Fluke 117/323 Electricians Multimeter Combo Kit
Combine the power of Fluke's 117 Electrician's Multimeter with a Fluke 323 clamp meter for productive and
effective troubleshooting.
Having the right tool for the job is essential. Having all the right tools when you need them is even better. The
Fluke 117/323 Electricians Multimeter Combo Kit gives you the best in a versatile, rugged multimeter and a
fast-acting, general purpose clamp meter.
The Fluke 117 provides non-contact voltage detection, an AutoV/LoZ function, Min/Max/Average readings,
plus frequency and capacitance measurements. It's easy to use and saves you time.
Electrical meters need to handle whatever comes up on the job. That's why the Fluke 117 Electrician's
Multimeter is certified for use in CAT III 600 V environments.
True RMS measurements and optimized ergonomics make the Fluke 323 True RMS Clamp Meter the best
general purpose clamp meter for commercial and residential electricians. The Fluke 323 model is ideally
suited for current measurements up to 400 A in tight cable compartments.
Together, the Fluke 117 Electricians Multimeter and 323 True-rms Clamp Meter give electricians the right
tools for the job.
Fluke 117 Electrician's Multimeter
• Fast go/no-go testing with VoltAlert™ non-contact voltage detection
• AutoVolt automatic AC/DC voltage selection
• Low input impedance helps prevent false readings due to ghost voltage
• Work in poorly lit areas with the Large white LED backlit display
• True RMS voltage and current for accurate measurements on non-linear loads
• Measures 10 A directly (20 A overload for 30-seconds) without a current clamp
• Resistance, continuity, frequency and capacitance
• Record signal fluctuations using Min/Max/Average and elapsed time stamps
• Easy to use with one hand
• Hands free operation with optional magnetic hanger (ToolPak™)
• CAT III 600 V safety rated
Fluke 323 True-rms Clamp Meter
• 400 A AC current measurement
• 600 VAC and DC voltage measurement
• True RMS AC voltage and current for accurate measurements on non-linear signals
• Resistance measurement up to 40 k with continuity detection
Specifications
Maximum voltage between any 600 V
terminal and earth ground
Surge protection 6 kV peak per IEC 61010-1 600 VCAT III, Pollution Degree 2
Fuse for A input 11 A, 1000 V FAST Fuse (Fluke PN 803293)
Display Digital: 6,000 counts, updates 4 per second
Bar graph 33 segments, updates 32 per second
Operating temperature -10°C to +50°C
Storage temperature -40°C to +60°C
Battery type 9 volt Alkaline, NEDA 1604A/ IEC 6LR61
Battery life 400 hours typical, without backlight
Accuracy Specifications
DC millivolts Range/Resolution 600.0 mV / 0.1 mV
Accuracy ±([% of reading] + [counts]): 0.5% + 2
DC volts Range/Resolution 6.000 V / 0.001 V
60.00 V / 0.01 V
600.00 V / 0.1 V
Accuracy ±([% of reading] + [counts]): 0.5% + 2
Auto volts Range/Resolution 600.0 V / 0.1 V
Accuracy 2.0% + 3 (DC, 45 Hz to 500 Hz)
4.0% + 3 (500 Hz to 1 kHz)
AC millivolts¹ True RMS Range/Resolution 600.0 mV / 0.1 mV
Accuracy 1.0% + 3 (DC, 45 Hz to 500 Hz)
2.0% + 3 (500 Hz to 1 kHz)
AC volts¹ True RMS Range/Resolution 6.000 V / 0.001 V
60.00 V / 0.01 V
600.0 V / 0.1 V
Accuracy 1.0% + 3 (DC, 45 Hz to 500 Hz)
2.0% + 3 (500 Hz to 1 kHz)
Continuity Range/Resolution 600 /1
Accuracy Beeper on < 20 , off > 250 ; detects opens or
shorts of
500 s or longer.
Ohms Range/Resolution 600.0 / 0.1
6.000 k / 0.001 k
60.00 k / 0.01 k
600.0 k / 0.1 k
6.000 M / 0.001 M
Accuracy 0.9% + 1
Range/Resolution 40.00 M / 0.01 M
Accuracy 5% + 2
Diode test Range/Resolution 2.00 V / 0.001 V
Accuracy 0.9% + 2
Capacitance Range/Resolution 1000 nF / 1 nF
10.00 F / 0.01 F
100.0 F / 0.1 F
9999 F / 1 F
100 F to 1000 F
Accuracy 1.9% + 2
Range/Resolution > 1000 F
Accuracy 5% + 20%
Lo-Z capacitance Range 1 nF to 500 F
Accuracy 10% + 2 typical
AC amps True RMS (45 Hz to 500 Hz) Range/Resolution 6.000 A / 0.1 A
10.00 A / 0.01 A
Accuracy 1.5% + 3
20 A continuous overload for 30 seconds max
DC amps Range/Resolution 6.000 A / 0.1 A10.00 A / 0.01 A
Accuracy 1.0% + 3
20 A continuous overload for 30 seconds max
Hz (V or A input)² Range/Resolution 99.99 Hz / 0.01 Hz
999.99 Hz / 0.1 Hz
9.999 Hz / 0.001 Hz
50.00 Hz / 0.01 Hz
Accuracy 0.1% + 2
1. All AC voltage ranges except Auto-V/LoZ are specified from 1% to 100% of range. Auto-V/LoZ is specified from 0.0 V.
2. Temperature uncertainty (accuracy) does not include the error of the thermocouple probe.
• Frequency is AC coupled, 5 Hz to 50 kHz for AC voltage. Frequency is DC coupled, 45 Hz to 5 kHz for AC current.
• Temperature Range/Resolution: -40°F to 752°F / 0.2°F.
Mechanical and General Specifications
Size 167 x 84 x 46 mm (6.57 x 3.31 x 1.82 in)
Weight 550 g
Warranty 3 years
Specifications
AC current Range 400.0 A
Accuracy 2% ±5 digits
(45 Hz to 65 Hz)
2.5% ±5 digits
(65 Hz to 400 Hz)
AC voltage Range 600.0 V
Accuracy 1.5% ±5 digits
DC voltage Range 600.0 V
Accuracy 1.0% ±5 digits
Resistance Range/Resolution 400.0 / 4000
Accuracy 1.0% ±5 digits
Continuity 70
AC response True RMS
Data hold Yes
Size H x W x D (mm) 207 x 75 x 34
Max wire diameter 30 mm (600 MCM)
Weight 265 g
Category rating CAT III 600 V
CAT IV 300 V