7 SG 15 Microtappcataloguesheet
7 SG 15 Microtappcataloguesheet
Protection
Devices
7SG15 – MicroTAPP
Automatic Voltage Control
Fig 1. MicroTAPP AVC Relay Runaway detection locks out the tap-changer to prevent
unwanted tap changes due to electrical or mechanical fail-
ure.
Description
VT Fuse Monitor. Negative-phase sequence (NPS) voltage
element detects blown VT fuses to prevent incorrect voltage
The MicroTAPP range of Automatic Voltage Control (AVC) control.
relays combines the power and flexibility of microprocessor Data Storage is provided through Events, 24-hour Waveforms
technology with the renowned operating philosophy and and Fault Records.
effectiveness of the established Transformer Automatic Par- IEC 60870-5-103 Communications for in-station monitoring
alleling Package (TAPP) method. and control.
Hardware and software watchdogs provide comprehensive
The relay provides three function areas: self-monitoring.
The efficient control of power system voltage levels through MicroTAPP 102
operation of an on-load tap changer
As for the MicroTAPP 101, plus:
Pseudo-VTTM allows control of voltage on remote side of
The monitoring and protection of the power system and tap-
transformer.
changer.
High integrity and confidence is maintained through the use 5 fixed LEDs
of watchdog self-monitoring and supervision, while inde-
pendent algorithms are provided for the voltage control and
monitoring functions.
Function Overview
MicroTAPP 101
Circulating Current voltage control.
Enhanced TAPP principle for voltage control.
MPPC status
Fig 2. Tap Change control with Deadband
Tap-changer Monitoring
An intelligent tap-position indicator and runaway prevention
algorithm monitors the entire tap-change operation. A Tap-
changer runaway is quickly detected and the resulting alarm
can be used to lock-out the tap-changer to prevent damage
to the system. Incomplete tap-changes are also detected and
indicated.
Tap Changer Maintenance This support software is common to the entire range of
Reyrolle numeric products. It provides the means for the user
A tap-changer operations count and a “sum of I2” count is
to apply settings to the Delta as well as to retrieve settings,
provided. Alarm levels can be set which, when reached, can
instruments, events, waveforms and 24 hour data.
be routed to a condition-based maintenance system.
Output Relays
Burden
AC Current Inputs Carry continuously 5A ac or dc
1A ≤ 0.1 VA Make and carry 20A ac or dc for 0.5s
5A ≤ 0.3 VA (L/R ≤ 40 ms and V ≤ 30A ac or dc for 0.2s
300V)
AC Voltage Inputs Breaking Capacity
( ≤ 5 A and ≤ 300 V):
≤ 0.01 VA
AC Resistive 1250 VA
AC Inductive 250 VA at p.f. ≤ 0.4
DC Auxiliary Supply DC Resistive 75 W
DC Inductive 30 W at L/R ≤ 40ms
Nominal Voltage Operating Range 50 W at L/R ≤ 10ms
30 VDC 24 to 37.5 VDC Minimum number of
1000 at maximum load
operations
48, 110 VDC 37.5 to 137.5 VDC
Minimum recommended
220 VDC 178 to 280 VDC 0.5 W limits 10mA or 5V
load
110 VAC 82.5 to 137.5 VAC RMS
Conduct limits
Mechanical Classification
IEC 60255-25
Durability In excess of 106
operations Frequency Range Limits dB(µV)
Quasi-peak Average
Recommended load 0.15 to 0.5 MHz 79 66
0.5 to 30 MHz 73 60
Minimum recommended load 0.5 W, limits 10 mA or
5V Radiated limits
IEC 60255-25
Transient Overvoltage
IEC 60255-5
Electrostatic Discharge
IEC 60255-22-2 Class III
Fast Transient
IEC 60255-22-4 Class IV
General Settings
Parameter Value
Transient Overreach of ≤ 5%
Highset/Lowset (X/R =
100)
Disengaging Time (1) < 42 ms
Overshoot Time < 40 ms
Indication
Relay Healthy
Method Green LED
Relay Failure Flashing or extinguished
High, Low Voltage
Method Red LEDs
Voltage Alarm Flashing
Normal Voltage
Method Green LED
Tap In Progress
Method Amber LED
Lockout Flashing
Frequency
Range Variation
47 Hz to 52 Hz Level: ≤ 5%
57 Hz to 62 Hz Operate Time: ≤ 5%
Harmonic content
Range Variation
Frequencies to 550Hz Setting: ≤ 5%
Control Elements
The AVC must be provided with the capability of inde- Protection is required that will detect incorrect tap
pendently protecting against incorrect operation which change operation at the earliest opportunity. An incorrect
would allow abnormal voltages to be applied to the net- tap change operation is defined as “a tap change opera-
work. tion that is not initiated by a ‘true’ control signal”. As an
example, a slow to clear ‘raise’ contactor may allow a
The AVC shall be capable of controlling at least 16 trans- motor drive to continue driving the mechanism at the end
formers operating in parallel as a group. of a tap change cycle such that the tap change maintain-
ing switch recloses and thus allows the tap change to ‘run
The operating characteristics of the voltage regulating away’.
relay is to be such that a raise or lower command will only
be issued after an initial time delay as set on the voltage The preferred scheme should not rely on timing
regulating relay. A definite time characteristic and an systems for determination of this situation, but intelli-
inversely related initial time characteristic shall be select- gently monitor the relationship between the control sig-
able. When a definite time delay is selected a fast tapping nals, the tap change in progress inputs and the tap posi-
feature which bypasses the initial time delay in the event tion.
of substantial voltage excursions above the set band is
preferred. Any subsequent corrective signals for the same If a lockout is required the AVC will initiate contacts
voltage deviation will be delayed by a separate inter-tap both for lockout and alarms. The lockout contacts shall
time delay. provide for the tripping of a mechanically latched contac-
tor or the permissive operation normally open contactor
The voltage regulating relay shall include a ‘Load Drop to remove the tap change motor power supply.
Compensation’ facility. LDC shall be used where the bus-
bar voltage is increased in proportion to the total substa- Inputs from plant
tion load current. The LDC effect shall be proportional to
Operator Controls
The AVC system shall provide the means to:
PSU
13 4
14 5
RL1
15 6
21 7
S1
23 8
RL2
25 9
S2
27 10
26 11
RL3
S3
28 12
17
RL5 RL4
19
18
20
1 IO1
CANH IO1 2
+ -
S4
3 CANL 4
5 CANGND 6
S5
7 8
9 B0 10
S6
11 B1 12
13 B2 14
S7
15 B3 Digital 16
17 B4 TPI 18
S9 S8
19 B5 20
21 COM 22
23 A+ 24
S11 S10
25 wiper Analogue 26
27 A- TPI 28
1 IO2 2
S12
- +
RL7 RL6
see note 3 3 4
5 6
S13
7 8
9 10
RL8
S14
11 12
13 14
RL9
S19 S18 S17 S16 S15
15 16
17 18
RL13,12 RL11,10
19 20
21 22
23 24
25 26
27 28
see note 2
AN1 CPU
23
IRIG-B
24 Ir
see note 1 VA 25
26 Vr Tx-1
VB 27
28 Vs
VC Rx-1
ISO Rx
2 FASCIA
3 Tx-2b
ISO Tx
4 Front serial
ISORTS
5 comms port 2a
ISODTR
ISODTR
6 25 way 'D' Rx-2b
ISOGND
7 connector
20 (female) Rear F.O.
ISODTR
comms ports
Notes
1. Analogue connections show use with a star-connected
VT, other arangements can be used.
2. CT connection is shown on blue phase, any connection
can used.
3. IO2 is provided on MT1-xxx xJ variants only
13
Fig. 4 shows two options for AC measuring connections, one using a 3-phase VT the other for when only a single-phase VT is
available. Any phase may be chosen for the CT.
Fig. 6 and 7 show typical control circuit connections. Fig. 6 is the traditional connection for use with a step-by-step contactor
(relay in ‘Basic’ mode). In Fig. 7 the step-by-step control is provided by the MICROTAPP software (relay in ‘step-by-step’
mode).
TRANSFORMER
A a
Single
Phase rotation phase VT
B b MicroTAPP
A-B-C or A-C-B
C c module
AN1
VT
MicroTAPP 23
module 24
AN1 25
23
26
24 27
25 28
26
27
28
MicroTAPP MicroTAPP
Top Tap
module IO1 module IO1
B0 9
B1 11
Tap
B2 13
Moving contact
23 position B3 15
25 Switch B4 17
Tap 1 27
B5 19
COM
21
Fig5. Tap position input connections for Resistor Chain and BCD/Binary sender units
14
110V ac CONTROL SUPPLY
MicroTAPP
A13 POWER A14
SUPPLY
S7
In Progress Motor
Contactors
Raise Operating DSS open
Limit
Switches handle during tap
Interlock change
Lowe Raise
Raise
r RL5
Lower
Lower
RL4
Lockout
RL
2
Master Lockout or
Step by Permissive relay
Raise Sense
S3
Step (runaway
prevention)
Lower Sense
S2
Block Raise
Directional Master Lockout
Sensing reset coil
Block Lower
Switch (closed (example only)
Ballast Resistor during tap
if Required change)
MicroTAPP
POWER
SUPPLY
S1
S7
In Progress Motor
Contactors
Raise Operating DSS open
Limit
Switches handle during tap
Interlock change
Lowe Raise Rais
r RL5 e
(mechanically
Lower maintained T/
Lower
RL4 C only)
Lockout
RL2
Master Lockout or
Permissive relay
Raise Sense Master (runaway
Lockout reset prevention)
S3
coil (example
Lower Sense only)
S2
Directional
Sensing
Switch (closed
Ballast Resistor
during tap
if Required
change)
Fig 7. Typical tap-change control circuit with step-by-step control internal to the MICROTAPP
15
3 1 5 3 1 5 5 1 3
7 7 7
Intermediate
MicroTAPP 1 MicroTAPP N
MicroTAPP
module IO1 module IO1 module IO1
MPPC line terminator MPPC screen earthing MPPC Screend twisted MPPC line terminator
link at a single point pair cable link
Maintaining switch
driven by
mechanism
Lowe
Raise
r
Operating
Overloa Raise Lower handle
Isolator Contactor Contactor Limit Switches Interlock
d
3 phase
power Motor
supply
Master Lockout
Relay trip or
Permissive close
(runaway
prevention)
16
Case Drawing
The MicroTAPP is supplied in either a size 8 or size 12 case, depending on the status input and output relay requirement, see
the table below.
Fig 10. Overall Dimensions and panel drilling for Epsilon E8 case
Fig 11. Overall Dimensions and panel drilling for Epsilon E12 case
17
Ordering Information - MICROTAPP 7SG151
Product description Variants Order No.
MICROTAPP 7 S G 1 5 □▲ 0 - □▲ □▲ □▲ □▲ □▲ - 0 □▲ □▲ 0
Transformer tap change control and monitoring. | | | | | | | |
| | | | | | | |
Relay type | | | | | | | |
Automatic voltage control (AVC) 1 | | | | | | |
| | | | | | |
Protection options | | | | | | |
Basic - Microprocessor based automatic voltage control (AVC) 1 | | | | | |
system operating on the well proven TAPP philosophy | | | | | | |
| | | | | | |
Advanced - As basic model only particularly suitable for em- 2 | | | | G |
bedded generation and traction system applications as this | | | | ||
model is capable of controlling the HV or LV voltage | | | | ||
| | | | | |
Auxiliary supply /binary input voltage | | | | | |
30 V DC auxiliary, 30 V DC/AC binary input A | | | | |
30 V DC auxiliary, 48 V DC/AC binary input B | | | | |
48/110 V DC auxiliary, 30 V DC/AC binary input C | | | | |
48/110 V DC auxiliary, 48 V DC/AC binary input 1) D | | | | |
48/110 V DC auxiliary, 110 V DC/AC low burden binary input E | | | | |
220 V DC auxiliary, 110 V DC/AC low burden binary input F | | | | |
220 V DC auxiliary, 220 V DC/AC low burden binary input G | | | | |
110 V AC auxiliary, 110 V DC/AC binary input H | | | | |
110 V AC auxiliary, 48 V DC/AC binary input X | | | | |
110 V AC auxiliary, 220 V DC/AC binary input J | | | | |
110 V AC auxiliary, 30 V DC/AC binary input K | | | | |
| | | | |
I/O range | | | | |
11 Binary Inputs / 5 Binary Outputs (incl. 3 changeover) E | | E |
19 Binary Inputs / 13 Binary Outputs (incl. 3 changeover and J | | G |
4 normally closed contacts) | | | | |
19 Binary Inputs / 13 Binary Outputs (incl. 3 changeover) K | | G |
| | | |
Frequency | | | |
50/60Hz 3 | | |
| | |
Nominal current | | |
1/ 5 A 0 | |
| |
Housing size | |
Case size E8 (4U high) E |
Case size E12 (4U high) G |
|
Communication interface |
Fibre optic (ST-connector) / IEC 60870-5-103 A
1) High burden 110/125V & 220/250V binary inputs compliant with ESI48-4 ESI 1 available via external dropper resistors with 48V binary input version
110/125 V application, order combination of the following resistor boxes to suit number of binary inputs
VCE: 2512H10064 (9 inputs, 110V)
VCE:2512H10065 (5 inputs, 110V)
VCE:2512H10066 (1 inputs, 110V)
220/250 V application, order resistor box 2512H10066 in addition
VCE:2512H10067 (5 inputs, 220V)
VCE:2512H10068 (1 inputs, 220V)
Refer to website for application note about ESI48-4 compliance
2) For use with resistor sender units, order mounting bracket assembly with 19 off 220ohm resistors – VCE:2512H10072
3) Milliamp transducer FTPT, order 7XG2300-1AA00-0AA0
Averaging VT FAVT, order 7XG2300-2AA00-0AA0
Tap position indication module FTIM, order 7XG2300-3AA00-0AA0
18
19
Published by and copyright © 2010:
Siemens AG
Energy Sector
Freyeslebenstrasse 1
91058 Erlangen, Germany
www. siemens.com/energy
20