M. Remote Annuciator (RA100z) - TDS

The document provides installation and maintenance instructions for the RA100Z and RA100ZA remote annunciators, detailing specifications such as voltage range, maximum alarm current, and temperature range. It emphasizes the importance of compliance with local codes and the correct wiring procedures, including the installation of a jumper for conventional systems. The devices are designed for both conventional and intelligent applications and must be mounted to a single gang electrical outlet box.

Uploaded by

jfaayonayon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
26 views1 page

M. Remote Annuciator (RA100z) - TDS

The document provides installation and maintenance instructions for the RA100Z and RA100ZA remote annunciators, detailing specifications such as voltage range, maximum alarm current, and temperature range. It emphasizes the importance of compliance with local codes and the correct wiring procedures, including the installation of a jumper for conventional systems. The devices are designed for both conventional and intelligent applications and must be mounted to a single gang electrical outlet box.

Uploaded by

jfaayonayon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

INSTALLATION AND MAINTENANCE INSTRUCTIONS

I56-0508-008
RA100Z and RA100ZA (Canadian) 3825 Ohio Avenue, St. Charles, Illinois 60174

Remote Annunciator 1-800-SENSOR2, FAX: 630-377-6495


www.systemsensor.com
SPECIFICATIONS
Voltage Range
Conventional System: 3.1 to 32 VDC ­— (Installation of jumper required) Note 1
Intelligent System: 18 to 32 VDC — (Do not install jumper)
Maximum Alarm Current: 10 mA maximum.
Temperature Range: –10° to 60°C (14° to 140°F)
Listing: UL, FM, CE

CAUTION
Install jumper when using an RA100Z or RA100ZA with any conventional duct detector (such as the System Sensor model D2 or D4120).

NOTE: RA100Z and RA100ZA replaces RA400Z and RA400ZA . FIGURE 1:


GENERAL INFORMATION
The National Fire Protection Association has published codes, standards, and
recommended practices for the installation and use of the above appliance. It
is recommended that the installer be familiar with these requirements, with
local codes, and any special requirements of the local authority having juris-
diction.
The models RA100Z & RA100ZA remote annunciators are polarized devices
designed for both conventional and intelligent applications. They have been
designed using an active current regulator so that the maximum current re-
quired from the system is 10mA when the input voltage is within the specified
voltage range.
INSTALLATION
The remote annunciator is intended to be mounted to a single gang electrical
outlet box. The wiring must be in compliance with all codes. The device must
be operated within its published specifications.
Wire the remote annunciator according to the instructions supplied with the
device being monitored. Polarity of the incoming wires must be observed and
connected to the proper terminals “+” and “–”. (See Figure 2.)
The provided jumper must be installed for use with System Sensor Conventional
systems. To install jumper: slide jumper over both pins. (see Figure 3/Note 1)

H0355-01

1 I56-0508-008
06-10