Control Valve Accessories
1
2
Contents:
⚫ Actuator
⚫ Air filter Regulator
⚫ Valve Positioner
⚫ Volume Booster
⚫ Air Lock Relay
⚫ Solenoid Valve
⚫ Limit switches
⚫ Position Transmitter
⚫ Interlock Detail
3
Actuators
Actuators
Electro-
Manual Diaphragm Motorized Piston
Hydraulic
4
Manual Actuators :
⚫ Useful where automatic control is not required.
⚫ For manual control of the process during maintenance
or shutdown of the automatic system.
⚫ Much less expensive than automatic actuators.
⚫ Are available in various sizes for both globe-style
valves and rotary-shaft valves.
5
6
FOR SLIDING-STEM VALVES FOR ROTARY-SHAFT VALVES
7
Diaphragm Actuators :
⚫ Uses input signal from the I/P converter , Positioner or
other source like Manual Loader.
⚫ Advantages :
- Dependable
- Simple
- Economical
⚫ Types :
- Direct Acting
- Reverse Acting
8
Diaphragm Actuators :
9
DIRECT-ACTING REVERSE-ACTING
10
Electro-Hydraulic Actuators :
11
Disadvantages :
- More complex.
- More expensive than pneumatic Actuators.
Offers Advantages where :
- No air supply source is available.
- Low ambient temperature could freeze the
condensed water in pneumatic supply.
- Large stem forces are needed.
12
Piston Actuators :
⚫ Uses high pressure plant air up to 150 psig.
⚫ Provides fast stroking speeds.
⚫ Types :
- single acting
- Double acting
13
Single acting Piston Actuators :
- Can produce work in only one direction.
- Uses Built-in spring.
⚫ Limitation :
- Stroke length is limited.
⚫ Applications :
- Fail open or fail closed operation.
14
Double Acting Piston Actuators :
⚫ No return spring.
⚫ Able to work in both directions.
⚫ Same two ports are used for supply and exhaust
ports.
⚫ Applications :
- mostly used where max. force is required in
both directions.
15
Control Valve with Double-Acting Piston actuator
16
ISO/DIN mounting
interface for low-profile Nylatron guide
direct mounting band provides 360°
piston rack support
17
Double Acting Piston Actuator
18
Valve Positioner
Valve Positioner
Pneumatic Positioner Electro pneumatic Digital valve
Positioner controller
19
Pneumatic Positioners :
20
Operational schematic
21
Pneumatic Positioner
22
Electro pneumatic Positioner :
23
Electro pneumatic Positioner
Operational schematic
24
Valve Positioner with Rotary Actuator
25
Positioner mounting
26
27
Digital Valve controllers :
⚫ Communicating (HART, Field-Bus) , Microprocessor
based current-to-pneumatic instruments.
⚫ Features :
- easy access to information which is critical to
process operation.
- avoids high cost of running separate power and
signal wiring.
28
Digital Valve controller
Digital Valve
Controller
With
With With
Diaphragm
Piston Actuator Rotary Actuator
Actuator
29
Digital valve controller mounted on Diaphragm Actuator
30
Digital valve controller
mounted on Piston Actuator
31
32
Digital valve controller with Rotary Actuator
33
Block Diagram
34
Principle Of Operation :
35
Electronic Position Transmitter
36
37
Limit Switches
1) Potential Free Contact Type
2) Proximity Type
38
1) Potential Free Contact Type :
39
Micro Switch :
40
2) Proximity switches :
⚫ Inductive proximity switches for metal object
⚫ capacitive proximity switch for plastic or paper or a
liquid (oil or water), granulate or powder.
41
Inductive proximity switches :
Working principle :
-Two oscillator coils are used to generate
electromagnetic fields.
- Target cuts the field. Eddy currents are
induced in the target.
- Power loss in resonant circuit.
- Oscillator amplitude consequently falls.
Trigger circuit activates the output
switching device once a certain amplitude
42
is reached.
43
Types of Design :
Rectangular Screw mounted Surface switches (FP)
proximity switches
Ring type inductive
proximity switches
proximity switches
44
Slot type inductive
proximity switches
Cylindrical
proximity
switches
45
Air Filter Regulator
46
Volume Booster
47
48
Solenoid Valves
PRINCIPLE OF OPERATION :
⚫ A solenoid valve is a combination of two
basic functional units:
1. Solenoid (electro-magnet) with its core (plunger).
2. A valve containing an orifice in which a disc or plug is
positioned to stop or allow flow.
⚫ The valve is opened or closed by movement of the magnetic core
which is drawn into a solenoid when the coil is energized.
49
Direct operated valve :
⚫ In a direct operated
valve the solenoid core
is mechanically
connected to the valve
disc and directly opens /
closes the orifice,
dependent upon
energisation or de-
energisation of the
solenoid.
50
Pilot Operated Valve :
51
Types Of Valves :
1) 2/2 (2-Way Valves)
- It has one inlet and one
outlet pipe connection.
-Normally Closed
Construction
Valve is closed when de-
energized and open when
energized.
-Normally Open
Construction
Valve is closed when
energized and open when
de-energized.
52
2) 3/2 (3-WayValves)
- Three pipe connections and two
orifices Used to alternately apply
pressure to and exhaust from
diaphragm.
- Normally closed Construction
- Normally Open
Construction
53
54
3) 4/2 and 5/2 (4-Way Valves)
- Four or five pipe connections one pressure, two
cylinder and one or two exhausts.
55
AIR LOCK RELAY
56
Pneumatic Hookup Double
Acting Piston Actuator
57
Pneumatic Hookup
Redundant Solenoid Valves
58
59