Chapter-16 TRANSFORMER AND TRANSFORMER FEEDER PROTECTION
Chapter-16 TRANSFORMER AND TRANSFORMER FEEDER PROTECTION
TRANSFORMER FEEDER
PROTECTION
Chapter 16
TRANSFORMER AND TRANSFORMER
FEEDER PROTECTION
16.6 Transformer Overcurrent Protection The considerations for a transformer protection package
vary with the application and importance of the trans-
16.7 Restricted Earth Fault Protection former. To reduce the effects of thermal stress and electro-
16.8 Differential Protection dynamic forces, it is advisable to ensure that the protection
package used minimises the time for disconnection in the
16.9 Differential Protection Stabilisation During event of a fault occurring within the transformer. Small distri-
Magnetising Inrush Conditions bution transformers can be protected satisfactorily, from both
16.10 Combined Differential and Restricted technical and economic considerations, by the use of fuses or
overcurrent relays. This results in time-delayed protection due
Earth Fault Schemes
to downstream co-ordination requirements. However, time-de-
16.11 Earthing Transformer Protection layed fault clearance is unacceptable on larger power trans-
16.12 Autotransformer Protection formers used in distribution, transmission and generator appli-
cations, due to system operation/stability and cost of repair/
16.13 Overfluxing Protection length of outage considerations.
16.14 Tank-Earth Protection Transformer faults are generally classified into five categories:
16.15 Oil and Gas Devices .. winding and terminal faults
16.16 Transformer-Feeder Protection .. core faults
16.17 Intertripping .. tank and transformer accessory faults
16.18 Examples of Transformer Protection .. on–load tap changer faults
16.19 Transformer Asset Management .. abnormal operating conditions
.. sustained or uncleared external faults
For faults originating in the transformer itself, the approximate
proportion of faults due to each of the causes listed above is
shown in Figure 16.1.
Winding and
Terminal
Core
Tank and
Accessories
OLTC
GEGridSolutions.com 16-1
Protection & Automation Application Guide
(percentage of winding)
90
Single-Phase Earth fault current
Fault current
80 (IF)
70 For secondary winding faults, the primary winding fault
60
current is determined by the variable transformation ratio; as
the secondary fault current magnitude stays high throughout
50
the winding, the primary fault current is large for most points
40
along the winding.
30
20
Primary Current 16.2.3 Delta-Connected Winding
10 (Ip)
No part of a delta-connected winding operates with a voltage
0 10 20 30 40 50 60 70 80 90 100 to earth of less than 50% of the phase voltage. The range of
Distance of fault from Neutral fault current magnitude is therefore less than for a star
(percentage of winding) winding. The actual value of fault current will still depend on
the method of system earthing; it should also be remembered
that the impedance of a delta winding is particularly high to
fault currents flowing to a centrally placed fault on one leg.
The impedance can be expected to be between 25% and 50%,
based on the transformer rating, regardless of the normal
Ip
balanced through-current impedance. As the prefault voltage
to earth at this point is half the normal phase voltage, the
IF earth fault current may be no more than the rated current, or
even less than this value if the source or system earthing
impedance is appreciable. The current will flow to the fault
from each side through the two half windings, and will be
16-2
Chapter 16 Transformer and Transformer Feeder Protection
Section 16.2.2. 40 4
16-3
Protection & Automation Application Guide
The thermal time constant of naturally cooled transformers lies 16.2.8.4 Reduced system frequency
between 2.5-5 hours. Shorter time constants apply in the case Reduction of system frequency has an effect with regard to flux
of force-cooled transformers. density, similar to that of overvoltage.
16.2.8.2 System faults It follows that a transformer can operate with some degree of
overvoltage with a corresponding increase in frequency, but
System short circuits produce a relatively intense rate of
operation must not be continued with a high voltage input at a
heating of the feeding transformers, the copper loss increasing
low frequency. Operation cannot be sustained when the ratio
in proportion to the square of the per unit fault current. The
of voltage to frequency, with these quantities given values in
typical duration of external short circuits that a transformer
per unit of their rated values, exceeds unity by more than a
can sustain without damage if the current is limited only by
small amount, for instance if V/f >1.1. If a substantial rise in
the self-reactance is shown in Table 16.1. IEC 60076 provides
system voltage has been catered for in the design, the base of
further guidance on short-circuit withstand levels.
'unit voltage' should be taken as the highest voltage for which
Transformer Reactance Fault Current Permitted Fault the transformer is designed.
(%) (Multiple of Rating) Duration (seconds)
4 25 2 16.3 MAGNETISING INRUSH
5 20 2 The phenomenon of magnetising inrush is a transient
6 16.6 2 condition that occurs primarily when a transformer is
7 14.2 2 energised. It is not a fault condition, and therefore transformer
protection must remain stable during the inrush transient.
Maximum mechanical stress on windings occurs during the Figure 16.5(a) shows a transformer magnetising
first cycle of the fault. Avoidance of damage is a matter of characteristic. To minimise material costs, weight and size,
transformer design. transformers are generally operated near to the ‘knee point’ of
the magnetising characteristic. Consequently, only a small
16.2.8.3 Overvoltages increase in core flux above normal operating levels will result in
Overvoltage conditions are of two kinds: a high magnetising current.
transient surge voltages Under normal steady-state conditions, the magnetising current
associated with the operating flux level is relatively small
power frequency overvoltage
(Figure 16.5(b)). However, if a transformer winding is
Transient overvoltages arise from faults, switching, and energised at a voltage zero, with no remanent flux, the flux
lightning disturbances and are liable to cause interturn faults, level during the first voltage cycle (2 x normal flux) will result
as described in Section 16.2.5. These overvoltages are usually in core saturation and a high non-sinusoidal magnetising
limited by shunting the high voltage terminals to earth either current waveform – see Figure 16.5(c). This current is
with a plain rod gap or by surge diverters, which comprise a referred to as magnetising inrush current and may persist for
stack of short gaps in series with a non-linear resistor. The several cycles.
surge diverter, in contrast to the rod gap, has the advantage of
Several factors affect the magnitude and duration of the
extinguishing the flow of power current after discharging a
magnetising current inrush:
surge, in this way avoiding subsequent isolation of the
transformer. residual flux – worst-case conditions result in the flux
peak value attaining 280% of normal value
Power frequency overvoltage causes both an increase in stress
on the insulation and a proportionate increase in the working point on wave switching
flux. The latter effect causes an increase in the iron loss and a number of banked transformers
disproportionately large increase in magnetising current. In transformer design and rating
addition, flux is diverted from the laminated core into
structural steel parts. The core bolts, which normally carry system fault level
little flux, may be subjected to a large flux diverted from the
highly saturated region of core alongside. This leads to a rapid
temperature rise in the bolts, destroying their insulation and
damaging coil insulation if the condition continues.
16-4
Chapter 16 Transformer and Transformer Feeder Protection
three-phase transformers.
at switching
The very high flux densities quoted above are so far beyond the 16.4 TRANSFORMER OVERHEATING
normal working range that the incremental relative
The rating of a transformer is based on the temperature rise
permeability of the core approximates to unity and the
above an assumed maximum ambient temperature; under this
inductance of the winding falls to a value near that of the 'air-
condition no sustained overload is usually permissible. At a
cored' inductance. The current wave, starting from zero,
lower ambient temperature some degree of sustained overload
increases slowly at first, the flux having a value just above the
can be safely applied. Short-term overloads are also
residual value and the permeability of the core being
permissible to an extent dependent on the previous loading
moderately high. As the flux passes the normal working value
conditions. IEC 60354 provides guidance in this respect.
and enters the highly saturated portion of the magnetising
characteristic, the inductance falls and the current rises rapidly The only certain statement is that the winding must not
to a peak that may be 500% of the steady state magnetising overheat; a temperature of about 95°C is considered to be the
current. When the peak is passed at the next voltage zero, the normal maximum working value beyond which a further rise of
16-5
Protection & Automation Application Guide
8°- 10°C, if sustained, will halve the insulation life of the unit. The fuse must have a rating well above the maximum
transformer load current to withstand the short duration
Protection against overload is therefore based on winding
overloads that may occur. Also, the fuses must withstand the
temperature, which is usually measured by a thermal
magnetising inrush currents drawn when power transformers
modelling technique. Protection is arranged to trip the
are energised. High Rupturing Capacity (HRC) fuses, although
transformer if excessive temperature is reached. The trip
very fast in operation with large fault currents, are extremely
signal is usually routed via a digital input of a protection relay
slow with currents of less than three times their rated value. It
on one side of the transformer, with both alarm and trip
follows that such fuses will do little to protect the transformer,
facilities made available through programmable logic in the
serving only to protect the system by disconnecting a faulty
relay. Intertripping between the relays on the two sides of the
transformer after the fault has reached an advanced stage.
transformer is usually applied to ensure total disconnection of
the transformer. Table 16.3 shows typical ratings of fuses for use with 11kV
transformers
Winding temperature protection may be included as a part of a
complete monitoring package. See Section 16.18 for more details. Transformer Rating Fuse
Full Load Current Rated Current Operating Time at 3 x
16.5 TRANSFORMER PROTECTION – kVA
(A) (A) Rating (s)
OVERVIEW 100 5.25 16 3.0
The problems relating to transformers described in Section 200 10.5 25 3.0
16.4 require some means of protection. Table 16.2 315 15.8 36 10.0
summarises the problems and the possible forms of protection 500 26.2 50 20.0
that may be used. The following sections provide more detail 1000 52.5 90 30.0
on the individual protection methods. It is normal for a
modern relay to provide all of the required protection functions
This table should be taken only as a typical example;
in a single package, in contrast to electromechanical types that
considerable differences exist in the time characteristics of
would require several relays complete with interconnections
different types of HRC fuses. Furthermore grading with
and higher overall CT burdens.
protection on the secondary side has not been considered.
Fault Type Protection Used
Primary winding Phase-phase fault Differential; Overcurrent 16.6.2 Overcurrent Relays
Primary winding Phase-earth fault Differential; Overcurrent With the advent of ring main units incorporating SF6 circuit
Secondary winding Phase-phase fault Differential breakers and isolators, protection of distribution transformers
Secondary winding Phase-earth fault Differential; Restricted Earth Fault can now be provided by overcurrent trips (e.g. tripping
Interturn Fault Differential, Buchholz controlled by time limit fuses connected across the secondary
Core Fault Differential, Buchholz windings of in-built current transformers) or by relays
Tank Fault Differential, Buchholz; Tank-Earth
connected to current transformers located on the transformer
primary side. Overcurrent relays are also used on larger
Overfluxing Overfluxing
transformers provided with standard circuit breaker control.
Overheating Thermal
Improvement in protection is obtained in two ways; the
excessive delays of the HRC fuse for lower fault currents are
avoided and an earth-fault tripping element is provided in
16.6 TRANSFORMER OVERCURRENT
addition to the overcurrent feature.
PROTECTION
Fuses may adequately protect small transformers, but larger The time delay characteristic should be chosen to discriminate
ones require overcurrent protection using a relay and CB, as with circuit protection on the secondary side. A high-set
instantaneous relay element is often provided, the current
fuses do not have the required fault breaking capacity.
setting being chosen to avoid operation for a secondary short
16.6.1 Fuses circuit. This enables high-speed clearance of primary terminal
short circuits.
Fuses commonly protect small distribution transformers
typically up to ratings of 1MVA at distribution voltages. In
many cases no circuit breaker is provided, making fuse
protection the only available means of automatic isolation.
16-6
Chapter 16 Transformer and Transformer Feeder Protection
16.7 RESTRICTED EARTH FAULT PROTECTION Earth fault protection applied to a delta-connected or
Conventional earth fault protection using overcurrent elements unearthed star winding is inherently restricted, since no zero
fails to provide adequate protection for transformer windings. sequence components can be transmitted through the
This applies particularly to a star-connected winding with an transformer to the other windings.
impedance-earthed neutral, as discussed in Section 16.2.1. Both windings of a transformer can be protected separately
The degree of protection is very much improved by the with restricted earth fault protection, thereby providing high-
application of restricted earth fault protection (or REF speed protection against earth faults for the whole transformer
protection). This is a unit protection scheme for one winding with relatively simple equipment. A high impedance relay is
of the transformer. It can be a high impedance type as shown used, giving fast operation and phase fault stability.
in Figure 16.6 or a biased low-impedance type. For the high-
impedance type, the residual current of three line current 16.8 DIFFERENTIAL PROTECTION
transformers is balanced against the output of a current The restricted earth fault schemes described above in Section
transformer in the neutral conductor. In the biased low- 16.7 depend entirely on the Kirchhoff principle that the sum of
impedance version, the three phase currents and the neutral the currents flowing into a conducting network is zero. A
current become the bias inputs to a differential element. differential system can be arranged to cover the complete
transformer; this is possible because of the high efficiency of
The system is operative for faults within the region between
transformer operation, and the close equivalence of ampere-
current transformers, that is, for faults on the star winding in
turns developed on the primary and secondary windings.
question. The system remains stable for all faults outside this
Figure 16.7 shows the principle. Current transformers on the
zone.
primary and secondary sides are connected to form a
circulating current system.
Id >
I >
16-7
Protection & Automation Application Guide
requirements for ratio and vector correction were met by the primary and secondary line CTs may not have the same
application of external interposing current transformers (ICTs), winding configuration. Phase compensation and associated
as a secondary replica of the main winding connections, or by relay data entry requires more detailed consideration in such
a delta connection of the main CTs to provide phase correction circumstances. Rarely, the available phase compensation
only. Digital/numerical relays implement ratio and correction facilities cannot accommodate the transformer winding
in the relay software instead, thus enabling most combinations connection, and in such cases interposing CTs must be used.
of transformer winding arrangements to be catered for,
irrespective of the winding connections of the primary CTs. 16.8.4 Filtering of Zero Sequence Currents
This avoids the additional space and cost requirements of As described in Chapter 10.8, it is essential to provide some
hardware interposing CTs. form of zero sequence filtering where a transformer winding
can pass zero sequence current to an external earth fault. This
16.8.2 Line Current Transformer Primary Ratings is to ensure that out-of-zone earth faults are not seen by the
Line current transformers have primary ratings selected to be transformer protection as an in-zone fault. This is achieved by
approximately equal to the rated currents of the transformer use of delta-connected line CTs or interposing CTs for older
windings to which they are applied. Primary ratings will relays, and hence the winding connection of the line and/or
usually be limited to those of available standard ratio CTs. interposing CTs must take this into account, in addition to any
phase compensation necessary. For digital/numerical relays,
16.8.3 Phase Correction the required filtering is applied in the relay software. Table
Correct operation of transformer differential protection requires 16.4 summarises the phase compensation and zero sequence
that the transformer primary and secondary currents, as filtering requirements. An example of an incorrect choice of
measured by the relay, are in phase. If the transformer is ICT connection is given in Section 16.19.1.
connected delta/star, as shown in Figure 16.8, balanced three- Clock Phase HV Zero LV Zero
phase through current suffers a phase change of 30°. If left Transformer Transformer
Face Compensation Sequence Sequence
Connection Phase Shift
uncorrected, this phase difference would lead to the relay Vector Required Filtering Filtering
seeing through current as an unbalanced fault current, and Yy0 Yes Yes
result in relay operation. Vector or phase correction must be Zd0 Yes
implemented. 0° 0 0°
Dz0 Yes
A Dd0
B Yz1 Zy1 Yes Yes
C
Yd1 -30° 1 30° Yes
Dy1 Yes
Yy6 Yes Yes
Zd6 Yes
-180° 1 180°
Dz6 Yes
Dd6
Id > Id > Id >
Yz11 Zy11 Yes Yes
Yd11 30° 11 -30° Yes
Dy11 Yes
Electromechanical and static relays use appropriate CT/ICT YyH YzH Yes Yes
connections to ensure that the primary and secondary currents YdH ZdH Yes
(H / 12) x 360° Hour ‘H’ -(H / 12) x 360°
applied to the relay are in phase. DzH DyH Yes
16-8
Chapter 16 Transformer and Transformer Feeder Protection
2
Operate Id >
70%
slope
1 (c) Three winding transformer with unloaded delta tertiary
Setting range 30%
(0.1 - 0.5Id ) Restrain slope
0 1 2 3 4 5 6
Effective bias (x In)
16-9
Protection & Automation Application Guide
16-10
Chapter 16 Transformer and Transformer Feeder Protection
100
(percentage of rated current)
n
tio
Primary operating current
80
ec
ot
pr
u lt
fa
60
rth
n
ea
tio
ec
d
ot
te
40
pr
ric
ial
t
es
nt
R
re
ffe
20 Di
0
100 80 60 40 20 0
Percentage of winding protected
16-11
Protection & Automation Application Guide
1/0.333
Earthing
transformer
16-12
Chapter 16 Transformer and Transformer Feeder Protection
is used, this and all the line current transformers can be 16.13 OVERFLUXING PROTECTION
connected in parallel to a single element relay, providing a The effects of excessive flux density are described in Section
scheme responsive to earth faults only; see Figure 16.19(a). 16.2.8. Overfluxing arises principally from the following system
conditions:
A
B high system voltage
C
low system frequency
geomagnetic disturbances
High The latter results in low frequency earth currents circulating
Id > impedance
relay through a transmission system.
Since momentary system disturbances can cause transient
(a) Earth fault scheme
overfluxing that is not dangerous, time delayed tripping is
required. The normal protection is an IDMT or definite time
A
characteristic, initiated if a defined V/f threshold is exceeded.
B
C
Often separate alarm and trip elements are provided. The
alarm function would be definite time-delayed and the trip
a
function would be an IDMT characteristic. A typical
b characteristic is shown in Figure 16.20.
c
Geomagnetic disturbances may result in overfluxing without
Id > Id > Id > the V/f threshold being exceeded. Some relays provide a 5th
n harmonic detection feature, which can be used to detect such
(b) Phase and earth fault scheme a condition, as levels of this harmonic rise under overfluxing
conditions.
Operating 0.80.18K
t
If current transformers are fitted in each phase at the neutral time (s) M12
end of the windings and a three-element relay is used, a 1000
differential system can be provided, giving full protection
against phase and earth faults; see Figure 16.19(b). This
provides high-speed sensitive protection. It is unaffected by 100
ratio changes on the transformer due to tap-changing and is K=63
immune to the effects of magnetising inrush current. K=40
damage to the transformer will have occurred. 1 1.1 1.2 1.3 1.4 1.5 1.6
V f
In addition, this scheme does not respond to any fault in a M
Set t i ng
tertiary winding. Unloaded delta-connected tertiary windings
are often not protected; alternatively, the delta winding can be
earthed at one point through a current transformer that
16.14 TANK-EARTH PROTECTION
energises an instantaneous relay. This system should be
separate from the main winding protection. If the tertiary This is also known as Howard protection. If the transformer
winding earthing lead is connected to the main winding tank is nominally insulated from earth (an insulation resistance
neutral above the neutral current transformer in an attempt to of 10 ohms being sufficient) earth fault protection can be
make a combined system, there may be ‘blind spots’ which the provided by connecting a relay to the secondary of a current
protection cannot cover. transformer the primary of which is connected between the
tank and earth. This scheme is similar to the frame-earth fault
busbar protection described in Chapter 15.
16-13
Protection & Automation Application Guide
16.15 OIL AND GAS DEVICES device may have to be slowed deliberately to avoid spurious
All faults below oil in an oil-immersed transformer result in tripping during circulation pump starts. Alternatively, sudden
localised heating and breakdown of the oil; some degree of pressure rise relays may have their output supervised by
arcing will always take place in a winding fault and the resulting instantaneous high-set overcurrent elements.
decomposition of the oil will release gases. When the fault is of
a very minor type, such as a hot joint, gas is released slowly, but 16.15.3 Buchholz Protection
a major fault involving severe arcing causes a very rapid release Buchholz protection is normally provided on all transformers
of large volumes of gas as well as oil vapour. The action is so fitted with a conservator. The Buchholz relay is contained in a
violent that the gas and vapour do not have time to escape but cast housing which is connected in the pipe to the conservator,
instead build up pressure and bodily displace the oil. as in Figure 16.21.
When such faults occur in transformers having oil conservators, 3 x internal pipe
the fault causes a blast of oil to pass up the relief pipe to the diameter (min) Conservator
conservator. A Buchholz relay is used to protect against such 5 x internal pipe
conditions. Devices responding to abnormally high oil pressure diameter (min)
or rate-of-rise of oil pressure are also available and may be used
in conjunction with a Buchholz relay.
16-14
Chapter 16 Transformer and Transformer Feeder Protection
valve is provided on the top of the housing for the gas to be moreover, the transformer-feeder can be protected as a single
released or collected for analysis. Transformers with forced oil zone or be provided with separate protections for the feeder
circulation may experience oil flow to/from the conservator on and the transformer. In the latter case, the separate
starting/stopping of the pumps. The Buchholz relay must not protections can both be unit type systems. An adequate
operate in this circumstance. alternative is the combination of unit transformer protection
with an unrestricted system of feeder protection, plus an
Cleaning operations may cause aeration of the oil. Under such
intertripping feature.
conditions, tripping of the transformer due to Buchholz
operation should be inhibited for a suitable period.
16.16.1 Non-Unit Schemes
Because of its universal response to faults within the The following sections describe how non-unit schemes are applied
transformer, some of which are difficult to detect by other to protect transformer-feeders against various types of fault.
means, the Buchholz relay is invaluable, whether regarded as
a main protection or as a supplement to other protection 16.16.1.1 Feeder phase and earth faults
schemes. Tests carried out by striking a high voltage arc in a
High-speed protection against phase and earth faults can be
transformer tank filled with oil, have shown that operation
provided by distance relays located at the end of the feeder
times of 0.05s-0.1s are possible. Electrical protection is
remote from the transformer. The transformer constitutes an
generally used as well, either to obtain faster operation for
appreciable lumped impedance. It is therefore possible to set a
heavy faults, or because Buchholz relays have to be prevented
distance relay zone to cover the whole feeder and reach part
from tripping during oil maintenance periods. Conservators
way into the transformer impedance. With a normal tolerance
are fitted to oil-cooled transformers above 1000kVA rating,
on setting thus allowed for, it is possible for fast Zone 1
except those to North American design practice that use a
protection to cover the whole of the feeder with certainty
different technique.
without risk of over-reaching to a fault on the low voltage side.
16.16 TRANSFORMER-FEEDER PROTECTION Although the distance zone is described as being set ’half way
A transformer-feeder comprises a transformer directly into the transformer’, it must not be thought that half the
connected to a transmission circuit without the intervention of transformer winding will be protected. The effects of auto-
switchgear. Examples are shown in Figure 16.22. transformer action and variations in the effective impedance of
the winding with fault position prevent this, making the
HV LV amount of winding beyond the terminals which is protected
very small. The value of the system is confined to the feeder,
which, as stated above, receives high-speed protection
throughout.
IS IF
100%
IF
The saving in switchgear so achieved is offset by increased
complication in the necessary protection. The primary where:
requirement is intertripping, since the feeder protection remote Is = setting current
from the transformer will not respond to the low current fault
IF = steady state r.m.s value of the fault current, which when
conditions that can be detected by restricted earth fault and
fully offset, just operates the relay.
Buchholz protections.
The instantaneous overcurrent relays must be set without risk
Either unrestricted or restricted protection can be applied;
16-15
Protection & Automation Application Guide
I s 1.2 1 t I F 2
IF1 IF2
16-16
Chapter 16 Transformer and Transformer Feeder Protection
in Section 16.7 is not applicable because of the remoteness of appreciable capacitance between each conductor and earth.
the transformer neutral. During an external earth fault the neutral will be displaced,
and the resulting zero sequence component of voltage will
Restricted protection can be applied using a directional earth
produce a corresponding component of zero sequence
fault relay. A simple sensitive and high-speed directional
capacitance current. In the limiting case of full neutral
element can be used, but attention must be paid to the
displacement, this zero sequence current will be equal in value
transient stability of the element. Alternatively, a directional
to the normal positive sequence current.
IDMT relay may be used, the time multiplier being set low.
The slight inverse time delay in operation will ensure that The resulting residual current is equal to three times the zero
unwanted transient operation is avoided. sequence current and hence to three times the normal line
charging current. The value of this component of in-zone
When the supply source is on the high voltage star side, an
current should be considered when establishing the effective
alternative scheme that does not require a voltage transformer
setting of earth fault relays.
can be used. The scheme is shown in Figure 16.24. For the
circuit breaker to trip, both relays A and B must operate, which
16.16.2 Unit Schemes
will occur for earth faults on the feeder or transformer winding.
The basic differences between the requirements of feeder and
External earth faults cause the transformer to deliver zero transformer protections lie in the limitation imposed on the
sequence current only, which will circulate in the closed delta transfer of earth fault current by the transformer and the need
connection of the secondary windings of the three auxiliary for high sensitivity in the transformer protection, suggesting
current transformers. No output is available to relay B. that the two components of a transformer-feeder should be
Through phase faults will operate relay B, but not the residual protected separately. This involves mounting current
relay A. Relay B must have a setting above the maximum transformers adjacent to, or on, the high voltage terminals of
load. As the earthing of the neutral at a receiving point is likely the transformer. Separate current transformers are desirable
to be solid and the earth fault current will therefore be for the feeder and transformer protections so that these can be
comparable with the phase fault current, high settings are not arranged in two separate overlapping zones. The use of
a serious limitation. common current transformers is possible, but may involve the
use of auxiliary current transformers, or special winding and
A
connection arrangements of the relays. Intertripping of the
B
remote circuit breaker from the transformer protection will be
C necessary, but this can be done using the communication
facilities of the feeder protection relays.
Relay A I >>
16-17
Protection & Automation Application Guide
16.25(b). Feeder A
Relay electromagnets
(bias inherent)
(b) Balanced voltage system
16-18
Chapter 16 Transformer and Transformer Feeder Protection
16-19
Protection & Automation Application Guide
600/1
16.18.2.3 Restricted earth fault protection
The KBCH relay implements high-impedance Restricted Earth
R=1000A Rstab
Fault (REF) protection. Operation is required for a primary
earth fault current of 25% rated earth fault current (i.e. 250A).
The prime task in calculating settings is to calculate the value
of the stabilising resistor Rstab and stability factor K.
Id >
A stabilising resistor is required to ensure through fault stability
Primary ICT's Unit Secondary ICT's
Yy0 protection Yd1 when one of the secondary CTs saturates while the others do
relay not. The requirements can be expressed as:
VS I S Rstab
16.18.2.1 Ratio correction
And
Transformer HV full load current on secondary of main CTs is:
VS KI f Rct 2Rl
175
0.7 where:
250
16-20
Chapter 16 Transformer and Transformer Feeder Protection
Rstab = stabilising resistor. Thus from Figure 16.30, with K = 0.5, the protection is
unstable.
For this example:
By adopting an iterative procedure for values of VK/VS and K,
VK = 97V
VK
RCT = 3.7Ω a final acceptable result of 4.55, K 0.6 is obtained.
VS
R1 = 0.057Ω This results in an operating time faster than 40ms.
For the relay used, the various factors are related by the graph The required earth fault setting current Iop is 250A. The
of Figure 16.30. chosen E/F CT has an exciting current Ie of 1%, and hence
using the equation:
70 0.1
I op CTratio I S nI e
Overall operation time - milliseconds
60
where:
50
0.2 n = no of CTs in parallel (=4)
40 Is = 0.377, use 0.38 nearest settable value.
K Factor
Overall Op 0.3
30 Time
The stabilising resistance Rstab can be calculated as 60.21.
0.4
Unstable The relay can only withstand a maximum of 3kV peak under
20 0.5
fault conditions. A check is required to see if this voltage is
Stable K Factor 0.6 exceeded – if it is, a non-linear resistor, known as a Metrosil,
10 0.7
0.8 must be connected across the relay and stabilising resistor.
0.9
0 1 The peak voltage is estimated using the formula:
1 2 3 4 5 6 7 8 9 10
Vk/Vs VP 2 2VK V f VK
where:
V
Starting with the desired operating time, the K ratio and K
VS V f I f RCT 2Rl Rstab
factor can be found. And
An operating of 40ms (2 cycles at 50Hz) is usually acceptable, If = fault current in secondary of CT circuit and substituting
and hence, from Figure 16.30, values, VP = 544V. Thus a Metrosil is not required.
VK
4, K 0.5 16.18.3 Unit Protection for On-Load Tap Changing
VS Transformer
The maximum earth fault current is limited by the earthing The previous example deals with a transformer having no taps.
resistor to 1000A (primary). The maximum phase fault In practice, most transformers have a range of taps to cater for
current can be estimated by assuming the source impedance different loading conditions. While most transformers have an
to be zero, so it is limited only by transformer impedance to off-load tap-changer, transformers used for voltage control in
5250A, or 10A secondary after taking account of the ratio a network are fitted with an on-load tap-changer. The
compensation. Hence the stability voltage can be calculated protection settings must then take the variation of tap-change
16-21
Protection & Automation Application Guide
position into account to avoid the possibility of spurious trips at reconditioning at a time of the asset-owner’s choosing is far
extreme tap positions. For this example, the same transformer more preferable than a forced unplanned outage due to failure.
as in Section 16.19.2 will be used, but with an on-load tapping
This section provides an overview of techniques commonly
range of +5% to -15%. The tap-changer is located on the
available in modern numerical transformer protection relays,
primary winding, while the tap-step usually does not matter.
which can extend to asset management of the protected
transformer.
16.18.3.1 Ratio correction
In accordance with Section 16.8.4 the mid-tap position is used 16.19.1 Loss of life monitoring
to calculate the ratio correction factors. The mid tap position is
Ageing of transformer insulation is a time-dependent function
–5%, and at this tap position:
of temperature, moisture, and oxygen content. The moisture
Primary voltage to give rated secondary voltage: and oxygen contributions to insulation deterioration are
= 33 x 0.95 = 31.35kV and Rated Primary Current = 184A minimised due to the preservation systems employed in the
design of most modern transformers. Therefore, temperature
Transformer HV full load current on secondary of main CTs is: is the key parameter in insulation ageing. Frequent excesses
184 of overloading will shorten the life-expectancy of the
0.737 transformer, due to the elevated winding temperatures.
250
Insulation deterioration is not uniform, and will be more
1
Ratio compensation = 1.36 pronounced at hot-spots within the transformer tank.
0.737 Therefore, any asset management system intended to model
525 the rate of deterioration and current estimated state of the
LV secondary current = 0.875 insulation must do so based on simulated real-time hot spot
600 temperature algorithms. These models may take ambient
1 temperature, top-oil temperature, load current flowing, the
Ratio compensation = 1.14 status of oil pumps (pumping or not), and the status of
0.875
radiator fans (forced cooling or not) as inputs.
Both of the above values can be set in the relay.
The MiCOM P640 provides such a loss of life monitoring
16.18.3.2 Bias slope setting facility, according to the thermal model defined in IEEE
Standard C57.91. The protection algorithm determines the
The on-load tapping range of +5% to -15% gives rise to a
current rate of losing life, and uses that to indicate the
maximum excursion of 10% from the -5% mid-tap position.
remaining years or hours until critical insulation health
As the differential scheme notionally balances at this mid-tap,
statuses are likely to be reached. Such criticalities will relate
this means that as an approximation, the maximum
typically to known percentage degradations in the tensile
differential current that can flow when at top or bottom tap is
strength of the insulation, degradation in the degree of
10% of the load (or fault current which may flow to an external
polymerisation, and other life-loss factors. The asset owner
fault). Those relays having an adjustable k1 bias slope setting
can be alerted in advance that an outage will be required for
should ensure that it is at least 10% higher than the percentage
reconditioning or rewinding, such that investment budgeting
excursion.
can be made years and months ahead of time.
16.19 TRANSFORMER ASSET MANAGEMENT
16.19.2 Through-fault monitoring
Due to the high capital cost of transformers, and the need for
Loss of life monitoring serves to track the deterioration caused
their in-service availability to be as high as possible to avoid
by long term, repeated overloading. However, it is not the
constraining load flows demanded on the network, protection
right technique to monitor short-term heavy fault currents
is no-longer the only concern. As cities expand, consumers’
which flow through the transformer, out to an external fault on
lifestyle expectations raise, and electric vehicle recharging
the downstream power system (e.g. fault IF2 in Figure 16.23).
loads become more prevalent, these combine to increase the
Through faults are a major cause of transformer damage and
demand on the network - and it is through the transformers,
failure, as they stress the insulation and mechanical integrity -
between the different voltage levels on the system, that the
such as the bracing of the windings.
demand is traditionally supplied. This increases the focus on
knowing the health of transformers, real-time, to be able to A specific through-fault monitor is recommended to monitor
schedule condition-based maintenance. Maintenance or currents which are due to external faults passing through, and
16-22
Chapter 16 Transformer and Transformer Feeder Protection
so may range from 3.5 times up to tens of times the rated Monitored Equipment Measured Quantity Health Information
current of the transformer. The MiCOM P640 performs an I2t Voltage
calculation when the through current exceeds a user-set Partial discharge measurement Insulation quality
threshold, such that the heating effect of the square of the (wideband voltage)
maximum phase current, and the duration of the fault event Bushings Loading
are calculated. Calculation results are added to cumulative Load current Permissible overload rating
values, and monitored so that utilities can schedule Hot-spot temperature
transformer maintenance or identify a need for system
Oil pressure Insulation quality
reinforcement.
Hot-spot temperature
Oil temperature
Permissible overload rating
16.19.3 CONDITION MONITORING OF
Oil quality
TRANSFORMERS Tank Gas-in-oil content
Winding insulation condition
It is possible to provide transformers with measuring devices to
Moisture-in-oil content Oil quality
detect early signs of degradation in various components and
Buchholz gas content Winding insulation condition
provide warning to the operator to avoid a lengthy and
Frequency of use of each tap
expensive outage due to failure. The technique, which can be Position
position
applied to other plant as well as transformers, is called
Tap changer Drive power consumption OLTC health
condition monitoring, as the intent is to provide the operator
Total switched load current OLTC contact wear
with regular information on the condition of the transformer.
By reviewing the trends in the information provided, the OLTC oil temperature OLTC health
operator can make a better judgement as to the frequency of Oil temperature difference
maintenance, and detect early signs of deterioration that, if Cooling air temperature Cooler efficiency
Coolers
ignored, would lead to an internal fault occurring. Such Ambient temperature
techniques are an enhancement to, but are not a replacement Pump status Cooling plant health
for, the protection applied to a transformer. Conservator Oil level Tank integrity
16-23