Report of :
O Erection
O Testing
Transmission & Distribution
Circuit Breaker Type SB6m SB6 72
Mod. 100 BUS Ed. 3 Eng Pag.1 di 6
Copy at : q GQ/ ....................………….….... q Client . ................………….….... q
.................…………………
Serial N. Supply Order Item Fider
Voltage (KV) Rated Current (A) Breaking Capacity (kA)
Plant Customer
Assembly Drawing Schematic Diagram
OPTIONAL
q Second opening circuit q ......................................
q De energized opening circuit q ......................................
1 CONTROL OF MATERIALS BEFORE ERECTION
1 QUANTITY CONTROL q Complete
q Material missing and or not corresponding to the packing list
(see enclosed list ............. )
q Material not corresponding the packing list
(see enclosed list ............. )
q Wrong packing list
(See enclosed list ............. )
2 QUALITY CONTROL
- Packing q Perfect q damaged ( see note attached .......................)
- Material q Perfect q damaged ( see note attached .......................)
3 – STORAGE BEFORE ERECTION :
q No q Indoor q Outdoor
q Correct R Not Correct (Storage Period ...............)
- Damage Due to Incorrect storage :
q No q Oxidation q Breakage q ......................
(See note attached ...........................)
4 - SF6 gas pressure in the pole before erection :
Polo R MPa Polo S MPa Polo T MPa q Adeguated
q Not adeguated
Business Unit Services Nuova Magrini Galileo – Via Circonvallazione est n° 1 – 24040 Stezzano Bergamo
Report of :
O Erection
O Testing
Transmission & Distribution
Circuit Breaker Type SB6m SB6 72
Mod. 100 BUS Ed. 3 Eng Pag.2 di 6
2 ERECTION
Personnel of erection :
q NMG q Sub contractor .......................... q Sub contractor ......................
With NMG supervision Without NMG supervision
Correspondence of materials to the dimension drawing :
q Yes q No (See note attached .................)
Correspondence of civil works to the dimension drawing:
q Yes q No (See note attached .................)
Difficulties of erection :
q Yes (see note attached ...............) q No
ERECTION PERIOD FROM TO
3 CONTROL AND TEST
1 q Control of pressure in the poles
Interrupting Unit : R MPa q Correct
S MPa q Not correct
Temp. ................... °C T Mpa..
2 q Control of correct assembly and regulation of transmission road
(Only for Circuit Breaker Type SB6m TRIP)
q Correct q Not correct
3 q Control of correct erection poles and base frame
q Correct q Not correct
4 q Control of correct erection Control cubical
q Correct q Not correct
5 q Control of correct erection densostat SF6 Gas
q Correct q Not correct
6 q Control correct Arrangement Interconnection Control Cubical/Mechanism/s
densostat/s
Business Unit Services Nuova Magrini Galileo – Via Circonvallazione est n° 1 – 24040 Stezzano Bergamo
Report of O Erection :
O Testing
Transmission & Distribution
Circuit Breaker Type SB6m SB6 72
Mod. 100 BUS Ed. 3 Eng Pag.3 di 6
q Correct q Not correct
7 q Control correct earth connection
q Correct q Not correct
8 qControl of operating mechanism
q Closing and Opening operation without damaged
q Control of regulation Pole R Vulcain operating mechanism (OnlyCircuitBreakerTypeSB6mTRIPOLARI)
Reference TEST 1 TEST 2 TEST 3
ANGLE IN OPENING POSITION.
ANGLE IN CLOSE POSITION.
ANGLE OF EXTERNAL CRANCK 52°+0°-1° (camera AF8)
51°+0°-1° (camera TSB)
Rated value Rated value Rated value Measured value
SB6m 145÷170 SB6m 245 . SB6 72
Loding time spring charge [s] ≤ 20 (≤ 10) ≤ 20 ≤ 10 R S T
Spring charge motor absorbment (110Vdc) [A] ≤ 7,3 (5) ≤ 7,3 ≤ 2,5
Spring charge motor absorbment (220Vdc) [A] ≤ 3.7 ≤ 3,7 ≤ 1,6
Spring charge motor absorbment (125Vdc) [A] ≤ 6.4 ≤ 6,4 ≤ 2,8
Spring charge motor absorbment (230Vac-50Hz) [A] ≤ 3.5 ≤ 3,5
Spring charge motor absorb (48Vdc) [A] ≤ 16.7
Note : The value among parenthesis are refer only for Circuit Breaker type SB6m 145-170 kV UNI
q Check correct functionality of operation counter
q Check correct mechanical position indicator CB
q Check correct mechanical spring status indicator
9 q Check correct sequence densostat contact
q Correct q Not correct
Rated value Misured Value
See schematic R (tripolare) S T
Diagram
Low pressure alarm
1° opening circuit lock
2° opening circuit lock
Temperatura amb. [°C]
20°
Gas Umidity mesurament
Rated Value Misured Value
Riferimento R S T
Umidity gas [PPm ≤ 150
]
Business Unit Services Nuova Magrini Galileo – Via Circonvallazione est n° 1 – 24040 Stezzano Bergamo
Report of :
O Erection
O Testing
Transmission & Distribution
Circuit Breaker Type SB6m SB6 72
Mod. 100 BUS Ed. 3 Eng Pag.4 di 6
Unconformty Mesured Adopted
q None q Density meter replaced
q Density meter unset q ........................................
q Gas leakage from interrupting unit q ........................................
10 q Control of regular performance of operating cycles Result
Cycle O – 03” – CO – 1’ – CO Starting conditions: Motor stop q Positive
q Negative
11 q Control of operating times
q Control of main circuit times (at RV– RP)
Referd Value Measured Value
Chamber type Chamber type SB6m SB6 72 kV POLE
AF8 TSB 245
R S T
Solo SB6m 145 SB6m 145/170 kV
Closing Time [ms 77±6 79±6 (74±6) 65±6 57±5
]
Opening Time 1° circuit [ms 27±3 28±4 (31±3) 27±3 36±5
]
Opening Time 2° circuit [ms 27±3 28±4 (31±3) 27±3 36±5
]
Cycle C-O1 [ms 42±5 40±5 (30±5) 30±8 33±5
]
Cycle C-O2 [ms 42±5 40±5 (30±5) 30±8 33±5
]
Phase Discrepancy (Cl) [ms ≤5 ≤ 5 (≤ 5) ≤5 ≤5
]
Phase Discrepancy (OP 1°) [ms ≤ 3,3 ≤ 3,3 (≤ 3,3) ≤ 3,3 ≤ 3,3
]
Phase Discrepancy (OP 2°) [ms ≤ 3,3 ≤ 3,3 (≤ 3,3) ≤ 3,3 ≤ 3,3
]
Value among the parenthesis are referred only for CB type SB6m UNI 145-170kV.
Unconformity Measure Adopted
q None q ........................................
q Opening Time out of tolerance q ........................................
q Closing Time out of tolerance q ........................................
q Phase discrepancy out of tolerance q …....................................
q ........................................ ( See note attached .................)
Business Unit Services Nuova Magrini Galileo – Via Circonvallazione est n° 1 – 24040 Stezzano Bergamo
Report of :
O Erection
O Testing
Transmission & Distribution
Circuit Breaker Type SB6m SB6 72
Mod. 100 BUS Ed. 3 Eng Pag.5 di 6
12 q Functional Test
q Absorbment heater and ant condensation Heater (A)
Rated Value Measure Value
See Schematic Diagram
Heater resistance Control Cubical [A]
Ant condensation heater Control Cubical [A]
Heater resistance operating mechanism/s [A]
Ant condesation Heater Operating mechanism/i [A]
q Control of Auxiliary Contact
q Check segalization and locks
Unconformity Measure Adopted
q None q Wiring modification
q Wiring not corresponding to schematic diagram q Replaced aux components
q Aux component not corrisponding q ........................................
q Missing aux conponents q ........................................
q Foulty Aux conponents q ........................................
q ........................................ q ........................................
(See Note Attached .................)
13 q Contact resistance mesurament
Valore di Valore Misurato
Riferimento R S T
POLE SB6m 145-170 kV [µΩ] 39±3 Chamber AF8
32±5 Chamber TSB e Uni
POLE SB6m 245 kV [µΩ] 35±5
POLOE SB6 72 [µΩ] 23±6
POLE+CLEMPS [µΩ] Pole +20
CONCLUSIONS
q The control have been performed successfully and the Circuit Breaker can be energized
q The defect found have been eliminated the Circuit Breaker can be energized.
q For The completation of the circuit Breaker Following works must be done :
Note: ......................................................................................................................................
................................................................................................................................................
Business Unit Services Nuova Magrini Galileo – Via Circonvallazione est n° 1 – 24040 Stezzano Bergamo
Report of O Erection :
O Testing
Transmission & Distribution
Circuit Breaker Type SB6m SB6 72
Mod. 100 BUS Ed. 3 Eng Pag.6 di 6
................................................................................................................................................
................................................................................................................................................
................................................................................................................................................
q Anyhow the Circuit Breaker can be energized.
q The circuit breaker has not completely inspected and therefore cannot energized..
q The circuit breaker shows major defects and cannot be energized.
q ................................................................................................................................................
Has been felled a report of faulty/ Defect q No q Yes N° ..............
The Circuit Breaker has been put in service q Yes (in date ............) q No
Date Name : Signature of Operator
For Client
....................................................................................................................