1-Phase Rack/Tower Online UPS
UM series 1000VA-3000VA
UM RT Series 1000-3000VA
1:1 Phase PF 0.9 (PF 1.0 optional) Power range: 1kVA~3kVA
3 kinds of LCD can be selected
Colourful LCD Blue LCD Advanced
Touch Screen
Battery cabinet Optimized battery configuration
(Optional) 7Ah/9Ah (12V)
Features
·Rack/Tower convertible design
·Online double conversion with full digital control
·Wide input voltage range: 110~300Vac
·Input power factor 0.99 with PFC
·Selectable output voltage: 208/220/230/240Vac
·Smart charger design for optimized battery performance
·Maximum charging current can be expanded to 12A (Long run unit)
Multifunctional The LCD panel can
·Emergency power off function (EPO) bracket be rotated
·ECO mode operation for energy saving
·Generator compatible
·Hot-Swappable battery design
·Cold start
·Intelligent fan speed regulation
·Load segment settable (Optional)
·Versatile LCD human-computer interface
·Multiple communication interface: RS232 (USB/EPO/Relay card
/SNMP card optional)
·Multiple protection function: short-circuit,overload,overheat, battery
Relay card SNMP
overcharge and overdischarge, output low voltage and fan fault alarm Optional socket
·PDU with maintenance bypass switch (Optional)
UM RT Series 1000-3000VA
Technical Specifications:
MODEL UM-RT 1000 UM-RT 1500 UM-RT 2000 UM-RT 3000
Capacity 1000VA / 900W 1500VA / 1350W 2000VA / 1800W 3000VA / 2700W
INPUT
Nominal voltage 208/220/230/240Vac
Input voltage range 110~300Vac (176~264Vac @ 100% load)
Power factor ≥0.99
FREQUENCY
Frequency range 40~70Hz (50/60Hz Auto-Sensing)
OUTPUT
Output voltage 208/220/230/240Vac
Voltage regulation ±1%
Power factor 0.9
Output Line mode 46~54Hz or 56~64Hz
frequency Bat. mode (50/60±0.1%)Hz
Crest factor 3:1
≤3% Linear load
Harmonic distortion (THDv)
≤5% Non linear load
AC mode to Bat.mode 0ms
Transfer time
Inverter to Bypass 4ms (Typical)
Output waveform Pure Sinewave
EFFICIENCY
AC mode 89% 89% 91% 92%
Battery mode 85% 85% 87% 88%
BATTERY
Battery number 2 3 4 6
Capacity (Standard unit) 9Ah/12V (7Ah/12V Optional)
Typical recharging time 4 hours (To 90% of full capacity)
Charging current (Max.) 1A
INDICATORS
LED display Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault
LCD display Input voltage,Input frequency,Output voltage,Output frequency,Load percentage,
Battery voltage,Inner temperature& Remaining battery backup time
ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continously beeping
PHYSICAL
Dimension (W x D x H) 440x325x86.5mm 440x460x86.5mm 440x460x86.5mm 440 x 600 x 86.5mm
Net weight 11.3kg 16.5kg 19.5kg 26kg
ENVIRONMENT
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20~95%RH @ 0~40℃ (Non condensing)
Altitude <1500m,derating required when>1500m
Noise level <50dB at 1 Meter
STANDARDS
Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
1. When output voltage is 208Vac, need to derate to 80% of the unit capacity
2. Specifications are subject to change without prior notice
3. Data above are typical values for reference only, not as a basis for engineering design