 hazardous locations,

• Use only factory-authorized replacement parts. Substitution of components can impair the suitability
of this equipment for hazardous locations.

For Division 2 hazardous locations:

When the equipment described in this Instruction in installed without safety barriers, the following
precautions should be observed. Switch off electrical power at its source (in non-hazardous location)
before connecting or disconnecting power, signal, or other wiring.

Précautions - Français

Emplacements dangereux de classe I, division 1 et classe I, division 2:

• Les pièces de rechange doivent être autorisées par l'usine. Les substitutions peuvent rendre cet
appareil impropre à l'utilisation dans les emplacements dangereux.

July 2008 5-7


SDQLCDM-1r9 Specifications

Emplacement dangereux de division 2:

Lorsque l'appareil décrit dans la notice ci-jointe est installé sans barrières de sécurité, on doit couper
l'alimentation électrique a la source (hors de l'emplacement dangereux) avant d'effectuer les opérations
suivantes branchment ou débranchement d'un circuit de puissance, de signalisation ou autre.

5-8 July 2008


Specifications SDQLCDM-1r9

5.5.2 Special Conditions for Safe Use

Always refer to the labels on the controller case for approvals and certifications applicable to that
instrument.

FM

Enclosure Requirements:

• The apparatus must be mounted within an enclosure or assembly to prevent personal injury resulting
from accessibility to live parts. The enclosure is typically user-supplied and, therefore, was not
examined as part of this Approval but shall comply with the requirements of this section.

• Accessibility - The system must be installed within the enclosure so that its circuits are accessible by
the use of a tool only. A part is accessible when either a.) the IEC articulate accessibility probe
applied in every possible position to the exterior or exposed surfaces, including the bottom; or b.) the
IEC rigid accessibility probe applied with a maximum force of 30 Newtons (6.75 lbs force) in every
possible position to the exterior or exposed surface, including the bottom, touches the part.

• Protection from Fire - If the enclosure is non-metallic, it shall have the proper flammability rating.

• Grounding - A metallic enclosure must have a protective grounding terminal and be marked as such.
All accessible non-current conductive parts must be bonded to the protective grounding terminal.

• General Construction - The equipment enclosure, or parts of the enclosure, required to be in place to
comply with the requirements for protection from electric shock, personal injury, protection of
internal parts and wiring and external cord and cable assembly strain relief shall comply with the
following tests for mechanical strength:

• Impact Tests - The equipment shall be held firmly against a rigid support and shall be subjected
to sets of three blows with 6.6 Joules (4.9 pound force-inch) from a spring-operated impact
hammer. The hammer shall be applied to any external part that when broken is likely to expose
live parts. A window of an indicating device shall withstand an impact of 0.085 Newton-meter
(0.753 pound force-inch) from a hollow steel impact sphere 50.8 mm (2 inches) in diameter and
an approximate mass of 113.4 grams (4 ounces).

• Pressure Tests - A force of 90 Newtons (20 pounds) shall be applied from a metal rod 12.7 mm
(0.50 inch) in diameter, the end of which is rounded. The force shall be applied for one minute to
any point on the overall enclosure except the bottom. The bottom shall sustain a force of 65
Newtons (15 pounds).

• Tip Stability Test - Equipment having a weight of 11 kilograms (24 pounds) or more shall not tip
over when placed at the center of an inclined plane that makes an angle of 10 degrees with the
horizontal and then turned to the position (with all doors, drawers, and other openable and sliding
parts in the least stable position) most likely to cause tip-over.

• Sharp Edges - An accessible edge, projection, or corner of an enclosure, opening, frame, guard,
handle, or the like shall be smooth and well rounded, and shall not cause a cut-type injury during
normal use of the equipment.

July 2008 5-9


SDQLCDM-1r9 Specifications

CE

• Use of the equipment in a manner not specified by the manufacturer may impair the protection
provided by the equipment.

• Route electrical power to the station through a clearly labeled circuit breaker or on-off switch that is
located near the station and is accessible by the operator. The breaker or switch should be located in
a non-explosive atmosphere unless suitable for use in an explosive atmosphere.

• The next page contains a Declaration of Conformance with the standards or other normative
documents stated on the certificate.

• Environmental Conditions, Per IEC 664, Installation Category II, Pollution Degree 2

5-10 July 2008

You might also like